HomeMy WebLinkAboutNAPLETON KIA OF CARMEL-ELEC-20190708FIRE PROTECTION SYMBOLS
FIRE ALARM CONTROL PANEL FACP
HORN/STROBE ALARM COMBO WEATHER PROOF
FS FLOW SWITCH
TS PIV TAMPER SWITCH
S SMOKE DETECTOR
DUCT SMOKE DETECTOR S SD
MAGNETIC LOCK WITH KEY PAD
H
KP
ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS ELECTRICAL SPECIFICATIONS
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE
BID IN STRICT ACCORDANCE WITH DESIGN BASIS
EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE
COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS
OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS
OF DESIGN. BIDDERS SHALL LIST ALL SUBSTITUTIONS ON
BID. ENGINEER RESERVES THE RIGHT TO REJECT
SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS
LISTED IN DESIGN BASIS.
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO
ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL SWITCH
GEAR, LOAD CENTERS AND PANEL BOARDS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS,
CONTRACTORS NAME AND PROJECT NAME. CLEARLY
INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES
AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN
PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER
DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES
THE RIGHT TO REJECT ANY SUBSTITUTE ITEM FOUND NOT
EQUAL TO THE SPECIFIED ITEM AS DESIGNED.
3. CONTRACTOR SHALL FURNISH A TEMPORARY SERVICE FOR
THE USE OF ALL TRADES DURING CONSTRUCTION AS
REQUIRED BY THE GENERAL CONTRACTOR. REMOVE ALL
TEMPORARY EQUIPMENT AS PERMANENT SERVICES
BECOME AVAILABLE.
4. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND
ARE NOT INTENDED TO DEFINE EXACT QUANTITIES,
LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS
SHOW GENERAL INTENT OF SYSTEMS. MODIFICATIONS IN
ELECTRICAL SYSTEM ROUTING AND LOCATIONS AS
REQUIRED TO MEET THE INTENT, SHALL BE PERFORMED
WITHOUT ADDITIONAL COST TO OWNER. SECURE AND PAY
FOR ALL REQUIRED PERMITS.
5. THE ELECTRICAL CONTRACTOR IS TO PROVIDE ALL
REQUIRED LABOR, MATERIALS, EQUIPMENT, AND
CONTRACTOR'S SERVICES NECESSARY TO COMPLETE THE
INSTALLATION OF SYSTEMS REQUIRED IN FULL
CONFORMITY WITH APPLICABLE CODES AND ORDINANCES.
THE FINISHED JOB SHALL BE FUNCTIONAL AND COMPLETE
IN EVERY DETAIL INCLUDING ANY AND ALL SUCH ITEMS FOR
A COMPLETE SYSTEM. CONTRACTOR SHALL GUARANTEE
ALL LABOR AND MATERIALS ENTERING INTO CONTRACT
FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
ACCEPTANCE.
6. ALL WORK SHALL IN BE IN FULL ACCORDANCE WITH 2009
INDIANA ELECTRICAL CODE (2008 NFPA 70), 2010 INDIANA
ENERGY CODE (ASHRAE 90.1-2007), PERTINENT STATE,
COUNTY, CODES AND ORDINANCE AND INDIANA
AMENDMENTS. COORDINATE WORK WITH OTHER TRADES.
ELECTRICAL CONTRACTOR SHALL BEAR ALL COSTS
RESULTING FROM ANY NON COMPLIANCE WITH CODE
REQUIREMENTS
7. MATERIALS AND EQUIPMENT SHALL BE NEW UNLESS
INDICATED OTHERWISE. MATERIAL SHALL BEAR U.L. LABEL
WHERE SUCH STANDARDS HAVE BEEN ESTABLISHED AND
LISTED BY U.L. MATERIALS AND EQUIPMENT SHALL
CONFORM WITH THE LATEST ISSUES OF APPLICABLE
TECHNICAL STANDARDS.
8. THE ELECTRICAL CONTRACTOR IS TO PROVIDE A
COMPLETE SYSTEM OF LIGHTING, RECEPTACLES, AND
POWER AS REQUIRED. VERIFY ALL VOLTAGES AND PHASE
REQUIREMENTS WITH MECHANICAL CONTRACTOR'S
EQUIPMENT PRIOR TO PERFORMING ANY WORK.
9. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND
VERIFY ALL EXISTING CONDITIONS BEFORE SUBMITTING A
BID. NO EXTRAS WILL BE ENTERTAINED FOR
CONTRACTORS FAILURE TO IDENTIFY EXISTING
CONDITIONS AND ADJUST AS REQUIRED TO MEET DESIGN
INTENT.
10. ALL CONDUIT COUPLINGS AND CONNECTIONS SHALL BE
COMPRESSION TYPE AND MADE TO ENSURE POSITIVE
GROUNDING CONTINUITY. MAKE CONNECTIONS TO
EQUIPMENT SUBJECT TO VIBRATION WITH 18 INCHES OF
FLEXIBLE WATERTIGHT CONDUIT WITH WATERTIGHT
FITTINGS. PROVIDE FOR SUPPORT AND SECURING OF ALL
CONDUIT AND EQUIPMENT. CONNECTIONS TO LIGHTING
FIXTURES SHALL BE MADE WITH SIX (6) FEET OF FLEXIBLE
CONDUIT FROM A BOX WITHIN TWO (2) FEET OF THE
FIXTURE. SPLICE ALL WIRES ONLY IN ACCESSIBLE BOXES.
ALL FIXTURE WHIPS TO BE FLEXIBLE METAL CONDUIT 1/2"
MINIMUM SIZE WITH COMPRESSION CONNECTORS WITH
INSULATED THROATS. WHIPS SHALL NOT EXCEED 6'.
FIXTURE WHIPS TO BE SUPPORTED FROM BUILDING
STRUCTURE.
11. ALL LIGHTING AND BRANCH CIRCUIT WIRING SHALL BE
SOLID COPPER MINIMUM SIZE #12 AWG. 600V INSULATION,
75 DEG. C., TYPE THW OR THWN, NOT LESS THAN #12 AWG.
ALL WIRE SERVING AS FEEDS TO DISTRIBUTION PANEL
BOARDS OR INTEGRAL HORSEPOWER MOTORS SHALL BE
EITHER STRANDED COPPER CONDUCTOR OR ASTM B800
ALUMINUM AA-8000 SERIES. THESE SHALL BE SIZED NOT
LESS THAN #10 AWG FOR COPPER AND NOT LESS THAN #8
AWG FOR ALUMINUM. EACH WITH MINIMUM 600V THW OR
THWN INSULATION, 75 DEG. C. ALL FEEDER SHALL BE
SIZED IN ACCORDANCE WITH NEC 310.15.
12. EXPOSED WIRING SHALL BE IN EMT RACEWAY. EXTERIOR
WIRING SHALL BE IN CONDUIT. CONCEALED WIRING SHALL
BE IN EMT OR METAL CLAD CABLE WHERE ALLOWED BY
CODE.
13. ALL LOW VOLTAGE WIRING IN PLENUM RATED CEILINGS OR
EXPOSED IN ROOMS SHALL BE PLENUM RATED CABLE.
14. ALL CABLE SHALL BE NEW WIRE OF RECENT
MANUFACTURE AND IN ACCORDANCE WITH THE LATEST
STANDARDS OF IPCEA AND NEMA AS A MINIMUM
15. PANELBOARDS SHALL BE A DEAD-LOCK SAFETY TYPE,
SURFACE OR RECESSED MOUNTED AS SHOWN, EQUIPPED
WITH THERMAL-MAGNETIC MOLDED CASE CIRCUIT
BREAKERS WITH FRAME AND TRIP RATINGS AS REQUIRED.
TERMINALS FOR FEEDER CONDUCTORS TO THE
PANELBOARD MAINS AND NEUTRAL SHALL BE U.L. LISTED
AS SUITABLE FOR THE TYPE OF CONDUCTOR SPECIFIED.
TERMINALS FOR BRANCH CIRCUIT WIRING, BOTH BREAKER
AND NEUTRAL, SHALL BE U.L. LISTED AND CONNECTORS
SHALL BE OF THE FULL COMPRESSION TYPE.THE
PANELBOARD BUS ASSEMBLY SHALL BE ENCLOSED IN A
STEEL CABINET. THE SIZE OF THE WIRING GUTTERS AND
GAUGE OF STEEL SHALL BE IN ACCORDANCE WITH NEMA
STANDARD PUBLICATION NO. PB-1971 AND U.L.
