HomeMy WebLinkAboutE0.1 ELECTRICAL LEGENDS, ABBRV & SPECIFICATIONS1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT NECESSARILY SHOW EVERY FITTING AND DETAIL. ALL WORK SHALL BE COMPLETED SO THAT JUNCTION BOXES, FITTINGS AND COMPONENTS WILL BE ACCESSIBLE FOR SERVICING. 2. ALL ELECTRICAL WORK PERFORMED DURING THIS SCOPE OF WORK SHALL COMPLY WITH ALL LOCAL BUILDING CODES, LAWS, REGULATIONS, ORDINANCES, AND THE REQUIREMENTS OF THE 2011 NATIONAL ELECTRICAL CODE. ALL WORK SHALL COMPLY WITH ANY OWNER SPECIFICATIONS NOT CALLED OUT ON THIS SET OF DRAWINGS. 3. ALL PENETRATIONS THRU RATED WALLS AND CEILINGS SHALL BE FIRE STOPPED PER NEC 300-21 AND NFPA 221. 4. PROVIDE ALL GROUNDING AS REQUIRED BY NEC OR ANY LOCAL CODES. 5. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRIC CODE, B.O.C.A. AND O.S.H.A. LATEST EDITIONS, AND ALL APPLICABLE LOCAL CODES. 6. ELECTRIC SERVICE SHALL BE COORDINATED WITH THE UTILITY CO. CONTRACTOR SHALL PAY ANY FEES LEVIED FOR SERVICE. PROVIDE METER CANS OR C/T CABINETS AS REQUIRED. 7. CONTRACTOR SHALL OBTAIN AND PAY FOR BOTH ROUGH AND FINAL UNDERWRITERS OR OTHER APPROVED INSPECTION AGENCY CERTIFICATE OF "ELECTRICAL INSPECTION". THESE CERTIFICATES SHALL BE PRESENTED WITH REQUEST FOR FINAL PAYMENT. 8. SERVICE SHOWN AS BEING UNDERGROUND ON ELECTRICAL RISER DIAGRAM, INCLUDE ANY CHANGES REQUIRED IN THE ELECTRICAL PANELS, SWITCHES, MOTORS, WIRING, BREAKER SIZES, AND EQUIPMENT NECESSARY TO ADAPT TO THE SERVICE AVAILABLE, THE REQUIREMENTS OF THE UTILITY COMPANY, LOCAL CODES OR THE SIZE OF HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SPECIFIED. 9. INSTALL CONCEALED TELEPHONE CONDUIT INCLUDING NECESSARY PULL BOXES AND FISH WIRE IN ACCORDANCE WITH LOCAL TELEPHONE COMPANY REQUIREMENTS TO LOCATIONS INDICATED ON THE DRAWINGS. WHEN CALLED FOR ON THE SITE DRAWING, ALSO PROVIDE NECESSARY CONDUIT TO OUTSIDE TELEPHONE BOOTH. 10. CONTRACTOR SHALL COOPERATE WITH OTHER SECTIONS FOR THE EXECUTION OF THIS WORK. SUPPLY AND COOPERATE IN THE PLACEMENT OF INSERTS, SLEEVES AND OTHER EQUIPMENT TO BE INSTALLED IN MASONRY. CAREFULLY CUT NECESSARY HOLES FOR THE INSTALLATION OF EQUIPMENT AND PATCH IN SUCH A MANNER AS TO MATCH THE ORIGINAL WORK. 11. WHERE MOUNTING HEIGHTS ARE SHOWN ON THE DRAWINGS, THE MEASUREMENT IS TO BE TAKEN FROM THE CENTERLINE OF THE DEVICE. 12. ALL WIRING MUST BE INSTALLED IN CONDUIT. TYPICAL CONDUIT SIZES ARE 1/2" EMT WITH 2#12, 1#12G. AWG UNLESS OTHERWISE NOTED. IF REQUIRED BY LOCAL CODE, USE BX ARMORED CABLE OR TYPE THHN WIRE ENCLOSED IN APPROVED METAL RACEWAYS. ALUMINUM WIRE SHALL NOT BE ALLOWED. 