HomeMy WebLinkAboutP001DATAREV.DATADWG.OF CARMELNAPLETON KIANapleton Automative GroupMEP Engineer874 Cheltenham WayAvon, IN 46123317.506.8151317.745.5761dave@gnaengineering.comGOODERUM & ASSOCIATES ENGINEERINGP: F: E: MUR
EDOOG.RDIVAD
PROFES
SIONA L E N G INEER D
E
NADIIN A
GER RTSIE
STATE OF
No.
10200395
ROOF JACK, MATCH ROOF COLOR
ROOF TOP UNIT
REVOLUTIONS PER MINUTE
SUPPLY AIR FAN
RJ
RPM
RTU
SAF
STATIC PRESSURESP
TCC
TSP TOTAL STATIC PRESSURE
WALL CAPWC
WALK IN COOLERWIC
WALK IN FREEZERWIF
ET EXPANSION TANK
ELECTRIC WATER COOLEREWC
TMV THERMOSTATIC MIXING VALVE
AFF ABOVE FINISH FLOOR
URINAL
SK SINK
MOP SINK
WATER CLOSET
WATER HEATER
CO CLEAN OUT
PLUMBING CONTRACTOR
STORM DRAIN
VENT THROUGH ROOF
SANITARY SEWER
ST STORAGE TANK
SD
SAN
CW COLD WATER DOMESTIC
PC
PRV
PSI
PRESSURE RELEIF VALVE
POUNDS PER SQUARE INCH
MS
LAV LAVATORY
HWS
HWR HOT WATER RETURN DOMESTIC
HOT WATER SUPPLY DOMESTIC
GPM GALLONS PER MINUTE
WH
GC GENERAL CONTRACTOR
VTR
UR
WC
FOOTFT
INCHIN
LEAVING AIR TEMPERATURE
LINEAR SLOT DIFFUSER
MANUAL
LAT
IR
MAN
LS
1000 BTUH
MECHANICAL CONTRACTOR
MOTOR CONTROL CENTER
MBH
MC
MCC
MFR MANUFACTURER
PRESSURE DROP
POOL DEHUMIDIFICATION UNIT
PACKAGE TERMINAL AIR CONDITIONER
POUNDS PER SQUARE INCH
PRESSURE RELEIF VALVE
PD
PDU
PTAC
PSI
PRV
INFRA-RED
AIR HANDLING UNIT
ACCU
AHU
BOTTOM OF DUCT
BACKDRAFT DAMPER
BOD
BDD
COMBUSTION AIR
CUBIC FEET PER MINUTE
CA
CFM
AIR COOLED CONDENSING UNIT
ENTERING AIR WET BULB
ENTERING AIR DRY BULB
DIAMETER
EAWB
EADB
Ø
DRY BULBDB
ELECTRICAL CONTRACTOREC
ELECTRIC WALL HEATER
EXHAUST FANEF
EWH
HOOD
EXTERNAL STATIC PRESSURE
ELECTRIC REHEAT COIL
H
ESP
ERC
E EXHAUST GRILLE OR REGISTER
FURNACE
FCU
F
FIRE DAMPER OR FLOOR DRAIN
FIRE AND SMOKE DAMPER
FD
FD/SD
FEET PER MINUTEFPM
FAN COIL UNIT
ABBREVIATIONS
UNLESS OTHERWISE NOTEDUON
TEMPERATURE CONTROL CONTRACTOR
REDUCED PRESSURE ZONED BACKFLOWRPZB
FSK FOIL SCRIM VAPOR BARRIER
RETURN AIRRA
SUPPLY AIRSA
EXHAUST AIR OR EACHEA
OUTSIDE AIROA
VARIABLE AIR VOLUME BOXVAV
FAN POWERED VAV BOXFPVAV
DEGREES FARENHEITDEG F
CND
HW
HWR
SD
SAN
RD
PIPING LINETYPES
CONDENSATE DRAIN
HEATING WATER SUPPLY DOMESTIC
HEATING WATER RETURN DOMESTIC
STORM DRAIN
SANITARY SEWER
COLD WATER DOMESTIC
ROOF DRAIN
SYMBOLS
COMPRESSED AIR