STANDARDS NO. 67 FOR PANELBOARDS. CABINET SHALL
BE FABRICATED FROM GALVANIZED STEEL OR EQUIVALENT
RUST-RESISTANT STEEL. FRONTS SHALL INCLUDE DOORS
AND HAVE FLUSH, BRUSHED STAINLESS STEEL, CYLINDER
TUMBLER-TYPE LOCKS WITH CATCHES AND SPRING
LOADED DOOR PULLS. THE FLUSH LOCK SHALL NOT
PROTRUDE BEYOND THE FRONT DOOR. ALL PANELBOARD
LOCKS SHALL BE KEYED ALIKE. FRONTS SHALL HAVE
ADJUSTABLE INDICATING TRIP CLAMPS WHICH SHALL BE
CONCEALED WHEN THE DOORS ARE CLOSED. DOORS
SHALL BE MOUNTED BY COMPLETELY CONCEALED STEEL
HINGES. FRONTS SHALL NOT BE REMOVABLE WITH DOOR
IN THE LOCATED POSITION. A CIRCUIT DIRECTORY FRAME
AND TYPE WRITTEN CARD WITH A CLEAR PLASTIC
COVERING SHALL BE PROVIDED ON THE INSIDE OF THE
DOOR. THE DIRECTORY CARD SHALL PROVIDE A SPACE AT
LEAST 1/4" HIGH X 3" LONG OR EQUIVALENT FOR EACH
CIRCUIT. FRONTS SHALL BE OF CODE GAUGE, FULL
FINISHED STEEL WITH RUST-INHIBITING PRIMER FACTORY
FINISHED ENAMEL PAINT.
16. CIRCUIT BREAKERS SHALL BE QUICK-MAKE, QUICK-BREAK,
THERMAL-MAGNETIC, TRIP INDICATING AND HAVE COMMON
TRIP ON ALL MULTI-POLE BREAKERS. BRANCH CIRCUIT
BREAKERS FEEDING CONVENIENCE OUTLETS SHALL HAVE
SENSITIVE INSTANTANEOUS TRIP SETTINGS OF NOT MORE
THAN 10 TIMES THE TRIP RATING OF BREAKER TO PREVENT
REPEATED ARCING SHORTS RESULTING FROM FRAYED
APPLIANCE CORDS. CONNECTION TO BUS SHALL BE BOLT
ON.
17. CONTRACTOR TO OBTAIN MAXIMUM FAULT CURRENT
AVAILABLE FROM THE UTILITY. CALCULATE THE FAULT
CURRENT AVAILABLE AT THE PANELS. ALL
PANELS/BREAKERS/SWITCHES ARE TO BE BRACED TO
EXCEED MAXIMUM AVAILABLE FAULT CURRENT AND
CIRCUIT BREAKERS ARE TO BE CAPABLE OF INTERRUPTING
FAULT CURRENT.MANUFACTURER SHALL PROVIDE ALL
REQUIRED FAULT CURRENT AND ARC-FLASH LABELING PER
110.16 AND 110.24.
18. MAXIMUM LOADING OF 20 AMP CIRCUITS SHALL NOT
EXCEED 1750 WATTS. VOLTAGE DROP OF BRANCH
CIRCUITS SHALL NOT EXCEED 3% AND FEEDER CIRCUITS
SHALL NOT EXCEED 2%. SEAL ALL PENETRATIONS
THROUGH WALLS, CEILINGS AND FLOORS AIR AND WATER
TIGHT. FIRE STOP WHERE REQUIRED.
19. CONTRACTOR SHALL PROVIDE ENGRAVED BAKELITE
NAMEPLATES FOR ALL ELECTRICAL PANELS,
DISCONNECTS, TRANSFORMERS AND MOTORS OVER 1 HP.
FURNISH TYPEWRITTEN PANEL DIRECTORIES TO IDENTIFY
ALL ELECTRICAL CIRCUITS BOTH NEW AND EXISTING.
20. VERIFY EXACT LOCATION, COLOR AND HEIGHTS OF ALL
OUTLETS, RECEPTACLES, LIGHT FIXTURES AND EQUIPMENT
WITH OWNER'S REPRESENTATIVE PRIOR TO START OF
WORK. FURNISH GENERAL SERVICE DUPLEX'S, 15 AMP
SWITCHES, 15/20 AMP GFICS, HEAVY DUTY DISCONNECTS,
HVAC SSU SWITCHES, PANEL BOARDS, LOAD CENTERS,
DISTRIBUTION PANELS ETC. AS REQUIRED.
21. DISCONNECT SWITCHES SHALL BE GENERAL DUTY, NEMA
TYPE 1 FOR INDOOR SERVICE AND NEMA TYPE 3R FOR
OUTDOOR SERVICE, SUITABLE FOR PADLOCKING, NUMBER
OF POLES, RATINGS, FUSES (IF REQUIRED) SHALL BE AS
INDICATED ON THE DRAWINGS.
22. DEVICES:
A. CONVENIENCE RECEPTACLES SHALL BE MOUNTED 18"
ABOVE FINISHED FLOOR (A.F.F.) TO BOTTOM UNLESS
NOTED OTHERWISE, SWITCHES AND PUSHBUTTONS SHALL
BE 42" A.F.F. TO BOTTOM UNLESS SPECIFIED OTHERWISE
ON THE DRAWINGS.
B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FINAL LOCATIONS
AND COLORS OF ALL DEVICES WITH OWNER.
C. INSTALL ALL DEVICES PARALLEL AND PERPENDICULAR TO
ADJACENT WALL AND CEILING, FLUSH WITH SURROUNDING
SURFACES AND FREE FROM ALL OBSTRUCTIONS.
REWORKING OF EQUIPMENT INSTALLED IMPROPERLY
SHALL BE AT THE CONTRACTOR'S EXPENSE.
D. SWITCHES, BOXES, ETC., SHALL BE NEMA TYPE 1
CONSTRUCTION FOR INDOOR APPLICATIONS AND NEMA
TYPE 3R CONSTRUCTION FOR OUTDOOR APPLICATIONS.
E. SWITCHES SHALL MEET NEMA STANDARDS, COLOR SHALL
BE BY ARCHITECT. SWITCHES SHALL BE EQUAL TO
HUBBELL COMMERCIAL SPECIFICATION GRADE 20/15
AMPERES, SINGLE POLE, 125/277V. MULTI-POLE OR
SPECIAL SWITCHING SHALL BE AS NOTED ON THE
DRAWINGS.
F. RECEPTACLES SHALL BE 125 VOLT, 15/20 AMPERES,
DUPLEX, GROUNDED HUBBELL COMMERCIAL
SPECIFICATION GRADE. SPECIAL RECEPTACLES SHALL BE
AS NOTED ON THE DRAWINGS.
G. MATCHING COVER PLATES SHALL BE PROVIDED FOR ALL
RECEPTACLES AND SWITCHES.
23. LIGHTING FIXTURES:
A. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
FIXTURES- MODEL NUMBERS, QUANTITY AND DISTANCE
BETWEEN LIGHTING FIXTURE PER FLOOR PLANS.
B. PRIOR TO ROUGH-IN E.C. SHALL VERIFY FIXTURE
QUANTITY, MODELS, STYLE, TRIM, LENS, ETC. WITH OWNER
FOR ALL FIXTURES.
C. PROVIDE LIGHTING FIXTURES COMPLETE WITH, BUT NOT
NECESSARILY LIMITED TO, HOUSINGS, LAMPS, LAMP
HOLDERS, REFLECTORS, BALLASTS, STARTERS AND
WIRING.
24. INSTALLATION OF LIGHTING FIXTURES:
A. INSTALL LIGHTING FIXTURES AT LOCATIONS AND HEIGHTS
AS INDICATED, IN ACCORDANCE WITH FIXTURE
MANUFACTURER'S WRITTEN INSTRUCTIONS, APPLICABLE
REQUIREMENTS OF NEC, NECA'S "STANDARD OF
INSTALLATION", NEMA STANDARDS, AND WITH RECOGNIZED
INDUSTRY PRACTICES TO ENSURE THAT LIGHTING
FIXTURES FULFILL REQUIREMENTS.
B. COORDINATE WITH OTHER ELECTRICAL WORK AS
APPROPRIATE TO PROPERLY INTERFACE INSTALLATION OF
INTERIOR LIGHTING FIXTURES WITH OTHER WORK.