13. A #12 GROUND SHALL BE PROVIDED FOR ALL MECHANICAL EQUIPMENT UNLESS NOTED OTHERWISE. ALL EQUIPMENT SHALL BE GROUNDED AT THE PANEL THAT FEEDS THE EQUIPMENT. 14. CONTRACTOR SHALL PROVIDE A TYPED PANEL SCHEDULE DIRECTORY LOCATED ON THE INSIDE COVER OF THE ELECTRICAL PANEL. ALL CIRCUITS, SPARES, AND SPACES SHALL BE CORRECTLY AND CLEARLY LABELED. ALL CARDS SHALL INDICATE AREAS AND DEVICES SERVED BY EACH CIRCUIT. 15. ALL BRANCH CIRCUIT HOMERUN CONDUCTORS SHALL BE PROVIDED WITH A SEPARATE INSULATED #12 AWG EQUIPMENT GROUNDING CONDUCTOR. 16. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK AND MATERIALS AGAINST ALL DEFECTS IN MATERIAL, DESIGN AND WORKMANSHIP FOR ONE YEAR EFFECTIVE THE DAY THE PROJECT IS ACCEPTED BY THE OWNER. FAILURE OF ANY PART OR PARTS DURING GUARANTEE, OWING TO ABOVE CAUSES, SHALL BE REPLACED PROMPTLY UPON NOTICE BY ARCHITECT, WITHOUT CHARGE TO THE OWNER. 17. BUILDING CODE SECTION 705.4 SHALL BE MET WITH ELECTRICAL DEVICES TO BE INSTALLED IN RATED WALLS. 18. ALL ELECTRICAL MATERIALS, DEVICES, AND EQUIPMENT SHALL BE LISTED BY UL OR OTHER STATE APPROVED THIRD PARTY TESTING AGENCY. 19. FIRE RATED SLEEVES SHALL BE PROVIDED AND ALL FIRESTOPPING SHALL BE PROVIDED AS REQUIRED BY CODE WHEN CABLING IS ROUTED THROUGH A FIRE RATED PARTITION. BLANK COVERS SHALL BE INSTALLED ON RINGS. 20. MOUNT ALL DISCONNECT SWITCHES TO STRUCTURE. DISCONNECTS SHALL NOT BE MOUNTED TO DUCTWORK OR MECHANICAL EQUIPMENT. 21. ALL LIGHT FIXTURES SHALL BE CLEANED, AND FULLY FUNCTIONAL AT MOVE-IN. THIS INCLUDES RE-LAMPING. 22. CONTRACTOR SHALL PROVIDE AND INSTALL PHENOLIC LABELED NAMEPLATES FOR ALL RECEPTACLES AND POWERED DEVICES (INCLUDING PANELBOARDS AND DISCONNECTS). INFORMATION ON NAMEPLATE SHALL INCLUDE ELECTRICAL PANEL AND CIRCUIT NUMBER FROM WHICH DEVICE IS POWERED. WHERE TWO SWITCHES OR MORE (INCLUDING DIMMERS) ARE LOCATED NEXT TO EACH OTHER, CONTRACTOR SHALL PROVIDE AND INSTALL A SINGLE SWITCH PLATE TO PROVIDE A NEATER APPEARANCE. ELECTRICAL SYMBOL AND ABBREVIATION LEGEND CONCEALED CONDUIT CONCEALED CONDUIT IN FLOOR OR UNDERGROUND CIRCUIT HOMERUN TO PANEL; EACH ARROWHEAD = 1 CIRCUIT NO. OF CONDUCTORS IN CONDUIT (EACH CROSSHATCH = 1 WIRE) GROUND WIRE IS NOT INDICATED WITHIN CROSSHATCH WIRES ELECTRICAL PANELBOARD FLUORESCENT OR LED LIGHT FIXTURE INDUSTRIAL TURRET OR STRIP FIXTURE TOGGLE LIGHT SWITCH DOWN LIGHT EXIT SIGN FIXTURE EMERGENCY EGRESS LIGHT EXIT SIGN EMERGENCY EGRESS LIGHT COMBO FIXTURE FLUORSECENT OR LED LIGHT FIXTURE WITH 1400 LUMEN EMERGENCY BATTERY BALLAST/PACK. 3 WAY AND 4 WAY TOGGLE SWITCHES WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH (WATT STOPPER MODEL DSW-301 OR APPROVED EQUAL) CEILING MOUNTED OCCUPANCY SENSOR - DUAL TECHNOLOGY LINE VOLTAGE TYPE (WATT STOPPER MODEL DT-355 OR APPROVED EQUAL) DUPLEX RECEPTACLE (18"AFF UNO) QUADRAPLEX RECEPTACLE (18" AFF UNO ) TELEPHONE/COMMUNICATIONS JACK (CONTRACTOR SHALL PROVIDE JUNCTION BOX 18" AFF UNO WITH 3/4" EMPTY CONDUIT WITH PULLSTRING TO UP ABOVE ACCESSIBLE CEILING) TELEPHONE BACKBOARD DISCONNECT SWITCH (FRAME / FUSE / POLES / NEMA RATING) MOTOR RATED SWITCH JUNCTION BOX JUNCTION BOX FOR TV CABLE DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER - EXACT LOCATION TO BE COORDINATED WITH MILLWORK 30A/NF/3P/N1 SPECIAL PURPOSE RECEPTACLE. VOLTAGE, AMP RATING, AND NUMBER OF WIRES AS INDICATED ON PLANS. AFC AFF BFC E EX / EXTG EC EWC FPMR GFI NF NIC WP XFMR UNO ABOVE FINISHED CEILING OR AVAILABLE FAULT CURRENT ABOVE FINISHED FLOOR BELOW FINISHED CEILING EXISTING ELECTRICAL CONTRACTOR ELECTRIC WATER COOLER FUSE PER MANUFACTURER'S RECOMMENDATIONS GROUND FAULT CIRCUIT INTERRUPTION NON-FUSED or NOT FUSED NOT IN CONTRACT WEATHERPROOF TRANSFORMER UNLESS NOTED OTHERWISE PHOTOCELL (WATT STOPPER MODEL ''EM-24' OR APPROVED EQUAL) EQUIPMENT TAG STRUCTURE SUSPENDED CEILING DISCONNECT, MOTOR RATED SWITCH, OR RECEPTACLE UNISTRUT SUPPORT ANCHORED TO STRUCTURAL SUPPORT ABOVE CEILING WITH HARDWARE AS REQUIRED. FLOOR 24. PROVIDE "FLASH HAZARD" WARNING LABELS ON ALL ELECTRICAL PANELS, AS PER NEC REQUIREMENTS. 25. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE OBTAINED AND PAID FOR BY THE ELECTRICAL CONTRACTOR. 26. ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID CONDUIT, INTERMEDIATE METAL CONDUIT, OR EMT. EMT SHALL NOT BE USED IN OR UNDER CONCRETE SLABS, OR IN MASONRY WALLS. USE SCHEDULE 40 PVC BELOW FLOOR SLAB OR OUTDOORS WHERE NOT SUBJECT TO PHYSICAL DAMAGE. 27. CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN 600 VOLTS. 28. ALL CONDUCTORS SHALL BE COPPER WITH TYPE "THHN" OR "THW" INSULATION. USE "THHN" FOR #10 OR SMALLER CONDUCTORS. USE "THW" FOR CONDUCTORS #8 OR LARGER. 29. THE MINIMUM WIRE SIZE SHALL BE #12 A.W.G. WITH A 75° DEGREE TEMPERATURE RATING. 30. FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK DUAL ELEMENT TIME DELAY WITH 200,000 AMPERE INTERRUPTING RATING AS MANUFACTURED BY BUSSMAN, UNLESS OTHERWISE NOTED. 31. INSTALL ALL ELECTRICAL OUTLET BOXES HORIZONTAL AND FLUSH IN WALLS WHERE POSSIBLE. PROVIDE APPROPRIATE FLUSH MOUNTING RECEPTACLE BOXES AND CONDUIT AS REQUIRED FOR MOUNTING OF OUTLETS ON CONCRETE WALLS. 