HomeMy WebLinkAboutNAPLETON KIA OF CARMEL-MECH-20190708MECHANICAL SPECIFICATIONS
GENERAL
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE
BASE BID IN STRICT ACCORDANCE WITH DESIGN BASIS
EQUIPMENT AND MATERIALS. PROJECT DOES
ENCOURAGE COMPETITIVE PRICING AND ALLOWS FOR
SUBSTITUTIONS OF EQUAL EQUIPMENT AND MATERIALS
AGAINST THE BASIS OF DESIGN. BIDDERS SHALL LIST
ALL SUBSTITUTIONS ON BID. ENGINEER RESERVES THE
RIGHT TO REJECT SUBSTITUTIONS FOUND NOT TO BE
EQUAL TO ITEMS LISTED IN DESIGN BASIS.
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL SUBMIT
TO ARCHITECT FULL SUBMITTALS FOR ALL ENERGY
CONSUMING OR PRODUCING ITEMS AND FOR ALL DUCT
ACCESSORIES, INSULATION, VAV BOXES, REGISTERS,
GRILLES, DIFFUSERS AND LOUVERS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON
PRINTS, CONTRACTORS NAME, PROJECT NAME.
CLEARLY INDICATE ALL MODEL NUMBERS AND ALL
ACCESSORIES AND OPTIONS BEING PROVIDED.
SUBMISSIONS SHALL BE IN PDF FORMAT. ALL
EQUIPMENT AND ITEMS SHALL BE PER DESIGN BASIS
OR APPROVED EQUAL. ENGINEER RESERVES THE
RIGHT TO REJECT ANY SUBSTITUTE ITEM.
3. CONTRACTOR SHALL BE RESPONSIBLE TO
COORDINATE ALL REQUIRED ELECTRICAL SUPPORT
NEEDED FROM THE ELECTRICAL CONTRACTOR.
ENSURE ALL SUBMITTALS FOR POWERED
COMPONENTS AND CONTROLS ARE PROVIDED AND
FULLY COORDINATED WITH ELECTRICAL
CONTRACTORS.
4. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE
SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY
WAY AFFECT THE EXECUTION OF HIS WORK. HE SHALL
ALSO EXAMINE THE DRAWINGS AND SPECIFICATIONS
FOR OTHER BRANCHES OF WORK MAKING REFERENCE
TO THEM FOR DETAILS OF EXISTING BUILDING
CONDITIONS. NO EXTRAS WILL BE ALLOWED FOR
FAILURE TO INCLUDE ALL REQUIRED WORK IN THE BID.
CONTRACTOR SHALL GUARANTEE ALL LABOR AND
MATERIALS ENTERING INTO CONTRACT FOR A PERIOD
OF ONE (1) YEAR FROM DATE OF ACCEPTANCE.
5. THE DRAWINGS IN THIS SECTION ARE DIAGRAMMATIC
AND ARE NOT INTENDED TO DEFINE EXACT
QUANTITIES, LOCATIONS OR CODIFIED REQUIREMENTS.
DRAWINGS SHOW GENERAL INTENT OF SYSTEMS. M.C.
SHALL PROVIDE AND PAY FOR ALL REQUIRED PERMITS.
6. PRIOR TO WORK COORDINATE ALL OPENINGS AND
INSTALLATIONS OF DUCT, PIPING, EQUIPMENT,
CONTROLS, DIFFUSERS AND GRILLES WITH G.C. AND
OTHER TRADES. PROVIDE INSTALLATIONS WITH
PROPER MANUFACTURERS RECOMMENDED
CLEARANCES.
7. UPON COMPLETION OF THE MECHANICAL
INSTALLATION, DEMONSTRATE TO THE ENGINEER AND
THE OWNER'S SATISFACTION THAT THE SYSTEMS HAVE
BEEN INSTALLED IN ACCORDANCE WITH THE
DRAWINGS, SPECIFICATIONS AND APPLICABLE CODES.
DEMONSTRATE THE DYNAMIC OPERATION OF EACH
SYSTEM. VERIFY PROPER OPERATION OF EQUIPMENT,
FILTERS ARE CLEAN AND COMPONENTS OF THE
SYSTEM ARE INSTALLED AND ADJUSTED IN FULL
ACCORDANCE WITH MANUFACTURER
RECOMMENDATIONS.
8. ALL WORK SHALL BE IN FULL ACCORDANCE WITH 2014
INDIANA MECHANICAL CODE (2012 INTERNATIONAL
MECHANICAL CODE), INDIANA ENERGY CODE (ASHRAE
90.1-2007) PERTINENT STATE, COUNTY, CITY CODES
AND ORDINANCES AND INDIANA AMENDMENTS.
9. MECHANICAL CONTRACTOR SHALL ENSURE
EMPLOYEES ARE MEETING AND DOCUMENTING ALL
OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS
REQUIRED BY LAW AND BY CONTRACT. PERSONAL
PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND
UTILIZED AS REQUIRED. MECHANICAL CONTRACTOR
SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE TO
COMPLY WITH OSHA REQUIREMENTS.
EQUIPMENT
1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT
SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO
LISTED EQUIPMENT SHALL BE AT RISK OF
CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE
ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS.
2. PROVIDE SUBMITTALS TO ELECTRICIAN AS REQUIRED
FOR COORDINATION OF ALL ELECTRICAL POWER
WIRING. INCLUDE WIRING DIAGRAMS AND CABLING
REQUIREMENTS FOR REFERENCE. COORDINATE ALL
INTERLOCKS AS NEEDED. PROVIDE SINGLE POINT
CONNECTION KITS AS NEEDED.
3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS AND
CLEARANCE REQUIREMENTS. PROVIDE ALL REQUIRED
MOUNTING OR HOUSEKEEPING PADS. G.C. SHALL
PROVIDE LEVEL GRADE FOR EXTERIOR MOUNTED
EQUIPMENT. M.C. SHALL PROVIDE ALL HOISTING AND
RIGGING NEEDED TO SET ALL HVAC EQUIPMENT.
4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED TO
PREVENT OBJECTIONABLE NOISE AND/OR VIBRATION.
M.C. SHALL PROVIDE VIBRATION PADS, SPRING
ISOLATORS, ATTENUATORS AND ACCESSORIES AS
NEEDED.
DUCTWORK
1. CONCEALED ROUND DUCTWORK SHALL BE
CONSTRUCTED PER SMACNA LOW PRESSURE
STANDARDS 1" PRESSURE CLASS, 5' MAXIMUM JOINT
LENGTHS, SEAL CLASS B LONGITUDINAL SEAM SNAP
LOCK PIPE AND ADJUSTABLE FITTINGS.
2. EXPOSED ROUND DUCTWORK (OR WHERE SPIRAL IS
INDICATED ON THE PLANS) SHALL BE LINDAB OR EQUAL
GALVANIZED STEEL CONFORMING TO ASTM
STANDARDS A653 AND A924 GASKETED SPIRAL
DUCTING WITH NO SEALER. EDPM RUBBER GASKET
SHALL BE U.L. CLASSIFIED RATING OF FLAME SPREAD 0
AND SMOKE DEVELOPED 5 IN ACCORDANCE WITH ASTM
STANDARD E84-91A SMACNA LEAKAGE CLASS 3.
FITTINGS SHALL BE MANUFACTURED USING ONE OR
MORE OF THE FOLLOWING CONSTRUCTION METHODS:
OVERLAPPED EDGES STITCH WELDED ALONG THE
ENTIRE LENGTH OF THE FITTING, STANDING SEAM
GORE LOCKED AND INTERNALLY SEALED, BUTTON
PUNCHED AND INTERNALLY SEALED. ELBOWS 3-INCH
THROUGH 12-INCH DIAMETER WILL BE DIE STAMPED
AND CONTINUOUSLY STITCH WELDED.
3. PROVIDE SHEET METAL 90 FOR ALL TURNS GREATER
THAN 45 DEGREES. DO NOT USE FLEXIBLE DUCT FOR
CHANGES IN DIRECTION GREATER THAN 45 DEG.
4. PROVIDE MANUAL BALANCING DAMPERS FOR ALL
SUPPLY AIR RUNS. ROUND DAMPERS SHALL BE
SECURED ON BOTH SIDES OF DUCT AND SHALL
CONTAIN LOCKING HANDLE. SPIRAL DUCTS SHALL USE
SPIRAL STYLE DAMPERS WITH FULL WIDTH SHAFTS
AND NYLON BEARINGS AT EACH END. RECTANGULAR
DUCTS SHALL USE MULTI OR SINGLE BLADE WELDED
FRAMED DAMPERS WITH JACK SHAFTS AND LOCKING
HANDLE. INSTALL NYLON RIBBON ON ALL DAMPER
HANDLES LOCATED IN INSULATED DUCTING. DO NOT
INSTALL DAMPERS IN NON ACCESSIBLE LOCATIONS.