CW
CA
GREASE/OIL/DIRT DRAIN LINE GL
GASGAS NATURAL OR PROPANE
ANCHOR / HANGER
BALL VALVE
BUTTERFLY VALVE
EXPANSION JOINT
GATE VALVE
GLOBE VALVE
GAS METER
PIPE GUIDE
"P" TRAP
TEST PLUG
PLUG VALVE
WATER METER
UNION
THERMOMETER
"Y" STRAINER
PRESSURE GAUGE
BALANCING VALVE
CHECK, SWING VALVE
FLEXIBLE PUMP CONNECTION
FLANGED CONNECTION
DROP
PITCH DOWN IN DIRECTION OF ARROW
RUN OUT OFF BOTTOM OF MAIN
RUN OUT OFF TOP OF MAIN
RISER
TEE OFF SIDE OF MAIN
PIPING SYMBOLS
M
GM
P
PENDANT STYLE FIRE SUPPRESSION HEAD
PLUMBING SPECIFICATIONS
GENERAL
1. BID INSTRUCTIONS: CONTRACTORS SHALL PROVIDE
BASE BID IN STRICT ACCORDANCE WITH DESIGN
BASIS EQUIPMENT AND MATERIALS. PROJECT DOES
ENCOURAGE COMPETITIVE PRICING AND ALLOWS
FOR SUBSTITUTIONS OF EQUIPMENT AND
MATERIALS AS ALTERNATE DEDUCTS TO BASIS OF
DESIGN BIDS. LIST ALL SUBSTITUTIONS ALONG WITH
DEDUCTS OFFERED ON BID. ENGINEER RESERVES
THE RIGHT TO REJECT SUBSTITUTIONS FOUND NOT
TO BE EQUAL TO ITEMS LISTED IN DESIGN BASIS.
2. PRIOR TO PROCUREMENT CONTRACTOR SHALL
SUBMIT TO ARCHITECT FULL SUBMITTALS FOR ALL
ENERGY CONSUMING OR PRODUCING ITEMS AND
FOR ALL PLUMBING FIXTURES, VALVES, DRAINS,
CLEAN OUTS, PIPING, PIPING ACCESSORIES,
INSULATION AND PIPING HANGERS. SUBMITTALS
SHALL BE DELINEATED WITH TAGS INDICATED ON
PRINTS, CONTRACTORS NAME, PROJECT NAME.
CLEARLY INDICATE ALL MODEL NUMBERS AND ALL
ACCESSORIES AND OPTIONS BEING PROVIDED.
SUBMISSIONS SHALL BE IN PDF FORMAT.ENGINEER
RESERVES THE RIGHT TO REJECT ANY SUBSTITUTE
ITEM.
3. CONTRACTOR SHALL BE RESPONSIBLE TO VISIT THE
SITE TO EXAMINE ALL CONDITIONS THAT MAY IN ANY
WAY AFFECT THE EXECUTION OF HIS WORK. HE
SHALL ALSO EXAMINE THE DRAWINGS AND
SPECIFICATIONS FOR OTHER BRANCHES OF WORK
MAKING REFERENCE TO THEM FOR DETAILS OF
EXISTING BUILDING CONDITIONS. NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO INCLUDE ALL
REQUIRED WORK IN THE BID. CONTRACTOR SHALL
GUARANTEE ALL LABOR AND MATERIALS ENTERING
INTO CONTRACT FOR A PERIOD OF ONE (1) YEAR
FROM DATE OF ACCEPTANCE.
4. THE DRAWINGS IN THIS SECTION ARE
DIAGRAMMATIC AND ARE NOT INTENDED TO DEFINE
EXACT QUANTITIES, LOCATIONS OR CODIFIED
REQUIREMENTS. DRAWINGS SHOW GENERAL INTENT
OF SYSTEMS. P.C. SHALL PROVIDE AND PAY FOR ALL
REQUIRED PERMITS.
