HomeMy WebLinkAboutNAPLETON KIA OF CARMEL-ELEC-20190708FIRE PROTECTION SYMBOLS FIRE ALARM CONTROL PANEL FACP HORN/STROBE ALARM COMBO WEATHER PROOF FS FLOW SWITCH TS PIV TAMPER SWITCH S SMOKE DETECTOR DUCT SMOKE DETECTOR S SD MAGNETIC LOCK WITH KEY PAD H KP ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS 1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS OF DESIGN. BIDDERS SHALL LIST ALL SUBSTITUTIONS ON BID. ENGINEER RESERVES THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS. 2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME AND PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM FOUND NOT EQUAL TO THE SPECIFIED ITEM AS DESIGNED. 3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR THE USE OF ALL TRADES DURING CONSTRUCTION AS REQUIRED BY THE GENERAL CONTRACTOR. REMOVE ALL TEMPORARY EQUIPMENT AS PERMANENT SERVICES BECOME AVAILABLE. 4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE EXACT QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY FOR ALL REQUIRED PERMITS. 5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL REQUIRED LABOR, MATERIALS, EQUIPMENT, AND CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE INSTALLATION OF SYSTEMS REQUIRED IN FULL CONFORMITY WITH APPLICABLE CODES AND ORDINANCES. THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2009 INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE, COUNTY, CODES AND ORDINANCE AND INDIANA AMENDMENTS. COORDINATE WORK WITH OTHER TRADES. ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS RESULTING FROM ANY NON COMPLIANCE WITH CODE REQUIREMENTS 7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND LISTED BY U.L. MATERIALS AND EQUIPMENT SHALL CONFORM WITH THE LATEST ISSUES OF APPLICABLE TECHNICAL STANDARDS. 8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND POWER AS REQUIRED. VERIFY ALL VOLTAGES AND PHASE REQUIREMENTS WITH MECHANICAL CONTRACTOR'S EQUIPMENT PRIOR TO PERFORMING ANY WORK. 9. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING A BID. NO EXTRAS WILL BE ENTERTAINED FOR CONTRACTORS FAILURE TO IDENTIFY EXISTING CONDITIONS AND ADJUST AS REQUIRED TO MEET DESIGN INTENT. 10. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE COMPRESSION TYPE AND MADE TO ENSURE POSITIVE GROUNDING CONTINUITY. MAKE CONNECTIONS TO EQUIPMENT SUBJECT TO VIBRATION WITH 18 INCHES OF FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT FITTINGS. PROVIDE FOR SUPPORT AND SECURING OF ALL CONDUIT AND EQUIPMENT. CONNECTIONS TO LIGHTING FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE CONDUIT FROM A BOX WITHIN TWO (2) FEET OF THE FIXTURE. SPLICE ALL WIRES ONLY IN ACCESSIBLE BOXES. ALL FIXTURE WHIPS TO BE FLEXIBLE METAL CONDUIT 1/2" MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH INSULATED THROATS. WHIPS SHALL NOT EXCEED 6'. FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING STRUCTURE. 11. ALL LIGHTING AND BRANCH CIRCUIT WIRING SHALL BE SOLID COPPER MINIMUM SIZE #12 AWG. 600V INSULATION, 75 DEG. C., TYPE THW OR THWN, NOT LESS THAN #12 AWG. ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE EITHER STRANDED COPPER CONDUCTOR OR ASTM B800 ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN #8 AWG FOR ALUMINUM. EACH WITH MINIMUM 600V THW OR THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE SIZED IN ACCORDANCE WITH NEC 310.15. 12. EXPOSED WIRING SHALL BE IN EMT RACEWAY. EXTERIOR WIRING SHALL BE IN CONDUIT. CONCEALED WIRING SHALL BE IN EMT OR METAL CLAD CABLE WHERE ALLOWED BY CODE. 13. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE. 14. ALL CABLE SHALL BE NEW WIRE OF RECENT MANUFACTURE AND IN ACCORDANCE WITH THE LATEST STANDARDS OF IPCEA AND NEMA AS A MINIMUM 15. PANELBOARDS SHALL BE A DEAD-LOCK SAFETY TYPE, SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED WITH THERMAL-MAGNETIC MOLDED CASE CIRCUIT BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED. TERMINALS FOR FEEDER CONDUCTORS TO THE PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED. TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS SHALL BE OF THE FULL COMPRESSION TYPE.THE PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA STANDARD PUBLICATION NO. PB-1971 AND U.L. STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT RUST-RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER TUMBLER-TYPE LOCKS WITH CATCHES AND SPRING LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE CONCEALED WHEN THE DOORS ARE CLOSED. DOORS SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME AND TYPE WRITTEN CARD WITH A CLEAR PLASTIC COVERING SHALL BE PROVIDED ON THE INSIDE OF THE DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT LEAST 1/4" HIGH X 3" LONG OR EQUIVALENT FOR EACH CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL FINISHED STEEL WITH RUST-INHIBITING PRIMER FACTORY FINISHED ENAMEL PAINT. 