PROVIDE INTEGRAL DAMPERS WITH DIFFUSER IN NECK
IF NO ACCESSIBLE LOCATION IS POSSIBLE. ALL SUPPLY
AIR RUNS SHALL HAVE MEANS OF BALANCE. RETURN
AND EXHAUST AIR RUNS SHALL CONTAIN DAMPERS
WHERE SHOWN ON PLANS.
5. INSULATED FLEXIBLE DUCTING SHALL NOT EXCEED 25
FEET. ALL FLEX SHALL BE LISTED FLEXIBLE DUCT,
FLEXIBLE CONNECTORS ARE NOT ACCEPTABLE.
FLEXIBLE DUCT EQUAL TO FLEXIBLE DUCT CLASS 1 AIR
DUCT, DOUBLE LAMINATED POLYESTER FILM ON STEEL
WIRE REINFORCING, INSULATED WITH SCRIM
REINFORCED METALIZED POLYESTER OUTER FIRE
RETARDANT JACKET. R-4.2 FOR CONDITIONED SPACES
AND R-6.0 FOR ANY SPACES OUTSIDE BUILDING
THERMAL ENVELOPE. FLEX DUCTS SHALL NOT BE RUN
THROUGH WALLS OR FLOORS. PROVIDE HARD DUCTED
SLEEVES AS NEEDED.
6. RECTANGULAR DUCTWORK SHALL BE CONSTRUCTED IN
ACCORDANCE WITH SMACNA LOW PRESSURE DUCT
STANDARDS, +/- 1.0" W.C. FROM ASTM A 653/A 653M G-90
COATED GALVANIZED SHEET STEEL. SEAMS SHALL BE
PITTSBURGH CONSTRUCTION, NO BUTTON PUNCH OR
SNAP LOCK SEAMS ARE ACCEPTABLE. SEAL ALL
TRANSVERSE AND LONGITUDINAL SEAMS WITH WATER
BASED DUCT SEALER, SEAL CLASS B. GAUGE AND
JOINT CLASSIFICATIONS ACCEPTABLE ARE AS
FOLLOWS, ALL SECTION LENGTHS ARE 48" MAXIMUM,
REFER TO SMACNA RIGIDITY TABLES FOR GAUGES ON
LONGER SECTIONS IF REQUIRED:
< 12" 26 GAUGE, FLAT S AND DRIVE
12"-24" 24 GAUGE, FLAT S AND DRIVE
25"-34" 22 GAUGE, STANDING S AND FLAT DRIVE
34"-40" 22 GAUGE, STANDING S AND STANDING
DRIVE
>40" REFER TO SMACNA FOR STANDARDS.
7. DUCT HANGERS: COMPLY WITH SMACNA'S "HVAC DUCT
CONSTRUCTION STANDARDS - METAL AND FLEXIBLE,"
CHAPTER 5, "HANGERS AND SUPPORTS." PROVIDE
GALVANIZED MINIMUM 22 GAUGE 1" WIDE STRAP TO
HANG RECTANGULAR DUCTWORK SMALLER THAN 30"
WIDE. DUCT HANGERS FOR RECTANGULAR SHEET
METAL DUCTS 30" AND LARGER SHALL BE TRAPEZE
STYLE USING UNI-STRUT AND 3/8" OR 1/2" ROD.
PROVIDE GRIPPLE, DURODYNE OR EQUAL CABLE
HANGERS FOR HANGING ROUND DUCTWORK. SUPPORT
ALL HANGERS FROM STRUCTURE PER SMACNA
STANDARDS.HANGERS FOR SPIRAL DUCTS GREATER
THAN 28" IN DIAMETER SHALL BE HUNG WITH ROD AND
DUCT CLAMP. FLEXIBLE DUCTING SHALL BE
SUPPORTED USING MINIMUM 2" WIDE NYLON STRAP.
ALL INTERVALS ARE PER SMACNA.
DUCT ACCESSORIES
1. COORDINATE WITH ARCHITECTURAL DRAWINGS AND
PROVIDE FIRE AND FIRE AND SMOKE DAMPERS AT FIRE
RATED ASSEMBLY PENETRATIONS IN ACCORDANCE
WITH THE INTERNATIONAL BUILDING CODE AND WHERE
SHOWN ON PLANS.
2. PROVIDE FLASHING MATERIALS AND OR SLEEVES AS
REQUIRED FOR ALL DUCT PENETRATIONS OF NON
RATED ELEMENTS. EXPOSED PENETRATIONS SHALL BE
FLASHED WITH SHEET METAL TIGHT TO WALLS.
3. PROVIDE HIGH EFFICIENCY TAKE OFFS, PEAL AND
STICK STYLE ATTACHED TO RECTANGULAR DUCTING
WITH SHEET METAL SCREWS FOR ALL ROUND SUPPLY
AIR TAKE OFFS AND SADDLES.
DUCT INSULATION
1. ALL DUCT INSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LESS (ON THE FLAME
SPREAD TEST SCALE) AND SMOKE DEVELOPMENT OF
50 OR LESS (ON THE SMOKE TEST SCALE) OR AS
DEFINED BY NFPA 255 STANDARD METHOD OF TESTING
OF SURFACE BURNING CHARACTERISTICS OF BUILDING
MATERIALS, LOCAL CODES AND LOCAL AUTHORITIES
HAVING JURISDICTION. DUCT WRAP SHALL BE
FIBERGLASS MATERIAL PER ASTM C-411,ASTM
C-1104,ASTM C665, ASTM C-1338, ASTM E-84, UL723,
NFPA 90A,CAN/ULC S102-1188,ASTM C1290, ASTM C553,
ASTM C1136.
2. INSULATION: INSTALL ALL INSULATION IN STRICT
ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS
IN A TIGHT AND NEAT MANOR. NO SAGGING, FRAYED
OR TORN INSULATION WILL BE EXCEPTED. UNLESS
OTHERWISE NOTED ON PLANS DUCTWORK SHALL BE
INSULATED AS FOLLOWS:
SA/RA- INTERNAL: 1-1/2" FIBERGLASS DUCT WRAP
WITH FSK FACING, 75 #/FT3 MINIMUM
APPLIED R-3.5 INSTALLED IN STRICT
ACCORDANCE WITH MANUFACTURERS
REQUIREMENTS.
SA/RA IN UNCONDITIONED OR ATTIC SPACES
OUTSIDE THE BUILDING INSULATION
ENVELOPE; 2" MINIMUM R-6 AS APPLIED
FSK DUCT WRAP.
LINERS: DUCT LINER FOR PLENUMS AND RTU
DROPS DUCTS SHALL BE
MINIMUM 1” THICK, 1-1/2 # DENSITY PER
CU. FT., HAVING MAT FACED OR
MONOLITHIC CONSTRUCTION WITH SKIN
SMOOTH MICROBIAL SURFACE TO
WITHSTAND VELOCITIES TO 4000 FPM.
INSULATION SHALL FIT SNUGLY AGAINST
THE INTERIOR DUCT SURFACES, AND BE
FASTENED TO THE DUCT WITH
A 50% HEAVY COAT OF RECOMMENDED
ADHESIVE AND METAL FASTENERS WHICH
DO NOT PIERCE THE DUCT, SPACED
AT 12” CENTERS. ALL EXPOSED EDGES OF
THE INSULATION SHALL BE COATED WITH
MANUFACTURED RECOMMENDED
ADHESIVE. SIZES ON PLANS INDICATE
FREE AREA.
EXTERIOR INSULATE WITH CONTINUOUS MINIMUM R-6
POLYISOCYANURATE FOAM SHEATHING
COVERED WATER TIGHT IN VENTURE CLAD
1577CW CLADDING..
CHECK TEST AND START UP REQUIREMENTS
1. LABEL ALL MAJOR PIECES OF EQUIPMENT WITH
LAMACOID PLASTIC, BLACK WITH WHITE LETTERS. SIZE
TO BE CONSISTENT WITH EQUIPMENT BEING LABELED.
LENGTH AND WIDTH VARY FOR REQUIRED LABEL
CONTENT. THERMOSTAT AND SENSOR LABELS SHALL
BE ADJUSTED TO PROVIDE ESTHETIC APPEARANCE.