32. ALL TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL BE IDENTIFIED FOR USE WITH THE MATERIAL (CU/AL) OF THE CONDUCTOR AND SHALL BE PROPERLY INSTALLED. ALL TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL BE IDENTIFIED FOR USE WITH 75° RATED CONDUCTORS. 33. ALL 15 AND 20 AMP, 125 VOLT RECEPTACLES LOCATED IN THE KITCHEN AND BREAK AREA SHALL BE GFCI PROTECTED. 34. ALL CONDUIT SHALL BE ZINC-COATED EMT EXCEPT IN WET, DAMP, OR UNDERGROUND LOCATIONS, WHERE ZINC-COATED RIGID STEEL SHALL BE USED. EMT FITTING SHALL BE STEEL SET-SCREW TYPES. ALL FITTINGS SHALL BE U.L. LISTED FOR CONCRETE TIGHT AND RAIN TIGHT CONSTRUCTION. ALL EMT ENTRANCE FITTINGS SHALL BE PROVIDED WITH INSULATED THROATS. KEEP ALL RACEWAYS A MINIMUM OF 6 INCHES AWAY FROM ALL PARALLEL RUNS OF FLUES, STEAM PIPES, AND HOT WATER PIPES. 35. RACEWAY AND OUTLET PENETRATIONS THROUGH SLABS AND FIRE RATED WALLS SHALL BE SEALED WITH IMPERVIOUS NON COMBUSTIBLE MATERIALS IN SUCH A MANNER AS TO RESTORE THE ORIGINAL FIRE RATING. MANUFACTURED MATERIALS SHALL BE EQUAL TO 3M AND SHALL BE UL LISTED. 36. WIRING DEVICES SHALL BE HUBBELL, LEVITON, OR EQUAL. PLATE AND DEVICES SHALL BE WHITE. 37. ALL ELECTRICAL CONDUCTORS SHALL BE TESTED FOR CONTINUITY AND GROUNDS BEFORE BEING ENERGIZED. ALL FAULTY CONDUCTORS SHALL BE REPLACED. 38. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, EXCEPT CONTROL WIRING PROVIDED BY OTHERS. #14 AWG SHALL BE MINIMUM SIZE FOR CONTROL CONDUCTORS PROVIDED BY ELECTRICAL CONTRACTOR. 39. CONNECTIONS TO MOTORS SHALL BE THROUGH FLEXIBLE METALLIC CONDUIT. WHERE EXTERIOR, MATERIALS SHALL BE NEOPRENE JACKETED WITH WATERTIGHT CONNECTIONS. A SEPARATE GREEN INSULATED GROUNDING CONDUCTOR SIZED PER NEC SHALL BE PROVIDED IN EACH NEW FEEDER CONDUIT AND EACH NEW BRANCH CIRCUIT WIRING CONDUIT. PROVIDE CONNECTIONS FOR PANEL BACKBOXES, RECEPTACLES, MOTOR FRAMES, AND OTHER DEVICES. 40. SAFETY SWITCHES SHALL BE FUSIBLE WITH AN EXTERNAL LEVER OR HANDLE FOR MANUAL OPERATION WITH INTERLOCKING COVER. OF THE SIZE AND FUSING INDICATED ON THE DRAWINGS. PROVIDE NEMA 1 ENCLOSURE FOR INDOOR SWITCHES AND NEMA 3R ENCLOSURE FOR OUTDOOR SWITCHES. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE. 41. MANUAL MOTOR STARTERS TO BE PROVIDED ELECTRICAL CONTRACTOR SHALL BE MOTOR SENTINEL TYPE WITH PROPERLY SIZED OVERLOAD HEATERS, MOUNTED IN NEMA 1 OR NEMA 3R ENCLOSURE AS REQUIRED. ELECTRICAL CONTRACTOR SHALL PROVIDE WHERE NOT SPECIFIED UNDER DIVISION PROVIDING EQUIPMENT. 42. ALL FLUORESCENT FIXTURES SHALL BE ELECTRONIC, UL AND CBM LISTED, ETL APPROVED, HAVING "A" SOUND RATING. PL LAMPS SHALL BE SP-35 TYPE. 43. PROVIDE LATERAL BRACING FOR CONDUIT, TRANSFORMERS AND OTHER FLOOR MOUNTED ELECTRICAL EQUIPMENT AS REQUIRED BY LOCAL CODE (AS APPLICABLE). 