C. E.C. TO FASTEN FIXTURES SECURELY DIRECTLY TO
BUILDING STRUCTURAL SYSTEM. LIGHT TROFFERS SHALL
BE SUPPORTED AT EACH CORNER OF FIXTURE BY WIRES
OF SAME GAUGE AS HANGER WIRE FOR CEILING GRID.
ATTACH EARTHQUAKE CLIPS TO GRID AS RECOMMENDED
BY LIGHT MANUFACTURER. USE SCREWS IF REQUIRED BY
MANUFACTURER. ATTACH THE WIRE TO THE STRUCTURE
ABOVE. LIGHTS SHALL NOT BE SUPPORTED IN ANYWAY BY
LAY-IN CEILING.
D. FIXTURE LOCATIONS SHALL BE AT APPROXIMATE
LOCATIONS AS SHOWN ON THE DRAWINGS FREE FROM ALL
OBSTRUCTIONS. CLEAN ALL LIGHTING EQUIPMENT AFTER
LIGHTING INSTALLATION AND GENERAL CONSTRUCTION IS
COMPLETE. REPAIR ANY FIXTURES DAMAGED DURING
CONSTRUCTIONS.
E. PROVIDE NECESSARY MOUNTING FRAMES, SUPPORTS AND
RELATED ITEMS REQUIRED TO PROPERLY INSTALL
FIXTURES. SUPPORT FIXTURES INDEPENDENTLY OF PIPING
AND DUCTWORK. MAKE MODIFICATIONS TO THE
STRUCTURE AS REQUIRED TO INSTALL FIXTURES. ANY
MODIFICATIONS TO THE STRUCTURE SHALL NOT IMPAIR
THE STRUCTURAL INTEGRITY OF THE BUILDING.
25. EQUIPMENT CONNECTIONS
A. ALL DEVICES AND EQUIPMENT SHALL BE SOLIDLY
GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS.
B. ALL SOLID CONDUCTOR WIRES MAY BE TERMINATED
UNDER SCREW HEADS. STRANDED WIRES MAY BE
TERMINATED BY USING PUSH-IN CLAMP TYPE
CONNECTORS FURNISHED WITH DEVICES OR TERMINATED
WITH COMPRESSION TYPE TERMINAL LUGS. SET SCREW
TYPE TERMINATIONS ARE NOT PERMITTED.
C. NO MOTORS ARE TO BE SUPPLIED UNDER THIS CONTRACT
UNLESS ITEMS REQUIRING A MOTOR ARE FURNISHED BY
THIS CONTRACTOR. THE CONTRACTOR SHALL FURNISH
ALL STARTERS FOR ALL MOTORS REQUIRING A STARTER.
THE CONTRACTOR SHALL CONNECT ALL POWER
EQUIPMENT IF & WHERE SHOWN ON PLANS UNLESS
OTHER-WISE SPECIFIED & ASSURE OWNER THE MOTORS
ARE IN GOOD RUNNING ORDER.
D. E.C. SHALL PROVIDE ALL COMPONENTS NEEDED TO MEET
MEANS OF DISCONNECT PER N.E.C. FOR ALL HARD WIRED
EQUIPMENT.
26. LOW VOLTAGE
A. ALL LOW VOLTAGE CABLE WHERE CONCEALED IN
CONSTRUCTION OR IN EXPOSED OPEN AREAS SHALL BE
FREE RUN. CONTRACTOR SHALL INSTALL 3/4" CONDUIT
(MINIMUM) FROM EACH LOW VOLTAGE ROUGH-IN LOCATION
TO ACCESSIBLE CEILING SPACE, LOW VOLTAGE WIRE
TRAY OR HANGERS AND THEN TO MDF, HEAD-IN, PBX
PUNCH DOWN, CONTROLLER ETC.
B. E.C. SHALL COORDINATE WITH LOCAL PHONE AND CABLE
PROVIDER AS CHOSEN BY OWNER AND PROVIDE
RACEWAYS FOR BRINGING IN SERVICES AS REQUIRED.
C. ALL LOW VOLTAGE CABLE SHALL BE PLENUM RATED IN
PLENUMS.
D. ALL DATA CABLE SHALL BE CAT 5E UNLESS OTHER WISE
NOTED. TERMINATE, LABEL AND TEST ALL WIRING.
27. CLOSE OUT
A. PROVIDE MANUFACTURERS OPERATION AND
MAINTENANCE MANUALS AND PROVIDE AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER
SELECTED PERSONNEL AS REQUESTED AND PROVIDE
WARRANTY INFORMATION FOR ALL MANUFACTURERS
WARRANTED EQUIPMENT
AMPS
MECHANICAL CONTRACTOR
ELECTRICAL ABBREVIATIONS
MANUFACTURER
MOUNTING HEIGHT
MFR
MH
MINIMUM
MOTOR OPERATED DAMPER
MLO
MIN
MOD
MOCP
MOUNTED
NOT IN CONTRACT
PLUMBING CONTRACTOR
ON CENTER
NOT TO SCALE
MTD
NIC
PC
NTS
OC
COMPANYCO
RUNNING LOAD AMPSRLA
ELECTRIC CONTRACTOR
DOWN
DRAWING(S)
ELECTRICAL DISTRIBUTION CENTER
EQUIPMENT
EC
DN
DWG(S)
EQUIP
EDC
EWC
ETR
FULL LOAD AMPS
MAXIMUM
FLA
MAX
MAIN BREAKERMB
MC
CONTRACTORCONTR
EXISTING TO REMAIN
ELECTRIC WATER COOLER
MIMIMUM CIRCUIT AMPS MCA
MAXIMUM OVER CURRENT PROTECTION
MAIN LUG ONLY
EMERGENCY EM
POUNDS PER SQUARE INCHPSI
REVOLUTIONS PER MINUTE RPM
HORSE POWER HP
GENERAL CONTRACTOR GC
ABOVE FINISHED FLOOR AFF
EX EXISTING
FLOW SWITCHFS
A
VOLTSV
UNLESS OTHERWISE NOTEDUON
LIGHTING
PANELBOARD SCHEDULE
ABBREVIATIONS
POWER NON-SEASONAL PN
MOTOR SUMMER
MOTOR NON-SEASONAL
MOTOR NON-SEASONAL INTERMITTENT
MOTOR WINTER
MS
MN
MNI
MW
POWER WINTER PW
KITCHENKT
RECEPTACLER
L
ELECTRICAL SYMBOLS
GFI
SPECIAL EQUIPMENT COORDINATE W/SUPPLIER
JUNCTION BOX
DISCONNECT
OUTLET - 4 WAY
MOTOR
OUTLET - GROUND FAULT INTERRUPT
OUTLET - DUPLEX
RECESSED DOWN LIGHT
LIGHT FIXTURE - ON NIGHT LIGHT CIRCUIT
LIGHT FIXTURE - LAYIN
LIGHT FIXTURE - SURFACE
EXIT SIGNAGE
WALL MOUNTED STRIP LIGHT
SUSPENDED STRIP LIGHT
LOW VOLTAGE TWO LINE
LOW VOLTAGE ONE LINE
ANALOG PHONE LINE
WIRELESS ACCESS POINT
OUTLET - 220
EXIT SIGNAGE WITH EMERGENCY HEADS
LIGHT FIXTURE - WALL SCONCE
LIGHT FIXTURE - PENDANT
LIGHT FIXTURE - FREE HANGING
J
FLOOR OUTLET WITH POWER, DATA AND PHONE
D
3
SWITCH
SWITCH WITH DIMMER
SWITCH - 3 WAY
OSSWITCH WITH OCCUPANCY SENSOR
OS CEILING MOUNTED OCCUPANCY SENSOR
4SWITCH - 4 WAY
GFI OUTLET - GROUND FAULT INTERRUPT WEATHERPROOF WP
LOW VOLTAGE # LINES #
TIME CLOCK TC
PHOTO CELL PC
PANEL DESIGATION
X: XX,XX,XX
CIRCUIT BREAKER NUMBERS
WAP
EMERGENCY LIGHTING UNIT
EMERGENCY EXIT EGRESS LIGHT
LIGHT FIXTURE - TRACK
LIGHT FIXTURE - UNDER COUNTER
LIGHT FIXTURE - RECESSED DOWN LIGHT
LIGHT FIXTURE - VANITY LIGHT
OUTLET - DUPLEX WITH USB
J DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
E001
WP
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
HA
PANEL
PRIMARY CONDUITS
UTILITY COMPANY
PAD MTD. TRANSFORMER
MAIN BUILDING
GROUND BUS MAIN
SWITCHBOARD
ROOM. (ALL
CONNECTIONS TO
THIS BUSS SHALL
BE EXOTHERMIC.