2. PROVIDE AIR BALANCE BY CONTRACTOR.
CONTRACTOR SHALL BALANCE SUPPLY, RETURN,
OUTSIDE, RELIEF AND EXHAUST AIR SYSTEMS IN
ACCORDANCE WITH CURRENT SMACNA, NEEB OR AABC
STANDARDS TO DESIGN VALUES AND PROVIDE
WRITTEN REPORT TO ARCHITECT. MECHANICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
ALL DEVICES, DRIVES, SHEAVES, MOTOR CHANGES
AND REWORK AS REQUIRED TO MEET DESIGN
REQUIREMENTS.
3. TEMPERATURE CONTROL WORK SHALL BE THE
RESPONSIBILITY OF THE HVAC CONTRACTOR. PROVIDE
ALL COMPONENTS INCLUDING T/S, T/S WIRE (PLENUM
RATED IN RA PLENUMS), SWITCHES, ACTUATORS ETC.
AS REQUIRED FOR A COMPLETE SYSTEM. PRIOR TO
ROUGH-IN COORDINATE FINAL LOCATION FOR ALL
CONTROLS WITH OWNERS REPRESENTATIVE.
4. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION
AND MAINTENANCE MANUALS, AIR BALANCE REPORT
AND AS BUILT DRAWINGS. PROVIDE (1) TRAINING
SESSION TO OWNER SELECTED PERSONNEL AS
REQUESTED AND PROVIDE WARRANTY INFORMATION
FOR ALL MANUFACTURERS WARRANTED EQUIPMENT
PIPING
1. REFRIGERATION PIPING;
A. SYSTEMS 5 TONS OR LESS; MANUFACTURED
REFRIGERANT LINE SETS: ANNEALED-COPPER
SUCTION AND LIQUID LINES FACTORYCLEANED, DRIED,
PRESSURIZED WITH NITROGEN, SEALED, AND WITH
SUCTION LINE INSULATED. PROVIDE IN STANDARD
LENGTHS FOR INSTALLATION WITHOUT JOINTS, EXCEPT
AT EQUIPMENT CONNECTIONS OR ACCESSIBLE
LOCATIONS. CONNECTIONS AND WROUGHT-COPPER
FITTINGS WHERE REQUIRED SHALL BE BRAZED WITH
MINIMUM 8% SIL-FLOS.
B. INSULATION; SUCTION AND ALL DUCTLESS SPLIT OR
VRF LINES; MINIMUM 1/2" THICK WALL INSULATION
SHALL BE A FLEXIBLE, CLOSED-CELL ELASTOMERIC
PIPE INSULATION, AP ARMAFLEX OR AC ACCOFLEX.
ADHESIVE SHALL BE ARMAFLEX 520, 520 BLACK OR 520
BLV ADHESIVE. THE INSULATION MUST CONFORM TO
ASTM C534 GRADE 1, TYPE I ARMAFLEX AND BE
INSTALLED IN STRICT ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS. (3/8" WALL
WILL NOT BE ACCEPTED).
C. ALL INSULATION EXPOSED TO OUTDOORS SHALL BE
EITHER PVC LAGGED OR SHALL BE PAINTED WITH
ARMA-FINISH FR UV PROTECTING PAINT.
D. LINES SHALL BE RUN KINK FREE AND GENERALLY
CONTINUOUS AND AT 90 DEGREE ANGLES TO
STRUCTURE. AVOID JOINTS WHEN POSSIBLE. ALL
REQUIRED JOINTS SHALL BE MADE IN ACCESSIBLE
LOCATIONS OR M.C. SHALL PROVIDE ACCESS PANELS
AS NEEDED. ALL BENDS SHALL BE MADE WITH LONG
RADIUS FITTINGS OR WITH MECHANICAL BENDING TOOL
TO PROVIDE SMOOTH LONG RADIUS TURNS. SUPPORT
ALL PIPING WITHOUT CRUSHING OR DEPRESSING
INSULATION. USE REFRIGERATION STYLE CUSH
CLAMPS MOUNTED TO STRUT, DO NOT LAY PIPING ON
STRUCTURAL BUILDING MEMBERS. SLEEVE ALL
PENETRATIONS AND SEAL WATER TIGHT.
E. PRESSURE TEST, TRIPLE EVACUATE AND PREPARE ALL
PIPING IN STRICT ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS.
2. CONDENSATE PIPING
A. PROVIDE TRAPS BUILT FROM INDIVIDUAL FITTINGS ON
ALL EVAPORATOR DRAIN PANS MINIMUM DEPTH 1.5
TIMES BLOWER BLOCKED TIGHT STATIC PRESSURE.
ALL TRAPS SHALL BE CONSTRUCTED WITH PVC 90S
(MANUFACTURED RUNNING TRAP FITTINGS ARE NOT
ACCEPTABLE). PROVIDE ALL TRAPS WITH CLEAN OUTS
AND REMOVABLE CAPS AS NEEDED FOR MAINTAINING
LINES.
B. HVAC CONTRACTOR SHALL COORDINATE CONDENSATE
DISPOSAL POINTS WITH P.C. HVAC CONTRACTOR IS
RESPONSIBLE FOR PIPING FROM EVAPORATOR COILS
TO DISPOSAL POINT. P.C. IS RESPONSIBLE FOR STAND
PIPES, FLOOR AND HUB DRAINS AS NEEDED.
C. POLYVINYL CHLORIDE DRAIN, WASTE AND VENT PIPE
(PVC) SCHEDULE 40 MINIMUM SIZE 3/4" . INSULATED IN
RETURN AIR PLENUMS.
D. PROVIDE CONDENSATE PUMPS AS REQUIRED WITH
HIGH LEVEL SHUT DOWN SWITCHES INTERLOCKED TO
A/C UNITS.
E. PITCH ALL PIPING MINIMUM 1
4" PER FOOT. SUPPORT
PIPING AT MINIMUM 5'-0" INTERVALS. SECURE FINAL
CONNECTION AT SEWER WITH MINIMUM 1-1/2" AIR GAP
CONNECTION.
F. INSULATE ALL PIPING IN RA PLENUMS AND ABOVE HARD
CEILINGS WITH MINIMUM 3/8" WALL ARMAFLEX
INSULATION.
FIRE STOPPING
a. FIRE STOPPING SYSTEMS SHALL BE IN FULL
COMPLIANCE WITH SECTIONS 713 OF THE IBC AND
SECTION 607 OF THE IMC.
b. CONTRACTOR SHALL MAKE REFERENCE TO
ARCHITECTURAL PLANS AND PROVIDE ALL REQUIRED
FIRE STOPPING.
c. CONTRACTOR SHALL PROVIDE FULL SUBMITTAL
INDICATING METHODS OF CONSTRUCTION AND UL
LISTING OF EACH SYSTEM.
d. DUCTS AND AIR TRANSFER OPENINGS.
PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS
BY DUCTS THAT ARE NOT PROTECTED WITH DAMPERS
SHALL COMPLY WITH SECTIONS 713.2 THROUGH
713.3.3 OF THE IBC. PENETRATIONS OF HORIZONTAL
ASSEMBLIES NOT PROTECTED WITH A SHAFT AS
PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND
NOT REQUIRED TO BE PROTECTED WITH FIRE
DAMPERS BY OTHER SECTIONS OF THE IBC CODE,
SHALL COMPLY WITH SECTIONS 713.4 THROUGH
713.4.2.2 OF THE IBC. DUCTS AND AIR TRANSFER
OPENINGS THAT ARE PROTECTED WITH DAMPERS
SHALL COMPLY WITH SECTION 716.
e. FIRE DAMPERS, SMOKE DAMPERS, COMBINATION
FIRE/SMOKE DAMPERS AND CEILING RADIATION
DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND
SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN
ACCORDANCE WITH THE REQUIREMENTS OF SECTION
607 OF THE IMC. AND THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS AND LISTING.
f. ACCESS DOORS SHALL BE PERMITTED IN CEILINGS OF
FIRE-RESISTANCE-RATED FLOOR/CEILING AND
ROOF/CEILING ASSEMBLIES PROVIDED SUCH DOORS
ARE TESTED IN ACCORDANCE WITH ASTM E 119 OR UL
263 AS HORIZONTAL ASSEMBLIES AND LABELED BY AN
APPROVED AGENCY FOR SUCH PURPOSE. ALL
ACCESS DOORS SHALL BE PROVIDED BY TRADE
MAKING PENETRATIONS.
