HomeMy WebLinkAboutE701 - ELECTRICAL SCHEMATICSCONTROLLED CIRCUITS TO EXTERIOR LIGHTING FIXTURES PROVIDE (1) 12-POLE MECHANICALLY HELD CONTACTORS RATED 20A, 600V TO CONTROL EXTERIOR LIGHTING AND SIGN CIRCUITS CIRCUITS AS SHOWN ON DRAWINGS CLOSE C OPEN CR 120V CONTROL CIRCUIT. CONNECT TO SPARE CIRCUIT BREAKER IN NEARBY 120V PANEL OR AS INDICATED. H-O-A SWITCH MOUNTED IN ENCLOSURE COVER PHOTOCELL MOUNTED ON ROOF TWO-WIRE CONTROL RELAY EMERGENCY LIGHTING INVERTER AS INDICATED ON DRAWINGS 2-CIRCUIT PROGRAMMABLE 24-HOUR TIME SWITCH LIKE INTERMATIC #ET1100C WITH BATTERY BACKUP OFF AUTOHAND TC TS 1. ALL CONTROL WIRING TO BE INSTALLED IN CONDUIT. NOTES: 2. PROVIDE NEMA 3R ENCLOSURES ON EXTERIOR MOUNTED DEVICES. FIRE ALARM CONTROL PANEL PROVIDE SIGNAL EXPANDER POWER SUPPLY AS REQUIRED. LOCATE EQUIPMENT IN ELECTRICAL ROOM. PROVIDE SPARE CAPACITY TO ADD (2) SIGNAL DEVICES (TYP. OF EACH SIGNAL CIRCUIT) ADDRESSABLE RELAY FOR CONTROL. PROVIDE ONE AT EACH AIR HANDLING UNIT SUPPLY AND RETURN FAN MOTOR CONTROLLER, AT EACH FIRE/SMOKE DAMPERS, AND AT EACH DOOR HOLDER RELEASE DEVICE. TYPICAL HVAC UNIT MOTOR CONTROLLER PROVIDE CONTROL WIRING IN CONDUIT AS REQUIRED TO OTHER DEVICES SEE FLOOR PLANS FIRE ALARM SYSTEM NOTES 1. FIRE ALARM SYSTEM AND ALL WORK SHALL MEET ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES AND REQUIREMENTS, AND THE LOCAL FIRE MARSHAL REQUIREMENTS FOR HIGH RISE BUILDINGS. PROVIDE ADDITIONAL EQUIPMENT AND DEVICES AS REQUIRED TO COMPLY WITH CODES AND REQUIREMENTS. 2. FIRE ALARM CONTROL PANEL WORK SHALL INCLUDE ALL PANELS, MODULES, EQUIPMENT, WIRING, AND PROGRAMMING NECESSARY TO SUPPORT THE DEVICES AS INDICATED. 3. REFER TO FLOOR PLANS FOR SYSTEM DEVICE LOCATIONS AND QUANTITIES. 4. FIRE ALARM SYSTEM VENDOR SHALL DETERMINE NOTIFICATION APPLIANCE AUDIBLE AND VISUAL DEVICE OUTPUT LEVELS AND REQUIREMENTS FOR EACH SPACE IN WHICH APPLICANCES ARE INSTALLED. PROVIDE ADDITIONAL APPLIANCES AS REQUIRED. 5. LABEL ALL FIRE ALARM DEVICES AS REQUIRED BY CODE REQUIREMENTS AND DIRECTED BY THE OWNER WITH EXTERNAL TAGS AND LABELS ON DEVICE BASES. 