GRADE
BUILDING STEEL
SUPPLY SIDE
WATER METER
GROUND BUS
NOTE:
CONNECTIONS SHALL BE FIRMLY
BONDED TO NEUTRAL BUS, BUILDING
STEEL, GROUNDING ROD AND WATER
PIPE.
METAL WATER PIPE
WITHIN 5 FT. OF
WATER SERVICE
ENTRANCE TO
BUILDING. PROVIDE
BONDED JUMPER
ACROSS WATER
PIPE.
#2/0 COPPER
GROUND
GROUND BUS FOR
DATA CLOSETS.
#2/0 COPPER
#2/0 COPPER
#2/0 COPPER NEUTRAL BUS
#2/0 COPPER
SUPPLEMENTAL
GROUNDING
ELECTRODE
M GROUND PER
NEC
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
GENERAL NOTES:
F20 12 12 3/4"
1P,1N,1G,
2P,1G
2P,1N,1G,
3P,1G 3P,1N,1G
EQUIP/SERV
GROUND
FEEDER/BRANCH CIRCUIT
LABEL
CONDUCTOR SIZE
PER CONDUIT
CONDUIT SIZE & QUANTITY
FEEDER & BRANCH CIRCUIT SCHEDULE (COPPER)
3P,2N,1G 3P,3N,1G 3P,1N,2G
PHASE &
NEUTRAL
3/4" 3/4" 3/4" 3/4" 3/4"
F30 10 10 3/4" 3/4" 3/4" 3/4" 3/4" 3/4"
F40 8 10 3/4" 3/4" 1" 1" 1" 1"
F50 6 10 1" 1" 1" 1-1/4" 1-1/4" 1"
F60 4 10 1" 1" 1-1/4" 1-1/4" 1-1/4" 1-1/4"
F70 4 8 1" 1-1/4" 1-1/4" 1-1/4" 1-1/2" 1-1/4"
F80 3 8 1" 1-1/4" 1-1/4" 1-1/2" 1-1/2" 1-1/4"
F90 2 8 1" 1-1/4" 1-1/2" 1-1/2" 2" 1-1/2"
F100 1 8 1-1/4" 1-1/2" 1-1/2" 2" 2" 2"
F110 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F125 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F150 1/0 6 1-1/4" 1-1/2" 2" 2" 2-1/2" 2"
F175 2/0 6 1-1/2" 2" 2" 2-1/2" 2-1/2" 2"
F200 3/0 6 1-1/2" 2" 2" 2-1/2" 3" 2-1/2"
F225 4/0 4 2" 2" 2-1/2" 3" 2-1/2"
F250 250 4 2" 2-1/2" 3" 3" 3"
F300 350 4 2" 2-1/2" 3" 3-1/2" 3"
F350 500 3 2-1/2" 3" 3-1/2" 4" 3-1/2"
F400 3/0 3 (2) 1-1/2" (2) 2" (2) 2-1/2" (2) 2-1/2" (2) 2-1/2"
F450 4/0 3 (2) 2" (2) 2" (2) 2-1/2" (2) 3" (2) 2-1/2"
F500 250 2 (2) 2" (2) 2-1/2" (2) 3" (2) 3" (2) 3"
F600 350 1 (2) 2-1/2" (2) 3" (2) 3" (2) 3-1/2" (2) 3"
F200
F600
1 SCALE: NONE
ELECTRICAL RISER DIAGRAM
TRANSFORMER TXA
150 KVA, 480-120/208V
3Ø-4W
T
GROUND PER
NEC
B
PANEL
A
PANEL
F200
2 SCALE: NONE
ELECTRICAL GROUNDING SYSTEM DIAGRAM
F400
UTILITY METER
AND CT.
CABINET
E002
GROUND PER
NEC
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
E003
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
E004
LIGHT FIXTURE SCHEDULE -EXTERIOR
MANUFACTURER TYPE VOLTAGE LAMPS MOUNTING DESCRIPTION
A3-16
WALL
A-16 390W LED 16' POLE277
A2-16
LSI-INDUSTRIES
LSI-INDUSTRIES
LSI-INDUSTRIES CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL
W1 LSI-INDUSTRIES
INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN
D-16 16' POLELSI-INDUSTRIES
DL138823 / FRONT ROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE
DL134479 / FORWARD THROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE
DL137144 / FORWARD THROW OPTIC / INTERNAL SHIELD / 390W LED / 16' POLE
DL135333 / TYPE 5 OPTIC / 390 WATT LED / 16' POLE
DL119453 / WALL MOUNT LED / FORWARD THROW OPTIC
31,841 LUMENS
16' POLE
16' POLE 277
277
277
277
CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL
INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN
CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL
INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN
CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL
INCLUDE FUSING AND GFCI OUTLETS AS SHOWN ON PLAN
390W LED
45,192 LUMENS
390W LED
28,632 LUMENS
390W LED
43,144 LUMENS
76W LED
8,654 LUMENS CONTROL VIA LIGHTING RELAY PANEL AND PHOTOCELL
VERIFY COLORS WITH ARCHITECT - COLORS MAY VARY
A2-16
A3-16
LIGHT FIXTURE SCHEDULE -INTERIOR
VENDOR TYPE VOLTAGE LAMPS MOUNTING DESCRIPTION
F9-4
F4
F13
F15
F17
32W LED CHAIN HUNG UE
120 OR 277 23.5 W LED
DL123228 4' STRIP WITH DIFFUSE LENS / CHAIN KIT
RECESSED / ADJ.
F1 UE LAY-IN 34W LED PEC22 LED SS RAD NW UE DIMLSI INDUSTRIES
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
F9-8 65W LED CHAIN HUNG UE
F18
EX1
EM1
EM2
4W LED WALL/CEILING CB2REM-RC RED LETTERUE
BATTERY RED L.E.D. EXIT SIGN WITH BATTERY
2 X 3.3 W LED
DL116029 RMR-16-LED
UE LOW PROFILE WALL OR CEILING MOUNT EMERGENCY UNIT
TWIN 3.3W LED MR LAMPS / 250 LUMENS PER LAMP
2 x 6.5 W LED
F5000 LED6.5 90 SD TBAR NC
UE REMOTE BATTERY BOX REQUIRED
E.C. TO SETUP AND TEST PRIOR TO AHJ INSPECTION
EM3 3.3 W LED WALL
DL111891 DECORATIVE DIE CAST EXTERIOR EGRESS
UE VERIFY COLOR TO MATCH BUILDING EXTERIOR (THIS CAN VARY)
THIS IS A LINE VOLTAGE REMOTE EGRESS
F8 120 OR 277 38W PER HEAD MESA GRID WITH 38W FIATO TRACK HEADS, 4000K / 25° BEAMINSIDE
TROUGH LENGTHS VARY - SEE PLAN FOR LENGTHS
F11
F12
F20
F21
F23
F14
RAF04OC 20L 40K MD DS10V RA4FOC SG PF
19W LED PENDANT UE 600-24-2-L3/830-UNV-SN / 3000K / 24" WALL SCONCE OVER VANITY
COORDINATE INSTALL W/ CASEWORK CONTRACTOR
F19
75W E26 PENDANT 120 BonBonne pendant with 75w 25 degree spot.
SET 96" A.F.F.
5-8W EDISON LED PENDANT 120 VIVO FR37507 BNI / LED VINTAGE EDISON BULB
SET 90" A.F.F.
