HomeMy WebLinkAboutNAPLETON KIA OF CARMEL-MECH-20190708MECHANICAL SPECIFICATIONS GENERAL 1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS EQUIPMENT AND MATERIALS. PROJECT DOES ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR SUBSTITUTIONS OF EQUAL EQUIPMENT AND MATERIALS AGAINST THE BASIS OF DESIGN. BIDDERS SHALL LIST ALL SUBSTITUTIONS ON BID. ENGINEER RESERVES THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS. 2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY CONSUMING OR PRODUCING ITEMS AND FOR ALL DUCT ACCESSORIES, INSULATION, VAV BOXES, REGISTERS, GRILLES, DIFFUSERS AND LOUVERS. SUBMITTALS SHALL BE DELINEATED WITH TAGS INDICATED ON PRINTS, CONTRACTORS NAME, PROJECT NAME. CLEARLY INDICATE ALL MODEL NUMBERS AND ALL ACCESSORIES AND OPTIONS BEING PROVIDED. SUBMISSIONS SHALL BE IN PDF FORMAT. ALL EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS OR APPROVED EQUAL. ENGINEER RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE ITEM. 3. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL REQUIRED ELECTRICAL SUPPORT NEEDED FROM THE ELECTRICAL CONTRACTOR. ENSURE ALL SUBMITTALS FOR POWERED COMPONENTS AND CONTROLS ARE PROVIDED AND FULLY COORDINATED WITH ELECTRICAL CONTRACTORS. 4. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY WAY AFFECT THE EXECUTION OF HIS WORK. HE SHALL ALSO EXAMINE THE DRAWINGS AND SPECIFICATIONS FOR OTHER BRANCHES OF WORK MAKING REFERENCE TO THEM FOR DETAILS OF EXISTING BUILDING CONDITIONS. NO EXTRAS WILL BE ALLOWED FOR FAILURE TO INCLUDE ALL REQUIRED WORK IN THE BID. CONTRACTOR SHALL GUARANTEE ALL LABOR AND MATERIALS ENTERING INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR FROM DATE OF ACCEPTANCE. 5. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE EXACT QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. M.C. SHALL PROVIDE AND PAY FOR ALL REQUIRED PERMITS. 6. PRIOR TO WORK COORDINATE ALL OPENINGS AND INSTALLATIONS OF DUCT, PIPING, EQUIPMENT, CONTROLS, DIFFUSERS AND GRILLES WITH G.C. AND OTHER TRADES. PROVIDE INSTALLATIONS WITH PROPER MANUFACTURERS RECOMMENDED CLEARANCES. 7. UPON COMPLETION OF THE MECHANICAL INSTALLATION, DEMONSTRATE TO THE ENGINEER AND THE OWNER'S SATISFACTION THAT THE SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE WITH THE DRAWINGS, SPECIFICATIONS AND APPLICABLE CODES. DEMONSTRATE THE DYNAMIC OPERATION OF EACH SYSTEM. VERIFY PROPER OPERATION OF EQUIPMENT, FILTERS ARE CLEAN AND COMPONENTS OF THE SYSTEM ARE INSTALLED AND ADJUSTED IN FULL ACCORDANCE WITH MANUFACTURER RECOMMENDATIONS. 8. ALL WORK SHALL BE IN FULL ACCORDANCE WITH 2014 INDIANA MECHANICAL CODE (2012 INTERNATIONAL MECHANICAL CODE), INDIANA ENERGY CODE (ASHRAE 90.1-2007) PERTINENT STATE, COUNTY, CITY CODES AND ORDINANCES AND INDIANA AMENDMENTS. 9. MECHANICAL CONTRACTOR SHALL ENSURE EMPLOYEES ARE MEETING AND DOCUMENTING ALL OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS REQUIRED BY LAW AND BY CONTRACT. PERSONAL PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND UTILIZED AS REQUIRED. MECHANICAL CONTRACTOR SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE TO COMPLY WITH OSHA REQUIREMENTS. EQUIPMENT 1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO LISTED EQUIPMENT SHALL BE AT RISK OF CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS. 2. PROVIDE SUBMITTALS TO ELECTRICIAN AS REQUIRED FOR COORDINATION OF ALL ELECTRICAL POWER WIRING. INCLUDE WIRING DIAGRAMS AND CABLING REQUIREMENTS FOR REFERENCE. COORDINATE ALL INTERLOCKS AS NEEDED. PROVIDE SINGLE POINT CONNECTION KITS AS NEEDED. 3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND CLEARANCE REQUIREMENTS. PROVIDE ALL REQUIRED MOUNTING OR HOUSEKEEPING PADS. G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR MOUNTED EQUIPMENT. M.C. SHALL PROVIDE ALL HOISTING AND RIGGING NEEDED TO SET ALL HVAC EQUIPMENT. 4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED TO PREVENT OBJECTIONABLE NOISE AND/OR VIBRATION. M.C. SHALL PROVIDE VIBRATION PADS, SPRING ISOLATORS, ATTENUATORS AND ACCESSORIES AS NEEDED. DUCTWORK 1. CONCEALED ROUND DUCTWORK SHALL BE CONSTRUCTED PER SMACNA LOW PRESSURE STANDARDS 1" PRESSURE CLASS, 5' MAXIMUM JOINT LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP LOCK PIPE AND ADJUSTABLE FITTINGS. 2. EXPOSED ROUND DUCTWORK (OR WHERE SPIRAL IS INDICATED ON THE PLANS) SHALL BE LINDAB OR EQUAL GALVANIZED STEEL CONFORMING TO ASTM STANDARDS A653 AND A924 GASKETED SPIRAL DUCTING WITH NO SEALER. EDPM RUBBER GASKET SHALL BE U.L. CLASSIFIED RATING OF FLAME SPREAD 0 AND SMOKE DEVELOPED 5 IN ACCORDANCE WITH ASTM STANDARD E84-91A SMACNA LEAKAGE CLASS 3. FITTINGS SHALL BE MANUFACTURED USING ONE OR MORE OF THE FOLLOWING CONSTRUCTION METHODS: OVERLAPPED EDGES STITCH WELDED ALONG THE ENTIRE LENGTH OF THE FITTING, STANDING SEAM GORE LOCKED AND INTERNALLY SEALED, BUTTON PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED AND CONTINUOUSLY STITCH WELDED. 