HomeMy WebLinkAboutE701 - ELECTRICAL SCHEMATICSCONTROLLED CIRCUITS
TO EXTERIOR LIGHTING
FIXTURES
PROVIDE (1) 12-POLE MECHANICALLY
HELD CONTACTORS RATED 20A, 600V
TO CONTROL EXTERIOR LIGHTING AND
SIGN CIRCUITS
CIRCUITS AS SHOWN
ON DRAWINGS
CLOSE
C
OPEN
CR
120V CONTROL CIRCUIT. CONNECT TO
SPARE CIRCUIT BREAKER IN NEARBY
120V PANEL OR AS INDICATED.
H-O-A SWITCH MOUNTED
IN ENCLOSURE COVER
PHOTOCELL MOUNTED
ON ROOF
TWO-WIRE
CONTROL RELAY
EMERGENCY LIGHTING
INVERTER AS
INDICATED ON DRAWINGS
2-CIRCUIT PROGRAMMABLE 24-HOUR
TIME SWITCH LIKE INTERMATIC
#ET1100C WITH BATTERY BACKUP
OFF
AUTOHAND
TC
TS
1. ALL CONTROL WIRING TO BE INSTALLED IN CONDUIT.
NOTES:
2. PROVIDE NEMA 3R ENCLOSURES ON EXTERIOR MOUNTED DEVICES.
FIRE ALARM
CONTROL PANEL
PROVIDE SIGNAL EXPANDER POWER
SUPPLY AS REQUIRED. LOCATE
EQUIPMENT IN ELECTRICAL ROOM.
PROVIDE SPARE CAPACITY
TO ADD (2) SIGNAL DEVICES
(TYP. OF EACH SIGNAL CIRCUIT)
ADDRESSABLE RELAY FOR CONTROL. PROVIDE ONE AT
EACH AIR HANDLING UNIT SUPPLY AND RETURN FAN
MOTOR CONTROLLER, AT EACH FIRE/SMOKE DAMPERS,
AND AT EACH DOOR HOLDER RELEASE DEVICE.
TYPICAL HVAC UNIT
MOTOR CONTROLLER
PROVIDE CONTROL
WIRING IN CONDUIT AS
REQUIRED
TO OTHER DEVICES
SEE FLOOR PLANS
FIRE ALARM SYSTEM NOTES
1. FIRE ALARM SYSTEM AND ALL WORK SHALL MEET ALL APPLICABLE FEDERAL,
STATE, AND LOCAL CODES AND REQUIREMENTS, AND THE LOCAL FIRE
MARSHAL REQUIREMENTS FOR HIGH RISE BUILDINGS. PROVIDE ADDITIONAL
EQUIPMENT AND DEVICES AS REQUIRED TO COMPLY WITH CODES AND
REQUIREMENTS.
2. FIRE ALARM CONTROL PANEL WORK SHALL INCLUDE ALL PANELS, MODULES,
EQUIPMENT, WIRING, AND PROGRAMMING NECESSARY TO SUPPORT THE
DEVICES AS INDICATED.
3. REFER TO FLOOR PLANS FOR SYSTEM DEVICE LOCATIONS AND QUANTITIES.
4. FIRE ALARM SYSTEM VENDOR SHALL DETERMINE NOTIFICATION APPLIANCE
AUDIBLE AND VISUAL DEVICE OUTPUT LEVELS AND REQUIREMENTS FOR EACH
SPACE IN WHICH APPLICANCES ARE INSTALLED. PROVIDE ADDITIONAL
APPLIANCES AS REQUIRED.
5. LABEL ALL FIRE ALARM DEVICES AS REQUIRED BY CODE REQUIREMENTS AND
DIRECTED BY THE OWNER WITH EXTERNAL TAGS AND LABELS ON DEVICE
BASES.
6. WHERE PREMITTED BY APPLICABLE CODES, FIRE ALARM SYSTEM WIRING MAY
BE INSTALLED WITHOUT CONDUIT OR OTHER RACEWAY SYSTEMS. WHERE
INSTALLATION WITHOUT CONDUIT OR OTHER RACEWAYS SYSTEMS IS NOT
PERMITTED, INSTALL ALL FIRE ALARM SYSTEM WIRING IN CONDUIT OR OTHER
RACEWAYS SYSTEMS.