ROOF JACK, MATCH ROOF COLOR
ROOF TOP UNIT
REVOLUTIONS PER MINUTE
SUPPLY AIR FAN
RJ
RPM
RTU
SAF
STATIC PRESSURESP
TCC
TSP TOTAL STATIC PRESSURE
WALL CAPWC
WALK IN COOLERWIC
WALK IN FREEZERWIF
ET EXPANSION TANK
ELECTRIC WATER COOLEREWC
TMV THERMOSTATIC MIXING VALVE
AFF ABOVE FINISH FLOOR
URINAL
SK SINK
MOP SINK
WATER CLOSET
WATER HEATER
CO CLEAN OUT
PLUMBING CONTRACTOR
STORM DRAIN
VENT THROUGH ROOF
SANITARY SEWER
ST STORAGE TANK
SD
SAN
CW COLD WATER DOMESTIC
PC
PRV
PSI
PRESSURE RELEIF VALVE
POUNDS PER SQUARE INCH
MS
LAV LAVATORY
HWS
HWR HOT WATER RETURN DOMESTIC
HOT WATER SUPPLY DOMESTIC
GPM GALLONS PER MINUTE
WH
GC GENERAL CONTRACTOR
VTR
UR
WC
FOOTFT
INCHIN
LEAVING AIR TEMPERATURE
LINEAR SLOT DIFFUSER
MANUAL
LAT
IR
MAN
LS
1000 BTUH
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MBH
MC
MCC
MFR MANUFACTURER
PRESSURE DROP
POOL DEHUMIDIFICATION UNIT
PACKAGE TERMINAL AIR CONDITIONER
POUNDS PER SQUARE INCH
PRESSURE RELEIF VALVE
PD
PDU
PTAC
PSI
PRV
INFRA-RED
AIR HANDLING UNIT
ACCU
AHU
BOTTOM OF DUCT
BACKDRAFT DAMPER
BOD
BDD
COMBUSTION AIR
CUBIC FEET PER MINUTE
CA
CFM
AIR COOLED CONDENSING UNIT
ENTERING AIR WET BULB
ENTERING AIR DRY BULB
ROUND
EAWB
EADB
Ø
DRY BULBDB
ELECTRICAL CONTRACTOREC
ELECTRIC WALL HEATER
EXHAUST FANEF
EWH
HOOD
EXTERNAL STATIC PRESSURE
ELECTRIC REHEAT COIL
H
ESP
ERC
EG EXHAUST GRILLE OR REGISTER
FURNACE
FCU
F
FIRE DAMPER OR FLOOR DRAIN
FIRE AND SMOKE DAMPER
FD
FD/SD
FEET PER MINUTEFPM
FAN COIL UNIT
ABBREVIATIONS
UNLESS OTHERWISE NOTEDUON
TEMPERATURE CONTROL CONTRACTOR
REDUCED PRESSURE ZONED BACKFLOWRPZB
FSK FOIL SCRIM VAPOR BARRIER
RETURN AIRRA
SUPPLY AIRSA
EACHEA
OUTSIDE AIROA
VARIABLE AIR VOLUME BOXVAV
FAN POWERED VAV BOXFPVAV
DEGREES FARENHEITDEG F
AIR COOLED CONDENSING UNIT
MANUAL VOLUME DAMPER LOCKING WITH SHAFT
FIRE DAMPER
ROUND MOTORIZED DAMPER
M
COMBINATION FIRE/SMOKE DAMPER
THERMOSTAT
LAY-IN EXHAUST GRILLE
ROOF EXHAUST FAN
TURNING VANES DOUBLE THICKNESS
SYMBOLS
XXX
X-#
EQUIPMENT SYMBOLS
FD
FD
SD
ROOF TOP UNIT
W/D
W/D
ECH
HORIZONTAL FURNACE OR FC WITH
DRAIN PAN
HORIZONTAL AIR COOLED CONDENSING UNIT
RECTANGULAR CENTERED DUCT TRANSISTION
RECTANGULAR ECCENTRIC DUCT TRANSITION
WALL MOUNTED EXHAUST FAN
LAY-IN SUPPLY AIR DIFFUSER
LAY-IN RETURN AIR REGISTER OR GRILLE
SURFACE MOUNTED SUPPLY AIR DIFFUSER
DUCT MOUNTED ROUND DIFFUSER
LINEAR OR SLOT DIFFUSER
ROOF MOUNTED INTAKE/EXHAUST HOOD
RECTANGULAR
ROOF MOUNTED INTAKE/EXHAUST HOOD
ROUND
SURFACE MOUNTED SUPPLY AIR DIFFUSER
CEILING MOUNTED EXHAUST FAN
MODULAR AIR HANDLING UNIT AHU
ACCU
REF
IH
RH
IH
RH
FC
F
AC
EF
EF
RTU
CEILING MOUNTED ELECTRIC HEATER
DIFFUSER SYMBOLS
DUCT SYMBOLS
DIRECT DUCT MOUNTED REGISTER
DIFFUSER TAG
EWHELECTRIC WALL HEATER
ECCENTRIC SQUARE TO ROUND TRANSITION
CENTERED SQUARE TO ROUND TRANSITION
SHEET METAL DUCT WIDTH BY DEPTH
LINED SHEET METAL DUCT FREE AREA WIDTH
BY DEPTH.
ACCESS DOOR
SQUARE SHEET METAL 90 PROVIDE WITH
DOUBLE THICKNESS TURNING VANES.
RADIUS SHEET METAL 90, R=1.5*D
ROUND HIGH EFFICIENCY BRANCH DUCT
TAKE OFF ON ROUND DUCT.
ROUND TAP BRANCH DUCT TAKE OFF ON
ROUND DUCT.
HIGH EFFICIENCY BRANCH DUCT TAKE OFF
ON RECTANGULAR.
STANDARD ROUND TAP BRANCH DUCT TAKE
OFF ON ROUND DUCT.
SQUARE SHEET METAL 90 PROVIDE WITH
DOUBLE THICKNESS TURNING VANES.
FULL BODY ROUND TEE FITTING
CONTROL SYMBOLS
THERMOSTAT IN LOCK BOX
SENSOR
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
NITROGEN OXIDE SENSOR
M
RECTANGULAR MOTORIZED DAMPER
DIRECT DUCT MOUNTED REGISTER
MARK
CFM
NO
CO2
CO
S
T
T
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
M001
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
55° SUSPENSIONDROP ROD
NOTE:
HOOKS ARE TO BE
CLOSED UP AFTER
ASSEMBLY
2/0 GA CHAIN
(TWISTED LINK,
PLATED)
EYE HOOK
PURLING FASTENERS
REFLECTOR
BRACKET
OPTIONAL
TURNBUCKLE
(±3" ADJUSTMENT)
3 8Ø ROD
CHAIN
('U' TYPE SHOWN)
2/0 GA CHAIN
(TWISTED LINK,
PLATED)
EYE HOOKS
* THESE ANGLES TO BE EQUAL
AND NOT MORE THAN 45°
**
**
ON U TUBE VARIANTS THE HEATER SHOULD SLOPE DOWNWARDS TOWARDS THE RETURN BEND AND
ON LINEAR VARIANTS SHOULD SLOPE DOWNWARDS TOWARDS BURNER BY APPROX. 1/2" FOR BOTH
HORIZONTAL AND WALL MOUNTED INSTALLATIONS.
WHERE CHAIN SUPPORTS
HAVE AN ANGLE OF
INCLINATION GREATER THAN
15° AN EQUAL AND OPPOSITE
SUPPORT IS RECOMMENDED
VERTICAL SUSPENSION CHAIN IDEAL. WHERE
SUPPORTS ARE INCLINED, MAXIMUM
RECOMMENDED ANGLE OF INCLINATION IS 15°
15°
MAX
LAY-IN DIFFUSER DETAIL
NO SCALEB
SECURE FLEXIBLE DUCT TO SUPPLY DIFFUSER
ELBOW FITTING WITH DRAWBAND.
SHEET METAL ELBOW
1-1/2" DUCT WRAP
SUPPLY DIFFUSER CEILING
MOUNT DIFFUSER IN
BOTTOM OF BRANCH
WITH SADDLE AS HIGH
AS POSSIBLE
SPIRAL BRANCH DUCT
TIGHT TO OR
THROUGH STRUCTURE
ADJUSTABLE GRIPPLE
STRANDED WIRE
HANGER TYPICAL.
