10200395
12" MIN.
METAL ROOF DECK
MECH. DUCT
INSULATION THICKNESS.
AS REQUIRED TO MATCH
TREATED WOOD BLOCKING
EXHAUST FAN
PROVIDE (2) LAG
SCREWS PER SIDE
WITH NEOPRENE
WASHSERS
SEAL FAN TO CURB
WITH NEOPRENE
GASKET AIR TIGHT
GRAVITY
BDD
3X3 ANGLE REF.
STRUCTURAL
PLANS.
(2) 3 X 3 X 5/16 ANGLES
FACE TO FACE
BOLTED TO ROOF JOIST
BY M.C.
FAN MOUNTING BRACKETS,
BOLTS, WASHERS AND SAFETY
CABLE BY FAN MANUFACTURER.
BOLT TO C CHANNEL OR TO
BOTTOM OF GIRDER.
SCALE : NONE
BIG ASS FAN MOUNTING DETAILA
SECTION AA
A
A
DUCT LESS SPLIT
TRAP SUCTION LINE
EVERY 10' UP RISER
NOT TO SCALE
MINI SPLIT INSTALLATION DETAILD
PATE PORTAL ROOF CURB
TYPICAL ALL LINE SETS. INSULATE
AND SEAL WATER TIGHT.
INVERTED SUCTION LINE TRAP.
SLOPE LINE BACK TO
COMPRESSOR.
DISCONNECT BY E.C.
AIR COOLED
CONDENSING
UNIT
WALL
WALL
BIRD SCREEN
CAULK INTERIOR AND EXTERIOR
PERIMETER WEATHER TIGHT WITH
SILICON CAULKING.
LOUVER WITH KYNAR FINISH TO
MATCH BLDG. COLOR
EXTERIOR
1"X1"X1/8" STEEL ANGLE. SCREW TO
LOUVER SLEEVE 6" O.C. # 10
SCREWS AND ANCHORED TO
MASONRY WALL 12" O.C. WITH 1/4"
MASONRY ANCHORS. TYPICAL TOP,
BOTTOM AND SIDES.
SCALE : NONE
EXHAUST FAN DETAIL B SCALE : NONE
WALL LOUVER DETAILC
GALVANIZED
EQUIPMENT
RAIL BY MC
1/2" HOSE TO OPEN SITE
INVERTED TEE IN PVC DRAIN LINE
BY MC ROUTE 3/4 SCH 40 PVC
LINE TO HUB/FLOOR DRAIN
PROVIDED BY P.C. AT MINIMUM
1/4" PER FT SUPPORT MIN. 5' OC.
MINI-WHITE TANK MINI SPLIT
CONDENSATE PUMP WITH HIGH
LEVEL CUT OUT. WIRE TO IDU PER
MANUFACTURES INSTRUCTIONS
MINIMUM 48"
PRIOR TO ROUGH-IN COORDINATE CLEARANCES OF BLADES WITH
ALL TRADES AND EQUIPMENT SUPPLIERS.
M003
OPTIONAL SUSPENDED CEILING INSTALLATION OF SUNTUBE HEATER
STANDARD REFLECTOR
12"
MINIMUM
SHIELD
NOTCH AS REQUIRED AROUND THE
REFLECTOR SUPPORT BRACKET
H
EXTENSION REFLECTOR
4'-0" LONG X 8", 12", OR 16" WIDE
SUSPENDED CEILING FRAME
2 FT. ALUMINUM LOUVER
SCALE : NONE
INFRARED HEATER SUSPENDED CEILING INSTALLATIONE
PARTICULAR CONSIDERATION MUST BE GIVEN TO CLEARANCES TO COMBUSTIBLES IN THIS TYPE OF INSTALLATION.
SINCE THE STANDARD REFLECTOR IS USED, THE CLEARANCE TO COMBUSTIBLES WILL BE THE SAME AS INDICATED IN
THE "SUMMARY OF SPECIFICATIONS" IN THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTION MANUAL.
VERIFY THAT THE CEILING PANELS ADJACENT TO EACH SIDE OF THE HEATER ARE ARE NOT COMBUSTIBLE OR THAT
THEY ARE MADE OF CLASS A MATERIALS. VERIFY THE INSTALLATION IS ACCEPTABLE TO LOCAL AUTHORITIES. IN
ADDITION, TO PROVIDE ADEQUATE COMFORT LEVELS, REFER TO "HEATER LOCATION" IN THE INSTALLATION, OPERATION
AND MAINTENANCE INSTRUCTION MANUAL TO IDENTIFY MINIMUM MOUNTING HEIGHT.
THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS IN THIS EQUIPMENT, OR COVER EVERY POSSIBLE
SITUATION TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD PROBLEMS ARISE
THAT ARE NOT COVERED SUFFICIENTLY IN THESE INSTRUCTIONS, THE PURCHASER IS ADVISED TO CONTACT THE
ENGINEERING DEPARTMENT AT SOLARONICS, INC. FOR FURTHER INFORMATION.
THE SUNTUBE LOW-INTENSITY GAS INFRARED HEATER CAN BE INSTALLED OVER SUSPENDED CEILINGS WITH AN
ALUMINUM LOUVER DIRECTLY BELOW THE HEATER. THE ALUMINUM LOUVER IS A 2 FOOT WIDE X 4 FOOT LONG BY 1/2"
THICK, NON-FLAMMABLE , 1/2" X 1/2" OPEN-GRID CELL PATTERN CONSTRUCTED OF 0.015" ALUMINUM WITH A MILL FINISH.
NEVER USE REGULAR CEILING TILES DIRECTLY BELOW THE HEATER SINCE IT WOULD CREATE AN UNSAFE CONDITION.
THE HEATER IS INSTALLED IN A NORMAL FASHION (AS DESCRIBED IN THE INSTRUCTION MANUAL) WITH THE TUBE
SUSPENDED OVER THE LOUVERS FROM A MINIMUM HEIGHT OF 4.000" TO A MAXIMUM HEIGHT OF 14.375" (DISTANCE H).
CALCULATE DISTANCE "H" BETWEEN THE BOTTOM OF THE HEAT EXCHANGER TUBE TO THE TOP OF THE LOUVER TO
DETERMINE THE SIZE OF THE EXTENSION REFLECTORS REQUIRED FROM THE FOLLOWING TABLE:
THE EXTENSION REFLECTORS ARE AVAILABLE IN STANDARD 4 FOOT SECTIONS AND ARE LAID ALONGSIDE THE
STANDARD REFLECTORS. IT MAY BE NECESSARY TO CUT NOTCHES FOR CLEARANCE AROUND THE REFLECTOR
SUPPORT BRACKETS.
A SHIELD,IS PLACED OVER THE SUSPENDED CEILING FRAME MEMBER WHICH PASS DIRECTLY UNDERNEATH THE
HEATER.
FOR YOUR SAFETY, GLOVES ARE TO BE WORN WHEN HANDLING THE ALUMINUM LOUVERS TO PROTECT THE HANDS
FROM SHARP EDGES. ALLOW A 12 INCH MINIMUM CLEARANCE FROM THE TOP AND SIDES OF THE BURNER.