16. CIRCUIT BREAKERS SHALL BE QUICK-MAKE, QUICK-BREAK, THERMAL-MAGNETIC, TRIP INDICATING AND HAVE COMMON TRIP ON ALL MULTI-POLE BREAKERS. BRANCH CIRCUIT BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT REPEATED ARCING SHORTS RESULTING FROM FRAYED APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT ON. 17. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT CURRENT AVAILABLE AT THE PANELS. ALL PANELS/BREAKERS/SWITCHES ARE TO BE BRACED TO EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND CIRCUIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING FAULT CURRENT.MANUFACTURER SHALL PROVIDE ALL REQUIRED FAULT CURRENT AND ARC-FLASH LABELING PER 110.16 AND 110.24. 18. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT EXCEED 1750 WATTS. VOLTAGE DROP OF BRANCH CIRCUITS SHALL NOT EXCEED 3% AND FEEDER CIRCUITS SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER TIGHT. FIRE STOP WHERE REQUIRED. 19. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE NAMEPLATES FOR ALL ELECTRICAL PANELS, DISCONNECTS, TRANSFORMERS AND MOTORS OVER 1 HP. FURNISH TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY ALL ELECTRICAL CIRCUITS BOTH NEW AND EXISTING. 20. VERIFY EXACT LOCATION, COLOR AND HEIGHTS OF ALL OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT WITH OWNER'S REPRESENTATIVE PRIOR TO START OF WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS, HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS, DISTRIBUTION PANELS ETC. AS REQUIRED. 21. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS INDICATED ON THE DRAWINGS. 22. DEVICES: A. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18" ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL BE 42" A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE ON THE DRAWINGS. B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FINAL LOCATIONS AND COLORS OF ALL DEVICES WITH OWNER. C. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING SURFACES AND FREE FROM ALL OBSTRUCTIONS. REWORKING OF EQUIPMENT INSTALLED IMPROPERLY SHALL BE AT THE CONTRACTOR'S EXPENSE. D. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1 CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS. E. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15 AMPERES, SINGLE POLE, 125/277V. MULTI-POLE OR SPECIAL SWITCHING SHALL BE AS NOTED ON THE DRAWINGS. F. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES, DUPLEX, GROUNDED HUBBELL COMMERCIAL SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE AS NOTED ON THE DRAWINGS. G. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL RECEPTACLES AND SWITCHES. 23. LIGHTING FIXTURES: A. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE BETWEEN LIGHTING FIXTURE PER FLOOR PLANS. B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FIXTURE QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER FOR ALL FIXTURES. C. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP HOLDERS, REFLECTORS, BALLASTS, STARTERS AND WIRING. 24. INSTALLATION OF LIGHTING FIXTURES: A. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS AS INDICATED, IN ACCORDANCE WITH FIXTURE MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE REQUIREMENTS OF NEC, NECA'S "STANDARD OF INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED INDUSTRY PRACTICES TO ENSURE THAT LIGHTING FIXTURES FULFILL REQUIREMENTS. B. COORDINATE WITH OTHER ELECTRICAL WORK AS APPROPRIATE TO PROPERLY INTERFACE INSTALLATION OF INTERIOR LIGHTING FIXTURES WITH OTHER WORK. C. E.C. TO FASTEN FIXTURES SECURELY DIRECTLY TO BUILDING STRUCTURAL SYSTEM. LIGHT TROFFERS SHALL BE SUPPORTED AT EACH CORNER OF FIXTURE BY WIRES OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID. ATTACH EARTHQUAKE CLIPS TO GRID AS RECOMMENDED BY LIGHT MANUFACTURER. USE SCREWS IF REQUIRED BY MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE ABOVE. LIGHTS SHALL NOT BE SUPPORTED IN ANYWAY BY LAY-IN CEILING. D. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL OBSTRUCTIONS. CLEAN ALL LIGHTING EQUIPMENT AFTER LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS COMPLETE. REPAIR ANY FIXTURES DAMAGED DURING CONSTRUCTIONS. E. PROVIDE NECESSARY MOUNTING FRAMES, SUPPORTS AND RELATED ITEMS REQUIRED TO PROPERLY INSTALL FIXTURES. SUPPORT FIXTURES INDEPENDENTLY OF PIPING AND DUCTWORK. MAKE MODIFICATIONS TO THE STRUCTURE AS REQUIRED TO INSTALL FIXTURES. ANY MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR THE STRUCTURAL INTEGRITY OF THE BUILDING. 