SPIRAL CAP
FULLY FRAMED OPENING IN
DRYWALL CEILING.
CONCEALED FASTENER LINEAR
SLOT DIFFUSER PER SCHEDULE.
CUSTOM FABRICATED OR
MANUFACTURERS INTERNALLY
LINED PLENUM BOX WITH
RECTANGULAR, OVAL OR ROUND
TAKE OFF SIZE PER PLANS.
INFRARED HEATER INSTALLATION DETAILS
NO SCALEG
LAY-IN DIFFUSER DETAIL
NO SCALE A
INTAKE/RELIEF HOOD DETAIL
NO SCALED
30° MAX
O
AIR FLOW
45 DEG.
OCL CONNECTION
TAKE OFF. HAMMER
LOCKED OR FLANGED AND FULLY SEALED
RECTANGULAR
DUCT
BRANCH
CONCENTRIC TRANSITION
MAX, 45 DEG. DIVERGING
AND 60 DEG. CONVERGING
OFFSET. PROVIDE
MINIMUM 2" STRAIGHT
SECTION AT EACH END.
MAX 30 DEG.
ECCENTRIC TRANSITION MAX, 30 DEG.
30° MAX
AIR FLOWV.D.
HIGH EFFICIENCY
FLANGED TAKE OFF
COMPLETELY SEALED
ROUND SHEET METAL
DUCT TO WITH IN
5'-0" OF
DIFFUSER
NOTE:
AIRFOIL BLADES TO BE USED WHERE
NORMAL RADIUS ELBOW IS
IMPRACTICAL
& WHERE ELBOW IS WITHIN 5 FT OF A
BRANCH TAKE-OFF.
NOTE:
IN GENERAL, ELBOWS TO HAVE
FULL TURNING RADIUS (R=A).
WHERE "R" IS EQUAL TO OR
GREATER THAN "A" MINIMUM
RADIUS (R) = 4 INCHES.
R=A 118"
A
SHEET METAL GAUGES AND RIGIDITY SHALL BE IN
ACCORDANCE WITH SMACNA PRESSURE CLASS 1.0" UNLESS
OTHERWISE SPECIFIED.
DUCT CONSTRUCTIN DETAILS
NO SCALEH
3/4 PVC TRAPPED COND.
DRAIN. PROVIDE TRAP DEPTH
PER MANUFACTURE WITH
CLEAN OUT PLUG.
FRESH AIR INTAKE HOOD
MAINTAIN MINIMUM OF 10'-0"
FROM ALL EXHAUST AND
PLUMBING VENTS
3" MIN.
48" LONG SHEET METAL
DROPS FULL CURB OPENING
SIZED AND LINED WITH 1"
DUCT LINER AND WITH FLEX
CONNECTOR
CUT ROOF DECK ONLY AS
NEEDED FOR DUCT DROPS.
PROVIDE R-13 BATT OR
ROOFING INSULATION PLACED
ON REMAINING DECK.
ELECTRICAL DISCONNECT
PER NEC
MAINTAIN MINIMUM OF 10'-0"
FOR EDGE OF ROOF
AGA GAS SHUT OFF, 2
PSIG-7" W.C. REGULATOR
DIRT LEG AND UNION BY PC.
PROVIDE NEOPRENE CURB
TAPE AT DUCT CONNECTION
SEAL AIR TIGHT.
PLACE EXTRA ROOF
MEMBRANE BETWEEN
MIRO 1.5 POLYCARBONATE
PIPE SUPPORTS PIPE
SUPPORT AND ROOF
MEMBRANE. TYP.
STEEL ANGLE FRAME BY STEEL
ERECTION CONTRACTOR COORDINATE
SIZES WITH STEEL SHOP DRAWINGS.
ROUND CHIMNEY TOP
METALBESTOS FLUE
RECOMMENDATIONS
MANUFACTURER'S
INSTALL PER
NOTE
FLASHING
ROOF
STORM COLLAR
METAL ROOF
AIR SPACE AROUND FLUE
LISTED
CONNECT TO APPLIANCE WITH B-VENT CONNECTOR
PIPING SLOPE AT MINIMUM 1/4" PER FOOT
14" HIGH MINIMUM
PRE-FABRICATED ROOF
CURB ATTACHED TO
CONCRETE ROOF
STRUCTURE WITH
CONCRETE ANCHORS.
SECURE VENT TO
ROOF CURB AS
REQUIRED WITH
SHEET METAL
SCREWS.
DUCT TO BE SAME
SIZE AS THROAT
SIZE OF VENT.
RELIEF VENT
PROVIDE 1/2" X 1/2" WELDED
WIRE MESH SCREEN OVER END
OF DUCT.
ROOF CONSTRUCTION.
REFER TO ARCHITECTURAL
DRAWINGS FOR TYPE.
SEAL ALL JOINTS.
MOTORIZED CONTROL DAMPER BY
RELIEF HOOD VENDOR.
SPIRAL DUCT DIFFUSER DETAIL
NO SCALE C
SPIRAL DUCT DIFFUSER DETAIL
NO SCALE E RTU INSTALLATION DETAIL
NO SCALEF
CAULK WATER TIGHT
ATTACH TO
ROOF DECK
W/ #10 SHEET
METAL SCREWS
MINIMUM 36" ABOVE ROOF LINE
METALBESTOS CONNECTOR
ROUTED FULLY TO APPLIANCE
NO SINGLE WALL ALLOWED.
INTAKE VENT
REFERENCE ARCHITECTURAL
REFLECTED CEILING PLAN AND
ELECTRICAL LIGHTING PLAN AND
COORDINATE INSTALLATION WITH
ALL CEILING ELEMENTS.
M002
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
12" MIN.
METAL ROOF DECK
MECH. DUCT
INSULATION THICKNESS.
AS REQUIRED TO MATCH
TREATED WOOD BLOCKING
EXHAUST FAN
PROVIDE (2) LAG
SCREWS PER SIDE
WITH NEOPRENE
WASHSERS
SEAL FAN TO CURB
WITH NEOPRENE
GASKET AIR TIGHT
GRAVITY
BDD
3X3 ANGLE REF.
STRUCTURAL
PLANS.
(2) 3 X 3 X 5/16 ANGLES
FACE TO FACE
BOLTED TO ROOF JOIST
BY M.C.
FAN MOUNTING BRACKETS,
BOLTS, WASHERS AND SAFETY
CABLE BY FAN MANUFACTURER.
BOLT TO C CHANNEL OR TO
BOTTOM OF GIRDER.
SCALE : NONE
BIG ASS FAN MOUNTING DETAILA
SECTION AA
A
A
DUCT LESS SPLIT
TRAP SUCTION LINE
EVERY 10' UP RISER
NOT TO SCALE
MINI SPLIT INSTALLATION DETAILD
PATE PORTAL ROOF CURB
TYPICAL ALL LINE SETS. INSULATE
AND SEAL WATER TIGHT.
INVERTED SUCTION LINE TRAP.
SLOPE LINE BACK TO
COMPRESSOR.
DISCONNECT BY E.C.
AIR COOLED
CONDENSING
UNIT
WALL
WALL
BIRD SCREEN
CAULK INTERIOR AND EXTERIOR
PERIMETER WEATHER TIGHT WITH
SILICON CAULKING.
LOUVER WITH KYNAR FINISH TO
MATCH BLDG. COLOR
EXTERIOR
1"X1"X1/8" STEEL ANGLE. SCREW TO
LOUVER SLEEVE 6" O.C. # 10
SCREWS AND ANCHORED TO
MASONRY WALL 12" O.C. WITH 1/4"
MASONRY ANCHORS. TYPICAL TOP,
BOTTOM AND SIDES.
SCALE : NONE
EXHAUST FAN DETAIL B SCALE : NONE
WALL LOUVER DETAILC
GALVANIZED
EQUIPMENT
RAIL BY MC
1/2" HOSE TO OPEN SITE
INVERTED TEE IN PVC DRAIN LINE
BY MC ROUTE 3/4 SCH 40 PVC
LINE TO HUB/FLOOR DRAIN
PROVIDED BY P.C. AT MINIMUM
1/4" PER FT SUPPORT MIN. 5' OC.
MINI-WHITE TANK MINI SPLIT
CONDENSATE PUMP WITH HIGH
LEVEL CUT OUT. WIRE TO IDU PER
MANUFACTURES INSTRUCTIONS
MINIMUM 48"
PRIOR TO ROUGH-IN COORDINATE CLEARANCES OF BLADES WITH
ALL TRADES AND EQUIPMENT SUPPLIERS.