3. PROVIDE SHEET METAL 90 FOR ALL TURNS GREATER THAN 45 DEGREES. DO NOT USE FLEXIBLE DUCT FOR CHANGES IN DIRECTION GREATER THAN 45 DEG. 4. PROVIDE MANUAL BALANCING DAMPERS FOR ALL SUPPLY AIR RUNS. ROUND DAMPERS SHALL BE SECURED ON BOTH SIDES OF DUCT AND SHALL CONTAIN LOCKING HANDLE. SPIRAL DUCTS SHALL USE SPIRAL STYLE DAMPERS WITH FULL WIDTH SHAFTS AND NYLON BEARINGS AT EACH END. RECTANGULAR DUCTS SHALL USE MULTI OR SINGLE BLADE WELDED FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER HANDLES LOCATED IN INSULATED DUCTING. DO NOT INSTALL DAMPERS IN NON ACCESSIBLE LOCATIONS. PROVIDE INTEGRAL DAMPERS WITH DIFFUSER IN NECK IF NO ACCESSIBLE LOCATION IS POSSIBLE. ALL SUPPLY AIR RUNS SHALL HAVE MEANS OF BALANCE. RETURN AND EXHAUST AIR RUNS SHALL CONTAIN DAMPERS WHERE SHOWN ON PLANS. 5. INSULATED FLEXIBLE DUCTING SHALL NOT EXCEED 25 FEET. ALL FLEX SHALL BE LISTED FLEXIBLE DUCT, FLEXIBLE CONNECTORS ARE NOT ACCEPTABLE. FLEXIBLE DUCT EQUAL TO FLEXIBLE DUCT CLASS 1 AIR DUCT, DOUBLE LAMINATED POLYESTER FILM ON STEEL WIRE REINFORCING, INSULATED WITH SCRIM REINFORCED METALIZED POLYESTER OUTER FIRE RETARDANT JACKET. R-4.2 FOR CONDITIONED SPACES AND R-6.0 FOR ANY SPACES OUTSIDE BUILDING THERMAL ENVELOPE. FLEX DUCTS SHALL NOT BE RUN THROUGH WALLS OR FLOORS. PROVIDE HARD DUCTED SLEEVES AS NEEDED. 6. RECTANGULAR DUCTWORK SHALL BE CONSTRUCTED IN ACCORDANCE WITH SMACNA LOW PRESSURE DUCT STANDARDS, +/- 1.0" W.C. FROM ASTM A 653/A 653M G-90 COATED GALVANIZED SHEET STEEL. SEAMS SHALL BE PITTSBURGH CONSTRUCTION, NO BUTTON PUNCH OR SNAP LOCK SEAMS ARE ACCEPTABLE. SEAL ALL TRANSVERSE AND LONGITUDINAL SEAMS WITH WATER BASED DUCT SEALER, SEAL CLASS B. GAUGE AND JOINT CLASSIFICATIONS ACCEPTABLE ARE AS FOLLOWS, ALL SECTION LENGTHS ARE 48" MAXIMUM, REFER TO SMACNA RIGIDITY TABLES FOR GAUGES ON LONGER SECTIONS IF REQUIRED: < 12" 26 GAUGE, FLAT S AND DRIVE 12"-24" 24 GAUGE, FLAT S AND DRIVE 25"-34" 22 GAUGE, STANDING S AND FLAT DRIVE 34"-40" 22 GAUGE, STANDING S AND STANDING DRIVE >40" REFER TO SMACNA FOR STANDARDS. 7. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS." PROVIDE GALVANIZED MINIMUM 22 GAUGE 1" WIDE STRAP TO HANG RECTANGULAR DUCTWORK SMALLER THAN 30" WIDE. DUCT HANGERS FOR RECTANGULAR SHEET METAL DUCTS 30" AND LARGER SHALL BE TRAPEZE STYLE USING UNI-STRUT AND 3/8" OR 1/2" ROD. PROVIDE GRIPPLE, DURODYNE OR EQUAL CABLE HANGERS FOR HANGING ROUND DUCTWORK. SUPPORT ALL HANGERS FROM STRUCTURE PER SMACNA STANDARDS.HANGERS FOR SPIRAL DUCTS GREATER THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD AND DUCT CLAMP. FLEXIBLE DUCTING SHALL BE SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP. ALL INTERVALS ARE PER SMACNA. DUCT ACCESSORIES 1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT FIRE RATED ASSEMBLY PENETRATIONS IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE AND WHERE SHOWN ON PLANS. 2. PROVIDE FLASHING MATERIALS AND OR SLEEVES AS REQUIRED FOR ALL DUCT PENETRATIONS OF NON RATED ELEMENTS. EXPOSED PENETRATIONS SHALL BE FLASHED WITH SHEET METAL TIGHT TO WALLS. 3. PROVIDE HIGH EFFICIENCY TAKE OFFS, PEAL AND STICK STYLE ATTACHED TO RECTANGULAR DUCTING WITH SHEET METAL SCREWS FOR ALL ROUND SUPPLY AIR TAKE OFFS AND SADDLES. DUCT INSULATION 1. ALL DUCT INSULATION MATERIALS SHALL HAVE A FLAME SPREAD RATING OF 25 OR LESS (ON THE FLAME SPREAD TEST SCALE) AND SMOKE DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST SCALE) OR AS DEFINED BY NFPA 255 STANDARD METHOD OF TESTING OF SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS, LOCAL CODES AND LOCAL AUTHORITIES HAVING JURISDICTION. DUCT WRAP SHALL BE FIBERGLASS MATERIAL PER ASTM C-411,ASTM C-1104,ASTM C665, ASTM C-1338, ASTM E-84, UL723, NFPA 90A,CAN/ULC S102-1188,ASTM C1290, ASTM C553, ASTM C1136. 2. INSULATION: INSTALL ALL INSULATION IN STRICT ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO SAGGING, FRAYED OR TORN INSULATION WILL BE EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS DUCTWORK SHALL BE INSULATED AS FOLLOWS: SA/RA- INTERNAL: 1-1/2" FIBERGLASS DUCT WRAP WITH FSK FACING, 75 #/FT3 MINIMUM APPLIED R-3.5 INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURERS REQUIREMENTS. SA/RA IN UNCONDITIONED OR ATTIC SPACES OUTSIDE THE BUILDING INSULATION ENVELOPE; 2" MINIMUM R-6 AS APPLIED FSK DUCT WRAP. LINERS: DUCT LINER FOR PLENUMS AND RTU DROPS DUCTS SHALL BE MINIMUM 1” THICK, 1-1/2 # DENSITY PER CU. FT., HAVING MAT FACED OR MONOLITHIC CONSTRUCTION WITH SKIN SMOOTH MICROBIAL SURFACE TO WITHSTAND VELOCITIES TO 4000 FPM. INSULATION SHALL FIT SNUGLY AGAINST THE INTERIOR DUCT SURFACES, AND BE FASTENED TO THE DUCT WITH A 50% HEAVY COAT OF RECOMMENDED ADHESIVE AND METAL FASTENERS WHICH DO NOT PIERCE THE DUCT, SPACED AT 12” CENTERS. ALL EXPOSED EDGES OF THE INSULATION SHALL BE COATED WITH MANUFACTURED RECOMMENDED ADHESIVE. SIZES ON PLANS INDICATE FREE AREA. EXTERIOR INSULATE WITH CONTINUOUS MINIMUM R-6 POLYISOCYANURATE FOAM SHEATHING COVERED WATER TIGHT IN VENTURE CLAD 1577CW CLADDING.. CHECK TEST AND START UP REQUIREMENTS 1. LABEL ALL MAJOR PIECES OF EQUIPMENT WITH LAMACOID PLASTIC, BLACK WITH WHITE LETTERS. SIZE TO BE CONSISTENT WITH EQUIPMENT BEING LABELED. LENGTH AND WIDTH VARY FOR REQUIRED LABEL CONTENT. THERMOSTAT AND SENSOR LABELS SHALL BE ADJUSTED TO PROVIDE ESTHETIC APPEARANCE. 