40 X 1.5 W LED PENDANT 120 GLOBE LIGHTING CBL36 / 30" DIA. / BRUSHED NICKLE / 160 POUND WEIGHT
SEE DETAIL FOR MOUNTING HEIGHTS
UE 23W LED LAD6 20 LED 40 52 UE TR6R SF SPC C27RECESSED
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
UE 30W LED LAD6SQ 27 LED 40 52 UE TSQ6 SF SPC C27RECESSED
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
UE 135W LED DL125514 LED HIGHBAY / 18,600 LUMEN / CABLE KIT - SERVICE BAYSCABLE HUNG
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 900 LUMEN EM
UE 40W LED CABLE HUNG
4' VAPOR TIGHT FOR TECH WRITERS OVER WORK STATION
UE 7W / FT LED LXC2-LENGTH-LED-NW-24VDC / REMOTE TRANSFORMERSSURFACE
MOUNTS IN SHOWROOM COVE FEATURE AND CEILING RECESSES AT ENTRANCE
UE 45W LED RECESSED
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
F26 UE 35W LED DL120556 2X4 LED PANEL - BACK OF HOUSERECESSED
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
F19W UE 52W LED DL126534 4' VAPOR TIGHT / 10' CABLE IT- WASH BAYSCABLE HUNG
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 900 LUMEN EM
F24 UE 45W LED RECESSED
"EM" DESIGNATED FIXTURES REQUIRE A MINIMUM 700 LUMEN EM
DIMMING
TYPE
0-10V
(1)
Light Fixture Schedule Notes:
1. Not all fixtures or rooms will have dimming. See rooms 130, 202, and 206 for dimming in this facility.
SPECTRUM LIGHTING 0-10V
AMERLUX LIGHTING
RECESSED TROUGH
TRACK HEADS
ELV
PREMIERE LUMINAIRE N / A
0-10V
0-10V
HINKLEY LIGHTING
LINEA INC
N / A
N / A
120 OR 277 27W PER HEAD MESA GRID WITH 27W FIATO TRACK HEADS, 4000K / 40° BEAMINSIDE
TROUGH LENGTHS VARY - SEE PLAN FOR LENGTHS
AMERLUX LIGHTING
RECESSED TROUGH
ELV
TRACK HEADS
SHAPER
LSI INDUSTRIES
LSI INDUSTRIES
0-10V
0-10V
N / A
LSI INDUSTRIES
0-10V
N / A
N / A
N / A
LAD6 41 LED 40 35 UE TR6R SF SPC C27
LAD6 41 LED 40 52 UE TR6R SF SPC C27
0-10V
0-10V
LSI INDUSTRIES
LSI INDUSTRIES
F25 UE 60W LED SGA6BX 60L 40K MD D010VOLT BH27 RA6FBX SG MFRECESSED
AIM AT KIA LOGO - FOR CEILINGS OVER 14' AFF
CBMC DESIGN-LIGHTING
0-10V
0-10V
RECESSED
WALL/CEILING
N / A
N / A
N / A
N / A
CBMC DESIGN-LIGHTING
CONCEALITE
CBMC DESIGN-LIGHTING
CBMC DESIGN-LIGHTING
CBMC DESIGN-LIGHTING
CBMC DESIGN-LIGHTING DL122820 8' STRIP WITH DIFFUSE LENS / CHAIN KIT
CBMC DESIGN-LIGHTING
CBMC DESIGN-LIGHTING
CBMC DESIGN-LIGHTING DL125083 4' VAPOR TIGHT / 10' CABLE IT- @APPROX. 10' AFF
SPECTRUM LIGHTING
09/21/20
A2-16
D-16
D-16
D-16
D-16
A-16
A-16
A-16
A-16
A-16
A-16
D-16
A-16
A-16
A-16
A-16
A-16
D-16
D-16
D-16
D-16
A-16
A-16
A-16
A-16
A2-16 A2-16
A3-16
A-16
A-16
HA:55,57
HA:55,57HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:55,57
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
HA:59,61
TUTILITY
TRANSFORMER
A:17
WP
A:17
WP
A:17
WP
A:17
WP
A:17
WP
A:17
WP
PYLON SIGN
HA:46,48
WP
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
E050
1 SCALE: 1" = 30'-0"
ELECTRICAL SITE PLAN
CANT AROUND TOP 1"
(8) #4 REBAR VERTICALY WITH #4 REBAR SPIRALED
AT 6" O.C. AND (3) LAYERS OF #4 REBAR AT TOP
AND BOTTOM OF BASE SPACED AT 2" O.C. MAINTAIN
MINIMUM OF 3" FROM REBAR TO EDGE OF
CONCRETE.
ANCHOR BOLTS
HAND HOLE
1. POLE SHALL BE CAPABLE OF WITH STANDING
130 MPH WIND GUSTS
2. CONCRETE SHALL BE MINIMUM 3000 PSI
3. MATCH ANCHOR BOLT PATTERN TO POLE
MANUFACTURERS BASE PLATE
#6 COPPER GROUND WIRE BONDED TO POLE.
5/8"X10' GROUND ROD WITH EXOTHERMIC
CONNECTION TO #6 GROUNDING CONDUCTOR.
NOTES
60"
GRADE
3/4" PVC
CONDUIT TO POLE
GROUND.
24"
2 NOT TO SCALE
LIGHT POLE DETAIL
GENERAL NOTES:
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE ARCHITECTURAL ELEVATIONS
FOR EXACT LOCATION OF WALL MOUNTED
LIGHT FIXTURES.
3. SITE LIGHTING CONDUITS TO BE A MINIMUM OF
1" IN SIZE.
4. PROVIDE WEATHERPROOF GFI RECEPTACLE
WITH WHILE IN USE COVER AT LIGHT POLES
WHERE INDICATED ON PLAN.
5. DIFFERENT VOLTAGE SYSTEMS BRANCH
CIRCUITRY SHALL BE RUN IN SEPARATE
CONDUIT(S).
6. ALL LIGHT FIXTURES SHOWN ON THIS
DRAWINGS SHALL BE FED FROM PANEL HA
UNLESS NOTED OTHERWISE.
7. ALL BRANCH CIRCUITRY ON THIS DRAWINGS
SHALL BE SIZE #8 MINIMUM.
8. ALL BRANCH CIRCUITRY SHALL HAVE
DEDICATED GROUND WIRE SIZED PER NEC.
9. ALL EXTERIOR LIGHT FIXTURES SHALL BE TIME
CLOCK CONTROLLED WITH PHOTOCELL
OVERRIDE. ROUTE ASSOCIATED BRANCH
CIRCUITRY THROUGH MULTI-POLE LIGHTING
CONTACTOR. REFER TO SHEET E101 FOR
ADDITIONAL INFORMATION.
KEY NOTES:
PROVIDE 120 VOLT CONNECTION TO POLE
MOUNTED GFI RECEPTACLE PROVIDED BY LIGHT
FIXTURE POLE MANUFACTURER. TYPICAL.
PROVIDE CONNECTION TO PYLON SIGN PER
SIGNAGE SHOP DRAWINGS. FIELD CONFIRM
VOLTAGE REQUIREMENTS AND ADJUST THE
SERVING BRANCH CIRCUITRY FROM EITHER PANEL
HA OR A AS APPROPRIATE. CIRCUITRY SHALL BE
CONTROLLED BY LIGHT VENDOR PROVIDED
LIGHTING RELAY PANEL.
1
2
1
1
1
1
1
1
2
TOP OF ALL POLE BASES TO BE SAME
ELEVATION AS MUCH AS POSSIBLE WITH
MINIMUM DIMENSION ABOVE GRADE OR
PAVING TO BE 2'-0". ALL "FRONT ROW" POLE
BASES TO BE SAME ELEVATION ALWAYS
09/21/20
3 5 10 13 15 16 17
C
E
H
J
M
O
S
2 1
9 6
D
B
A
F
18
T
G
L
N
7 4 11 12 14
K
28
R
P
31 31
31 31
31 31
31 31
31 31
31 31
33
31 31
B:10
31
31
B:10 31
31
B:10
31
31
31
31
31
B:10
31 31
31 31
31 31
31 31
31 31
31 31
31
31
31
31 31
31 31
31 31 31
31
31
31
31
35 35
35 35
35 35
35 35
35 35
35 35
35 35
35 35
35
35 35
35
31 31
31
31
31 31
33 33 33 33
33 33 33 33
33 33 33 33
33 33 33 33
33 33 33 33
33 33 33 33
B:11
B:11
B:11
B:11 33 33 33 33
33
33
35
35
35
35
35
35 35
35 35
35 35
35 35
35
35
35
35
35
35
35 35
35 35
353535
35
35
35 35
35 35
35 35
35 35
42 42 42 42
33
33
B:11
B:11
B:11 B:11
37
39 39
OS
c
d d
d
d
d
31
c c
c
c
c
c
c
c
c
c
3b
b
b
b
b
b
b b
b
b b b b
bb
b
b
b b
b
b
b b
b
b b
b
b
b
b
b b
b
b
b
b
b
bb
3b
b
b
b
b
Dlv
D
lv
D
lv
D
lv
Dlv
Dlv
Dlv
KK
Dlv
Dlv
OS OS OS
(zb)
(zb)(zb)
(zb)
SEE ARCHITECTURAL COVE DETAIL FOR EXACT LENGTH.
MOUNT FIXTURE OPPOSITE SIDE OF WALL. TILT 45 DEGREES.