5. UPON COMPLETION OF THE PLUMBING
INSTALLATION, DEMONSTRATE TO THE ENGINEER
AND/OR THE OWNER'S SATISFACTION THAT THE
SYSTEMS HAVE BEEN INSTALLED IN ACCORDANCE
WITH THE DRAWINGS, SPECIFICATIONS AND
APPLICABLE CODES. DEMONSTRATE THE DYNAMIC
OPERATION OF EACH SYSTEM. VERIFY PROPER
OPERATION OF EQUIPMENT, FILTERS ARE CLEAN
AND COMPONENTS OF THE SYSTEM ARE INSTALLED
AND ADJUSTED IN FULL ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS.
6. PLUMBING WORK SHALL BE COMPLETE IN EVERY
DETAIL AND ALL MISCELLANEOUS ITEMS OF
MATERIAL AND LABOR NECESSARY TO COMPLETE
THE WORK DESCRIBED, SHOWN OR REASONABLY
IMPLIED ON DRAWINGS OR SPECIFICATIONS SHALL
BE INCLUDED IN THE CONTRACT. CONTRACTOR
SHALL MAKE MINOR ADJUSTMENTS TO THE WORK
WHERE REQUIRED, WHEN SUCH ADJUSTMENTS ARE
NECESSARY FOR PROPER OPERATION AND WITHIN
THE INTENT OF THE CONTRACT. CONTRACTOR
SHALL GUARANTEE ALL LABOR AND MATERIALS
ENTERING INTO CONTRACT FOR A PERIOD OF ONE
(1) YEAR FROM DATE OF ACCEPTANCE.
7. ALL WORK SHALL BE IN FULL ACCORDANCE WITH
2012 INDIANA PLUMBING CODE (INTERNATIONAL
PLUMBING CODE 2006), 2010 INDIANA ENERGY CODE
(2007 ASHRAE 90.1), 2014 INDIANA FUEL GAS CODE
(2012 INTERNATIONAL FUEL GAS CODE) AND ALL
PERTINENT STATE, COUNTY, CITY CODES AND
ORDINANCES WITH INDIANA AMENDMENTS.
8. PLUMBING CONTRACTOR SHALL ACCEPT SOLE AND
COMPLETE RESPONSIBILITY FOR CONDITIONS OF
THE JOB SITE, INCLUDING SAFETY OF ALL PERSONS
AND PROPERTY DURING PERFORMANCE OF THE
WORK.
9. PLUMBING CONTRACTOR SHALL VERIFY AND BE
RESPONSIBLE FOR ALL WATER, GAS, STORM AND
SEWER UTILITY ROUGH-INS AND SHALL CONSULT
WITH THE CIVIL PLANS AND WITH LOCAL UTILITY
COMPANY(S) PROVIDING ALL MATERIALS AND LABOR
AND PAYING ALL COSTS NOT BORNE BY THE LOCAL
UTILITY COMPANY(S) FOR INSTALLATION OF
SERVICES INCLUDING SECURING AND PAYING FOR
ALL REQUIRED PERMITS.
10. PLUMBING CONTRACTOR SHALL ENSURE
EMPLOYEES ARE MEETING AND DOCUMENTING ALL
OSHA AND JOB SPECIFIC SAFETY REQUIREMENTS AS
REQUIRED BY LAW AND BY CONTRACT. PERSONAL
PROTECTIVE EQUIPMENT SHALL BE PROVIDED AND
UTILIZED AS REQUIRED. MECHANICAL CONTRACTOR
SHALL PAY ALL FINES LEVIED BY OSHA FOR FAILURE
TO COMPLY WITH OSHA REQUIREMENTS.
11. ALL PLUMBING MATERIALS INSTALLED IN RETURN
AIR PLENUMS SHALL BE INSTALLED OR COVERED
WITH MATERIALS AS REQUIRED TO PROVIDE FLAME
RATING OF NOT MORE THAN 25 AND A SMOKE
DEVELOPED INDEX OF NOT MORE THAN 50. PRIOR
TO ROUGH-IN CONSULT WITH M.C. TO VERIFY ALL
LOCATIONS OF RETURN AIR PLENUMS.