SPEAKER ZONES
1. ZONE THE BUILDING PER LOCAL CODES.
M SD HD
SV
DD
R
AR
PROVIDE SPARE CAPACITY
TO ADD 20% FUTURE DEVICES
ON EACH INITIATION LOOP
REMOTE INDICATOR
STATION FOR DUCT
DETECTOR
FS TS AR
DR
FIRE ALARM
POWER
TYPICAL DOOR
HOLD/RELEASE
DEVICE
AR
TYPICAL
FIRE/SMOKE
DAMPER
RI
120V
SD
TYPICAL SMOKE DETECTOR
WITH SOUNDER BASE
FIRE ALARM
ANNUNCIATOR
PANEL
(2) TELECOM/INFORMATION
CABLES TO TELECOM MDF FOR
OUTPUT TO MONITOR SERVICE
(1) TELECOM/INFORMATION CABLE
TO TELECOM IDF FOR TELEPHONE
INPUT FOR EMERGENCY
ANNOUNCEMENTS
PROVIDE ADDRESSABLE FIRE
ALARM CONTROL PANEL
TO POWER AS SHOWN
ON DRAWINGS
120V
FACPSD
PROVIDE CONTROL
WIRING IN CONDUIT AS
REQUIRED (TYPICAL)
(2) TELEPHONE CABLE
NOTES:
1. CONTRACTOR SHALL VERIFY AND COORDINATE ALL ASPECTS OF
ELEVATOR AND ELECTRICAL EQUIPMENT INSTALLTION WITH
ELEVATOR SUPPLIER.
2. PROVIDE ALL CONTROL WIRING IN CONDUIT AS REQUIRED.
3. PROVIDE ADDITIONAL SUPPORT STRUCTURE AS REQUIRED.
4. REFER TO FLOOR PLANS FOR DEVICE QUANTITIES.
TELE.
OUTLET
PROVIDE CONTROL
WIRING IN CONDUIT AS
REQUIRED (TYPICAL)
INDUSTRIAL
LIGHT FIXTURE(S)
ELEVATOR
HOISTWAY
RECEPTACLE
GFCI
ELEVATOR FEEDER
CAB
CONTROL
CAB LIGHTS
BY DIVISION 26
BY ELEVATOR
MANUFACTURER /
INSTALLER
PANEL PER
PLANS
TOP OF
HOISTWAY
IN ELEVATOR
EQUIPMENT
ROOM
FIRST
FLOOR
LOBBY
TO 208/120V
PANEL
DEDICATED
CIRCUIT
ELEVATOR
RECEPTACLE
GFCI
MACHINE ROOM
LIGHT
FIXTURE(S)
FUSIBLE DISCONNECT
IN ELEVATOR MACHINE
ROOM
TO 208/120V
PANEL PER
PLANS
SD SD SD SD SD
THIRD
FLOOR
LOBBY
FOURTH
FLOOR
LOBBY
SECOND
FLOOR
LOBBY
AR
AR
TOP OF
HOISTWAY
DESIGNATED
LEVEL
AR
ALTERNATE
LEVEL
120V, 1P ELEVATOR
CAB FEEDER
HD
TOP OF
HOISTWAY
IN ELEVATOR
EQUIPMENT
ROOM
HD
120V
(ELEVATOR EQUIPMENT
ROOM RECEPTACLE
CIRCUIT) FUSIBLE
DISCONNECT
IN ELEVATOR
MACHINE ROOM
SMOKE
VENT
CONTACTOR FOR ELEVATOR
SHUT DOWN. PROVIDE
RESET SWITCH IN COVER.
IN ELEVATOR
EQUIPMENT
ROOM
AR
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/15/2020 3:07:36 PME701
ELECTRICAL
SCHEMATICS
2019.00780
7.14.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
NO SCALE1EXTERIOR LIGHTING CONTROL SYSTEM SCHEMATIC
NO SCALE2FIRE ALARM SYSTEM SCHEMATIC
NO SCALE3TYPICAL ELEVATOR SCHEMATIC
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20