(zc)
D
lv
KEY PLAN
AB
N
INSTALL DIMMING CONTROL STATION SIMILAR TO
GRAFIX EYE QS. SYSTEM SHALL HAVE 4 CHANNEL
(ZONE) DIMMING CAPABILITY. ZONES SHALL BE
DESIGNATED WITH A "zn" NOTATION. FIELD
COORDINATE DIMMING SETTINGS WITH OWNER.
CONTROL EXTERIOR LIGHT FIXTURE BY
MULTI-POLE LIGHTING CONTACTOR IN MAIN
ELECTRICAL ROOM. REFER TO SHEET E101 FOR
ADDITIONAL INFORMATION.
MOUNT LIGHT FIXTURE ABOVE AND CENTERED
WITH MIRROR. VERIFY IN FIELD EXACT LOCATION
OF LIGHT FIXTURE.
REFER TO SHEET E200 FOR LIGHT FIXTURES IN
THIS AREA.
KEY NOTES:
1
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN - AREA 'A'
E100
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. ALL BRANCH CIRCUITRY SHOWN ON THIS
SHEET SHALL BE FED FROM BRANCH PANEL HA
UNLESS NOTED OTHERWISE.
3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS,
AND NIGHT LIGHTS SHALL HAVE UNSWITCHED
CONDUCTORS.
4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS
EMERGENCY ON ONLY. CONNECT TO NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
GENERAL NOTES:
2
3
2 2 2 2
1
3 3
4
4
4
4
09/21/20
18
LC
LIGHTING
CONTACTOR
PANEL
37
42424242424242
42
42
42 42 42 42
42 42
26
26
26
2626 26
2626 26
2626 26
2626 26
2626 26
2626 26
2626 26
26
26
26
28
28 28 28 28
28 28 28 28
28
28
28
28 28
28 28
28 28 28 28
28 28 28 28
32
32
32
32
32
32
32 32 32 32 32 32 32
32 32 32 32 32 32 32
30 30 30 30 30
30 30 30 30 30 30 30
30 30 30 30 30 3030 30
30
30
30 30 30 30 30 30
30
lv
(zc)
3a
3a
a
a a a
aa
a a a
aa a
a a
a a a
a a a
a a
3b
3c
3b3c
b b b
b
b
b b b b
b
b
b
b b
b
b
b b b b
c c c c c
c c c c
c c c c c c c
c
3d 3d
d
c c c c c c
d d d d d d
d d d d d
c
TC
PC
A:19
KEY PLAN
AB
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR LIGHTING PLAN - AREA 'B'
E101
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. ALL BRANCH CIRCUITRY SHOWN ON THIS
SHEET SHALL BE FED FROM BRANCH PANEL HA
UNLESS NOTED OTHERWISE.
3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS,
AND NIGHT LIGHTS SHALL HAVE UNSWITCHED
CONDUCTORS.
4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS
EMERGENCY ON ONLY. CONNECT TO NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
GENERAL NOTES:
CONTROL EXTERIOR LIGHT FIXTURE BY
MULTI-POLE LIGHTING CONTACTOR IN MAIN
ELECTRICAL ROOM.
PROVIDE MULTI-POLE CONTACTOR(S) AS REQUIRED
TO ALLOW FOR CONTROL OF EXTERIOR LIGHT
FIXTURES. TIE IN CONTACTOR WITH TIME CLOCK.
INSTALL PHOTOCELL ON NORTH FACE OF BUILDING
AS HIGH AS POSSIBLE. TIE PHOTOCELL INTO TIME
CLOCK.
TIME CLOCK SHALL BE SIMILAR TO TORK #DG100A.
FIELD COORDINATE TIME CLOCK SETTINGS WITH
OWNER.
KEY NOTES:
1
1111111
1
1
1 1 1 1
1 1
2
3
3
4
4
2
09/21/20
7 4 11 12 14 28
KEY PLAN
AB
N
C
E
H
J
M
O
S
B
A
F
T
G
L
N
K
R
P
37
37
39
39
41
41
TV
J
TV
a
b
c
d
9 6
D
IR-2
ECH-1
EWH-1
T
T
T
T
J WP
BUILDING
SIGN
J WP
BUILDING
SIGN
WP
GALLERY
LIGHT BOX
B:4
B:2
B:6, B:8
DC DC
DCDC DCDC DC DC DCDC DC DC DC
37 39 41
38
38 38
38
38
3030
30
32
32
32
34
34
32
32
36 36
36
15 15
15 1515 15 15
13
16
16
16 31
31
23
21
19
24 26
35
35
3535
35
2222
22
22
22
20
20
1818
18 18
31 2927
33
33
3333
HA:50
20
20
XX
30
28
32
13
13
13
13
17
17
19
19
10
+42"
HA:50
12
+42"
14
+42"
J
16
18 18
20
20
22
19
25
33
+48" +48"
36
30
23
70
70
e DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR POWER PLAN - AREA 'A'
E102
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. E.C. SHALL PROVIDE ALL RACEWAYS AND
CONDUCTORS FOR HVAC INTERLOCKS AND
THERMOSTATS. PRIOR TO ROUGH-IN
COORDINATE EXACT REQUIREMENTS WITH
M.C.
3. PRIOR TO ROUGH-IN VERIFY ALL LOCATIONS
AND MOUNTING HEIGHTS OF DEVICES WITH
OWNER AND ADJUST AS DIRECTED.
4. E.C. SHALL PROVIDE J-BOX ROUGH-IN @ +48"
AT EACH TSTAT LOCATION. ROUTE 3/4"
CONDUIT FROM J-BOX ROUGH-IN TO
MECHANICAL UNIT LOCATION. REFER TO
MECHANICAL PLANS FOR UNIT AND T-STAT
LOCATIONS.
5. LINEWORK SHOWN DASHED INDICATES
CONDUIT RUN UNDER SLAB.
6. ALL BRANCH CIRCUITRY SHOWN ON THIS
SHEET SHALL BE FED FROM BRANCH PANEL B
UNLESS NOTED OTHERWISE. REFERENCE
SHEET E200 FOR PANEL B LOCATION.
GENERAL NOTES:
ROUGH-IN DEVICE CONCEALED BEHIND
ELECTRICAL WATER COOLER. FIELD VERIFY
EXACT ROUGH-IN LOCATION.
GARAGE DOOR WITH SIDE MOUNTED MOTOR.
GARAGE DOOR OPERATOR. COORDINATE FINAL
LOCATION WITH OWNER/ARCHITECT PRIOR TO
INSTALLATION.
PROPOSED ROUTING FOR UNDERGROUND
CONDUITS TO FEED FLOOR MOUNTED
TELEPHONE/DATA/RECEPTACLE OUTLETS. ROUTE
CONDUIT TO NEAREST FULL HEIGHT WALL.
COORDINATE WITH ARCHITECT. 1-1/2"C MIN. SIZE
FOR DATA/TELEPHONE, 3/4" CONDUIT FOR POWER.
PROVIDE (4) OVERHEAD DOOR CONTROLLER
STATIONS, 1 FOR EACH OVERHEAD DOOR IN
SERVICE RECEPTION, MOUNTED ON WALL BEHIND
SERVICE WRITERS DESK. CONTROLLERS SHALL
OPERATE IN TANDEM WITH LOCAL CONTROLLERS
AT OVERHEAD DOORS.
INSTALL DEVICES CONCEALED BEHIND TV. INSURE
THAT DEVICE LOCATIONS DO NOT INTERFERE WITH
TV MOUNTING HARDWARE. REFER TO
ARCHITECTURAL INTERIOR ELEVATIONS.
ROUTE VESTIBULE BRANCH CIRCUITRY FROM
UNDER SLAB UP THROUGH COLUMN INTO
VESTIBULE CEILING SPACE. COORDINATE ALL
STRUCTURAL COLUMN PENETRATIONS WITH
STRUCTURAL CONTRACTOR.
PROVIDE DEDICATED 120 VOLT BRANCH CIRCUIT
TO SIGN THROUGH LIGHTING CONTACTOR.
INSTALL JUNCTION BOX ON STRUCTURE ABOVE
ABOVE ACCESSIBLE CEILING. EXTEND BRANCH
CIRCUITRY THRU WALL FRAMING TO SIGN. REFER
TO ARCHITECTURAL SHEETS FOR ADDITIONAL
INFORMATION. ELECTRICAL CONTRACTOR SHALL
MAKE FINAL CONNECTIONS. COORDINATE WITH
SIGN VENDOR.