12. FURNISH AND INSTALL ACCESS PANELS FOR ALL
CONCEALED EQUIPMENT, PIPING VALVES,
CLEANOUTS, ETC. ACCESS PANELS SHALL BE OF
SUFFICIENT SIZE TO PROVIDE ADEQUATE WORKING
CLEARANCE AND ACCESS.
13. PLUMBING CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL REQUIRED CUTTING AND PATCHING
INCLUDING SAW CUTTING AND PATCHING OF
EXISTING FLOORS AS REQUIRED TO ACCEPT NEW
FLOORING.
EQUIPMENT
1. PROVIDE EQUIPMENT AS SHOWN ON EQUIPMENT
SCHEDULES AND PLAN NOTES. SUBSTITUTIONS TO
LISTED EQUIPMENT SHALL BE AT RISK OF
CONTRACTOR. SUBSTITUTIONS SHALL ONLY BE
ALLOWED IF ITEMS ARE EQUAL IN ALL ASPECTS.
2. PROVIDE SUBMITTALS TO ELECTRICIAN AS
REQUIRED FOR COORDINATION OF ALL REQUIRED
ELECTRICAL POWER WIRING. INCLUDE WIRING
DIAGRAMS AND CABLING REQUIREMENTS FOR
REFERENCE. COORDINATE ALL INTERLOCKS AS
NEEDED. PROVIDE SINGLE POINT CONNECTION KITS
AS NEEDED.
3. INSTALL ALL EQUIPMENT IN FULL ACCORDANCE
WITH MANUFACTURERS RECOMMENDATIONS AND
CLEARANCE REQUIREMENTS. PROVIDE ALL
REQUIRED MOUNTING OR HOUSEKEEPING PADS.
G.C. SHALL PROVIDE LEVEL GRADE FOR EXTERIOR
MOUNTED EQUIPMENT. P.C. SHALL PROVIDE ALL
HOISTING AND RIGGING NEEDED TO SET ALL
PLUMBING EQUIPMENT.
4. ALL EQUIPMENT SHALL BE INSTALLED AS NEEDED
TO PREVENT OBJECTIONABLE NOISE AND/OR
VIBRATION. P.C. SHALL PROVIDE VIBRATION PADS,
SPRING ISOLATORS, ATTENUATORS AND
ACCESSORIES AS NEEDED.
5. PROVIDE ALL BLOCKING, HANGERS, SHELVES,
BRACKETS ETC. AS REQUIRED TO INSTALL ALL
PLUMBING EQUIPMENT.
6. INSTALL WATER HEATERS IN ACCORDANCE WITH
NFPA-70, AND THE NATIONAL ELECTRICAL CODE.
PROVIDE BRASS DRAIN VALVE, 3/4" RELIEF VALVE
AND COLD WATER DIP TUBE. INSTALL HEATERS PER
MANUFACTURES INSTALLATION INSTRUCTIONS.
PROVIDE SHUT-OFF VALVES FOR SERVICE WORK.
7. THERMOSTATS ON WATER HEATER SHALL NOT BE
USED FOR LIMITING HOT WATER TEMPERATURES.
P.C. SHALL PROVIDE MIXING VALVES FOR HOT
WATER TO ALL FAUCETS ACCESSIBLE TO
OCCUPANTS. MIXING VALVE SYSTEMS SHALL LIMIT
WATER TEMPERATURE AT FAUCETS TO 110 DEG F.
OR LESS.
8. PROVIDE SCHEDULE 40 PVC PIPING AND FITTINGS
FOR ALL COMBUSTION AIR AND VENT PIPING IN
ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS ON ALL DIRECT VENT WATER
HEATERS OR BOILERS.