25. EQUIPMENT CONNECTIONS A. ALL DEVICES AND EQUIPMENT SHALL BE SOLIDLY GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS. B. ALL SOLID CONDUCTOR WIRES MAY BE TERMINATED UNDER SCREW HEADS. STRANDED WIRES MAY BE TERMINATED BY USING PUSH-IN CLAMP TYPE CONNECTORS FURNISHED WITH DEVICES OR TERMINATED WITH COMPRESSION TYPE TERMINAL LUGS. SET SCREW TYPE TERMINATIONS ARE NOT PERMITTED. C. NO MOTORS ARE TO BE SUPPLIED UNDER THIS CONTRACT UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BY THIS CONTRACTOR. THE CONTRACTOR SHALL FURNISH ALL STARTERS FOR ALL MOTORS REQUIRING A STARTER. THE CONTRACTOR SHALL CONNECT ALL POWER EQUIPMENT IF & WHERE SHOWN ON PLANS UNLESS OTHER-WISE SPECIFIED & ASSURE OWNER THE MOTORS ARE IN GOOD RUNNING ORDER. D. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET MEANS OF DISCONNECT PER N.E.C. FOR ALL HARD WIRED EQUIPMENT. 26. LOW VOLTAGE A. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN CONSTRUCTION OR IN EXPOSED OPEN AREAS SHALL BE FREE RUN. CONTRACTOR SHALL INSTALL 3/4" CONDUIT (MINIMUM) FROM EACH LOW VOLTAGE ROUGH-IN LOCATION TO ACCESSIBLE CEILING SPACE, LOW VOLTAGE WIRE TRAY OR HANGERS AND THEN TO MDF, HEAD-IN, PBX PUNCH DOWN, CONTROLLER ETC. B. E.C. SHALL COORDINATE WITH LOCAL PHONE AND CABLE PROVIDER AS CHOSEN BY OWNER AND PROVIDE RACEWAYS FOR BRINGING IN SERVICES AS REQUIRED. C. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATED IN PLENUMS. D. ALL DATA CABLE SHALL BE CAT 5E UNLESS OTHER WISE NOTED. TERMINATE, LABEL AND TEST ALL WIRING. 27. CLOSE OUT A. PROVIDE MANUFACTURERS OPERATION AND MAINTENANCE MANUALS AND PROVIDE AS BUILT DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER SELECTED PERSONNEL AS REQUESTED AND PROVIDE WARRANTY INFORMATION FOR ALL MANUFACTURERS WARRANTED EQUIPMENT AMPS MECHANICAL CONTRACTOR ELECTRICAL ABBREVIATIONS MANUFACTURER MOUNTING HEIGHT MFR MH MINIMUM MOTOR OPERATED DAMPER MLO MIN MOD MOCP MOUNTED NOT IN CONTRACT PLUMBING CONTRACTOR ON CENTER NOT TO SCALE MTD NIC PC NTS OC COMPANYCO RUNNING LOAD AMPSRLA ELECTRIC CONTRACTOR DOWN DRAWING(S) ELECTRICAL DISTRIBUTION CENTER EQUIPMENT EC DN DWG(S) EQUIP EDC EWC ETR FULL LOAD AMPS MAXIMUM FLA MAX MAIN BREAKERMB MC CONTRACTORCONTR EXISTING TO REMAIN ELECTRIC WATER COOLER MIMIMUM CIRCUIT AMPS MCA MAXIMUM OVER CURRENT PROTECTION MAIN LUG ONLY EMERGENCY EM POUNDS PER SQUARE INCHPSI REVOLUTIONS PER MINUTE RPM HORSE POWER HP GENERAL CONTRACTOR GC ABOVE FINISHED FLOOR AFF EX EXISTING FLOW SWITCHFS A VOLTSV UNLESS OTHERWISE NOTEDUON LIGHTING PANELBOARD SCHEDULE ABBREVIATIONS POWER NON-SEASONAL PN MOTOR SUMMER MOTOR NON-SEASONAL MOTOR NON-SEASONAL INTERMITTENT MOTOR WINTER MS MN MNI MW POWER WINTER PW KITCHENKT RECEPTACLER L ELECTRICAL SYMBOLS GFI SPECIAL EQUIPMENT COORDINATE W/SUPPLIER JUNCTION BOX DISCONNECT OUTLET - 4 WAY MOTOR OUTLET - GROUND FAULT INTERRUPT OUTLET - DUPLEX RECESSED DOWN LIGHT LIGHT FIXTURE - ON NIGHT LIGHT CIRCUIT LIGHT FIXTURE - LAYIN LIGHT FIXTURE - SURFACE EXIT SIGNAGE WALL MOUNTED STRIP LIGHT SUSPENDED STRIP LIGHT LOW VOLTAGE TWO LINE LOW VOLTAGE ONE LINE ANALOG PHONE LINE WIRELESS ACCESS POINT OUTLET - 220 EXIT SIGNAGE WITH EMERGENCY HEADS LIGHT FIXTURE - WALL SCONCE LIGHT FIXTURE - PENDANT LIGHT FIXTURE - FREE HANGING J FLOOR OUTLET WITH POWER, DATA AND PHONE D 3 SWITCH SWITCH WITH DIMMER SWITCH - 3 WAY OSSWITCH WITH OCCUPANCY SENSOR OS CEILING MOUNTED OCCUPANCY SENSOR 4SWITCH - 4 WAY GFI OUTLET - GROUND FAULT INTERRUPT WEATHERPROOF WP LOW VOLTAGE # LINES # TIME CLOCK TC PHOTO CELL PC PANEL DESIGATION X: XX,XX,XX CIRCUIT BREAKER NUMBERS WAP EMERGENCY LIGHTING UNIT EMERGENCY EXIT EGRESS LIGHT LIGHT FIXTURE - TRACK LIGHT FIXTURE - UNDER COUNTER LIGHT FIXTURE - RECESSED DOWN LIGHT LIGHT FIXTURE - VANITY LIGHT OUTLET - DUPLEX WITH USB J DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 E001 WP 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 HA PANEL PRIMARY CONDUITS UTILITY COMPANY PAD MTD. TRANSFORMER MAIN BUILDING GROUND BUS MAIN SWITCHBOARD ROOM. (ALL CONNECTIONS TO THIS BUSS SHALL BE EXOTHERMIC. GRADE BUILDING STEEL SUPPLY SIDE WATER METER GROUND BUS NOTE: CONNECTIONS SHALL BE FIRMLY BONDED TO NEUTRAL BUS, BUILDING STEEL, GROUNDING ROD AND WATER PIPE. METAL WATER PIPE WITHIN 5 FT. OF WATER SERVICE ENTRANCE TO BUILDING. PROVIDE BONDED JUMPER ACROSS WATER PIPE. #2/0 COPPER GROUND GROUND BUS FOR DATA CLOSETS. #2/0 COPPER #2/0 COPPER #2/0 COPPER NEUTRAL BUS #2/0 COPPER SUPPLEMENTAL GROUNDING ELECTRODE M GROUND PER NEC 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. GENERAL NOTES: F20 12 12 3/4" 1P,1N,1G, 2P,1G 2P,1N,1G, 3P,1G 3P,1N,1G EQUIP/SERV GROUND FEEDER/BRANCH CIRCUIT LABEL CONDUCTOR SIZE PER CONDUIT CONDUIT SIZE & QUANTITY FEEDER & BRANCH CIRCUIT SCHEDULE (COPPER) 3P,2N,1G 3P,3N,1G 3P,1N,2G PHASE & NEUTRAL 3/4" 3/4" 3/4" 3/4" 3/4" F30 10 10 3/4" 3/4" 3/4" 3/4" 3/4" 3/4" F40 8 10 3/4" 3/4" 1" 1" 1" 1" F50 6 10 1" 1" 1" 1-1/4" 1-1/4" 1" F60 4 10 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4" F70 4 8 1" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/4" F80 3 8 1" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/4" F90 2 8 1" 1-1/4" 1-1/2" 1-1/2" 2" 1-1/2" F100 1 8 1-1/4" 1-1/2" 1-1/2" 2" 2" 2" F110 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2" F125 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2" F150 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2" F175 2/0 6 1-1/2" 2" 2" 2-1/2" 2-1/2" 2" F200 3/0 6 1-1/2" 2" 2" 2-1/2" 3" 2-1/2" F225 4/0 4 2" 2" 2-1/2" 3" 2-1/2" F250 250 4 2" 2-1/2" 3" 3" 3" F300 350 4 2" 2-1/2" 3" 3-1/2" 3" F350 500 3 2-1/2" 3" 3-1/2" 4" 3-1/2" F400 3/0 3 (2) 1-1/2" (2) 2" (2) 2-1/2" (2) 2-1/2" (2) 2-1/2" F450 4/0 3 (2) 2" (2) 2" (2) 2-1/2" (2) 3" (2) 2-1/2" F500 250 2 (2) 2" (2) 2-1/2" (2) 3" (2) 3" (2) 3" F600 350 1 (2) 2-1/2" (2) 3" (2) 3" (2) 3-1/2" (2) 3" F200 F600 1 SCALE: NONE ELECTRICAL RISER DIAGRAM TRANSFORMER TXA 150 KVA, 480-120/208V 3Ø-4W T GROUND PER NEC B PANEL A PANEL F200 2 SCALE: NONE ELECTRICAL GROUNDING SYSTEM DIAGRAM F400 UTILITY METER AND CT. CABINET E002 GROUND PER NEC 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 E003 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 E004 LIGHT FIXTURE SCHEDULE -EXTERIOR MANUFACTURER TYPE VOLTAGE LAMPS MOUNTING DESCRIPTION A3-16 WALL A-16 390W LED 16' POLE277 A2-16 LSI-INDUSTRIES LSI-INDUSTRIES LSI-INDUSTRIES CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL W1 LSI-INDUSTRIES INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN D-16 16' POLELSI-INDUSTRIES DL138823 / FRONT ROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE DL134479 / FORWARD THROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE DL137144 / FORWARD THROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE DL135333 / TYPE 5 OPTIC / 390 WATT LED / 16' POLE DL119453 / WALL MOUNT LED / FORWARD THROW OPTIC 31,841 LUMENS 16' POLE 16' POLE 277 277 277 277 CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN 390W LED 45,192 LUMENS 390W LED 28,632 LUMENS 390W LED 43,144 LUMENS 76W LED 8,654 LUMENS CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL VERIFY COLORS WITH ARCHITECT - COLORS MAY VARY A2-16 A3-16 LIGHT FIXTURE SCHEDULE -INTERIOR VENDOR TYPE VOLTAGE LAMPS MOUNTING DESCRIPTION F9-4 F4 F13 F15 F17 32W LED CHAIN HUNG UE 120 OR 277 23.5 W LED DL123228 4' STRIP WITH DIFFUSE LENS / CHAIN KIT RECESSED / ADJ. F1 UE LAY-IN 34W LED PEC22 LED SS RAD NW UE DIMLSI INDUSTRIES "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM F9-8 65W LED CHAIN HUNG UE F18 EX1 EM1 EM2 4W LED WALL/CEILING CB2REM-RC RED LETTERUE BATTERY RED L.E.D. EXIT SIGN WITH BATTERY 2 X 3.3 W LED DL116029 RMR-16-LED UE LOW PROFILE WALL OR CEILING MOUNT EMERGENCY UNIT TWIN 3.3W LED MR LAMPS / 250 LUMENS PER LAMP 2 x 6.5 W LED F5000 LED6.5 90 SD TBAR NC UE REMOTE BATTERY BOX REQUIRED E.C. TO SETUP AND TEST PRIOR TO AHJ INSPECTION EM3 3.3 W LED WALL DL111891 DECORATIVE DIE CAST EXTERIOR EGRESS UE VERIFY COLOR TO MATCH BUILDING EXTERIOR (THIS CAN VARY) THIS IS A LINE VOLTAGE REMOTE EGRESS F8 120 OR 277 38W PER HEAD MESA GRID WITH 38W FIATO TRACK HEADS, 4000K / 25° BEAMINSIDE TROUGH LENGTHS VARY - SEE PLAN FOR LENGTHS F11 F12 F20 F21 F23 F14 RAF04OC 20L 40K MD DS10V RA4FOC SG PF 19W LED PENDANT UE 600-24-2-L3/830-UNV-SN / 3000K / 24" WALL SCONCE OVER VANITY COORDINATE INSTALL W/ CASEWORK CONTRACTOR F19 75W E26 PENDANT 120 BonBonne pendant with 75w 25 degree spot. SET 96" A.F.F. 5-8W EDISON LED PENDANT 120 VIVO FR37507 BNI / LED VINTAGE EDISON BULB SET 90" A.F.F. 40 X 1.5 W LED PENDANT 120 GLOBE LIGHTING CBL36 / 30" DIA. / BRUSHED NICKLE / 160 POUND WEIGHT SEE DETAIL FOR MOUNTING HEIGHTS UE 23W LED LAD6 20 LED 40 52 UE TR6R SF SPC C27RECESSED "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM UE 30W LED LAD6SQ 27 LED 40 52 UE TSQ6 SF SPC C27RECESSED "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM UE 135W LED DL125514 LED HIGHBAY / 18,600 LUMEN / CABLE KIT - SERVICE BAYSCABLE HUNG "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 900 LUMEN EM UE 40W LED CABLE HUNG 4' VAPOR TIGHT FOR TECH WRITERS OVER WORK STATION UE 7W / FT LED LXC2-LENGTH-LED-NW-24VDC / REMOTE TRANSFORMERSSURFACE MOUNTS IN SHOWROOM COVE FEATURE AND CEILING RECESSES AT ENTRANCE UE 45W LED RECESSED "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM F26 UE 35W LED DL120556 2X4 LED PANEL - BACK OF HOUSERECESSED "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM F19W UE 52W LED DL126534 4' VAPOR TIGHT / 10' CABLE IT- WASH BAYSCABLE HUNG "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 900 LUMEN EM F24 UE 45W LED RECESSED "EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM DIMMING TYPE 0-10V (1) Light Fixture Schedule Notes: 1. Not all fixtures or rooms will have dimming. See rooms 130, 202, and 206 for dimming in this facility. SPECTRUM LIGHTING 0-10V AMERLUX LIGHTING RECESSED TROUGH