2. PROVIDE AIR BALANCE BY CONTRACTOR. CONTRACTOR SHALL BALANCE SUPPLY, RETURN, OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN ACCORDANCE WITH CURRENT SMACNA, NEEB OR AABC STANDARDS TO DESIGN VALUES AND PROVIDE WRITTEN REPORT TO ARCHITECT. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL DEVICES, DRIVES, SHEAVES, MOTOR CHANGES AND REWORK AS REQUIRED TO MEET DESIGN REQUIREMENTS. 3. TEMPERATURE CONTROL WORK SHALL BE THE RESPONSIBILITY OF THE HVAC CONTRACTOR. PROVIDE ALL COMPONENTS INCLUDING T/S, T/S WIRE (PLENUM RATED IN RA PLENUMS), SWITCHES, ACTUATORS ETC. AS REQUIRED FOR A COMPLETE SYSTEM. PRIOR TO ROUGH-IN COORDINATE FINAL LOCATION FOR ALL CONTROLS WITH OWNERS REPRESENTATIVE. 4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION AND MAINTENANCE MANUALS, AIR BALANCE REPORT AND AS BUILT DRAWINGS. PROVIDE (1) TRAINING SESSION TO OWNER SELECTED PERSONNEL AS REQUESTED AND PROVIDE WARRANTY INFORMATION FOR ALL MANUFACTURERS WARRANTED EQUIPMENT PIPING 1. REFRIGERATION PIPING; A. SYSTEMS 5 TONS OR LESS; MANUFACTURED REFRIGERANT LINE SETS: ANNEALED-COPPER SUCTION AND LIQUID LINES FACTORYCLEANED, DRIED, PRESSURIZED WITH NITROGEN, SEALED, AND WITH SUCTION LINE INSULATED. PROVIDE IN STANDARD LENGTHS FOR INSTALLATION WITHOUT JOINTS, EXCEPT AT EQUIPMENT CONNECTIONS OR ACCESSIBLE LOCATIONS. CONNECTIONS AND WROUGHT-COPPER FITTINGS WHERE REQUIRED SHALL BE BRAZED WITH MINIMUM 8% SIL-FLOS. B. INSULATION; SUCTION AND ALL DUCTLESS SPLIT OR VRF LINES; MINIMUM 1/2" THICK WALL INSULATION SHALL BE A FLEXIBLE, CLOSED-CELL ELASTOMERIC PIPE INSULATION, AP ARMAFLEX OR AC ACCOFLEX. ADHESIVE SHALL BE ARMAFLEX 520, 520 BLACK OR 520 BLV ADHESIVE. THE INSULATION MUST CONFORM TO ASTM C534 GRADE 1, TYPE I ARMAFLEX AND BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. (3/8" WALL WILL NOT BE ACCEPTED). C. ALL INSULATION EXPOSED TO OUTDOORS SHALL BE EITHER PVC LAGGED OR SHALL BE PAINTED WITH ARMA-FINISH FR UV PROTECTING PAINT. D. LINES SHALL BE RUN KINK FREE AND GENERALLY CONTINUOUS AND AT 90 DEGREE ANGLES TO STRUCTURE. AVOID JOINTS WHEN POSSIBLE. ALL REQUIRED JOINTS SHALL BE MADE IN ACCESSIBLE LOCATIONS OR M.C. SHALL PROVIDE ACCESS PANELS AS NEEDED. ALL BENDS SHALL BE MADE WITH LONG RADIUS FITTINGS OR WITH MECHANICAL BENDING TOOL TO PROVIDE SMOOTH LONG RADIUS TURNS. SUPPORT ALL PIPING WITHOUT CRUSHING OR DEPRESSING INSULATION. USE REFRIGERATION STYLE CUSH CLAMPS MOUNTED TO STRUT, DO NOT LAY PIPING ON STRUCTURAL BUILDING MEMBERS. SLEEVE ALL PENETRATIONS AND SEAL WATER TIGHT. E. PRESSURE TEST, TRIPLE EVACUATE AND PREPARE ALL PIPING IN STRICT ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. 2. CONDENSATE PIPING A. PROVIDE TRAPS BUILT FROM INDIVIDUAL FITTINGS ON ALL EVAPORATOR DRAIN PANS MINIMUM DEPTH 1.5 TIMES BLOWER BLOCKED TIGHT STATIC PRESSURE. ALL TRAPS SHALL BE CONSTRUCTED WITH PVC 90S (MANUFACTURED RUNNING TRAP FITTINGS ARE NOT ACCEPTABLE). PROVIDE ALL TRAPS WITH CLEAN OUTS AND REMOVABLE CAPS AS NEEDED FOR MAINTAINING LINES. B. HVAC CONTRACTOR SHALL COORDINATE CONDENSATE DISPOSAL POINTS WITH P.C. HVAC CONTRACTOR IS RESPONSIBLE FOR PIPING FROM EVAPORATOR COILS TO DISPOSAL POINT. P.C. IS RESPONSIBLE FOR STAND PIPES, FLOOR AND HUB DRAINS AS NEEDED. C. POLYVINYL CHLORIDE DRAIN, WASTE AND VENT PIPE (PVC) SCHEDULE 40 MINIMUM SIZE 3/4" . INSULATED IN RETURN AIR PLENUMS. D. PROVIDE CONDENSATE PUMPS AS REQUIRED WITH HIGH LEVEL SHUT DOWN SWITCHES INTERLOCKED TO A/C UNITS. E. PITCH ALL PIPING MINIMUM 1 4" PER FOOT. SUPPORT PIPING AT MINIMUM 5'-0" INTERVALS. SECURE FINAL CONNECTION AT SEWER WITH MINIMUM 1-1/2" AIR GAP CONNECTION. F. INSULATE ALL PIPING IN RA PLENUMS AND ABOVE HARD CEILINGS WITH MINIMUM 3/8" WALL ARMAFLEX INSULATION. FIRE STOPPING a. FIRE STOPPING SYSTEMS SHALL BE IN FULL COMPLIANCE WITH SECTIONS 713 OF THE IBC AND SECTION 607 OF THE IMC. b. CONTRACTOR SHALL MAKE REFERENCE TO ARCHITECTURAL PLANS AND PROVIDE ALL REQUIRED FIRE STOPPING. c. CONTRACTOR SHALL PROVIDE FULL SUBMITTAL INDICATING METHODS OF CONSTRUCTION AND UL LISTING OF EACH SYSTEM. d. DUCTS AND AIR TRANSFER OPENINGS. PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTIONS 713.2 THROUGH 713.3.3 OF THE IBC. PENETRATIONS OF HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND NOT REQUIRED TO BE PROTECTED WITH FIRE DAMPERS BY OTHER SECTIONS OF THE IBC CODE, SHALL COMPLY WITH SECTIONS 713.4 THROUGH 713.4.2.2 OF THE IBC. DUCTS AND AIR TRANSFER OPENINGS THAT ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION 716. e. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION FIRE/SMOKE DAMPERS AND CEILING RADIATION DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION 607 OF THE IMC. AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND LISTING. f. ACCESS DOORS SHALL BE PERMITTED IN CEILINGS OF FIRE-RESISTANCE-RATED FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES PROVIDED SUCH DOORS ARE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL 263 AS HORIZONTAL ASSEMBLIES AND LABELED BY AN APPROVED AGENCY FOR SUCH PURPOSE. ALL ACCESS DOORS SHALL BE PROVIDED BY TRADE MAKING PENETRATIONS. ROOF JACK, MATCH ROOF COLOR ROOF TOP UNIT REVOLUTIONS PER MINUTE SUPPLY AIR FAN RJ RPM RTU SAF STATIC PRESSURESP TCC TSP TOTAL STATIC PRESSURE WALL CAPWC WALK IN COOLERWIC WALK IN FREEZERWIF ET EXPANSION TANK ELECTRIC WATER COOLEREWC TMV THERMOSTATIC MIXING VALVE AFF ABOVE FINISH FLOOR URINAL SK SINK MOP SINK WATER CLOSET WATER HEATER CO CLEAN OUT PLUMBING CONTRACTOR STORM DRAIN VENT THROUGH ROOF SANITARY SEWER ST STORAGE TANK SD SAN CW COLD WATER DOMESTIC PC PRV PSI PRESSURE RELEIF VALVE POUNDS PER SQUARE INCH MS LAV LAVATORY HWS HWR HOT WATER RETURN DOMESTIC HOT WATER SUPPLY DOMESTIC GPM GALLONS PER MINUTE WH GC GENERAL CONTRACTOR VTR UR WC FOOTFT INCHIN LEAVING AIR TEMPERATURE LINEAR SLOT DIFFUSER MANUAL LAT IR MAN LS 1000 BTUH MECHANICAL CONTRACTOR MOTOR CONTROL CENTER MBH MC MCC MFR MANUFACTURER PRESSURE DROP POOL DEHUMIDIFICATION UNIT PACKAGE TERMINAL AIR CONDITIONER POUNDS PER SQUARE INCH PRESSURE RELEIF VALVE PD PDU PTAC PSI PRV INFRA-RED AIR HANDLING UNIT ACCU AHU BOTTOM OF DUCT BACKDRAFT DAMPER BOD BDD COMBUSTION AIR CUBIC FEET PER MINUTE CA CFM AIR COOLED CONDENSING UNIT ENTERING AIR WET BULB ENTERING AIR DRY BULB ROUND EAWB EADB Ø DRY BULBDB ELECTRICAL CONTRACTOREC ELECTRIC WALL HEATER EXHAUST FANEF EWH HOOD EXTERNAL STATIC PRESSURE ELECTRIC REHEAT COIL H ESP ERC EG EXHAUST GRILLE OR REGISTER FURNACE FCU F FIRE DAMPER OR FLOOR DRAIN FIRE AND SMOKE DAMPER FD FD/SD FEET PER MINUTEFPM FAN COIL UNIT ABBREVIATIONS UNLESS OTHERWISE NOTEDUON TEMPERATURE CONTROL CONTRACTOR REDUCED PRESSURE ZONED BACKFLOWRPZB FSK FOIL SCRIM VAPOR BARRIER RETURN AIRRA SUPPLY AIRSA EACHEA OUTSIDE AIROA VARIABLE AIR VOLUME BOXVAV FAN POWERED VAV BOXFPVAV DEGREES FARENHEITDEG F AIR COOLED CONDENSING UNIT MANUAL VOLUME DAMPER LOCKING WITH SHAFT FIRE DAMPER ROUND MOTORIZED DAMPER M COMBINATION FIRE/SMOKE DAMPER THERMOSTAT LAY-IN EXHAUST GRILLE ROOF EXHAUST FAN TURNING VANES DOUBLE THICKNESS SYMBOLS XXX X-# EQUIPMENT SYMBOLS FD FD SD ROOF TOP UNIT W/D W/D ECH HORIZONTAL FURNACE OR FC WITH DRAIN PAN HORIZONTAL AIR COOLED CONDENSING UNIT RECTANGULAR CENTERED DUCT TRANSISTION RECTANGULAR ECCENTRIC DUCT TRANSITION WALL MOUNTED EXHAUST FAN LAY-IN SUPPLY AIR DIFFUSER LAY-IN RETURN AIR REGISTER OR GRILLE SURFACE MOUNTED SUPPLY AIR DIFFUSER DUCT MOUNTED ROUND DIFFUSER LINEAR OR SLOT DIFFUSER ROOF MOUNTED INTAKE/EXHAUST HOOD RECTANGULAR ROOF MOUNTED INTAKE/EXHAUST HOOD ROUND SURFACE MOUNTED SUPPLY AIR DIFFUSER CEILING MOUNTED EXHAUST FAN MODULAR AIR HANDLING UNIT AHU ACCU REF IH RH IH RH FC F AC EF EF RTU CEILING MOUNTED ELECTRIC HEATER DIFFUSER SYMBOLS DUCT SYMBOLS DIRECT DUCT MOUNTED REGISTER DIFFUSER TAG EWHELECTRIC WALL HEATER ECCENTRIC SQUARE TO ROUND TRANSITION CENTERED SQUARE TO ROUND TRANSITION SHEET METAL DUCT WIDTH BY DEPTH LINED SHEET METAL DUCT FREE AREA WIDTH BY DEPTH. ACCESS DOOR SQUARE SHEET METAL 90 PROVIDE WITH DOUBLE THICKNESS TURNING VANES. RADIUS SHEET METAL 90, R=1.5*D ROUND HIGH EFFICIENCY BRANCH DUCT TAKE OFF ON ROUND DUCT. ROUND TAP BRANCH DUCT TAKE OFF ON ROUND DUCT. HIGH EFFICIENCY BRANCH DUCT TAKE OFF ON RECTANGULAR. STANDARD ROUND TAP BRANCH DUCT TAKE OFF ON ROUND DUCT. SQUARE SHEET METAL 90 PROVIDE WITH DOUBLE THICKNESS TURNING VANES. FULL BODY ROUND TEE FITTING CONTROL SYMBOLS THERMOSTAT IN LOCK BOX SENSOR CARBON MONOXIDE SENSOR CARBON DIOXIDE SENSOR NITROGEN OXIDE SENSOR M RECTANGULAR MOTORIZED DAMPER DIRECT DUCT MOUNTED REGISTER MARK CFM NO CO2 CO S T T DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 M001 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 55° SUSPENSIONDROP ROD NOTE: HOOKS ARE TO BE CLOSED UP AFTER ASSEMBLY 2/0 GA CHAIN (TWISTED LINK, PLATED) EYE HOOK PURLING FASTENERS REFLECTOR BRACKET OPTIONAL TURNBUCKLE (±3" ADJUSTMENT) 3 8Ø ROD CHAIN ('U' TYPE SHOWN) 2/0 GA CHAIN (TWISTED LINK, PLATED) EYE HOOKS * THESE ANGLES TO BE EQUAL AND NOT MORE THAN 45° ** ** ON U TUBE VARIANTS THE HEATER SHOULD SLOPE DOWNWARDS TOWARDS THE RETURN BEND AND ON LINEAR VARIANTS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. 