FIXTURES
1. REFERENCE FIXTURE SCHEDULES ON PLANS AND
PROVIDE ALL REQUIRED CARRIERS, BLOCKING,
HANGERS, TAIL PIECES, TRAPS, RISERS,
ESCUTCHEONS, GRIDS, PUTTY, GASKETS, CAULKING,
ETC. AS REQUIRED TO INSTALL ALL PLUMBING
FIXTURES.
2. REVIEW SUBMITTALS FOR ALL OWNER PROVIDED
EQUIPMENT AND PROVIDE ANY REQUIRED
ACCESSORIES AS NEEDED FOR A COMPLETE
INSTALLATION. P.C. SHALL BE RESPONSIBLE TO
RECEIVE AND INSTALL ALL OWNER PROVIDED
FIXTURES.
3. FIXTURES DESIGNATED FOR HANDICAP
ACCESSIBILITY SHALL COMPLY WITH ANSI A 117.1,
LATEST EDITION, INCLUDING ADOPTED INDIANA
AMENDMENTS.
4. PROVIDE ALL CODE REQUIRED BACKFLOW DEVICES
FOR PROCESS HVAC EQUIPMENT AND FOR WATER
SERVING ANY DRINKING OR FOOD PREPARATION
FIXTURES.
5. PROVIDE BELLOWS TYPE WATER HAMMER
ARRESTERS, STAINLESS STEEL CASHING AND
BELLOWS, 250 PSI, INSTALL PER PDI STANDARD
WH201.
PIPING
1. ALL EXPOSED SUPPLY PIPES AND METAL TRIM IN
CONNECTION WITH THE FIXTURES SHALL BE
CHROME PLATED RED BRASS OR BRONZE, PROVIDE
CHROME PLATED STOP VALVES IN ALL SUPPLIES TO
ALL FIXTURES. PLASTIC STOPS OR TRIM SHALL NOT
BE ACCEPTABLE. CAULK ALL FIXTURES WITH
WATERPROOF SILICONE CAULK. TRAPS SHALL HAVE
CLEANOUT PLUGS. INSTALL ONE PIECE CHROME
ESCUTCHEON PLATE WITH SET SCREW AT WALL
PENETRATIONS.
2. WASTE AND VENT PIPING MAINS SHALL BE PITCHED
AT 1/8" PER FOOT. LATERAL BRANCHES SHALL BE
PITCHED 1/4" PER FOOT TOWARD THE SANITARY
SEWER MAIN. THEY SHALL BE INSTALLED AND
TESTED IN ACCORDANCE WITH THE CURRENT
INDIANA PLUMBING CODE AND TESTED PER
AUTHORITY HAVING JURISDICTION.
3. VERIFY LOCATION, DEPTH AND SIZE OF SANITARY
SEWER CONNECTION POINTS. CONNECT AS
REQUIRED. OUTSIDE SEWER SHALL BE INSTALLED
WITH MINIMUM OF 3'-0" COVER. COORDINATE
CONNECTIONS WITH SITE CONTRACTOR AND LOCAL
UTILITY
4. ALL OUTSIDE WATER PIPING SHALL BE COVERED
WITH A MINIMUM OF 52".
5. ALL INTERIOR PIPING PENETRATIONS THROUGH
WALLS, CEILINGS, ROOFS AND FLOORS SHALL BE
SLEEVED AND SEALED. PROVIDE UL LISTED FIRE
STOPPING WHERE REQUIRED.
6. ALL EXTERIOR UNDERGROUND PENETRATIONS OF
BUILDING FOUNDATIONS OR SLAB FLOORS SHALL BE
SLEEVED AND SEALED. PENETRATIONS BELOW
GRADE INTO THE BUILDING SHALL BE DONE WITH
MECHANICAL SEALS LIKE "LINK SEAL" OR EQUAL.
7. NO PLUMBING PIPING SHALL PASS DIRECTLY OVER
ELECTRICAL PANELS OR DISTRIBUTION CABINETS.
PRIOR TO ROUGH IN COORDINATE WITH E.C.