TRACK HEADS ELV PREMIERE LUMINAIRE N / A 0-10V 0-10V HINKLEY LIGHTING LINEA INC N / A N / A 120 OR 277 27W PER HEAD MESA GRID WITH 27W FIATO TRACK HEADS, 4000K / 40° BEAMINSIDE TROUGH LENGTHS VARY - SEE PLAN FOR LENGTHS AMERLUX LIGHTING RECESSED TROUGH ELV TRACK HEADS SHAPER LSI INDUSTRIES LSI INDUSTRIES 0-10V 0-10V N / A LSI INDUSTRIES 0-10V N / A N / A N / A LAD6 41 LED 40 35 UE TR6R SF SPC C27 LAD6 41 LED 40 52 UE TR6R SF SPC C27 0-10V 0-10V LSI INDUSTRIES LSI INDUSTRIES F25 UE 60W LED SGA6BX 60L 40K MD D010VOLT BH27 RA6FBX SG MFRECESSED AIM AT KIA LOGO - FOR CEILINGS OVER 14' AFF CBMC DESIGN-LIGHTING 0-10V 0-10V RECESSED WALL/CEILING N / A N / A N / A N / A CBMC DESIGN-LIGHTING CONCEALITE CBMC DESIGN-LIGHTING CBMC DESIGN-LIGHTING CBMC DESIGN-LIGHTING CBMC DESIGN-LIGHTING DL122820 8' STRIP WITH DIFFUSE LENS / CHAIN KIT CBMC DESIGN-LIGHTING CBMC DESIGN-LIGHTING CBMC DESIGN-LIGHTING DL125083 4' VAPOR TIGHT / 10' CABLE IT- @APPROX. 10' AFF SPECTRUM LIGHTING 09/21/20 A2-16 D-16 D-16 D-16 D-16 A-16 A-16 A-16 A-16 A-16 A-16 D-16 A-16 A-16 A-16 A-16 A-16 D-16 D-16 D-16 D-16 A-16 A-16 A-16 A-16 A2-16 A2-16 A3-16 A-16 A-16 HA:55,57 HA:55,57HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:55,57 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 HA:59,61 TUTILITY TRANSFORMER A:17 WP A:17 WP A:17 WP A:17 WP A:17 WP A:17 WP PYLON SIGN HA:46,48 WP DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 E050 1 SCALE: 1" = 30'-0" ELECTRICAL SITE PLAN CANT AROUND TOP 1" (8) #4 REBAR VERTICALY WITH #4 REBAR SPIRALED AT 6" O.C. AND (3) LAYERS OF #4 REBAR AT TOP AND BOTTOM OF BASE SPACED AT 2" O.C. MAINTAIN MINIMUM OF 3" FROM REBAR TO EDGE OF CONCRETE. ANCHOR BOLTS HAND HOLE 1. POLE SHALL BE CAPABLE OF WITH STANDING 130 MPH WIND GUSTS 2. CONCRETE SHALL BE MINIMUM 3000 PSI 3. MATCH ANCHOR BOLT PATTERN TO POLE MANUFACTURERS BASE PLATE #6 COPPER GROUND WIRE BONDED TO POLE. 5/8"X10' GROUND ROD WITH EXOTHERMIC CONNECTION TO #6 GROUNDING CONDUCTOR. NOTES 60" GRADE 3/4" PVC CONDUIT TO POLE GROUND. 24" 2 NOT TO SCALE LIGHT POLE DETAIL GENERAL NOTES: 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION OF WALL MOUNTED LIGHT FIXTURES. 3. SITE LIGHTING CONDUITS TO BE A MINIMUM OF 1" IN SIZE. 4. PROVIDE WEATHERPROOF GFI RECEPTACLE WITH WHILE IN USE COVER AT LIGHT POLES WHERE INDICATED ON PLAN. 5. DIFFERENT VOLTAGE SYSTEMS BRANCH CIRCUITRY SHALL BE RUN IN SEPARATE CONDUIT(S). 6. ALL LIGHT FIXTURES SHOWN ON THIS DRAWINGS SHALL BE FED FROM PANEL HA UNLESS NOTED OTHERWISE. 7. ALL BRANCH CIRCUITRY ON THIS DRAWINGS SHALL BE SIZE #8 MINIMUM. 8. ALL BRANCH CIRCUITRY SHALL HAVE DEDICATED GROUND WIRE SIZED PER NEC. 9. ALL EXTERIOR LIGHT FIXTURES SHALL BE TIME CLOCK CONTROLLED WITH PHOTOCELL OVERRIDE. ROUTE ASSOCIATED BRANCH CIRCUITRY THROUGH MULTI-POLE LIGHTING CONTACTOR. REFER TO SHEET E101 FOR ADDITIONAL INFORMATION. KEY NOTES: PROVIDE 120 VOLT CONNECTION TO POLE MOUNTED GFI RECEPTACLE PROVIDED BY LIGHT FIXTURE POLE MANUFACTURER. TYPICAL. PROVIDE CONNECTION TO PYLON SIGN PER SIGNAGE SHOP DRAWINGS. FIELD CONFIRM VOLTAGE REQUIREMENTS AND ADJUST THE SERVING BRANCH CIRCUITRY FROM EITHER PANEL HA OR A AS APPROPRIATE. CIRCUITRY SHALL BE CONTROLLED BY LIGHT VENDOR PROVIDED LIGHTING RELAY PANEL. 1 2 1 1 1 1 1 1 2 TOP OF ALL POLE BASES TO BE SAME ELEVATION AS MUCH AS POSSIBLE WITH MINIMUM DIMENSION ABOVE GRADE OR PAVING TO BE 2'-0". ALL "FRONT ROW" POLE BASES TO BE SAME ELEVATION ALWAYS 09/21/20 3 5 10 13 15 16 17 C E H J M O S 2 1 9 6 D B A F 18 T G L N 7 4 11 12 14 K 28 R P 31 31 31 31 31 31 31 31 31 31 31 31 33 31 31 B:10 31 31 B:10 31 31 B:10 31 31 31 31 31 B:10 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 31 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 31 31 31 31 31 31 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 33 B:11 B:11 B:11 B:11 33 33 33 33 33 33 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 353535 35 35 35 35 35 35 35 35 35 35 42 42 42 42 33 33 B:11 B:11 B:11 B:11 37 39 39 OS c d d d d d 31 c c c c c c c c c c 3b b b b b b b b b b b b b bb b b b b b b b b b b b b b b b b b b b b b b bb 3b b b b b Dlv D lv D lv D lv Dlv Dlv Dlv KK Dlv Dlv OS OS OS (zb) (zb)(zb) (zb) SEE ARCHITECTURAL COVE DETAIL FOR EXACT LENGTH. MOUNT FIXTURE OPPOSITE SIDE OF WALL. TILT 45 DEGREES. (zc) D lv KEY PLAN AB N INSTALL DIMMING CONTROL STATION SIMILAR TO GRAFIX EYE QS. SYSTEM SHALL HAVE 4 CHANNEL (ZONE) DIMMING CAPABILITY. ZONES SHALL BE DESIGNATED WITH A "zn" NOTATION. FIELD COORDINATE DIMMING SETTINGS WITH OWNER. CONTROL EXTERIOR LIGHT FIXTURE BY MULTI-POLE LIGHTING CONTACTOR IN MAIN ELECTRICAL ROOM. REFER TO SHEET E101 FOR ADDITIONAL INFORMATION. MOUNT LIGHT FIXTURE ABOVE AND CENTERED WITH MIRROR. VERIFY IN FIELD EXACT LOCATION OF LIGHT FIXTURE. REFER TO SHEET E200 FOR LIGHT FIXTURES IN THIS AREA. KEY NOTES: 1 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR LIGHTING PLAN - AREA 'A' E100 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. ALL BRANCH CIRCUITRY SHOWN ON THIS SHEET SHALL BE FED FROM BRANCH PANEL HA UNLESS NOTED OTHERWISE. 