6. WHERE PREMITTED BY APPLICABLE CODES, FIRE ALARM SYSTEM WIRING MAY BE INSTALLED WITHOUT CONDUIT OR OTHER RACEWAY SYSTEMS. WHERE INSTALLATION WITHOUT CONDUIT OR OTHER RACEWAYS SYSTEMS IS NOT PERMITTED, INSTALL ALL FIRE ALARM SYSTEM WIRING IN CONDUIT OR OTHER RACEWAYS SYSTEMS. SPEAKER ZONES 1. ZONE THE BUILDING PER LOCAL CODES. M SD HD SV DD R AR PROVIDE SPARE CAPACITY TO ADD 20% FUTURE DEVICES ON EACH INITIATION LOOP REMOTE INDICATOR STATION FOR DUCT DETECTOR FS TS AR DR FIRE ALARM POWER TYPICAL DOOR HOLD/RELEASE DEVICE AR TYPICAL FIRE/SMOKE DAMPER RI 120V SD TYPICAL SMOKE DETECTOR WITH SOUNDER BASE FIRE ALARM ANNUNCIATOR PANEL (2) TELECOM/INFORMATION CABLES TO TELECOM MDF FOR OUTPUT TO MONITOR SERVICE (1) TELECOM/INFORMATION CABLE TO TELECOM IDF FOR TELEPHONE INPUT FOR EMERGENCY ANNOUNCEMENTS PROVIDE ADDRESSABLE FIRE ALARM CONTROL PANEL TO POWER AS SHOWN ON DRAWINGS 120V FACPSD PROVIDE CONTROL WIRING IN CONDUIT AS REQUIRED (TYPICAL) (2) TELEPHONE CABLE NOTES: 1. CONTRACTOR SHALL VERIFY AND COORDINATE ALL ASPECTS OF ELEVATOR AND ELECTRICAL EQUIPMENT INSTALLTION WITH ELEVATOR SUPPLIER. 2. PROVIDE ALL CONTROL WIRING IN CONDUIT AS REQUIRED. 3. PROVIDE ADDITIONAL SUPPORT STRUCTURE AS REQUIRED. 4. REFER TO FLOOR PLANS FOR DEVICE QUANTITIES. TELE. OUTLET PROVIDE CONTROL WIRING IN CONDUIT AS REQUIRED (TYPICAL) INDUSTRIAL LIGHT FIXTURE(S) ELEVATOR HOISTWAY RECEPTACLE GFCI ELEVATOR FEEDER CAB CONTROL CAB LIGHTS BY DIVISION 26 BY ELEVATOR MANUFACTURER / INSTALLER PANEL PER PLANS TOP OF HOISTWAY IN ELEVATOR EQUIPMENT ROOM FIRST FLOOR LOBBY TO 208/120V PANEL DEDICATED CIRCUIT ELEVATOR RECEPTACLE GFCI MACHINE ROOM LIGHT FIXTURE(S) FUSIBLE DISCONNECT IN ELEVATOR MACHINE ROOM TO 208/120V PANEL PER PLANS SD SD SD SD SD THIRD FLOOR LOBBY FOURTH FLOOR LOBBY SECOND FLOOR LOBBY AR AR TOP OF HOISTWAY DESIGNATED LEVEL AR ALTERNATE LEVEL 120V, 1P ELEVATOR CAB FEEDER HD TOP OF HOISTWAY IN ELEVATOR EQUIPMENT ROOM HD 120V (ELEVATOR EQUIPMENT ROOM RECEPTACLE CIRCUIT) FUSIBLE DISCONNECT IN ELEVATOR MACHINE ROOM SMOKE VENT CONTACTOR FOR ELEVATOR SHUT DOWN. PROVIDE RESET SWITCH IN COVER. IN ELEVATOR EQUIPMENT ROOM AR Project Number CERTIFIED BY ISSUANCE INDEX DATE: PROJECT PHASE:7/15/2020 3:07:36 PME701 ELECTRICAL SCHEMATICS 2019.00780 7.14.2020 CONSTRUCTION DOCUMENTS CARMEL MEDICAL ARTS PAVILION 12174 N. Meridian Street Carmel, Indiana 46032 NO SCALE1EXTERIOR LIGHTING CONTROL SYSTEM SCHEMATIC NO SCALE2FIRE ALARM SYSTEM SCHEMATIC NO SCALE3TYPICAL ELEVATOR SCHEMATIC REVISION SCHEDULE NO. DESCRIPTION DATE 09/17/20