1/2" FOR BOTH HORIZONTAL AND WALL MOUNTED INSTALLATIONS. WHERE CHAIN SUPPORTS HAVE AN ANGLE OF INCLINATION GREATER THAN 15° AN EQUAL AND OPPOSITE SUPPORT IS RECOMMENDED VERTICAL SUSPENSION CHAIN IDEAL. WHERE SUPPORTS ARE INCLINED, MAXIMUM RECOMMENDED ANGLE OF INCLINATION IS 15° 15° MAX LAY-IN DIFFUSER DETAIL NO SCALEB SECURE FLEXIBLE DUCT TO SUPPLY DIFFUSER ELBOW FITTING WITH DRAWBAND. SHEET METAL ELBOW 1-1/2" DUCT WRAP SUPPLY DIFFUSER CEILING MOUNT DIFFUSER IN BOTTOM OF BRANCH WITH SADDLE AS HIGH AS POSSIBLE SPIRAL BRANCH DUCT TIGHT TO OR THROUGH STRUCTURE ADJUSTABLE GRIPPLE STRANDED WIRE HANGER TYPICAL. SPIRAL CAP FULLY FRAMED OPENING IN DRYWALL CEILING. CONCEALED FASTENER LINEAR SLOT DIFFUSER PER SCHEDULE. CUSTOM FABRICATED OR MANUFACTURERS INTERNALLY LINED PLENUM BOX WITH RECTANGULAR, OVAL OR ROUND TAKE OFF SIZE PER PLANS. INFRARED HEATER INSTALLATION DETAILS NO SCALEG LAY-IN DIFFUSER DETAIL NO SCALE A INTAKE/RELIEF HOOD DETAIL NO SCALED 30° MAX O AIR FLOW 45 DEG. OCL CONNECTION TAKE OFF. HAMMER LOCKED OR FLANGED AND FULLY SEALED RECTANGULAR DUCT BRANCH CONCENTRIC TRANSITION MAX, 45 DEG. DIVERGING AND 60 DEG. CONVERGING OFFSET. PROVIDE MINIMUM 2" STRAIGHT SECTION AT EACH END. MAX 30 DEG. ECCENTRIC TRANSITION MAX, 30 DEG. 30° MAX AIR FLOWV.D. HIGH EFFICIENCY FLANGED TAKE OFF COMPLETELY SEALED ROUND SHEET METAL DUCT TO WITH IN 5'-0" OF DIFFUSER NOTE: AIRFOIL BLADES TO BE USED WHERE NORMAL RADIUS ELBOW IS IMPRACTICAL & WHERE ELBOW IS WITHIN 5 FT OF A BRANCH TAKE-OFF. NOTE: IN GENERAL, ELBOWS TO HAVE FULL TURNING RADIUS (R=A). WHERE "R" IS EQUAL TO OR GREATER THAN "A" MINIMUM RADIUS (R) = 4 INCHES. R=A 118" A SHEET METAL GAUGES AND RIGIDITY SHALL BE IN ACCORDANCE WITH SMACNA PRESSURE CLASS 1.0" UNLESS OTHERWISE SPECIFIED. DUCT CONSTRUCTIN DETAILS NO SCALEH 3/4 PVC TRAPPED COND. DRAIN. PROVIDE TRAP DEPTH PER MANUFACTURE WITH CLEAN OUT PLUG. FRESH AIR INTAKE HOOD MAINTAIN MINIMUM OF 10'-0" FROM ALL EXHAUST AND PLUMBING VENTS 3" MIN. 48" LONG SHEET METAL DROPS FULL CURB OPENING SIZED AND LINED WITH 1" DUCT LINER AND WITH FLEX CONNECTOR CUT ROOF DECK ONLY AS NEEDED FOR DUCT DROPS. PROVIDE R-13 BATT OR ROOFING INSULATION PLACED ON REMAINING DECK. ELECTRICAL DISCONNECT PER NEC MAINTAIN MINIMUM OF 10'-0" FOR EDGE OF ROOF AGA GAS SHUT OFF, 2 PSIG-7" W.C. REGULATOR DIRT LEG AND UNION BY PC. PROVIDE NEOPRENE CURB TAPE AT DUCT CONNECTION SEAL AIR TIGHT. PLACE EXTRA ROOF MEMBRANE BETWEEN MIRO 1.5 POLYCARBONATE PIPE SUPPORTS PIPE SUPPORT AND ROOF MEMBRANE. TYP. STEEL ANGLE FRAME BY STEEL ERECTION CONTRACTOR COORDINATE SIZES WITH STEEL SHOP DRAWINGS. ROUND CHIMNEY TOP METALBESTOS FLUE RECOMMENDATIONS MANUFACTURER'S INSTALL PER NOTE FLASHING ROOF STORM COLLAR METAL ROOF AIR SPACE AROUND FLUE LISTED CONNECT TO APPLIANCE WITH B-VENT CONNECTOR PIPING SLOPE AT MINIMUM 1/4" PER FOOT 14" HIGH MINIMUM PRE-FABRICATED ROOF CURB ATTACHED TO CONCRETE ROOF STRUCTURE WITH CONCRETE ANCHORS. SECURE VENT TO ROOF CURB AS REQUIRED WITH SHEET METAL SCREWS. DUCT TO BE SAME SIZE AS THROAT SIZE OF VENT. RELIEF VENT PROVIDE 1/2" X 1/2" WELDED WIRE MESH SCREEN OVER END OF DUCT. ROOF CONSTRUCTION. REFER TO ARCHITECTURAL DRAWINGS FOR TYPE. SEAL ALL JOINTS. MOTORIZED CONTROL DAMPER BY RELIEF HOOD VENDOR. SPIRAL DUCT DIFFUSER DETAIL NO SCALE C SPIRAL DUCT DIFFUSER DETAIL NO SCALE E RTU INSTALLATION DETAIL NO SCALEF CAULK WATER TIGHT ATTACH TO ROOF DECK W/ #10 SHEET METAL SCREWS MINIMUM 36" ABOVE ROOF LINE METALBESTOS CONNECTOR ROUTED FULLY TO APPLIANCE NO SINGLE WALL ALLOWED. INTAKE VENT REFERENCE ARCHITECTURAL REFLECTED CEILING PLAN AND ELECTRICAL LIGHTING PLAN AND COORDINATE INSTALLATION WITH ALL CEILING ELEMENTS. M002 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 12" MIN. METAL ROOF DECK MECH. DUCT INSULATION THICKNESS. AS REQUIRED TO MATCH TREATED WOOD BLOCKING EXHAUST FAN PROVIDE (2) LAG SCREWS PER SIDE WITH NEOPRENE WASHSERS SEAL FAN TO CURB WITH NEOPRENE GASKET AIR TIGHT GRAVITY BDD 3X3 ANGLE REF. STRUCTURAL PLANS. (2) 3 X 3 X 5/16 ANGLES FACE TO FACE BOLTED TO ROOF JOIST BY M.C. FAN MOUNTING BRACKETS, BOLTS, WASHERS AND SAFETY CABLE BY FAN MANUFACTURER. BOLT TO C CHANNEL OR TO BOTTOM OF GIRDER. SCALE : NONE BIG ASS FAN MOUNTING DETAILA SECTION AA A A DUCT LESS SPLIT TRAP SUCTION LINE EVERY 10' UP RISER NOT TO SCALE MINI SPLIT INSTALLATION DETAILD PATE PORTAL ROOF CURB TYPICAL ALL LINE SETS. INSULATE AND SEAL WATER TIGHT. INVERTED SUCTION LINE TRAP. SLOPE LINE BACK TO COMPRESSOR. DISCONNECT BY E.C. AIR COOLED CONDENSING UNIT WALL WALL BIRD SCREEN CAULK INTERIOR AND EXTERIOR PERIMETER WEATHER TIGHT WITH SILICON CAULKING. LOUVER WITH KYNAR FINISH TO MATCH BLDG. COLOR EXTERIOR 1"X1"X1/8" STEEL ANGLE. SCREW TO LOUVER SLEEVE 6" O.C. # 10 SCREWS AND ANCHORED TO MASONRY WALL 12" O.C. WITH 1/4" MASONRY ANCHORS. TYPICAL TOP, BOTTOM AND SIDES. SCALE : NONE EXHAUST FAN DETAIL B SCALE : NONE WALL LOUVER DETAILC GALVANIZED EQUIPMENT RAIL BY MC 1/2" HOSE TO OPEN SITE INVERTED TEE IN PVC DRAIN LINE BY MC ROUTE 3/4 SCH 40 PVC LINE TO HUB/FLOOR DRAIN PROVIDED BY P.C. AT MINIMUM 1/4" PER FT SUPPORT MIN. 5' OC. MINI-WHITE TANK MINI SPLIT CONDENSATE PUMP WITH HIGH LEVEL CUT OUT. WIRE TO IDU PER MANUFACTURES INSTRUCTIONS MINIMUM 48" PRIOR