Loading...
HomeMy WebLinkAboutE.02 ONE LINE DIAGRAM & SCHEDULESDETAIL NOTES: 1. COORDINATE METERING AND TRANSFORMER REQUIREMENTS WITH UTILITY BEFORE THE PURCHASE OR INSTALLATION OF ANY EQUIPMENT. 2. COORDINATE AVAILABLE FAULT CURRENT WITH UTILITY DURING DESIGN. PERFORM FAULT CURRENT CALCULATION BASED ON AVAILABLE FAULT CURRENT AND SPECIFY EQUIPMENT TO WITHSTAND CALCULATED FAULT CURRENT. PANEL 'A' 208/120V 200A MCB (4) 4" PVC CONDUITS TO IPL TRANSFORMER (ETR) EXTERIOR INTERIOR 120/208V JUNCTION CABINET (ETR) ELEC. CO. TAP BOX 200A HOUSE PANEL (ETR) 200A HOUSE 400A A1 400A A2 200A A3 200A A4 GROUND PER NEMA STANDARDS (ETR) GROUND PER NEMA STANDARDS (ETR) 4#3/0,1#6GND-3"C SCALE: NONE 2 E0.2 ELECTRICAL RISER DIAGRAM M GROUNDED CONDUCTOR (NEUTRAL) FROM UTILITY COMPANY TRANSFORMER 10' 10' 10' WITHIN 5' OF WATER ENTRANCE TO BUILDING SCALE: NONE 1 E0.2 SERVICE GROUNDING AND BONDING DETAIL INCOMING CONDUIT GROUND (IF STEEL CONDUIT) EQUIPMENT GROUNDING BUS EQUIPMENT BONDING JUMPER ENCLOSURE GROUND MAIN BONDING JUMPER (#4) PER NEC 250.102.(C)(1). #6 AWG MINIMUM 10" X 2" X 1/4" COPPER GROUND BAR. INSTALL ON TELEPHONE BACKBOARD WITH (2) UL LISTED STANDOFF INSULATORS. BONDING JUMPER SOURCE (DIRECT CONTACT WITH EARTH FOR 10' OR MORE) COPPER CLAD STEEL, 10' x 3/4" WITH TOP OF ROD 6" BELOW FINISH GRADE (TYPICAL) CLAMPS SUITABLE FOR DIRECT BURIAL (TYPICAL) NON-METALLIC PROTECTIVE SLEEVE CONNECTOR LISTED FOR PURPOSE CONCRETE ENCASED ELECTRODE (REINFORCING STEEL) EXOTHERMIC CONNECTION (TYPICAL) METAL FRAME OF BUILDING STRUCTURE BONDING JUMPER (#4) PER NEC 250.102.(C)(1) GROUNDING ELECTRODE CONDUCTOR (#4) PER NEC 250.66. GROUNDED OR NEUTRAL BUS SERVICE EQUIPMENT #4 FMAX=17,401A ONE LINE DIAGRAM AND SCHEDULES XXX EJR ISSUE DATE THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. COPYRIGHT 2020, CURRAN ARCHITECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES F :: 317 . 288 . 0753 O :: 317 . 288 . 0681 INDIANAPOLIS, IN 46216 5719 LAWTON LOOP E. DR. #212 T E S E N G I N E E R I N G Cleveland, OH 44145 25760 First Street P 440 871 2410 F 440 871 7954 tesengineering.com DRAWN BY: ________ CHECKED BY: ________ PROJECT NUMBER: 200079 TIDE CLEANERS 2801 E. 116TH STREET CARMEL, INDIANA 46033 DROP STORE OWNER CHANGE 09/11/2020 E0.2 1 1 1 09/24/20