8. DIELECTRIC UNIONS SHALL BE USED TO CONNECT
DISSIMILAR METALS OR METAL PIPING SHALL HAVE
METAL CONNECTIONS ON EACH END THREADED TO
MATCH THE ADJACENT PIPING. METAL
COMPONENTS SHALL BE SEPARATED BY A NYLON
INSULATOR TO PREVENT CURRENT FLOW BETWEEN
DISSIMILAR METALS. UNIONS SHALL BE SUITABLE
FOR THE SYSTEM OPERATING PRESSURES AND
TEMPERATURE WELD TYPE: ASTM A-234.
9. PIPING SLEEVES; INTERIOR OR EXTERIOR ABOVE
GRADE; GALVANIZED-STEEL-PIPE SLEEVES OR
PVC-PIPE SLEEVES. VERIFY, WITH FIRE AUTHORITIES
HAVING JURISDICTION, THAT PVC MATERIALS ARE
ALLOWED FOR SLEEVES. BELOW GRADE; ALL;
MECHANICAL GALVANIZED-STEEL PIPE SLEEVE
SYSTEM LIKE LINK-SEAL. ALL SLEEVES SHALL BE
FIRE STOPPED OR CAULKED. EXTERIOR SLEEVES
SHALL PROVIDE WATER/AIR TIGHT PENETRATION
SYSTEM.
10. PROVIDE HANGERS PER MSS AND IPC STANDARDS
BASED ON PIPING TYPES AND SIZES.
11. PIPING MATERIALS UNLESS OTHERWISE NOTED ON
THE PLANS SHALL BE AS FOLLOWS:
GAS/AIR ABOVE GRADE, 2" AND SMALLER; BLACK
STEEL SCHEDULE 40 TYPE E OR S PIPE
GRADE B; ASTM A53 / A53M, A105 OR A120
WITH THREADED ENDS; FITTINGS SHALL
BE MALLEABLE IRON THREADED FITTINGS
ASTM B16.3 CLASS 150.
2-1/2" AND LARGER: BLACK STEEL
SCHEDULE 40 TYPE E OR S PIPE GRADE B;
ASTM A53 / A53M, A105 OR A120 WITH PLAIN
ENDS. FITTINGS; WROUGHT STEEL
WELDING FITTINGS TO ASTM A 234/A 234M
FOR BUTT AND SOCKET WELDING.
WATER COPPER TUBING (INSIDE BUILDING): ASTM
B 88, TYPE 'L' HARD WATER TUBE DRAWN
TEMPER. WITH CAST-COPPER
SOLDER-JOINT FITTINGS: ANSI B16.18. OR
WROUGHT-COPPER SOLDER JOINT
FITTINGS: ANSI B16.22
SEWER/VENT BELOW GRADE: POLYVINYL CHLORIDE
SEWER PIPE (PVC) SOLID: ASTM D1866,
ASTM D 2665, ASTM D 2949, ASTM D 3034,
CSA B181.2 CSA B182.1,.2,.4 SCHEDULE 40
SOLID DRAIN WASTE AND VENT PIPE.
JOINTS SHALL BE PVC SOCKET WELDED
FITTINGS DESIGNED TO FIT PIPING
DIAMETERS ASTM D 2855 ASSEMBLED
WITH PRIMER ASTM F 656 AND SOLVENT
CEMENT ASTM D 2564, CSA B181.2.
SEWER/VENT ABOVE GRADE: POLYVINYL CHLORIDE
SEWER PIPE (PVC) CELLULAR CORE: ASTM
F 891 DRAIN WASTE AND VENT PIPE.
JOINTS SHALL BE PVC SOCKET WELDED
FITTINGS DESIGNED TO FIT PIPING
DIAMETERS ASTM D 2855 WITH PRIMER
ASTM F 656 AND SOLVENT CEMENT ASTM D
2564, CSA B181.2. ALL PIPING IN RETURN
AIR PLENUMS SHALL CONFORM TO
REQUIREMENTS FOR PLENUM MATERIALS.
