HomeMy WebLinkAboutE801 - ELECTRICAL DETAILSSUPPORT CONNECTED TO STRUCTURE ABOVE
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
LAY-IN CEILING
LAY-IN CEILING
JUNCTION BOX
W/#12 WIRE (6' MAX.)
FLEXIBLE CONDUIT
LAY-IN CEILING
LAY-IN CEILING
SEISMIC
CLIP
EXIT
STEEL BEAM OR JOIST
ROD SUPPORT OR
SAFETY WIRE
- 1 PER FIXTURE
CEILING
TIE WIRE
LAY-IN CEILING
GRID TEE
ADJUSTABLE SUPPORT
BRACKET -2 PER
FIXTURE (ATTACHED TO
CEILING GRID TEE)
LAY-IN CEILING TILE
JUNCTION
BOXES
HIGH VOLTAGE
WIRING
LOW VOLTAGE
WIRING
OCCUPANCY
SENSOR POWER
PACK / RELAY PACK
NOTE:
DO NOT INSTALL POWER PACK CLOSER
THAN 6-12 INCHES FROM SENSOR.
WALL SWITCH
OCCUPANCY SENSOR
HOT BLK
WHTNEUTRAL
(UNSWITCHED)
RED 120VLOADBAS / HVAC CONTROL
INTERFACE WIRING BY
TERMPERATURE
CONTROL
CONTRACTOR
120V-10A SPDT PILOT
CONTROL RELAY PACK LIKE
FUNCTIONAL DEVICES
#RIB2421C
EMERGENCY CIRCUIT
(HOT+NEUTRAL) WHERE INDICATED
3/4"x10' COPPER-
CLAD GROUND ROD
ANCHOR BOLTS
AS FURNISHED
BY FIXTURE MFR.
(6)#5 VERTICAL
#3 TIES AT 12"
PROVIDE 1/4" PREFORMED
JOINT FILLER WHEN SLAB
ABUTS POLE BASE (TYP.)
EXOTHERMIC
WELDED
CONNECTION
#6 BARE COPPER
BOLT PATTERN PER TEMPLATE AS
FURNISHED BY FIXTURE MANUFACTURER
POLE STANDARD
BASE PLATE COVER
HAND HOLE
GROUND LUG
CONCRETE BASE
CONDUIT
1/8" SLOPE
FINISH GRADE
NOTE: FOR PAVED PARKING AREA
1/2"C
30" MIN.
D 6".30" MIN.L3/4"x10' COPPER-CLAD ROD
ANCHOR BOLTS
AS FURNISHED
BY FIXTURE MFR.
(6)#5 VERTICAL
#3 TIES AT 12"
PROVIDE 1/4" PREFORMED JOINT
FILLER WHEN SLAB ABUTS POLE BASE (TYP.)
CADWELD
#6 BARE COPPER
BOLT PATTERN PER TEMPLATE AS
FURNISHED BY FIXTURE MANUFACTURERPOLE STANDARD
BASE PLATE COVER
HAND HOLE
GROUND LUG
CONCRETE BASE
CONDUIT
1/8" SLOPE
FINISH GRADE
1/2"C
D 30" MIN.6".2".LDIMENSIONS
D
2'-0"
1'-6"
3'-0"
2'-6"
L
5'-0"
4'-6"12'-0"
20'-0"
Height
Pole
7'-0"
6'-0"30'-0"
40'-0"
NOTES:
1.VERIFY ANCHOR BOLT LOCATIONS
WITH MANUFACTURER'S TEMPLATE
PRIOR TO BASE CONSTRUCTION
CADDY SCREW
GUN BRACKET
NOTE: FOR METAL STUD WALL CONSTRUCTION ONLY.
4" SQUARE BOX
METAL STUDS
CONDUIT
BOX MOUNTING
BRACKET
ROOF CURB
ROOFTOP UNIT
CONDULET FILLED
WITH SEALANT
LIQUID TIGHT
CONDUIT (TYPICAL)
PITCH POCKET OR
ROOF MEMBRANE BOOT
WIRE WAY
2 1-3/8"21-3/8 "14-3/4"12 -7/8 "24"
12"
12"14 -3/4 "12-7/8"4"X8" KNOCKOUT
ONE CENTERED IN
EACH WALL
CR
FIRE ALARM CONNECTION TO
RELEASE OF DOOR AS REQUIRED
CONTROL WIRING
PROVIDED BY OTHERS
DOOR SECURITY ACCESS CONTROL UNIT
LOCATED AS DIRECTED BY OWNER
TYPICAL DOOR
SWITCH IN
DOOR FRAME
DOOR
TYPICAL
MAGNETIC LOCK OR
ELECTRIC STRIKE
3/4"C TO ABOVE CORRIDOR
ACCESSIBLE CEILING
NOTE:
FOR A DOUBLE DOOR PROVIDE AN ADDITIONAL DOOR
SWITCH AND ELECTRIC HINGE OR ELECTRIC POWER
TRANSFER CABLE ROUGH-IN AND CONNECTION
TYPICAL CARD READER.
INSTALL AT +46" A.F.F.
PROVIDE TWO-GANG
BOX WITH ONE-GANG
PLASTER RING. REX
AUTOMATIC DOOR OPERATOR
IF DOOR IS EQUIPPED.
INTERLOCK DOOR SECURITY
SYSTEM TO OPERATE DOOR
AS REQUIRED
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/15/2020 3:07:41 PME801
ELECTRICAL DETAILS
2019.00780
7.14.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
NO SCALE1LAY IN LIGHT FIXTURE DETAIL
NO SCALE2LAY-IN CEILING EXIT SIGN MOUNTING DETAIL
NO SCALE3TYPICAL OCCUPANCY SENSOR POWER/RELAY PACK DETAIL
NO SCALE4TYPICAL WALL SWITCH OCCUPANCY SENSOR SCHEMATIC
NO SCALE5POLE BASE DETAIL -RASIED BASE
NO SCALE6POLE BASE DETAIL -FLUSH BASE.
NO SCALE7POLE BASE DIMENSIONS
NO SCALE8WALL BOX INSTALLATION DETAIL
NO SCALE9ROOFTOP UNIT INSTALLATION DETAIL
NO SCALE10TYPICAL HANDHOLE DETAIL
NO SCALE11DOOR SECURITY ACCESS CONTROL INSTALLATION DETAIL
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20