3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS, AND NIGHT LIGHTS SHALL HAVE UNSWITCHED CONDUCTORS. 4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS EMERGENCY ON ONLY. CONNECT TO NEAREST UNSWITCHED LIGHTING BRANCH CIRCUIT. GENERAL NOTES: 2 3 2 2 2 2 1 3 3 4 4 4 4 09/21/20 18 LC LIGHTING CONTACTOR PANEL 37 42424242424242 42 42 42 42 42 42 42 42 26 26 26 2626 26 2626 26 2626 26 2626 26 2626 26 2626 26 2626 26 26 26 26 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 32 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 3030 30 30 30 30 30 30 30 30 30 30 lv (zc) 3a 3a a a a a aa a a a aa a a a a a a a a a a a 3b 3c 3b3c b b b b b b b b b b b b b b b b b b b b c c c c c c c c c c c c c c c c c 3d 3d d c c c c c c d d d d d d d d d d d c TC PC A:19 KEY PLAN AB N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR LIGHTING PLAN - AREA 'B' E101 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. ALL BRANCH CIRCUITRY SHOWN ON THIS SHEET SHALL BE FED FROM BRANCH PANEL HA UNLESS NOTED OTHERWISE. 3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS, AND NIGHT LIGHTS SHALL HAVE UNSWITCHED CONDUCTORS. 4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS EMERGENCY ON ONLY. CONNECT TO NEAREST UNSWITCHED LIGHTING BRANCH CIRCUIT. GENERAL NOTES: CONTROL EXTERIOR LIGHT FIXTURE BY MULTI-POLE LIGHTING CONTACTOR IN MAIN ELECTRICAL ROOM. PROVIDE MULTI-POLE CONTACTOR(S) AS REQUIRED TO ALLOW FOR CONTROL OF EXTERIOR LIGHT FIXTURES. TIE IN CONTACTOR WITH TIME CLOCK. INSTALL PHOTOCELL ON NORTH FACE OF BUILDING AS HIGH AS POSSIBLE. TIE PHOTOCELL INTO TIME CLOCK. TIME CLOCK SHALL BE SIMILAR TO TORK #DG100A. FIELD COORDINATE TIME CLOCK SETTINGS WITH OWNER. KEY NOTES: 1 1111111 1 1 1 1 1 1 1 1 2 3 3 4 4 2 09/21/20 7 4 11 12 14 28 KEY PLAN AB N C E H J M O S B A F T G L N K R P 37 37 39 39 41 41 TV J TV a b c d 9 6 D IR-2 ECH-1 EWH-1 T T T T J WP BUILDING SIGN J WP BUILDING SIGN WP GALLERY LIGHT BOX B:4 B:2 B:6, B:8 DC DC DCDC DCDC DC DC DCDC DC DC DC 37 39 41 38 38 38 38 38 3030 30 32 32 32 34 34 32 32 36 36 36 15 15 15 1515 15 15 13 16 16 16 31 31 23 21 19 24 26 35 35 3535 35 2222 22 22 22 20 20 1818 18 18 31 2927 33 33 3333 HA:50 20 20 XX 30 28 32 13 13 13 13 17 17 19 19 10 +42" HA:50 12 +42" 14 +42" J 16 18 18 20 20 22 19 25 33 +48" +48" 36 30 23 70 70 e DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR POWER PLAN - AREA 'A' E102 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. E.C. SHALL PROVIDE ALL RACEWAYS AND CONDUCTORS FOR HVAC INTERLOCKS AND THERMOSTATS. PRIOR TO ROUGH-IN COORDINATE EXACT REQUIREMENTS WITH M.C. 3. PRIOR TO ROUGH-IN VERIFY ALL LOCATIONS AND MOUNTING HEIGHTS OF DEVICES WITH OWNER AND ADJUST AS DIRECTED. 4. E.C. SHALL PROVIDE J-BOX ROUGH-IN @ +48" AT EACH TSTAT LOCATION. ROUTE 3/4" CONDUIT FROM J-BOX ROUGH-IN TO MECHANICAL UNIT LOCATION. REFER TO MECHANICAL PLANS FOR UNIT AND T-STAT LOCATIONS. 5. LINEWORK SHOWN DASHED INDICATES CONDUIT RUN UNDER SLAB. 6. ALL BRANCH CIRCUITRY SHOWN ON THIS SHEET SHALL BE FED FROM BRANCH PANEL B UNLESS NOTED OTHERWISE. REFERENCE SHEET E200 FOR PANEL B LOCATION. GENERAL NOTES: ROUGH-IN DEVICE CONCEALED BEHIND ELECTRICAL WATER COOLER. FIELD VERIFY EXACT ROUGH-IN LOCATION. GARAGE DOOR WITH SIDE MOUNTED MOTOR. GARAGE DOOR OPERATOR. COORDINATE FINAL LOCATION WITH OWNER/ARCHITECT PRIOR TO INSTALLATION. PROPOSED ROUTING FOR UNDERGROUND CONDUITS TO FEED FLOOR MOUNTED TELEPHONE/DATA/RECEPTACLE OUTLETS. ROUTE CONDUIT TO NEAREST FULL HEIGHT WALL. COORDINATE WITH ARCHITECT. 1-1/2"C MIN. SIZE FOR DATA/TELEPHONE, 3/4" CONDUIT FOR POWER. PROVIDE (4) OVERHEAD DOOR CONTROLLER STATIONS, 1 FOR EACH OVERHEAD DOOR IN SERVICE RECEPTION, MOUNTED ON WALL BEHIND SERVICE WRITERS DESK. CONTROLLERS SHALL OPERATE IN TANDEM WITH LOCAL CONTROLLERS AT OVERHEAD DOORS. INSTALL DEVICES CONCEALED BEHIND TV. INSURE THAT DEVICE LOCATIONS DO NOT INTERFERE WITH TV MOUNTING HARDWARE. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS. ROUTE VESTIBULE BRANCH CIRCUITRY FROM UNDER SLAB UP THROUGH COLUMN INTO VESTIBULE CEILING SPACE. COORDINATE ALL STRUCTURAL COLUMN PENETRATIONS WITH STRUCTURAL CONTRACTOR. PROVIDE DEDICATED 120 VOLT BRANCH CIRCUIT TO SIGN THROUGH LIGHTING CONTACTOR. INSTALL JUNCTION BOX ON STRUCTURE ABOVE ABOVE ACCESSIBLE CEILING. EXTEND BRANCH CIRCUITRY THRU WALL FRAMING TO SIGN. REFER TO ARCHITECTURAL SHEETS FOR ADDITIONAL INFORMATION. ELECTRICAL CONTRACTOR SHALL MAKE FINAL CONNECTIONS. COORDINATE WITH SIGN VENDOR. TAMPER RESISTANT RECEPTACLE. PROVIDE SURFACE-MOUNTED WEATHERPROOF J-BOX WITH (2) DEDICATED 20 AMP CIRCUITS AS SHOWN. J-BOX TO BE MOUNTED 2'-0" OFF THE DEALER ENTRANCE. REFER TO ARCHITECTURAL SHEET A-411 FOR ADDITIONAL INFORMATION. FIELD VERIFY FLOOR BOX LOCATIONS WITH OWNER. PROVIDE FLUSH MOUNTED PULL BOXES WITHIN ACCESSIBLE FURNITURE BASE FOR FEED-THRU TO DEVICES MOUNTED IN FURNITURE. EXTEND WIRING AND CONDUITS FROM PULL BOXES TO DEVICES MOUNTED IN FURNITURE. FIELD COORDINATE INSTALLATION WITH FURNITURE SHOP DRAWINGS. PROVIDE CONNECTION TO ELECTRIC HAND DRYER PER MANUFACTURER'S WRITTEN INSTRUCTION. FIELD VERIFY EXACT ROUGH-IN LOCATION. PROVIDE CONNECTION TO DOOR OPERATOR PER MANUFACTURER'S WRITTEN INSTRUCTIONS. KEY NOTES: 1 2 3 4 5 6 7 8 9 10 11 10 8 8 12 12 13 13 13 1 22 3 3 4 4 4 4 4 4 5 4 4 4 6 7 9 11 11 1111 11 11 11 14 14 6 09/21/20 J A MDP HA T UTILITY METER/ CT CABINET 18 T RTU-7 7.5 TON IR-2 IR-2 IR-3 BAF-1BAF-1 CF-1T T CF-1 IR-3COMS UH-1 UH-1 IR-3 IR-3 IR-1 T T T EWH-1 BBS SC MS CO NOx BBS SC MS CO NOx OAOA J J J J J J J J J J WP BUILDING SIGN a b c d J J J J DC DC KP DC DCDC DC DC DC DC DCDC DC DC DC DCDCDC 13 TYPICAL TYPICAL 21 21 21 21 23 23 21 25,27 29,31 2,4 6,8 10,12 14,16 18,20 22,24 26,28 30,32 34,36 38,40 HA:67,69,71 HA:73,75,77 33 33 35 35 37 37 39 39 41 41 43 45 47 49 51 53 55 57 59 61,63 #10 65,67 #10 69,71 #10 73 75 56 58 60 60 44,46 #10 48,50 #10 52,54 #10 42 42 42 42 42 42 66 FACP S FS TS FS TS HS WP TS PIV 77,79 81,83 62 WP #10 #10 WP WP 64 WP 64 WP 66 66 66 68 68 HA:54 70 70 70 70 72 e KEY PLAN AB N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR POWER & SYSTEMS PLAN - AREA 'B' E103 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. E.C. SHALL PROVIDE ALL RACEWAYS AND CONDUCTORS FOR HVAC INTERLOCKS AND THERMOSTATS. PRIOR TO ROUGH-IN COORDINATE EXACT REQUIREMENTS WITH M.C. 3. ALL WORK RECEPTACLES IN SERVICE AND CLEAN-UP BAYS SHALL BE MOUNTED AT 48" AFF. 4. PRIOR TO ROUGH-IN VERIFY ALL LOCATIONS AND MOUNTING HEIGHTS OF DEVICES WITH OWNER AND ADJUST AS DIRECTED. 5. ALL ELECTRICAL DEVICES IN CAR WASH BAY SHALL BE RATED FOR WET LOCATION SERVICE. ALL ELECTRICAL COVERS AND SWITCH PLATES SHALL BE GALVANIZED STEEL FOR SHOP AND ASSOCIATED ROOMS. 6. E.C. SHALL PROVIDE J-BOX ROUGH-IN @ +48" AT EACH TSTAT LOCATION. ROUTE 3/4" CONDUIT FROM J-BOX ROUGH-IN TO MECHANICAL UNIT LOCATION. REFER TO MECHANICAL PLANS FOR UNIT AND T-STAT LOCATIONS. 7. LINEWORK SHOWN DASHED INDICATES CONDUIT RUN UNDER SLAB. 8. ALL BRANCH CIRCUITRY SHOWN ON THIS SHEET SHALL BE FED FROM BRANCH PANEL A UNLESS NOTED OTHERWISE. GENERAL NOTES: VARIABLE SPEED FAN CONTROLLER. PROVIDE 3/4" EMT CONDUIT FROM FAN TO CONTROLLER. COORDINATE CONDUCTOR REQUIREMENTS WITH M.C. CONTROLLER AND FAN BY M.C. CONDUIT AND CONDUCTORS BY E.C. MOUNT ALL DATA AND RECEPTACLES FOR WORK STATIONS AT 48" AFF. RECEPTACLES SHALL BE GFI TYPE. PRIOR TO ROUGH-IN VERIFY FINAL LOCATION AND HEIGHT WITH OWNER. TIRE CHANGER AND WHEEL BALANCER. COORDINATE EXACT REQUIREMENTS WITH OWNERS EQUIPMENT VENDOR. SERVICE FEEDER TO UTILITY TRANSFORMER. REFER TO CIVIL DRAWINGS FOR LOCATION OF UTILITY TRANSFORMER. REFER TO ELECTRICAL RISER DIAGRAM FOR ADDITIONAL INFORMATION. GARAGE DOOR WITH SIDE MOUNTED MOTOR. GARAGE DOOR OPERATOR. COORDINATE FINAL LOCATION WITH OWNER/ARCHITECT PRIOR TO INSTALLATION. IR HEATERS. PROVIDE EMT RACEWAYS AND LINE VOLTAGE CONDUCTORS BETWEEN BURNERS, DRAFT FANS AND IRTCP. PROVIDE LOW VOLTAGE RELAYS FOR IR TEMPERATURE CONTROL SYSTEM FOR SENSORS. COORDINATE WITH HVAC CONTRACTOR. SEE DETAIL #1 ON SHEET E002. PROVIDE (5) OVERHEAD DOOR CONTROLLER STATIONS, 1 FOR EACH OVERHEAD DOOR IN SERVICE RECEPTION. CONTROLLERS SHALL OPERATE IN TANDEM WITH LOCAL CONTROLLERS AT OVERHEAD DOORS. VEHICLE FRAME RACK: (1) 30 AMP DISCONNECT 208V, 1 PHASE MOUNTED ON WALL. PROVIDE CONDUIT ROUTED UNDERGROUND TO STUB-UP POINT IN RACK SUPPORT LOCATION. VERIFY EXACT REQUIREMENTS WITH LIFT PROVIDER. TYPICAL. PROVIDE DEDICATED 120 VOLT BRANCH CIRCUIT TO SIGN THROUGH LIGHTING CONTACTOR. INSTALL JUNCTION BOX ON STRUCTURE ABOVE ABOVE ACCESSIBLE CEILING. EXTEND BRANCH CIRCUITRY THRU WALL FRAMING TO SIGN. REFER TO ARCHITECTURAL SHEETS FOR ADDITIONAL INFORMATION. ELECTRICAL CONTRACTOR SHALL MAKE FINAL CONNECTIONS. COORDINATE WITH SIGN VENDOR. PROVIDE 208V 1PH CONNECTION FOR LIFT. FIELD VERIFY EXACT REQUIREMENTS WITH LIFT SUPPLIER. PROVIDE 208V 1PH CONNECTION FOR PRESSURE WASHER. FIELD VERIFY EXACT REQUIREMENTS WITH PRESSURE WASHER SUPPLIER. PROVIDE HOA MOTOR STARTER FOR CO EXTRACTION SYSTEM. FIELD VERIFY REQUIREMENTS AND LOCATION WITH OWNER'S CO EXTRACTION SYSTEM VENDOR. KEY NOTES: 1 2 3 4 5 6 7 8 9 10 11 12 13 1 1 2 2 3 3 3 4 55 5 5 5 5 5 5 6 6 66 6 6 5 7 7 7 7 7 7 9 9 9 9 9 9 9 9 9 1111 11 12 12 13 09/21/20 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 4141 41 41 41 41 41 41 41 41 41 41 41 41 39 39 