M003
OPTIONAL SUSPENDED CEILING INSTALLATION OF SUNTUBE HEATER
STANDARD REFLECTOR
12"
MINIMUM
SHIELD
NOTCH AS REQUIRED AROUND THE
REFLECTOR SUPPORT BRACKET
H
EXTENSION REFLECTOR
4'-0" LONG X 8", 12", OR 16" WIDE
SUSPENDED CEILING FRAME
2 FT. ALUMINUM LOUVER
SCALE : NONE
INFRARED HEATER SUSPENDED CEILING INSTALLATIONE
PARTICULAR CONSIDERATION MUST BE GIVEN TO CLEARANCES TO COMBUSTIBLES IN THIS TYPE OF INSTALLATION.
SINCE THE STANDARD REFLECTOR IS USED, THE CLEARANCE TO COMBUSTIBLES WILL BE THE SAME AS INDICATED IN
THE "SUMMARY OF SPECIFICATIONS" IN THE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTION MANUAL.
VERIFY THAT THE CEILING PANELS ADJACENT TO EACH SIDE OF THE HEATER ARE ARE NOT COMBUSTIBLE OR THAT
THEY ARE MADE OF CLASS A MATERIALS. VERIFY THE INSTALLATION IS ACCEPTABLE TO LOCAL AUTHORITIES. IN
ADDITION, TO PROVIDE ADEQUATE COMFORT LEVELS, REFER TO "HEATER LOCATION" IN THE INSTALLATION, OPERATION
AND MAINTENANCE INSTRUCTION MANUAL TO IDENTIFY MINIMUM MOUNTING HEIGHT.
THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS IN THIS EQUIPMENT, OR COVER EVERY POSSIBLE
SITUATION TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD PROBLEMS ARISE
THAT ARE NOT COVERED SUFFICIENTLY IN THESE INSTRUCTIONS, THE PURCHASER IS ADVISED TO CONTACT THE
ENGINEERING DEPARTMENT AT SOLARONICS, INC. FOR FURTHER INFORMATION.
THE SUNTUBE LOW-INTENSITY GAS INFRARED HEATER CAN BE INSTALLED OVER SUSPENDED CEILINGS WITH AN
ALUMINUM LOUVER DIRECTLY BELOW THE HEATER. THE ALUMINUM LOUVER IS A 2 FOOT WIDE X 4 FOOT LONG BY 1/2"
THICK, NON-FLAMMABLE , 1/2" X 1/2" OPEN-GRID CELL PATTERN CONSTRUCTED OF 0.015" ALUMINUM WITH A MILL FINISH.
NEVER USE REGULAR CEILING TILES DIRECTLY BELOW THE HEATER SINCE IT WOULD CREATE AN UNSAFE CONDITION.
THE HEATER IS INSTALLED IN A NORMAL FASHION (AS DESCRIBED IN THE INSTRUCTION MANUAL) WITH THE TUBE
SUSPENDED OVER THE LOUVERS FROM A MINIMUM HEIGHT OF 4.000" TO A MAXIMUM HEIGHT OF 14.375" (DISTANCE H).
CALCULATE DISTANCE "H" BETWEEN THE BOTTOM OF THE HEAT EXCHANGER TUBE TO THE TOP OF THE LOUVER TO
DETERMINE THE SIZE OF THE EXTENSION REFLECTORS REQUIRED FROM THE FOLLOWING TABLE:
THE EXTENSION REFLECTORS ARE AVAILABLE IN STANDARD 4 FOOT SECTIONS AND ARE LAID ALONGSIDE THE
STANDARD REFLECTORS. IT MAY BE NECESSARY TO CUT NOTCHES FOR CLEARANCE AROUND THE REFLECTOR
SUPPORT BRACKETS.
A SHIELD,IS PLACED OVER THE SUSPENDED CEILING FRAME MEMBER WHICH PASS DIRECTLY UNDERNEATH THE
HEATER.
FOR YOUR SAFETY, GLOVES ARE TO BE WORN WHEN HANDLING THE ALUMINUM LOUVERS TO PROTECT THE HANDS
FROM SHARP EDGES. ALLOW A 12 INCH MINIMUM CLEARANCE FROM THE TOP AND SIDES OF THE BURNER.
09/21/20
DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
WATTS
SERVICE BAY BAF-1
NOTESVOLTRPM HP
MOTOR DATA
ØLOCATIONMODEL # TAG
BIG ASS FAN SCHEDULE
DESCRIPTION
TYPE FAN ANDBIG ASS FAN
1
1 PROVIDE WITH WALL MOUNTED VARIABLE SPEED CONTROLLER AND ALL REQUIRED MOUNTING HARDWARE.
20' BASIC 6 346085 1.5 20' CEILING FAN
WATTS
170.3
SERVICE BAY EF-1
NOTESVOLTRPM HP
MOTOR DATA
Ø LOCATIONMODEL # TAG
EXHAUST FAN SCHEDULE
DESCRIPTION
TYPE FAN AND CFM SP SONES
GREENHECK
G-123-A
EF-2
ROOF 1800 1/2 115 1EF-3
G-070-G ROOF EF-4
ROOF
EF-5 G-080-D
1115 150
ROOF
0.26 2.8
1115 300 0.32 7.3
GB-180 34601334 1-1/25000 ROOF 0.25 22
525 0.31G-090-D 7.4 11151725 1/15
ACCESSORIES/REMARKSVOLTAGE
2774.0 KW
HEATING KW
QMARK
MANUFCTR MARK
EWH-1 AWH
MODEL NO.
ELECTRIC HEATER SCHEDULE
PHASE
1 1
PROVIDE WITH HANGING BRACKET AND DISCONNECT SWITCH.2
1 RECESSED WALL HEATER, PROVIDE WITH INTEGRAL THERMOSTAT AND DISCONNECT
OR
WATTS PER FT.
PROVIDE WITH MOTORIZED LOW LEAKAGE TWO POSITION DAMPER AND BELIMO 120V ACTUATOR.
PROVIDE WITH BIRD SCREEN AND BAKED ENAMEL PAINT, COLOR TO BE SELECTED BY ARCHITECT
LV-1
NOTES: MODEL MFR DESCRIPTIONTAG
LOUVERS/ROOF VENTS
COMPRESSOR INTAKE LOUVER
SIZE
32/32IH-1 GREENHECK FGI
IH-2 GREENHECK FGI 22/22
FREE
AREA FT2
WRITE-UP BAY GRAVITY INTAKE HOOD WITH
MOTORIZED DAMPER.
CFM
5000
1800
5 200/25110.80
CAPACITY CAPACITY
NOTESMOCP
ELECTRICAL DATA
MCA VOLTS/PH/HZ NOM. TONSSENS MBH TOTAL MBH
COOLING
OUTPUT INPUT
GAS HEAT (MBH)
BRYANTRTU-1
TAG
ROOFTOP UNIT SCHEDULE - 460 VOLT - 3 PHASE
MANUFACTURER MODEL WEIGHT EER CFM CFM
O.A. E.S.P.
(IN W.G.)
2247 248/310 187.14 249.58 20 460/3/60 49.8 60
ACCESSORIES
PROVIDE INSULATED FLAT ROOF CURB AND ECONOMIZER WITH BAROMETRIC RELIEF.
664580JE25D310A6A7YD 1 2
1
PROVIDE PROGRAMMABLE THERMOSTAT AND IAQ OA CONTROL WITH ROOM CO2 SENSOR.2
MARK QTY. CONFIGURATION
HEATING DATA ELECTRICAL DATA UNIT
WEIGHT
(LBS)
MANUFACTURER WITH MODEL
NUMBER NOTESINPUT
MBH FUEL TYPE LENGTH
(FT) AMPS VOLTS PH
IR1 1 U TUBE 60 NAT. GAS 18' 1.2 120 1 200 AMBIRAD VSUSN100-ER-S50 1-10
IR2 2 STRAIGHT TUBE 75 NAT. GAS 40' 1.2 120 1 200 AMBIRAD VSUSN75-ER-S40 1-7
IR3 4 125 NAT. GAS 42' 1.2 120 1 200 1-7
NOTES PLEASE PROVIDE THE FOLLOWING ACCESSORIES
1 BALL VALVE AND STAINLESS STEEL FLEX GAS CONNECTOR
2 4", 16GA. ALUMINIZED STEEL TUBING
3 STAINLESS STEEL REFLECTORS
4 STAINLESS STEEL REFLECTOR END CAPS
5 PROVIDE SMART COM TEMPERATURE CONTROL PANEL ZONED AS SHOWN ON PLANS.
6 4" VENT ADAPTER & OUTSIDE COMBUSTION AIR ADAPTERS
7 HANGING CHAIN SETS (CHAIN, KARABINER CLIPS, BEAM CLAMPS, EYE BOLTS)
8 STAINLESS STEEL TUBES
9 STAINLESS STEEL BURNER CABINET
10 WATERTIGHT (NEMA4X) THERMOSTAT
1 2
BRYANTRTU-3 5 460/3/60 1 2
RTU-4
S-2
-0-120STEEL SCD-6" NECKPRICE24X24 LAY-IN DIFFUSER S-1
NOTES:
COLOR : WHITE
REFER TO FLOOR PLAN FOR EXACT CFM.