44. ROOFTOP MECHANICAL UNITS SHALL HAVE A GFCI WP OUTLET. 45. ALL RECEPTACLES AND DATA/COMM. DEVICES SHALL BE MOUNTED AT 18"AFF, UNLESS OTHERWISE NOTED. 46. WHERE FLUORESCENT LIGHT FIXTURES ARE INSTALLED IN SUSPENDED CEILINGS, THEY ARE TO BE INDEPENDENTLY SUPPORTED AND SECURED TO THE BUILDING STRUCTURE BY WIRES ON OPPOSING CORNERS. 47. CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO ALL LESSEE'S OR FRANCHISE OWNER'S SIGNS AND EQUIPMENT AND FURNISH AND INSTALL FITTINGS OR INCIDENTAL ACCESSORIES THAT MAY BE NECESSARY OR THAT MAY BE REQUIRED BY LOCAL CODES FOR COMPLETING FINAL CONNECTIONS AND MAKING EQUIPMENT READY FOR OPERATION. 48. CONTRACTOR SHALL COORDINATE WITH THE APPROVED SIGN INSTALLATION COMPANY AND, IN CONJUNCTION WITH THE SIGN COMPANY, MAKE FINAL CONNECTIONS TO SIGNS AT THE TIME OF INSTALLATION. 49. UNDERGROUND CONDUITS FOR PYLON SIGN AND AREA LIGHTING SHALL BE HEAVY WALL, SCHEDULE 40 PVC. CONDUIT SHALL BE CAPPED DURING CONSTRUCTION TO PREVENT ENTRANCE OF FOREIGN MATTER. IF THE USE OF PVC IS NOT PERMITTED BY LOCAL CODES, ALL UNDERGROUND CONDUIT SHALL BE RIGID STEEL, HEAVY WALL GALVANIZED. CONDUIT FITTINGS EXPOSED TO WEATHER SHALL BE OF A TYPE APPROVED FOR SUCH USE AND SHALL BE PROVIDED WITH GASKETS OR OTHER MEANS OF EXCLUDING MOISTURE. 50. "SWAB" CONDUIT DRY BEFORE PULLING WIRES. THREADS SHALL BE PROTECTED. UNDERGROUND CONDUIT IN YARD RUNS SHALL BE LAID WITH 2FT. MINIMUM COVER OF SAND OR AS REQUIRED BY LOCAL CODE. WHERE REQUIRED BY LOCAL CODE, USE RIGID STEEL CONDUIT, HEAVY WALL GALVANIZED FOR ALL WORK WITHIN BUILDING. OTHERWISE, WHERE RACEWAYS ARE REQUIRED USE THIN WALL ELECTRIC METALLIC TUBING. 51. SEALTITE CONDUIT AND FITTINGS SHALL BE USED FOR FINAL MOTOR CONNECTIONS. SMALLEST SIZE CONDUIT FOR BRANCH CIRCUIT WIRING SHALL BE 1/2 INCH CONDUIT, UNLESS OTHERWISE NOTED. 52. ALL TOGGLE SWITCHES AND RECEPTACLES SHALL BE FLUSH MOUNTED WITH THE FINISHED WALL, UNLESS SPECIFICALLY NOTED OTHERWISE. 53. INTERIOR FLUSH BOXES SHALL BE CODE GRADE STEEL, SECURELY FASTENED WITH APPROVED DEVICES TO STUDS OR MASONRY AND SHALL BE AS MANUFACTURED BY RACO, OR APPROVED EQUAL. 54. TOGGLE SWITCHES SHALL BE TYPE 54521-2-I (WHITE) AS MANUFACTURED BY LEVITON, INC., AND SHALL BE TUMBLER TYPE 20 AMP, QUIET TYPE. 55. ALL INDOOR CONVENIENCE OUTLETS SHALL BE TYPE CR-15 AS MANUFACTURED BY LEVITON. ALL OUTLET COVERPLATES SHALL BE WHITE. 56. LAMPS SHALL BE MANUFACTURED BY SYLVANIA, WESTINGHOUSE, GENERAL ELECTRIC, OR APPROVED EQUAL. 