HomeMy WebLinkAboutE001FIRE PROTECTION SYMBOLS FIRE ALARM CONTROL PANEL FACP HORN/STROBE ALARM COMBO WEATHER PROOF FS FLOW SWITCH TS PIV TAMPER SWITCH S SMOKE DETECTOR DUCT SMOKE DETECTOR S SD MAGNETIC LOCK WITH KEY PAD H KP ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS 1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS OF DESIGN. BIDDERS SHALL LIST ALL SUBSTITUTIONS ON BID. ENGINEER RESERVES THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS. 2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME AND PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM FOUND NOT EQUAL TO THE SPECIFIED ITEM AS DESIGNED. 3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR THE USE OF ALL TRADES DURING CONSTRUCTION AS REQUIRED BY THE GENERAL CONTRACTOR. REMOVE ALL TEMPORARY EQUIPMENT AS PERMANENT SERVICES BECOME AVAILABLE. 4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE EXACT QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY FOR ALL REQUIRED PERMITS. 5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, AND CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE INSTALLATION OF SYSTEMS REQUIRED IN FULL CONFORMITY WITH APPLICABLE CODES AND ORDINANCES. THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2009 INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE, COUNTY, CODES AND ORDINANCE AND INDIANA AMENDMENTS. COORDINATE WORK WITH OTHER TRADES. ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS RESULTING FROM ANY NON COMPLIANCE WITH CODE REQUIREMENTS 7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND LISTED BY U.L. MATERIALS AND EQUIPMENT SHALL CONFORM WITH THE LATEST ISSUES OF APPLICABLE TECHNICAL STANDARDS. 8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND POWER AS REQUIRED. VERIFY ALL VOLTAGES AND PHASE REQUIREMENTS WITH MECHANICAL CONTRACTOR'S EQUIPMENT PRIOR TO PERFORMING ANY WORK. 9. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING A BID. NO EXTRAS WILL BE ENTERTAINED FOR CONTRACTORS FAILURE TO IDENTIFY EXISTING CONDITIONS AND ADJUST AS REQUIRED TO MEET DESIGN INTENT. 10. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE COMPRESSION TYPE AND MADE TO ENSURE POSITIVE GROUNDING CONTINUITY. MAKE CONNECTIONS TO EQUIPMENT SUBJECT TO VIBRATION WITH 18 INCHES OF FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT FITTINGS. PROVIDE FOR SUPPORT AND SECURING OF ALL CONDUIT AND EQUIPMENT. CONNECTIONS TO LIGHTING FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE CONDUIT FROM A BOX WITHIN TWO (2) FEET OF THE FIXTURE. SPLICE ALL WIRES ONLY IN ACCESSIBLE BOXES. ALL FIXTURE WHIPS TO BE FLEXIBLE METAL CONDUIT 1/2" MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH INSULATED THROATS. WHIPS SHALL NOT EXCEED 6'. FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING STRUCTURE. 11. ALL LIGHTING AND BRANCH CIRCUIT WIRING SHALL BE SOLID COPPER MINIMUM SIZE #12 AWG. 600V INSULATION, 75 DEG. C., TYPE THW OR THWN, NOT LESS THAN #12 AWG. ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE EITHER STRANDED COPPER CONDUCTOR OR ASTM B800 ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN #8 AWG FOR ALUMINUM. EACH WITH MINIMUM 600V THW OR THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE SIZED IN ACCORDANCE WITH NEC 310.15. 12. EXPOSED WIRING SHALL BE IN EMT RACEWAY. EXTERIOR WIRING SHALL BE IN CONDUIT. CONCEALED WIRING SHALL BE IN EMT OR METAL CLAD CABLE WHERE ALLOWED BY CODE. 13. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE. 14. ALL CABLE SHALL BE NEW WIRE OF RECENT MANUFACTURE AND IN ACCORDANCE WITH THE LATEST STANDARDS OF IPCEA AND NEMA AS A MINIMUM 15. PANELBOARDS SHALL BE A DEAD-LOCK SAFETY TYPE, SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED WITH THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED. TERMINALS FOR FEEDER CONDUCTORS TO THE PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED. TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS SHALL BE OF THE FULL COMPRESSION TYPE.THE PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA STANDARD PUBLICATION NO. PB-1971 AND U.L. STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT RUST-RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER TUMBLER-TYPE LOCKS WITH CATCHES AND SPRING LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE CONCEALED WHEN THE DOORS ARE CLOSED. DOORS SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME AND TYPE WRITTEN CARD WITH A CLEAR PLASTIC COVERING SHALL BE PROVIDED ON THE INSIDE OF THE DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT LEAST 1/4" HIGH X 3" LONG OR EQUIVALENT FOR EACH CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL FINISHED STEEL WITH RUST-INHIBITING PRIMER FACTORY FINISHED ENAMEL PAINT. 