TO ROUGH-IN COORDINATE CLEARANCES OF BLADES WITH ALL TRADES AND EQUIPMENT SUPPLIERS. M003 OPTIONAL SUSPENDED CEILING INSTALLATION OF SUNTUBE HEATER STANDARD REFLECTOR 12" MINIMUM SHIELD NOTCH AS REQUIRED AROUND THE REFLECTOR SUPPORT BRACKET H EXTENSION REFLECTOR 4'-0" LONG X 8", 12", OR 16" WIDE SUSPENDED CEILING FRAME 2 FT. ALUMINUM LOUVER SCALE : NONE INFRARED HEATER SUSPENDED CEILING INSTALLATIONE PARTICULAR CONSIDERATION MUST BE GIVEN TO CLEARANCES TO COMBUSTIBLES IN THIS TYPE OF INSTALLATION. SINCE THE STANDARD REFLECTOR IS USED, THE CLEARANCE TO COMBUSTIBLES WILL BE THE SAME AS INDICATED IN THE "SUMMARY OF SPECIFICATIONS" IN THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTION MANUAL. VERIFY THAT THE CEILING PANELS ADJACENT TO EACH SIDE OF THE HEATER ARE ARE NOT COMBUSTIBLE OR THAT THEY ARE MADE OF CLASS A MATERIALS. VERIFY THE INSTALLATION IS ACCEPTABLE TO LOCAL AUTHORITIES. IN ADDITION, TO PROVIDE ADEQUATE COMFORT LEVELS, REFER TO "HEATER LOCATION" IN THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTION MANUAL TO IDENTIFY MINIMUM MOUNTING HEIGHT. THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS IN THIS EQUIPMENT, OR COVER EVERY POSSIBLE SITUATION TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD PROBLEMS ARISE THAT ARE NOT COVERED SUFFICIENTLY IN THESE INSTRUCTIONS, THE PURCHASER IS ADVISED TO CONTACT THE ENGINEERING DEPARTMENT AT SOLARONICS, INC. FOR FURTHER INFORMATION. THE SUNTUBE LOW-INTENSITY GAS INFRARED HEATER CAN BE INSTALLED OVER SUSPENDED CEILINGS WITH AN ALUMINUM LOUVER DIRECTLY BELOW THE HEATER. THE ALUMINUM LOUVER IS A 2 FOOT WIDE X 4 FOOT LONG BY 1/2" THICK, NON-FLAMMABLE , 1/2" X 1/2" OPEN-GRID CELL PATTERN CONSTRUCTED OF 0.015" ALUMINUM WITH A MILL FINISH. NEVER USE REGULAR CEILING TILES DIRECTLY BELOW THE HEATER SINCE IT WOULD CREATE AN UNSAFE CONDITION. THE HEATER IS INSTALLED IN A NORMAL FASHION (AS DESCRIBED IN THE INSTRUCTION MANUAL) WITH THE TUBE SUSPENDED OVER THE LOUVERS FROM A MINIMUM HEIGHT OF 4.000" TO A MAXIMUM HEIGHT OF 14.375" (DISTANCE H). CALCULATE DISTANCE "H" BETWEEN THE BOTTOM OF THE HEAT EXCHANGER TUBE TO THE TOP OF THE LOUVER TO DETERMINE THE SIZE OF THE EXTENSION REFLECTORS REQUIRED FROM THE FOLLOWING TABLE: THE EXTENSION REFLECTORS ARE AVAILABLE IN STANDARD 4 FOOT SECTIONS AND ARE LAID ALONGSIDE THE STANDARD REFLECTORS. IT MAY BE NECESSARY TO CUT NOTCHES FOR CLEARANCE AROUND THE REFLECTOR SUPPORT BRACKETS. A SHIELD,IS PLACED OVER THE SUSPENDED CEILING FRAME MEMBER WHICH PASS DIRECTLY UNDERNEATH THE HEATER. FOR YOUR SAFETY, GLOVES ARE TO BE WORN WHEN HANDLING THE ALUMINUM LOUVERS TO PROTECT THE HANDS FROM SHARP EDGES. ALLOW A 12 INCH MINIMUM CLEARANCE FROM THE TOP AND SIDES OF THE BURNER. 09/21/20 DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 WATTS SERVICE BAY BAF-1 NOTESVOLTRPM HP MOTOR DATA ØLOCATIONMODEL # TAG BIG ASS FAN SCHEDULE DESCRIPTION TYPE FAN ANDBIG ASS FAN 1 1 PROVIDE WITH WALL MOUNTED VARIABLE SPEED CONTROLLER AND ALL REQUIRED MOUNTING HARDWARE. 20' BASIC 6 346085 1.5 20' CEILING FAN WATTS 170.3 SERVICE BAY EF-1 NOTESVOLTRPM HP MOTOR DATA Ø LOCATIONMODEL # TAG EXHAUST FAN SCHEDULE DESCRIPTION TYPE FAN AND CFM SP SONES GREENHECK G-123-A EF-2 ROOF 1800 1/2 115 1EF-3 G-070-G ROOF EF-4 ROOF EF-5 G-080-D 1115 150 ROOF 0.26 2.8 1115 300 0.32 7.3 GB-180 34601334 1-1/25000 ROOF 0.25 22 525 0.31G-090-D 7.4 11151725 1/15 ACCESSORIES/REMARKSVOLTAGE 2774.0 KW HEATING KW QMARK MANUFCTR MARK EWH-1 AWH MODEL NO. ELECTRIC HEATER SCHEDULE PHASE 1 1 PROVIDE WITH HANGING BRACKET AND DISCONNECT SWITCH.2 1 RECESSED WALL HEATER, PROVIDE WITH INTEGRAL THERMOSTAT AND DISCONNECT OR WATTS PER FT. PROVIDE WITH MOTORIZED LOW LEAKAGE TWO POSITION DAMPER AND BELIMO 120V ACTUATOR. PROVIDE WITH BIRD SCREEN AND BAKED ENAMEL PAINT, COLOR TO BE SELECTED BY ARCHITECT LV-1 NOTES: MODEL MFR DESCRIPTIONTAG LOUVERS/ROOF VENTS COMPRESSOR INTAKE LOUVER SIZE 32/32IH-1 GREENHECK FGI IH-2 GREENHECK FGI 22/22 FREE AREA FT2 WRITE-UP BAY GRAVITY INTAKE HOOD WITH MOTORIZED DAMPER. CFM 5000 1800 5 200/25110.80 CAPACITY CAPACITY NOTESMOCP ELECTRICAL DATA MCA VOLTS/PH/HZ NOM. TONSSENS MBH TOTAL MBH COOLING OUTPUT INPUT GAS HEAT (MBH) BRYANTRTU-1 TAG ROOFTOP UNIT SCHEDULE - 460 VOLT - 3 PHASE MANUFACTURER MODEL WEIGHT EER CFM CFM O.A. E.S.P. (IN W.G.) 2247 248/310 187.14 249.58 20 460/3/60 49.8 60 ACCESSORIES PROVIDE INSULATED FLAT ROOF CURB AND ECONOMIZER WITH BAROMETRIC RELIEF. 664580JE25D310A6A7YD 1 2 1 PROVIDE PROGRAMMABLE THERMOSTAT AND IAQ OA CONTROL WITH ROOM CO2 SENSOR.2 MARK QTY. CONFIGURATION HEATING DATA ELECTRICAL DATA UNIT WEIGHT (LBS) MANUFACTURER WITH MODEL NUMBER NOTESINPUT MBH FUEL TYPE LENGTH (FT) AMPS VOLTS PH IR1 1 U TUBE 60 NAT. GAS 18' 1.2 120 1 200 AMBIRAD VSUSN100-ER-S50 1-10 IR2 2 STRAIGHT TUBE 75 NAT. GAS 40' 1.2 120 1 200 AMBIRAD VSUSN75-ER-S40 1-7 IR3 4 125 NAT. GAS 42' 1.2 120 1 200 1-7 NOTES PLEASE PROVIDE THE FOLLOWING ACCESSORIES 1 BALL VALVE AND STAINLESS STEEL FLEX GAS CONNECTOR 2 4", 16GA. ALUMINIZED STEEL TUBING 3 STAINLESS STEEL REFLECTORS 4 STAINLESS STEEL REFLECTOR END CAPS 5 PROVIDE SMART COM TEMPERATURE CONTROL PANEL ZONED AS SHOWN ON PLANS. 