VENTING POLYVINYL CHLORIDE DRAIN, WASTE AND
VENT PIPE (PVC): ASTM D2665.
INSULATED IN RETURN AIR PLENUMS.
STORM POLYVINYL CHLORIDE SEWER PIPE (PVC):
ASTM D2665 SOLID DRAIN WASTE AND
VENT OR ASTM F 891 CELLULAR CORE
SCHEDULE 40 WITH PVC SOCKET WELDED
FITTINGS DESIGNED TO FIT PIPING
DIAMETERS. INSULATED IN RETURN AIR
PLENUMS.
PLUMBING INSULATION
1. ALL PIPING INSULATION MATERIALS SHALL HAVE A
FLAME SPREAD RATING OF 25 OR LESS (ON THE
FLAME SPREAD TEST SCALE) AND SMOKE
DEVELOPMENT OF 50 OR LESS (ON THE SMOKE TEST
SCALE) OR AS DEFINED BY NFPA 255 STANDARD
METHOD OF TESTING OF SURFACE BURNING
CHARACTERISTICS OF BUILDING MATERIALS, LOCAL
CODES AND LOCAL AUTHORITIES HAVING
JURISDICTION. ALL PVC PIPING LOCATED IN RETURN
AIR PLENUM SPACES OR EXPOSED SHALL BE
INSULATED.
2. INSULATION: INSTALL ALL INSULATION IN STRICT
ACCORDANCE WITH MANUFACTURERS
INSTRUCTIONS IN A TIGHT AND NEAT MANOR. NO
SAGGING, FRAYED OR TORN INSULATION WILL BE
EXCEPTED. UNLESS OTHERWISE NOTED ON PLANS
PIPING SHALL BE INSULATED AS FOLLOWS:
ALL PLUMBING PIPING SHALL BE
INSULATED TO THE FOLLOWING
THICKNESS.
a. HW, HWR: 1/2" THICKNESS FOR PIPE
SIZES UPTO 1-1/2", 1" THICKNESS
FOR GREATER THAN 1-1/2.
b. CW: 1/2" THICKNESS FOR PIPE SIZES.
c. STM: 1/2" THICKNESS FOR ALL PIPE
SIZES.
PRE-FORMED TYPE I, 850 DEG F MINERAL
OR GLASS FIBERS BONDED WITH A
THERMOSETTING RESIN AND HINGED WITH
SELF SEALING LAP. COMPLY WITH
ASTM C 547, TYPE I, GRADE A, WITH
FACTORY-APPLIED ASJ.
FLEXIBLE ELASTOMERIC CLOSED CELL OR
EXPANDED RUBBER PIPE INSULATION
WITH PRESSURE SENSITIVE ADHESIVE
SYSTEM, ASTM C534, ASTM E84 CLASS A
300 DEG F.
EXTERIOR/EXPOSED JACKETS: UV
RESISTANT PVC PIPE JACKETS AND
PREFORMED FITTING COVERS COMPLIANT
WITH ASTM D257, D638, D790, D792, D1784,
D3679, E84 AND E136.
CHECK TEST AND START UP REQUIREMENTS
1. CLOSE OUT: PROVIDE MANUFACTURERS OPERATION
AND MAINTENANCE MANUALS AND AS BUILT
DRAWINGS. PROVIDE (1) TRAINING SESSION TO
OWNER SELECTED PERSONNEL AS REQUESTED.
2. FILL SYSTEMS WITH FRESH WATER AND INSPECT
ALL CONNECTIONS FOR LEAKAGE. REMOVE ALL
PACKING AND PROTECTIVE SHIPPING MATERIALS.
CLEAN ALL FIXTURES AND START-UP ALL WATER
HEATERS, PUMPS, AND EQUIPMENT. VERIFY PROPER
OPERATION. OPERATE ALL FAUCETS AND INSPECT
STOPS, RISERS, TRAPS AND DRAINS. CORRECT ALL
LEAKS, WATER HAMMER AND VIBRATIONS AS
REQUIRED.
P001