INTEGRALMAT'L. CFMMODEL MFR TAG DESCRIPTION
DIFFUSER, REGISTERS AND GRILLES
PROVIDE WITH SQUARE TO ROUND REGISTER BOX.3
2
1
S-3
S-4
NC
MAXIMUM
R-2
R-1
R-3
24x24 LAY-IN BAR FACE GRILLE
24x12 LAY-IN BAR FACE GRILLE
44"x18" SURFACE BAR FACE GRILLE
PRICE
PRICE
PRICE
0-2000
0-1000
1650
STEEL
STEEL
STEEL
30
DAMPER
-
-
-
530 -
-530
530 -
1
1
1
1
1
1
1
2
2
2
2
2
2
2
3
3
3
S-5
S-6 PRICE14X4 SPIRAL DUCT GRILLE 100-200 STEEL SDGE
120-220STEEL SCD-8" NECKPRICE24X24 LAY-IN DIFFUSER 30
230-420STEEL SCD-10" NECKPRICE24X24 LAY-IN DIFFUSER 30
1 2
-
-
-
2
2 BASE BID TO BE BIG ASS FAN, VOLUNTARY ALTERNATE TO BE MACRO AIR FAN OF EQUAL PERFORMANCE.
SERVICE BAY GRAVITY INTAKE HOOD WITH
MOTORIZED DAMPER.
PROVIDE WITH INSULATED FLAT ROOF CURB.
1
1
1
1
1
1 PROVIDE WITH FLAT ROOF CURB, DISCONNECT AND BACKDRAFT DAMPER.
GAS-FIRED RADIANT HEATER SCHEDULE
EF-6 G-095-D ROOF 1115 675 0.33 8.6
2773.0 KWQMARKECH-1 CDF 1 1 3
PROVIDE WITH INTEGRAL THERMOSTAT AND DISCONNECT 3
DUCTLESS SPLIT SCHEDULE
MANUFACTURERTAG NOTES:
MS-1 MITSUBISHI
1
AIR FLOW
HI CFM
COOLING CAPACITY
R410A
REFG.
ELECTRICAL SPECIFICATIONS
MOCP(V-Ph-Hz)
ELEC.
208/230-1-60 25
2
PROVIDE WIRED REMOTE T/S CONTROLLER
1
MODEL
INDOOR OUTDOOR MBH
SENSIBLE
MBH
TOTAL
- 24000
SEER
LOW AMBIENT TO 0 DEG. F.
2PKA-A24KA4 PUY-A24NHA4 425 17
8000 0.5
SEER
YES
9314.10BRYANTRTU-2 597 115 46.23 61.84 5 460/3/60 145582JE06A115A2A7YA2000 0.5
1 298/14811.00BRYANT930 120/180 76.37 102.79 8.5 460/3/60 329580JE09D180A2A7YD3000 0.5
14 20
20 25
PROVIDE PROGRAMMABLE THERMOSTAT.3
PROVIDE RA SMOKE DETECTOR.4
4
4
4
4
1725
RPM
1300
1550
1334
1550
1550
FAN DATA
1725
1300
1550
1550
1/60
1/20
1/8 1
20/22ESD-435 1500 GREENHECK 1.3
2
30
30
E-2
E-1 12x12 LAY-IN BAR FACE GRILLE
6X6 SURFACE FACE GRILLE
PRICE
PRICE
0-1000
0-1000
STEEL
STEEL
-
YES
530 -
-530
1
1
2
2
3
3
2 PROVIDE MOTOR STARTER WITH HOA, RUN/STOP LIGHTS AND DAMPER CONTROL.
3
2
3 FAN SHALL RUN CONTINUOUS, COORDINATE WITH E.C.
4 PROVIDE WITH COOLING ONLY LINE VOLTAGE THERMOSTAT AND COORDINATE WITH E.C.
2
3
3
3
1 2
2
1
2
2
3
3
3
RTU-7 1 3 98/14811.00BRYANT835 120/180 68.90 90.10 7.5 460/3/60 300580JE08D180A2A7YD3000 0.5 20 25 4
66/9314.00BRYANTRTU-6 490 1200 0.5 82/115 26.71 36.41 3 460/3/60 11 15407582JE04A115A2A7YA 1 3
RTU-5 1 35 460/3/60 4
9314.10597 115 46.23 61.84 217582JE06A115A2A7YA2000 0.5 14 20
9314.10597 115 46.23 61.84 150582JE06A115A2A7YA2000 0.5 14 20BRYANT
RESTROOM
RESTROOM
STRAIGHT TUBE AMBIRAD VSUSN125-ER-S40
1 2PRICE48 x (2) SLOT DIFFUSER SDS075 -AL 400 30
420-600STEEL SCD-12" NECKPRICE24X24 LAY-IN DIFFUSER
M004
EF-7
EF-8
EF-9
EF-10
WRITE UP BAY
SERVICE BAY
WRITE UP BAY
225 G-070-D RESTROOM ROOF 1115 0.33 4.51550 1550 1/30
150 G-070-G RESTROOM ROOF 1115 0.26 2.81300 1300 1/30
1500 GB-131 AIR COMPRESSOR ROOF 1115 0.3 10.21202 1202 1/4
100 SP-A125 TOOL ROOM CEILING 1115 0.27 4.51100 1100 -
EF-10 100 SP-A125 ELECT. ROOM CEILING 11150.27 4.51100 1100 -
1 3
1 3
1 4
2
4
PROVIDE HEATING ONLY THERMOSTAT
629
TOTAL
CFM
2 1/60/115
(V-Ph-Hz) MOCP
ELECTRICAL SPECIFICATIONS
24.6 30
MBH OUT MBH IN
HEATING CAPACITY
UDAP-30
1
REZNOR UH-1
NOTES:MODELMARK MANUFACTURER
GAS UNIT HEATER
PROVIDE FACTORY CEILING HANGER KIT.2
MCA
20 1 2
09/21/20
3 5 10 13 15 16 17
C
E
H
J
M
O
S
2 1
9 6
D
B
A
F
18
T
G
L
N
7 4 11 12 14
K
28
R
P
300
E-1
300
E-1
75
E-2
120
S-1
120
S-1
120
R-1
120
S-1
120
R-1
120
S-1
120
R-1
120
S-1
120
R-1
275
S-3
275
S-3
200
S-2
120
S-1
120
S-1
150
S-2
120
R-1
220
R-1
200
R-1
22"Ø
22"Ø
140
S-2
140
S-2
300
S-3
300
S-3
120
S-1
120
S-1
120
S-1
220
S-2
220
S-2
220
S-2
220
S-2
220
S-2
220
S-2
100
S-1
75
S-1
220
S-1
75
R-1
100
R-1
120
R-1
120
R-1
600
R-1
280
R-1
150
R-1
1400
R-2
240
S-3
220
R-1
120
R-1
220
S-2
12"Ø16"Ø 20Ø
20"Ø 16'Ø
RTU-46"Ø6"Ø6"Ø6"Ø6"Ø6"Ø8"Ø8"Ø8"Ø8"Ø8"Ø10"Ø6"Ø 8"Ø 8"Ø6"Ø8"Ø8"Ø10"Ø12/106"Ø
6"Ø16/14 22/14ECH-1
EWH-1
T
T
T
T 18/1422/1420/1414"Ø 120
R-1 12"Ø 6"Ø10"Ø 16/14 120
R-1
120
R-1
14/14
12"ØKEY PLAN
AB
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR HVAC PLAN - AREA 'A'
KEY NOTES:
GENERAL NOTES:
1 ROUTE DUCTING BELOW 2ND FLOOR FRAMING
TIGHT TO I BEAMS. COORDINATE WITH PLUMBING,
SPRINKLER AND ELECTRICAL CONTRACTORS.