TAMPER RESISTANT RECEPTACLE.
PROVIDE SURFACE-MOUNTED WEATHERPROOF
J-BOX WITH (2) DEDICATED 20 AMP CIRCUITS AS
SHOWN. J-BOX TO BE MOUNTED 2'-0" OFF THE
DEALER ENTRANCE. REFER TO ARCHITECTURAL
SHEET A-411 FOR ADDITIONAL INFORMATION.
FIELD VERIFY FLOOR BOX LOCATIONS WITH
OWNER.
PROVIDE FLUSH MOUNTED PULL BOXES WITHIN
ACCESSIBLE FURNITURE BASE FOR FEED-THRU TO
DEVICES MOUNTED IN FURNITURE. EXTEND
WIRING AND CONDUITS FROM PULL BOXES TO
DEVICES MOUNTED IN FURNITURE. FIELD
COORDINATE INSTALLATION WITH FURNITURE
SHOP DRAWINGS.
PROVIDE CONNECTION TO ELECTRIC HAND DRYER
PER MANUFACTURER'S WRITTEN INSTRUCTION.
FIELD VERIFY EXACT ROUGH-IN LOCATION.
PROVIDE CONNECTION TO DOOR OPERATOR PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
KEY NOTES:
1
2
3
4
5
6
7
8
9
10
11
10
8
8
12
12 13 13 13
1
22
3
3
4
4
4
4
4
4
5
4
4
4
6
7
9
11
11
1111
11
11
11
14
14
6
09/21/20
J
A
MDP
HA
T
UTILITY METER/
CT CABINET
18
T
RTU-7
7.5 TON
IR-2 IR-2
IR-3
BAF-1BAF-1 CF-1T
T
CF-1
IR-3COMS
UH-1
UH-1
IR-3
IR-3
IR-1
T
T
T EWH-1
BBS
SC
MS
CO
NOx
BBS
SC
MS
CO
NOx
OAOA
J J
J J
J J
J J
J
J WP
BUILDING
SIGN
a b
c d
J J
J J
DC DC KP DC DCDC DC DC DC DC
DCDC DC DC DC DCDCDC 13
TYPICAL
TYPICAL
21
21
21
21
23 23
21
25,27
29,31
2,4 6,8 10,12 14,16
18,20 22,24 26,28 30,32 34,36 38,40
HA:67,69,71 HA:73,75,77
33
33
35 35
37 37
39
39 41 41
43 45
47
49 51
53 55
57
59
61,63
#10
65,67
#10
69,71
#10
73
75
56
58
60
60
44,46
#10
48,50
#10
52,54
#10
42
42 42 42
42
42
66
FACP
S
FS TS
FS TS
HS
WP
TS PIV
77,79
81,83
62
WP
#10
#10
WP
WP
64
WP
64
WP
66 66 66
68
68
HA:54
70
70
70
70
72
e
KEY PLAN
AB
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR POWER & SYSTEMS PLAN - AREA 'B'
E103
1. REFERENCE SHEET E-001 FOR
LEGENDS, ABBREVIATIONS,
SPECIFICATIONS AND NOTES.
2. E.C. SHALL PROVIDE ALL RACEWAYS
AND CONDUCTORS FOR HVAC
INTERLOCKS AND THERMOSTATS.
PRIOR TO ROUGH-IN COORDINATE
EXACT REQUIREMENTS WITH M.C.
3. ALL WORK RECEPTACLES IN SERVICE
AND CLEAN-UP BAYS SHALL BE
MOUNTED AT 48" AFF.
4. PRIOR TO ROUGH-IN VERIFY ALL
LOCATIONS AND MOUNTING HEIGHTS
OF DEVICES WITH OWNER AND
ADJUST AS DIRECTED.
5. ALL ELECTRICAL DEVICES IN CAR
WASH BAY SHALL BE RATED FOR
WET LOCATION SERVICE. ALL
ELECTRICAL COVERS AND SWITCH
PLATES SHALL BE GALVANIZED
STEEL FOR SHOP AND ASSOCIATED
ROOMS.
6. E.C. SHALL PROVIDE J-BOX ROUGH-IN
@ +48" AT EACH TSTAT LOCATION.
ROUTE 3/4" CONDUIT FROM J-BOX
ROUGH-IN TO MECHANICAL UNIT
LOCATION. REFER TO MECHANICAL
PLANS FOR UNIT AND T-STAT
LOCATIONS.
7. LINEWORK SHOWN DASHED
INDICATES CONDUIT RUN UNDER
SLAB.
8. ALL BRANCH CIRCUITRY SHOWN ON
THIS SHEET SHALL BE FED FROM
BRANCH PANEL A UNLESS NOTED
OTHERWISE.
GENERAL NOTES:
VARIABLE SPEED FAN CONTROLLER. PROVIDE 3/4"
EMT CONDUIT FROM FAN TO CONTROLLER.
COORDINATE CONDUCTOR REQUIREMENTS WITH
M.C. CONTROLLER AND FAN BY M.C. CONDUIT AND
CONDUCTORS BY E.C.
MOUNT ALL DATA AND RECEPTACLES FOR WORK
STATIONS AT 48" AFF. RECEPTACLES SHALL BE
GFI TYPE. PRIOR TO ROUGH-IN VERIFY FINAL
LOCATION AND HEIGHT WITH OWNER.
TIRE CHANGER AND WHEEL BALANCER.
COORDINATE EXACT REQUIREMENTS WITH
OWNERS EQUIPMENT VENDOR.
SERVICE FEEDER TO UTILITY TRANSFORMER.
REFER TO CIVIL DRAWINGS FOR LOCATION OF
UTILITY TRANSFORMER. REFER TO ELECTRICAL
RISER DIAGRAM FOR ADDITIONAL INFORMATION.
GARAGE DOOR WITH SIDE MOUNTED MOTOR.
GARAGE DOOR OPERATOR. COORDINATE FINAL
LOCATION WITH OWNER/ARCHITECT PRIOR TO
INSTALLATION.
IR HEATERS. PROVIDE EMT RACEWAYS AND LINE
VOLTAGE CONDUCTORS BETWEEN BURNERS,
DRAFT FANS AND IRTCP. PROVIDE LOW VOLTAGE
RELAYS FOR IR TEMPERATURE CONTROL SYSTEM
FOR SENSORS. COORDINATE WITH HVAC
CONTRACTOR. SEE DETAIL #1 ON SHEET E002.
PROVIDE (5) OVERHEAD DOOR CONTROLLER
STATIONS, 1 FOR EACH OVERHEAD DOOR IN
SERVICE RECEPTION. CONTROLLERS SHALL
OPERATE IN TANDEM WITH LOCAL CONTROLLERS
AT OVERHEAD DOORS.
VEHICLE FRAME RACK: (1) 30 AMP DISCONNECT
208V, 1 PHASE MOUNTED ON WALL. PROVIDE
CONDUIT ROUTED UNDERGROUND TO STUB-UP
POINT IN RACK SUPPORT LOCATION. VERIFY
EXACT REQUIREMENTS WITH LIFT PROVIDER.
TYPICAL.
PROVIDE DEDICATED 120 VOLT BRANCH CIRCUIT
TO SIGN THROUGH LIGHTING CONTACTOR.
INSTALL JUNCTION BOX ON STRUCTURE ABOVE
ABOVE ACCESSIBLE CEILING. EXTEND BRANCH
CIRCUITRY THRU WALL FRAMING TO SIGN. REFER
TO ARCHITECTURAL SHEETS FOR ADDITIONAL
INFORMATION. ELECTRICAL CONTRACTOR SHALL
MAKE FINAL CONNECTIONS. COORDINATE WITH
SIGN VENDOR.
PROVIDE 208V 1PH CONNECTION FOR LIFT. FIELD
VERIFY EXACT REQUIREMENTS WITH LIFT
SUPPLIER.
PROVIDE 208V 1PH CONNECTION FOR PRESSURE
WASHER. FIELD VERIFY EXACT REQUIREMENTS
WITH PRESSURE WASHER SUPPLIER.
PROVIDE HOA MOTOR STARTER FOR CO
EXTRACTION SYSTEM. FIELD VERIFY
REQUIREMENTS AND LOCATION WITH OWNER'S CO
EXTRACTION SYSTEM VENDOR.