6 4" VENT ADAPTER & OUTSIDE COMBUSTION AIR ADAPTERS 7 HANGING CHAIN SETS (CHAIN, KARABINER CLIPS, BEAM CLAMPS, EYE BOLTS) 8 STAINLESS STEEL TUBES 9 STAINLESS STEEL BURNER CABINET 10 WATERTIGHT (NEMA4X) THERMOSTAT 1 2 BRYANTRTU-3 5 460/3/60 1 2 RTU-4 S-2 -0-120STEEL SCD-6" NECKPRICE24X24 LAY-IN DIFFUSER S-1 NOTES: COLOR : WHITE REFER TO FLOOR PLAN FOR EXACT CFM. INTEGRALMAT'L. CFMMODEL MFR TAG DESCRIPTION DIFFUSER, REGISTERS AND GRILLES PROVIDE WITH SQUARE TO ROUND REGISTER BOX.3 2 1 S-3 S-4 NC MAXIMUM R-2 R-1 R-3 24x24 LAY-IN BAR FACE GRILLE 24x12 LAY-IN BAR FACE GRILLE 44"x18" SURFACE BAR FACE GRILLE PRICE PRICE PRICE 0-2000 0-1000 1650 STEEL STEEL STEEL 30 DAMPER - - - 530 - -530 530 - 1 1 1 1 1 1 1 2 2 2 2 2 2 2 3 3 3 S-5 S-6 PRICE14X4 SPIRAL DUCT GRILLE 100-200 STEEL SDGE 120-220STEEL SCD-8" NECKPRICE24X24 LAY-IN DIFFUSER 30 230-420STEEL SCD-10" NECKPRICE24X24 LAY-IN DIFFUSER 30 1 2 - - - 2 2 BASE BID TO BE BIG ASS FAN, VOLUNTARY ALTERNATE TO BE MACRO AIR FAN OF EQUAL PERFORMANCE. SERVICE BAY GRAVITY INTAKE HOOD WITH MOTORIZED DAMPER. PROVIDE WITH INSULATED FLAT ROOF CURB. 1 1 1 1 1 1 PROVIDE WITH FLAT ROOF CURB, DISCONNECT AND BACKDRAFT DAMPER. GAS-FIRED RADIANT HEATER SCHEDULE EF-6 G-095-D ROOF 1115 675 0.33 8.6 2773.0 KWQMARKECH-1 CDF 1 1 3 PROVIDE WITH INTEGRAL THERMOSTAT AND DISCONNECT 3 DUCTLESS SPLIT SCHEDULE MANUFACTURERTAG NOTES: MS-1 MITSUBISHI 1 AIR FLOW HI CFM COOLING CAPACITY R410A REFG. ELECTRICAL SPECIFICATIONS MOCP(V-Ph-Hz) ELEC. 208/230-1-60 25 2 PROVIDE WIRED REMOTE T/S CONTROLLER 1 MODEL INDOOR OUTDOOR MBH SENSIBLE MBH TOTAL - 24000 SEER LOW AMBIENT TO 0 DEG. F. 2PKA-A24KA4 PUY-A24NHA4 425 17 8000 0.5 SEER YES 9314.10BRYANTRTU-2 597 115 46.23 61.84 5 460/3/60 145582JE06A115A2A7YA2000 0.5 1 298/14811.00BRYANT930 120/180 76.37 102.79 8.5 460/3/60 329580JE09D180A2A7YD3000 0.5 14 20 20 25 PROVIDE PROGRAMMABLE THERMOSTAT.3 PROVIDE RA SMOKE DETECTOR.4 4 4 4 4 1725 RPM 1300 1550 1334 1550 1550 FAN DATA 1725 1300 1550 1550 1/60 1/20 1/8 1 20/22ESD-435 1500 GREENHECK 1.3 2 30 30 E-2 E-1 12x12 LAY-IN BAR FACE GRILLE 6X6 SURFACE FACE GRILLE PRICE PRICE 0-1000 0-1000 STEEL STEEL - YES 530 - -530 1 1 2 2 3 3 2 PROVIDE MOTOR STARTER WITH HOA, RUN/STOP LIGHTS AND DAMPER CONTROL. 3 2 3 FAN SHALL RUN CONTINUOUS, COORDINATE WITH E.C. 4 PROVIDE WITH COOLING ONLY LINE VOLTAGE THERMOSTAT AND COORDINATE WITH E.C. 2 3 3 3 1 2 2 1 2 2 3 3 3 RTU-7 1 3 98/14811.00BRYANT835 120/180 68.90 90.10 7.5 460/3/60 300580JE08D180A2A7YD3000 0.5 20 25 4 66/9314.00BRYANTRTU-6 490 1200 0.5 82/115 26.71 36.41 3 460/3/60 11 15407582JE04A115A2A7YA 1 3 RTU-5 1 35 460/3/60 4 9314.10597 115 46.23 61.84 217582JE06A115A2A7YA2000 0.5 14 20 9314.10597 115 46.23 61.84 150582JE06A115A2A7YA2000 0.5 14 20BRYANT RESTROOM RESTROOM STRAIGHT TUBE AMBIRAD VSUSN125-ER-S40 1 2PRICE48 x (2) SLOT DIFFUSER SDS075 -AL 400 30 420-600STEEL SCD-12" NECKPRICE24X24 LAY-IN DIFFUSER M004 EF-7 EF-8 EF-9 EF-10 WRITE UP BAY SERVICE BAY WRITE UP BAY 225 G-070-D RESTROOM ROOF 1115 0.33 4.51550 1550 1/30 150 G-070-G RESTROOM ROOF 1115 0.26 2.81300 1300 1/30 1500 GB-131 AIR COMPRESSOR ROOF 1115 0.3 10.21202 1202 1/4 100 SP-A125 TOOL ROOM CEILING 1115 0.27 4.51100 1100 - EF-10 100 SP-A125 ELECT. ROOM CEILING 11150.27 4.51100 1100 - 1 3 1 3 1 4 2 4 PROVIDE HEATING ONLY THERMOSTAT 629 TOTAL CFM 2 1/60/115 (V-Ph-Hz) MOCP ELECTRICAL SPECIFICATIONS 24.6 30 MBH OUT MBH IN HEATING CAPACITY UDAP-30 1 REZNOR UH-1 NOTES:MODELMARK MANUFACTURER GAS UNIT HEATER PROVIDE FACTORY CEILING HANGER KIT.2 MCA 20 1 2 09/21/20 3 5 10 13 15 16 17 C E H J M O S 2 1 9 6 D B A F 18 T G L N 7 4 11 12 14 K 28 R P 300 E-1 300 E-1 75 E-2 120 S-1 120 S-1 120 R-1 120 S-1 120 R-1 120 S-1 120 R-1 120 S-1 120 R-1 275 S-3 275 S-3 200 S-2 120 S-1 120 S-1 150 S-2 120 R-1 220 R-1 200 R-1 22"Ø 22"Ø 140 S-2 140 S-2 300 S-3 300 S-3 120 S-1 120 S-1 120 S-1 220 S-2 220 S-2 220 S-2 220 S-2 220 S-2 220 S-2 100 S-1 75 S-1 220 S-1 75 R-1 100 R-1 120 R-1 120 R-1 600 R-1 280 R-1 150 R-1 1400 R-2 240 S-3 220 R-1 120 R-1 220 S-2 12"Ø16"Ø 20Ø 20"Ø 16'Ø RTU-46"Ø6"Ø6"Ø6"Ø6"Ø6"Ø8"Ø8"Ø8"Ø8"Ø8"Ø10"Ø6"Ø 8"Ø 8"Ø6"Ø8"Ø8"Ø10"Ø12/106"Ø 6"Ø16/14 22/14ECH-1 EWH-1 T T T T 18/1422/1420/1414"Ø 120 R-1 12"Ø 6"Ø10"Ø 16/14 120 R-1 120 R-1 14/14 12"ØKEY PLAN AB N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR HVAC PLAN - AREA 'A' KEY NOTES: GENERAL NOTES: 1 ROUTE DUCTING BELOW 2ND FLOOR FRAMING TIGHT TO I BEAMS. COORDINATE WITH PLUMBING, SPRINKLER AND ELECTRICAL CONTRACTORS. 1. REFERENCE SHEET M-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE SHEETS M-002 THOUGH M-004 FOR DETAILS, SCHEDULES AND NOTES. 3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO PROVIDE ALL MOTOR STARTERS, RACEWAYS AND LINE VOLTAGE CONDUCTORS. 