39 3939 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39 39 42 4239 39 42 39 42 3939 39 39 39 39 39 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 39 39 39 39 39 39 39 37 37 37 37 37 37 37 37 37 39 39 39 39 3939 39 39 393939 37 39 39 39 39 39 39 39 3939 39 39 39 39 39 39 39 39 41 41 41 41 41 41 41 41 41 41 41 41 41 41 41 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 37 42 42 42 42 39 39 39 39 39 39 41 41 41 41 41 41 41 41 41 (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za)(za)(za) (za) (za) (za) (za) (za)(za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za)(za) (za) (za) (za) D lv D lv D lv (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (zc) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) OS OS OS KEY PLAN C D N 11 12 14 7 2 C E H J M O S B A T G L N F T B B:43 B:43 B:43 B:43 +42" +42" B:49 B:51 B:51 B:53 B:53 B:53 B:46 B:46 B:46 B:46 B:48 B:50 B:53 B:44 B:44 B:44 MS-1 B:46 B:45 B:47 +42" H J M O S T G L N 11 7 2 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 2 SCALE: 1/8" = 1'-0" MEZZANINE LEVEL LIGHTING PLAN - AREA 'C' 1 SCALE: 1/8" = 1'-0" POWER & SYSTEMS PLAN - AREA 'C' MEZZANINE LEVEL E200 LIGHTING DESIGNATED WITH A "zn" NOTATION SHALL BE CONTROLLED BY DIMMING CONTROL STATION LOCATED IN SALES MANAGER 104. CONTROL EXTERIOR LIGHT FIXTURE BY MULTI-POLE LIGHTING CONTACTOR IN MAIN ELECTRICAL ROOM. REFER TO SHEET E101 FOR ADDITIONAL INFORMATION. LIGHTS IN VEHICLE DELIVERY CENTER 125 CONTROLLED BY SWITCH IN THIS ROOM AS SHOWN ON SHEET E100. ROUTE (2) 3" CONDUITS FROM IT CLOSET TO TELECOMMUNICATIONS UTILITY TIE-IN POINT. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION. PROVIDE PULL STRING AND BUSHING FOR CONDUITS. 3 4" PLYWOOD WITH 2 COATS OF FIRE RETARDANT PAINT. PLYWOOD TO EXTEND FROM FLOOR TO CEILING. FURNISH AND INSTALL ALL NECESSARY POWER CONDUIT AND WIRING BETWEEN OUTDOOR UNIT AND INDOOR UNIT. KEY NOTES: 1 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. ALL BRANCH CIRCUITRY SHOWN ON THIS SHEET SHALL BE FED FROM BRANCH PANEL HA UNLESS NOTED OTHERWISE. 3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS, AND NIGHT LIGHTS SHALL HAVE UNSWITCHED CONDUCTORS. 4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS EMERGENCY ON ONLY. CONNECT TO NEAREST UNSWITCHED LIGHTING BRANCH CIRCUIT. GENERAL NOTES: 2 3 3 1 1 1 2 2 2 2 2 2 2 2 4 5 4 5 6 6 09/21/20 HB:43,45,47 #10 HB:49,51,53 #10 A:15 DRYER IWH HA:44 A:42 A:74 A:74 A:74 A:74 A:76 A:78 A:80 A:82 +42" +42" +42" KEY PLAN C D N 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 28 d d d d d d d d d d d d d d dd d d d d REFER TO SHEET E101 FOR SWITCHLEG 'd' SWITCH LOCATION(S) OS OS OS DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 102003951 SCALE: 1/8" = 1'-0" MEZZANINE LEVEL POWER AND SYSTEMS PLAN - AREA 'D' 2 SCALE: 1/8" = 1'-0" MEZZANINE LEVEL LIGHTING PLAN - AREA 'D' E201 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. E.C. SHALL PROVIDE ALL RACEWAYS AND CONDUCTORS FOR HVAC INTERLOCKS AND THERMOSTATS. PRIOR TO ROUGH-IN COORDINATE EXACT REQUIREMENTS WITH M.C. 3. PRIOR TO ROUGH-IN VERIFY ALL LOCATIONS AND MOUNTING HEIGHTS OF DEVICES WITH OWNER AND ADJUST AS DIRECTED. 4. E.C. SHALL PROVIDE J-BOX ROUGH-IN @ +48" AT EACH TSTAT LOCATION. ROUTE 3/4" CONDUIT FROM J-BOX ROUGH-IN TO MECHANICAL UNIT LOCATION. REFER TO MECHANICAL PLANS FOR UNIT AND T-STAT LOCATIONS. 5. LINEWORK SHOWN DASHED INDICATES CONDUIT RUN UNDER SLAB. GENERAL NOTES: 09/21/20 RTU-1 RTU-2 RTU-3 RTU-4 RTU-5 20 TON 5 TON 5 TON 8.5 TON 5 TON EF-6 RTU-7 7.5 TON RTU-6 5 TON IH-1 EF-1 EF-2 IH-2 EF-3 EF-7 EF-5 MS-1 EF-4 M M M EF-8 EF-9 S SD S SD S SD S SD S SD S SD WP WP WP WP WP WP WP WP HA:8,10,12 HA:2,4,6 HA:13,15,17 HA:7,9,11 HA:1,3,5 #6 HA:14,16,18 HA:20,22,24 #10 #10 3/4"C, 3#16 TO INDOOR MS-1 UNIT HA:25,27,29 WP B:1 B:3 WP B:5 WP B:5 WP A:1WP A:1 WP A:1 WP A:1 A:1 A:1 A:1 A:7 A:5 A:9 A:13 A:11 A:3 B:7,9 #10 E.C. SHALL PROVIDE COMBINATION MOTOR STARTERS WITH OL AND AUX CONTACTS FOR EF-1 AND EF-3. AUTO MODE SHALL BE WIRED TO CO DETECTOR. FANS SHALL START UPON CO ALARM. CO DETECTOR BY M.C. FURNISH AND INSTALL ALL NECESSARY POWER CONDUIT AND WIRING BETWEEN OUTDOOR UNIT AND INDOOR UNIT. ROUTE POWER THROUGH LINE VOLTAGE THERMOSTAT. REFER TO HVAC DRAWINGS FOR THERMOSTAT LOCATION. EF-2, EF-4, EF-5, EF-6, EF-7, & EF-8 SHALL RUN CONTINUOUSLY. E.C. SHALL INTERLOCK WIRING BETWEEN EXHAUST FAN AND MOTORIZED LOUVER. LOUVER SHALL OPEN WHEN FAN IS RUNNING. FAN AND DAMPER MOTOR SHALL BE PROVIDED BY M.C. KEY NOTES: 1 1. REFERENCE SHEET E-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES.DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEERD E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 3/32" = 1'-0" ROOF ELECTRICAL PLAN GENERAL NOTES: E300 2 3 4 1 1 2 3 4 4 4 4 4 4 5 5 5 5 09/21/20