KEY NOTES:
1
2
3
4
5
6
7
8
9
10
11
12
13
1
1
2
2
3
3
3
4
55
5
5 5
5
5 5
6
6
66
6
6
5
7
7
7 7
7
7
9 9 9 9
9
9
9 9
9
1111
11
12
12
13
09/21/20
41 41
41
41
41
41
41
41
41
41 41
41 41
41
41
41 41
41 41
41 41
4141
41 41 41 41
41 41 41 41
41 41 41 41
39 39 39
3939 39
39 39 39
39 39 39
39 39 39
39 39 39
39 39 39
39 42
4239
39 42
39 42
3939 39 39 39 39 39 37 37 37 37 37 37 37 37 37
37 37 37 37 37 37 37 37 37 39 39
39
39 39 39
39
37 37 37 37 37 37 37 37 37 39 39 39 39
3939 39 39 393939 37
39 39 39 39 39 39 39
3939 39 39 39 39
39 39 39 39
41
41
41
41
41
41
41
41
41
41
41
41
41
41
41
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
42 42 42 42
39
39
39
39
39
39
41
41 41
41
41
41 41
41 41
(za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za)
(za)
(za)
(za)
(za)
(za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za) (za)
(za) (za) (za) (za) (za) (za) (za) (za)(za)(za)
(za)
(za)
(za) (za) (za)(za) (za) (za) (za)
(za) (za) (za)
(za) (za) (za) (za) (za) (za) (za)
(za) (za) (za) (za)
(za) (za) (za)(za) (za) (za) (za)
D lv
D
lv
D
lv
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc) (zc)
(zc) (zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(zc)
(za) (za) (za)
(za) (za)
(za) (za) (za)
(za) (za) (za)
(za) (za) (za)
(za) (za)
(za) (za) (za)
OS
OS
OS
KEY PLAN
C
D
N
11 12 14 7 2
C
E
H
J
M
O
S
B
A
T
G
L
N
F
T
B
B:43
B:43
B:43
B:43
+42" +42" B:49
B:51
B:51
B:53
B:53
B:53
B:46
B:46
B:46
B:46
B:48 B:50
B:53
B:44
B:44 B:44
MS-1
B:46
B:45 B:47
+42"
H
J
M
O
S
T
G
L
N
11 7 2
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
2 SCALE: 1/8" = 1'-0"
MEZZANINE LEVEL LIGHTING PLAN - AREA 'C'
1 SCALE: 1/8" = 1'-0"
POWER & SYSTEMS PLAN - AREA 'C'
MEZZANINE LEVEL
E200
LIGHTING DESIGNATED WITH A "zn" NOTATION
SHALL BE CONTROLLED BY DIMMING CONTROL
STATION LOCATED IN SALES MANAGER 104.
CONTROL EXTERIOR LIGHT FIXTURE BY
MULTI-POLE LIGHTING CONTACTOR IN MAIN
ELECTRICAL ROOM. REFER TO SHEET E101 FOR
ADDITIONAL INFORMATION.
LIGHTS IN VEHICLE DELIVERY CENTER 125
CONTROLLED BY SWITCH IN THIS ROOM AS SHOWN
ON SHEET E100.
ROUTE (2) 3" CONDUITS FROM IT CLOSET TO
TELECOMMUNICATIONS UTILITY TIE-IN POINT.
REFER TO CIVIL DRAWINGS FOR ADDITIONAL
INFORMATION. PROVIDE PULL STRING AND
BUSHING FOR CONDUITS.
3
4" PLYWOOD WITH 2 COATS OF FIRE RETARDANT
PAINT. PLYWOOD TO EXTEND FROM FLOOR TO
CEILING.
FURNISH AND INSTALL ALL NECESSARY POWER
CONDUIT AND WIRING BETWEEN OUTDOOR UNIT
AND INDOOR UNIT.
KEY NOTES:
1
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. ALL BRANCH CIRCUITRY SHOWN ON THIS
SHEET SHALL BE FED FROM BRANCH PANEL HA
UNLESS NOTED OTHERWISE.
3. ALL EXIT SIGNS, EMERGENCY LIGHTING UNITS,
AND NIGHT LIGHTS SHALL HAVE UNSWITCHED
CONDUCTORS.
4. TYPE EM3 LIGHT FIXTURES SHALL OPERATE AS
EMERGENCY ON ONLY. CONNECT TO NEAREST
UNSWITCHED LIGHTING BRANCH CIRCUIT.
GENERAL NOTES:
2
3
3
1
1
1
2
2
2
2
2 2 2 2
4
5
4 5
6
6
09/21/20
HB:43,45,47
#10
HB:49,51,53
#10
A:15
DRYER
IWH
HA:44
A:42
A:74
A:74
A:74
A:74
A:76 A:78 A:80 A:82
+42" +42" +42"
KEY PLAN
C
D
N
28
28
28 28 28 28 28 28 28 28 28
28 28
28 28 28
28
28
28 28 28 28 28 28 28 28 28
d d d d d d d d d d
d d d d dd d d d d
REFER TO SHEET E101 FOR SWITCHLEG 'd' SWITCH LOCATION(S)
OS
OS
OS
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
102003951 SCALE: 1/8" = 1'-0"
MEZZANINE LEVEL POWER AND SYSTEMS PLAN - AREA 'D'
2 SCALE: 1/8" = 1'-0"
MEZZANINE LEVEL LIGHTING PLAN - AREA 'D'
E201
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. E.C. SHALL PROVIDE ALL RACEWAYS AND
CONDUCTORS FOR HVAC INTERLOCKS AND
THERMOSTATS. PRIOR TO ROUGH-IN
COORDINATE EXACT REQUIREMENTS WITH
M.C.
3. PRIOR TO ROUGH-IN VERIFY ALL LOCATIONS
AND MOUNTING HEIGHTS OF DEVICES WITH
OWNER AND ADJUST AS DIRECTED.
4. E.C. SHALL PROVIDE J-BOX ROUGH-IN @ +48"
AT EACH TSTAT LOCATION. ROUTE 3/4"
CONDUIT FROM J-BOX ROUGH-IN TO
MECHANICAL UNIT LOCATION. REFER TO
MECHANICAL PLANS FOR UNIT AND T-STAT
LOCATIONS.
5. LINEWORK SHOWN DASHED INDICATES
CONDUIT RUN UNDER SLAB.
GENERAL NOTES:
09/21/20
RTU-1
RTU-2
RTU-3
RTU-4
RTU-5
20 TON
5 TON
5 TON
8.5 TON
5 TON
EF-6
RTU-7
7.5 TON
RTU-6
5 TON
IH-1
EF-1
EF-2
IH-2
EF-3
EF-7
EF-5
MS-1
EF-4
M
M
M
EF-8
EF-9
S SD
S SD
S SD
S SD
S SD
S SD
WP
WP
WP
WP
WP
WP
WP
WP
HA:8,10,12
HA:2,4,6
HA:13,15,17
HA:7,9,11
HA:1,3,5
#6
HA:14,16,18
HA:20,22,24
#10
#10
3/4"C, 3#16 TO
INDOOR MS-1 UNIT
HA:25,27,29
WP
B:1
B:3
WP
B:5
WP
B:5
WP
A:1WP
A:1
WP
A:1
WP
A:1
A:1
A:1
A:1
A:7
A:5
A:9
A:13
A:11
A:3
B:7,9
#10
E.C. SHALL PROVIDE COMBINATION MOTOR
STARTERS WITH OL AND AUX CONTACTS FOR EF-1
AND EF-3. AUTO MODE SHALL BE WIRED TO CO
DETECTOR. FANS SHALL START UPON CO ALARM.
CO DETECTOR BY M.C.
FURNISH AND INSTALL ALL NECESSARY POWER
CONDUIT AND WIRING BETWEEN OUTDOOR UNIT
AND INDOOR UNIT.
ROUTE POWER THROUGH LINE VOLTAGE
THERMOSTAT. REFER TO HVAC DRAWINGS FOR
THERMOSTAT LOCATION.
EF-2, EF-4, EF-5, EF-6, EF-7, & EF-8 SHALL RUN
CONTINUOUSLY.
E.C. SHALL INTERLOCK WIRING BETWEEN EXHAUST
FAN AND MOTORIZED LOUVER. LOUVER SHALL
OPEN WHEN FAN IS RUNNING. FAN AND DAMPER
MOTOR SHALL BE PROVIDED BY M.C.
KEY NOTES:
1
1. REFERENCE SHEET E-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEERD
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 3/32" = 1'-0"
ROOF ELECTRICAL PLAN
GENERAL NOTES:
E300
2
3
4
1
1
2
3
4
4
4
4
4
4
5
5
5
5
09/21/20