16. CIRCUIT BREAKERS SHALL BE QUICK-MAKE, QUICK-BREAK, THERMAL-MAGNETIC, TRIP INDICATING AND HAVE COMMON TRIP ON ALL MULTI-POLE BREAKERS. BRANCH CIRCUIT BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT REPEATED ARCING SHORTS RESULTING FROM FRAYED APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT ON. 17. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT CURRENT AVAILABLE AT THE PANELS. ALL PANELS/BREAKERS/SWITCHES ARE TO BE BRACED TO EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND CIRCUIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING FAULT CURRENT.MANUFACTURER SHALL PROVIDE ALL REQUIRED FAULT CURRENT AND ARC-FLASH LABELING PER 110.16 AND 110.24. 18. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT EXCEED 1750 WATTS. VOLTAGE DROP OF BRANCH CIRCUITS SHALL NOT EXCEED 3% AND FEEDER CIRCUITS SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER TIGHT. FIRE STOP WHERE REQUIRED. 19. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE NAMEPLATES FOR ALL ELECTRICAL PANELS, DISCONNECTS, TRANSFORMERS AND MOTORS OVER 1 HP. FURNISH TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY ALL ELECTRICAL CIRCUITS BOTH NEW AND EXISTING. 20. VERIFY EXACT LOCATION, COLOR AND HEIGHTS OF ALL OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT WITH OWNER'S REPRESENTATIVE PRIOR TO START OF WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS, HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS, DISTRIBUTION PANELS ETC. AS REQUIRED. 21. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS INDICATED ON THE DRAWINGS. 22. DEVICES: A. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18" ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL BE 42" A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE ON THE DRAWINGS. B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FINAL LOCATIONS AND COLORS OF ALL DEVICES WITH OWNER. C. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING SURFACES AND FREE FROM ALL OBSTRUCTIONS. REWORKING OF EQUIPMENT INSTALLED IMPROPERLY SHALL BE AT THE CONTRACTOR'S EXPENSE. D. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1 CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS. E. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15 AMPERES, SINGLE POLE, 125/277V. MULTI-POLE OR SPECIAL SWITCHING SHALL BE AS NOTED ON THE DRAWINGS. F. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES, DUPLEX, GROUNDED HUBBELL COMMERCIAL SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE AS NOTED ON THE DRAWINGS. G. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL RECEPTACLES AND SWITCHES. 23. LIGHTING FIXTURES: A. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE BETWEEN LIGHTING FIXTURE PER FLOOR PLANS. B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FIXTURE QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER FOR ALL FIXTURES. C. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP HOLDERS, REFLECTORS, BALLASTS, STARTERS AND WIRING. 24. INSTALLATION OF LIGHTING FIXTURES: A. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS AS INDICATED, IN ACCORDANCE WITH FIXTURE MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC, NECA'S "STANDARD OF INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT LIGHTING FIXTURES FULFILL REQUIREMENTS. B. COORDINATE WITH OTHER ELECTRICAL WORK AS APPROPRIATE TO PROPERLY INTERFACE INSTALLATION OF INTERIOR LIGHTING FIXTURES WITH OTHER WORK. C. E.C. TO FASTEN FIXTURES SECURELY DIRECTLY TO BUILDING STRUCTURAL SYSTEM. LIGHT TROFFERS SHALL BE SUPPORTED AT EACH CORNER OF FIXTURE BY WIRES OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID. ATTACH EARTHQUAKE CLIPS TO GRID AS RECOMMENDED BY LIGHT MANUFACTURER. USE SCREWS IF REQUIRED BY MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE ABOVE. LIGHTS SHALL NOT BE SUPPORTED IN ANYWAY BY LAY-IN CEILING. D. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL OBSTRUCTIONS. CLEAN ALL LIGHTING EQUIPMENT AFTER LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS COMPLETE. REPAIR ANY FIXTURES DAMAGED DURING CONSTRUCTIONS. E. PROVIDE NECESSARY MOUNTING FRAMES, SUPPORTS AND RELATED ITEMS REQUIRED TO PROPERLY INSTALL FIXTURES. SUPPORT FIXTURES INDEPENDENTLY OF PIPING AND DUCTWORK. MAKE MODIFICATIONS TO THE STRUCTURE AS REQUIRED TO INSTALL FIXTURES. ANY MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR THE STRUCTURAL INTEGRITY OF THE BUILDING. 25. EQUIPMENT CONNECTIONS A. ALL DEVICES AND EQUIPMENT SHALL BE SOLIDLY GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS. B. ALL SOLID CONDUCTOR WIRES MAY BE TERMINATED UNDER SCREW HEADS. STRANDED WIRES MAY BE TERMINATED BY USING PUSH-IN CLAMP TYPE CONNECTORS FURNISHED WITH DEVICES OR TERMINATED WITH COMPRESSION TYPE TERMINAL LUGS. SET SCREW TYPE TERMINATIONS ARE NOT PERMITTED. C. NO MOTORS ARE TO BE SUPPLIED UNDER THIS CONTRACT UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BY THIS CONTRACTOR. THE CONTRACTOR SHALL FURNISH ALL STARTERS FOR ALL MOTORS REQUIRING A STARTER. THE CONTRACTOR SHALL CONNECT ALL POWER EQUIPMENT IF & WHERE SHOWN ON PLANS UNLESS OTHER-WISE SPECIFIED & ASSURE OWNER THE MOTORS ARE IN GOOD RUNNING ORDER. D. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET MEANS OF DISCONNECT PER N.E.C. FOR ALL HARD WIRED EQUIPMENT. 26. LOW VOLTAGE A. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN CONSTRUCTION OR IN EXPOSED OPEN AREAS SHALL BE FREE RUN. CONTRACTOR SHALL INSTALL 3/4" CONDUIT (MINIMUM) FROM EACH LOW VOLTAGE ROUGH-IN LOCATION TO ACCESSIBLE CEILING SPACE, LOW VOLTAGE WIRE TRAY OR HANGERS AND THEN TO MDF, HEAD-IN, PBX PUNCH DOWN, CONTROLLER ETC. B. E.C. SHALL COORDINATE WITH LOCAL PHONE AND CABLE PROVIDER AS CHOSEN BY OWNER AND PROVIDE RACEWAYS FOR BRINGING IN SERVICES AS REQUIRED. C. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATED IN PLENUMS. D. ALL DATA CABLE SHALL BE CAT 5E UNLESS OTHER WISE NOTED. TERMINATE, LABEL AND TEST ALL WIRING. 27. CLOSE OUT A. PROVIDE MANUFACTURERS OPERATION AND MAINTENANCE MANUALS AND PROVIDE AS BUILT DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER SELECTED PERSONNEL AS REQUESTED AND PROVIDE WARRANTY INFORMATION FOR ALL MANUFACTURERS WARRANTED EQUIPMENT AMPS MECHANICAL CONTRACTOR ELECTRICAL ABBREVIATIONS MANUFACTURER MOUNTING HEIGHT MFR MH MINIMUM MOTOR OPERATED DAMPER MLO MIN MOD MOCP MOUNTED NOT IN CONTRACT PLUMBING CONTRACTOR ON CENTER NOT TO SCALE MTD NIC PC NTS OC COMPANYCO RUNNING LOAD AMPSRLA ELECTRIC CONTRACTOR DOWN DRAWING(S) ELECTRICAL DISTRIBUTION CENTER EQUIPMENT EC DN DWG(S) EQUIP EDC EWC ETR FULL LOAD AMPS MAXIMUM FLA MAX MAIN BREAKERMB MC CONTRACTORCONTR EXISTING TO REMAIN ELECTRIC WATER COOLER MIMIMUM CIRCUIT AMPS MCA MAXIMUM OVER CURRENT PROTECTION MAIN LUG ONLY EMERGENCY EM POUNDS PER SQUARE INCHPSI REVOLUTIONS PER MINUTE RPM HORSE POWER HP GENERAL CONTRACTOR GC ABOVE FINISHED FLOOR AFF EX EXISTING FLOW SWITCHFS A VOLTSV UNLESS OTHERWISE NOTEDUON LIGHTING PANELBOARD SCHEDULE ABBREVIATIONS POWER NON-SEASONAL PN MOTOR SUMMER MOTOR NON-SEASONAL MOTOR NON-SEASONAL INTERMITTENT MOTOR WINTER MS MN MNI MW POWER WINTER PW KITCHENKT RECEPTACLER L ELECTRICAL SYMBOLS GFI SPECIAL EQUIPMENT COORDINATE W/SUPPLIER JUNCTION BOX DISCONNECT OUTLET - 4 WAY MOTOR OUTLET - GROUND FAULT INTERRUPT OUTLET - DUPLEX RECESSED DOWN LIGHT LIGHT FIXTURE - ON NIGHT LIGHT CIRCUIT LIGHT FIXTURE - LAYIN LIGHT FIXTURE - SURFACE EXIT SIGNAGE WALL MOUNTED STRIP LIGHT SUSPENDED STRIP LIGHT LOW VOLTAGE TWO LINE LOW VOLTAGE ONE LINE ANALOG PHONE LINE WIRELESS ACCESS POINT OUTLET - 220 EXIT SIGNAGE WITH EMERGENCY HEADS LIGHT FIXTURE - WALL SCONCE LIGHT FIXTURE - PENDANT LIGHT FIXTURE - FREE HANGING J FLOOR OUTLET WITH POWER, DATA AND PHONE D 3 SWITCH SWITCH WITH DIMMER SWITCH - 3 WAY OSSWITCH WITH OCCUPANCY SENSOR OS CEILING MOUNTED OCCUPANCY SENSOR 4SWITCH - 4 WAY GFI OUTLET - GROUND FAULT INTERRUPT WEATHERPROOF WP LOW VOLTAGE # LINES # TIME CLOCK TC PHOTO CELL PC PANEL DESIGATION X: XX,XX,XX CIRCUIT BREAKER NUMBERS WAP EMERGENCY LIGHTING UNIT EMERGENCY EXIT EGRESS LIGHT LIGHT FIXTURE - TRACK LIGHT FIXTURE - UNDER COUNTER LIGHT FIXTURE - RECESSED DOWN LIGHT LIGHT FIXTURE - VANITY LIGHT OUTLET - DUPLEX WITH USB J DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 E001 WP 09/21/20