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEETS M-002 THOUGH M-004 FOR
DETAILS, SCHEDULES AND NOTES.
3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE
CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE
ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO
PROVIDE ALL MOTOR STARTERS, RACEWAYS AND
LINE VOLTAGE CONDUCTORS.
1
M100
09/21/20
18
250
T
100
S-1
100
S-1
250
S-6
250
S-6 250
S-6 S-6
250
S-6
250
S-6
200
S-6 200
S-6
200
S-6
200
S-6
200
S-6
RTU-7
7.5 TON
IR-2 IR-2
IR-3 RTU-48"Ø 10"Ø
12"Ø 14"Ø 16"Ø
8"Ø 10"Ø 12"Ø 14"Ø 16"Ø 16"Ø 16"Ø100
S-1
100
S-1
120
8" W.C.10"Ø8"Ø 12"Ø6"Ø
6"Ø 6"Ø
12"Ø UP
BAF-1BAF-1 CF-1T
T
CF-1
IR-3
6"Ø FLUECOMS
UH-1
UH-1
16/16 UP
TO IH-2
8"Ø UP
TO EF-4
18"Ø UP
TO EF-3
R-2
R-2
S-4S-4 S-4
IR-3
IR-3
6"Ø FLUEIR-1
100
EF-11
100
EF-10
8"Ø 6"Ø16"Ø
12"Ø12"Ø 12"Ø
100
S-6
T
T
T
200
S-6
EWH-1
BBS
SC
MS
CO
NOx
BBS
SC
MS
CO
NOx
OAOA
KEY PLAN
AB
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
FIRST FLOOR HVAC PLAN - AREA 'B'
KEY NOTES:
GENERAL NOTES:
1 IR HEATERS SHALL BE SIMULTANEOUSLY
CONTROLLED IN GROUPS BY SMARTCOM
MULTIZONE IR TEMPERATURE CONTROL PANEL
WITH REMOTE BLACK BULB AND OA SENSOR.
RACEWAYS FOR TCC AND BURNER/BLOWER
INTERLOCKS ARE BY E.C. ALL CONTROLS AND
HEATER COMPONENTS BY M.C.
COORDINATE AND LOCATION OF ALL INFRARED
HEATERS WITH OWNER AND INSTALL PER
MANUFACTURES RECOMMENDED CLEARANCES
WITH REGARD TO CAR LIFTS AND GARAGE
EQUIPMENT. SEE DETAILS ON SHEET M002 FOR
MORE INFORMATION. TYPICAL. PIPE CA FOR
DETAIL BAY HEATER TO WALL CAP, ALL OTHER
HEATERS TO DRAW CA FROM INDOORS.
ROUTE DUCTING BELOW 2ND FLOOR FRAMING
TIGHT TO I BEAMS. COORDINATE WITH PLUMBING,
SPRINKLER AND ELECTRICAL CONTRACTORS.
MOUNT CEILING FAN TO ROOF JOIST PER
MANUFACTURERS INSTRUCTIONS, ELEVATION TO
BE COORDINATED WITH THE LIGHTING SYSTEMS
AND IR HEATERS. SEE DETAIL ON SHEET M002.
INSTALL SERVICE WRITE UP BAY 100 MBH, 40'
LONG STRAIGHT TUBE IR HEATERS SIMILAR TO
RH1 MOUNTED ABOVE ACOUSTIC CEILING WITH
MANUFACTURERS CEILING KITS. INSTALL
ALUMINUM GRILLES AND T-BAR SHIELDS PER
INSTRUCTIONS
BOTTOM OF RADIANT TUBE HEATER NEED TO BE
AT 12'-0 OFF OF FINISHED FLOOR
ROUTE ALL DUCT WORK IN SERVICE DEPARTMENT
IN TRUST SPACE.
ROUTE ALL DUCT WORK UP IN JOIST SPACE.
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEETS M-002 THOUGH M-004 FOR
DETAILS, SCHEDULES AND NOTES.
3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE
CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE
ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO
PROVIDE ALL MOTOR STARTERS, RACEWAYS AND
LINE VOLTAGE CONDUCTORS.
2
3
4
5
1
1
2
2
5
5
2 2
2
2
3
44
M101
3
6
6 6
7
7
7
8
09/21/20
3 5 10 13 15 16 17
C
E
H
J
M
O
S
2 1
B
A
T
G
L
N
11 12 14 7 2
F
18
75
E-2
75
E-2
75
E-2
16"Ø
200
S-2
200
S-2
200
S-2
200
S-2
120
S-1
75
S-1
75
S-1
120
S-1
220
S-1
220
S-1
1000
R-2
1000
R-2
800
R-1
400
S-4
600
S-4
600
S-4
600
S-4
600
S-4
600
S-4
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
400
S-5
1600
R-2
1600
R-2
375
S-5
375
S-5
375
S-5
375
S-5
EF-6
18"Ø
30/30
30/30
1600
R-2
1600
R-2
1600
R-2
24/16 22/12 18/12 12/1210"Ø30/16 30/20 30/22 30/26 10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø12"Ø12"Ø12"Ø12"Ø12"Ø30/20 30/26 22/20 18"Ø18"Ø18"Ø
18"Ø 18"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø
14"Ø14"Ø8"Ø
8"Ø
10"Ø120
R-1
14"ØS-1
200
10"Ø 8"Ø10"Ø 8"Ø10"Ø14"Ø200
R-1
440
R-1
AHU-1
T
120
R-1
10"Ø
10"Ø
12/10 UP
TO EF-5
8/8 UP
TO EF-6
18"Ø
18"Ø
18"Ø
18"Ø
18"Ø
18"Ø 30/28KEY PLAN
B
C
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
SECOND FLOOR HVAC PLAN - AREA 'C'
KEY NOTES:
GENERAL NOTES:
1 ROUTE DUCTING BELOW 2ND FLOOR FRAMING
TIGHT TO I BEAMS. COORDINATE WITH PLUMBING,
SPRINKLER AND ELECTRICAL CONTRACTORS.
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEETS M-002 THOUGH M-004 FOR
DETAILS, SCHEDULES AND NOTES.
3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE
CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE
ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO
PROVIDE ALL MOTOR STARTERS, RACEWAYS AND
LINE VOLTAGE CONDUCTORS.
1
M200
09/21/20
18
150
S-6
150
S-6
150
S-6
150
S-6
150
S-6
150
S-6
E-1
350
250
S-3
300
S-3
10"Ø 12"Ø 14"Ø 18/1414/14 250
R-1
1650
R-3 22/1422/14 DROP
18/18 UP
TO EF-9
M
LV-1
12"Ø DN
KEY PLAN
C
D
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
SECOND FLOOR HVAC PLAN - AREA 'D'
KEY NOTES:
GENERAL NOTES:
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEETS M-002 THOUGH M-004 FOR
DETAILS, SCHEDULES AND NOTES.
3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE
CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE
ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO
PROVIDE ALL MOTOR STARTERS, RACEWAYS AND
LINE VOLTAGE CONDUCTORS.
M201
09/21/20
09/21/20
RTU-1
RTU-2
RTU-3
RTU-4
RTU-5
20 TON
5 TON
5 TON
8.5 TON
5 TON
RTU-7
7.5 TON
RTU-6
5 TON
30/30
IH-1
EF-1
EF-2
IH-2
EF-3
EF-5
MS-1
EF-4
M
M
M
EF-8
EF-9
KEY PLAN
AB
N DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
1 SCALE: 1/8" = 1'-0"
ROOF HVAC PLAN - AREA 'B'
KEY NOTES:
GENERAL NOTES:
1. REFERENCE SHEET M-001 FOR LEGENDS,
ABBREVIATIONS, SPECIFICATIONS AND NOTES.
2. REFERENCE SHEETS M-002 THOUGH M-004 FOR
DETAILS, SCHEDULES AND NOTES.
3. PRIOR TO ROUGH IN, COORDINATE TEMPERATURE
CONTROL RACEWAYS WITH E.C. M.C. TO PROVIDE
ALL CONTROLS AND LOW VOLTAGE CABLES, E.C. TO
PROVIDE ALL MOTOR STARTERS, RACEWAYS AND
LINE VOLTAGE CONDUCTORS.
M301
1 SEE SHEET M300 FOR DUCT WORK INSTALLATION
INFORMATION.
1
1
1
1
1
09/21/20