1 M100 09/21/20 18 250 T 100 S-1 100 S-1 250 S-6 250 S-6 250 S-6 S-6 250 S-6 250 S-6 200 S-6 200 S-6 200 S-6 200 S-6 200 S-6 RTU-7 7.5 TON IR-2 IR-2 IR-3 RTU-48"Ø 10"Ø 12"Ø 14"Ø 16"Ø 8"Ø 10"Ø 12"Ø 14"Ø 16"Ø 16"Ø 16"Ø100 S-1 100 S-1 120 8" W.C.10"Ø8"Ø 12"Ø6"Ø 6"Ø 6"Ø 12"Ø UP BAF-1BAF-1 CF-1T T CF-1 IR-3 6"Ø FLUECOMS UH-1 UH-1 16/16 UP TO IH-2 8"Ø UP TO EF-4 18"Ø UP TO EF-3 R-2 R-2 S-4S-4 S-4 IR-3 IR-3 6"Ø FLUEIR-1 100 EF-11 100 EF-10 8"Ø 6"Ø16"Ø 12"Ø12"Ø 12"Ø 100 S-6 T T T 200 S-6 EWH-1 BBS SC MS CO NOx BBS SC MS CO NOx OAOA KEY PLAN AB N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" FIRST FLOOR HVAC PLAN - AREA 'B' KEY NOTES: GENERAL NOTES: 1 IR HEATERS SHALL BE SIMULTANEOUSLY CONTROLLED IN GROUPS BY SMARTCOM MULTIZONE IR TEMPERATURE CONTROL PANEL WITH REMOTE BLACK BULB AND OA SENSOR. RACEWAYS FOR TCC AND BURNER/BLOWER INTERLOCKS ARE BY E.C. ALL CONTROLS AND HEATER COMPONENTS BY M.C. COORDINATE AND LOCATION OF ALL INFRARED HEATERS WITH OWNER AND INSTALL PER MANUFACTURES RECOMMENDED CLEARANCES WITH REGARD TO CAR LIFTS AND GARAGE EQUIPMENT. SEE DETAILS ON SHEET M002 FOR MORE INFORMATION. TYPICAL. PIPE CA FOR DETAIL BAY HEATER TO WALL CAP, ALL OTHER HEATERS TO DRAW CA FROM INDOORS. ROUTE DUCTING BELOW 2ND FLOOR FRAMING TIGHT TO I BEAMS. COORDINATE WITH PLUMBING, SPRINKLER AND ELECTRICAL CONTRACTORS. MOUNT CEILING FAN TO ROOF JOIST PER MANUFACTURERS INSTRUCTIONS, ELEVATION TO BE COORDINATED WITH THE LIGHTING SYSTEMS AND IR HEATERS. SEE DETAIL ON SHEET M002. INSTALL SERVICE WRITE UP BAY 100 MBH, 40' LONG STRAIGHT TUBE IR HEATERS SIMILAR TO RH1 MOUNTED ABOVE ACOUSTIC CEILING WITH MANUFACTURERS CEILING KITS. INSTALL ALUMINUM GRILLES AND T-BAR SHIELDS PER INSTRUCTIONS BOTTOM OF RADIANT TUBE HEATER NEED TO BE AT 12'-0 OFF OF FINISHED FLOOR ROUTE ALL DUCT WORK IN SERVICE DEPARTMENT IN TRUST SPACE. ROUTE ALL DUCT WORK UP IN JOIST SPACE. 1. REFERENCE SHEET M-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE SHEETS M-002 THOUGH M-004 FOR DETAILS, SCHEDULES AND NOTES. 3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO PROVIDE ALL MOTOR STARTERS, RACEWAYS AND LINE VOLTAGE CONDUCTORS. 2 3 4 5 1 1 2 2 5 5 2 2 2 2 3 44 M101 3 6 6 6 7 7 7 8 09/21/20 3 5 10 13 15 16 17 C E H J M O S 2 1 B A T G L N 11 12 14 7 2 F 18 75 E-2 75 E-2 75 E-2 16"Ø 200 S-2 200 S-2 200 S-2 200 S-2 120 S-1 75 S-1 75 S-1 120 S-1 220 S-1 220 S-1 1000 R-2 1000 R-2 800 R-1 400 S-4 600 S-4 600 S-4 600 S-4 600 S-4 600 S-4 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 400 S-5 1600 R-2 1600 R-2 375 S-5 375 S-5 375 S-5 375 S-5 EF-6 18"Ø 30/30 30/30 1600 R-2 1600 R-2 1600 R-2 24/16 22/12 18/12 12/1210"Ø30/16 30/20 30/22 30/26 10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø12"Ø12"Ø12"Ø12"Ø12"Ø30/20 30/26 22/20 18"Ø18"Ø18"Ø 18"Ø 18"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø 14"Ø14"Ø8"Ø 8"Ø 10"Ø120 R-1 14"ØS-1 200 10"Ø 8"Ø10"Ø 8"Ø10"Ø14"Ø200 R-1 440 R-1 AHU-1 T 120 R-1 10"Ø 10"Ø 12/10 UP TO EF-5 8/8 UP TO EF-6 18"Ø 18"Ø 18"Ø 18"Ø 18"Ø 18"Ø 30/28KEY PLAN B C N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" SECOND FLOOR HVAC PLAN - AREA 'C' KEY NOTES: GENERAL NOTES: 1 ROUTE DUCTING BELOW 2ND FLOOR FRAMING TIGHT TO I BEAMS. COORDINATE WITH PLUMBING, SPRINKLER AND ELECTRICAL CONTRACTORS. 1. REFERENCE SHEET M-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE SHEETS M-002 THOUGH M-004 FOR DETAILS, SCHEDULES AND NOTES. 3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO PROVIDE ALL MOTOR STARTERS, RACEWAYS AND LINE VOLTAGE CONDUCTORS. 1 M200 09/21/20 18 150 S-6 150 S-6 150 S-6 150 S-6 150 S-6 150 S-6 E-1 350 250 S-3 300 S-3 10"Ø 12"Ø 14"Ø 18/1414/14 250 R-1 1650 R-3 22/1422/14 DROP 18/18 UP TO EF-9 M LV-1 12"Ø DN KEY PLAN C D N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" SECOND FLOOR HVAC PLAN - AREA 'D' KEY NOTES: GENERAL NOTES: 1. REFERENCE SHEET M-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE SHEETS M-002 THOUGH M-004 FOR DETAILS, SCHEDULES AND NOTES. 3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO PROVIDE ALL MOTOR STARTERS, RACEWAYS AND LINE VOLTAGE CONDUCTORS. M201 09/21/20 09/21/20 RTU-1 RTU-2 RTU-3 RTU-4 RTU-5 20 TON 5 TON 5 TON 8.5 TON 5 TON RTU-7 7.5 TON RTU-6 5 TON 30/30 IH-1 EF-1 EF-2 IH-2 EF-3 EF-5 MS-1 EF-4 M M M EF-8 EF-9 KEY PLAN AB N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR EDOOG.RDIVAD PROFES SIONA L E N G INEER D E NADIIN A GER RTSIE STATE OF No. 10200395 1 SCALE: 1/8" = 1'-0" ROOF HVAC PLAN - AREA 'B' KEY NOTES: GENERAL NOTES: 1. REFERENCE SHEET M-001 FOR LEGENDS, ABBREVIATIONS, SPECIFICATIONS AND NOTES. 2. REFERENCE SHEETS M-002 THOUGH M-004 FOR DETAILS, SCHEDULES AND NOTES. 3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO PROVIDE ALL MOTOR STARTERS, RACEWAYS AND LINE VOLTAGE CONDUCTORS. M301 1 SEE SHEET M300 FOR DUCT WORK INSTALLATION INFORMATION. 1 1 1 1 1 09/21/20