HomeMy WebLinkAboutM-5012X DI A.STR AIGHT
DUCTAT INLETSUPPORT TERMINAL
UNIT WITH DUCT STRAP
AT ALL FOUR CORNERS
CONTROL ENCLOSURE,
MAINTAIN 2'-0" CLEARANCE
MEDIUM OR
HIGH PRESSURE
PRIMARY SUPPLY
DUCTWORK
TRANSITION TO
INLET SIZE TYPICAL VAV
TERMINAL UNIT
FASTEN WITH TWO
SCREWS MINIMUM
REHEAT COIL ON DISCHARGE,
REFER TO PIPING DIAGRAM
SLIP AND DRIVE
CONNECTION
FINISHED FLOOR AS SCHEDULED
LIGHTING CONTROLS, INTERCOM, PULL STATION,
THERMOSTAT
DOOR FRAME/WALL OPENING WHERE OCCURS
LOCATE DEVICES 6" FROM DOOR/WALL
OPENING, OR AS DIMENSIONED. WHERE
NOT DIMENSIONED, LOCATE AT NEAREST
STUD FROM LOCATION SHOWN ON FLOOR
PLAN
6"UON44" UONSPECIFICATION FOR JOINING AND ATTACHING FLEXIBLE DUCT
DUCTWORK
SPIN-IN
FITTING
W/VOLUME
DAMPER
FLEXIBLE DUCT-MAXIMUM 6'-0"
LENGTH AND NO MORE THAN TWO (2)
90° BENDS.
SQUARE TO ROUND FITTING
CEILINGAIR TERMINAL
A. METALLIC FLEXIBLE DUCT SHALL BE ATTACHED
USING A MINIMUM OF THREE #8 SHEET METAL
SCREWS EQUALLY SPACED AROUND THE DUCT'S
CIRCUMFERENCE; DUCTS LARGER THAN 12"Ø
SHALL HAVE A MINIMUM OF FIVE #8 SHEET METAL
SCREWS. SCREWS SHALL BE LOCATED AT LEAST
8" FROM THE DUCT END.
B. NON-METALLIC FLEXIBLE DUCT SHALL BE
SECURED TO THE SLEEVE OR COLLAR USING A
DRAW BAND. IF THE DUCT COLLAR EXCEEDS 12"Ø,
THE DRAW BAND MUST BE POSITIONED BEHIND A
BEAD ON THE METAL COLLAR.
C. INSULATION AND VAPOR BARRIERS PRESENT ON
FACTORY-FABRICATED DUCTS SHALL BE FITTED
OVER THE CORE CONNECTION AND SHALL BE
SUPPLEMENTALLY SECURED WITH A DRAW BAND.
D. FLEXIBLE DUCT SEALING SHALL BE A CLASS "B"
FOR LOW PRESSURE DUCT.
UPBLAST CENTRIFUGAL EXHAUST FAN
BIRDSCREEN
NEMA 3R DISCONNECT FACTORY
WIRED FROM MOTOR TO DISCONNECT
THROUGH THE BREATHER TUBE
LIQUID TIGHT FLEXIBLE CONDUIT
(BY OTHERS)
PREFABRICATED ROOF CURB
ROOF
AUTO BACKDRAFT DAMPER
SEE PLANS FOR DUCT SIZE
PROVIDE HOLE
THRU ROOF
SEE ARCH PLANS
FOR ROOF
CONSTRUCTION
TYPICAL
PACKAGED
ROOFTOP UNIT
PLUG
VALVE
UNION
PIPE REDUCER
PRESSURE
REDUCING
VALVE
DIRT
LEG
PIPING BRANCH
REFER TO PLANS
FOR SIZE
PIPE
SUPPORT
(TYPICAL)
INSTALL GROMMET
AT PENETRATION THRU
CABINET
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:7/14/2020 12:53:49 PMM-501
MECHANICAL
DETAILS
2019.01176
07/14/2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL ARTS
PAVILION -FIRST FLOOR
TENANT BUILD-OUTS
12174 N. Meridian Street
Carmel, Indiana 46032
12" = 1'-0"
VAV WITH REHEAT TERMINAL UNIT DETAIL 1
1/2" = 1'-0"
TYPICAL THERMOSTAT MOUNTING DETAIL2
12" = 1'-0"
TYPICAL AIR TERMINAL INSTALLATION DETAIL3
12" = 1'-0"
TYPICAL EXHAUST FAN (UPBLAST) DETAIL4
12" = 1'-0"
ROOFTOP UNIT GAS PIPING DETAIL5
REVISION SCHEDULE
NO. DESCRIPTION DATE
09/17/20