57. FLUORESCENT FIXTURE BALLASTS SHALL BE "P" RATED, WITH POWER FACTOR, CBM-ETL CERTIFIED AND LISTED BY THE UNDERWRITER'S LABORATORIES. ALL BALLASTS TO HAVE INTEGRAL THERMAL PROTECTION WITH AUTOMATIC RESET, UNIVERSAL OR APPROVED EQUAL. 58. ALL PANELBOARDS SHALL BE DEAD-FRONT, SAFETY-TYPE EQUIPPED WITH SINGLE OR MULTI-POLE CIRCUIT BREAKERS, SPECIFIED IN THIS SECTION AND AS SCHEDULED ON THE DRAWINGS. 59. ALL CIRCUIT BREAKERS SHALL BE BOLTED-TYPE, QUICK-MADE AND QUICK-BREAK TYPE OF MANUAL OPERATION, TRIP FEE, AND WITH INVERSE TIME CHARACTERISTICS SECURED THROUGH THE USE OF BIMETALLIC THERMAL-MAGNETIC TRIPPING ELEMENTS. ALL MULTI-POLE BREAKERS SHALL HAVE A SIMULTANEOUS TRIP. 60. SINGLE POLE, DOUBLE AND THREE-POLE CIRCUIT BREAKERS FOR LIGHTING AND POWER PANELBOARDS SHALL BE 240 VOLT, TYPE THQB FROM 15 AMPS THROUGH 100 AMPS, HAVING NEMA INTERRUPTING CAPACITY NOT LESS THAN 10,000 AMPERES A.C. AT 240 VOLTS OR LESS. 61. PANELBOARDS SHALL BE TYPE AQ PANEL BOARDS MANUFACTURED BY GE, SQUARE 'D', SIEMENS, WESTINGHOUSE OR PETERSON. 62. CIRCUIT BREAKERS IN LIGHTING PANEL SHALL BE APPROVED "SWITCHING TYPE" CIRCUIT BREAKERS. 63. NEUTRAL CONDUCTORS SHALL BE SOLID THROUGHOUT SAFETY SWITCHES AND FUSES. SAFETY SWITCHES SHALL BE TYPE TH AS MANUFACTURED BY GE, SQUARE D, ITE, OR WESTINGHOUSE. ALL FUSES INSTALLED IN SAFETY SWITCHES THROUGHOUT THE CONTRACT SHALL BE NON-RENEWABLE DUAL ELEMENT TYPE. FUSES. 64. INSTALL CONCEALED TELEPHONE CONDUIT INCLUDING NECESSARY PULL BOXES AND FISH WIRE IN ACCORDANCE WITH LOCAL TELEPHONE COMPANY REQUIREMENTS TO LOCATIONS INDICATED ON THE DRAWINGS. WHEN CALLED FOR ON THE SITE DRAWING, ALSO PROVIDE NECESSARY CONDUIT TO OUTSIDE TELEPHONE BOOTH. 65. AT CASH REGISTERS, PROVIDE CAT6 10BASE-T AND RJ45 TERMINATION POINTS AS INDICATED ON DRAWINGS. PULL WIRE TO EACH TERMINAL, USING EQUAL LENGTHS OF CABLE FROM MIDDLE OF FRONT COUNTER. NETWORK HUB IS LOCATED AT FRONT LINE. PROVIDE ISOLATED SECOND GROUND FOR EACH CASH REGISTER. ELECTRICAL SPECIFICATIONS SCALE: NONE 1 E0.1 UNISTRUT MOUNTING RACK ELECTRICAL LEGENDS, ABBREVIATIONS & SPECIFICATIONS JDJ EJR ISSUE DATE THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. PROJECT INFORMATION CERTIFICATION ISSUE DATES F :: 317 . 288 . 0753 O :: 317 . 288 . 0681 INDIANAPOLIS, IN 46216 5719 LAWTON LOOP E. DR. #212 T E S E N G I N E E R I N G Cleveland, OH 44145 25760 First Street P 440 871 2410 F 440 871 7954 tesengineering.com DRAWN BY: ________ CHECKED BY: ________ PROJECT NUMBER: 200079 TIDE CLEANERS 2801 E. 116TH STREET CARMEL, INDIANA 46033 DROP STORE E0.1 06/04/2020 09/24/20