HomeMy WebLinkAboutE0.1 ELECTRICAL LEGENDS, ABBRV & SPECIFICATIONS1. THE DRAWINGS ARE DIAGRAMMATIC IN NATURE AND DO NOT
NECESSARILY SHOW EVERY FITTING AND DETAIL. ALL WORK
SHALL BE COMPLETED SO THAT JUNCTION BOXES, FITTINGS
AND COMPONENTS WILL BE ACCESSIBLE FOR SERVICING.
2. ALL ELECTRICAL WORK PERFORMED DURING THIS SCOPE OF
WORK SHALL COMPLY WITH ALL LOCAL BUILDING CODES,
LAWS, REGULATIONS, ORDINANCES, AND THE
REQUIREMENTS OF THE 2011 NATIONAL ELECTRICAL CODE.
ALL WORK SHALL COMPLY WITH ANY OWNER
SPECIFICATIONS NOT CALLED OUT ON THIS SET OF
DRAWINGS.
3. ALL PENETRATIONS THRU RATED WALLS AND CEILINGS
SHALL BE FIRE STOPPED PER NEC 300-21 AND NFPA 221.
4. PROVIDE ALL GROUNDING AS REQUIRED BY NEC OR ANY
LOCAL CODES.
5. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL
ELECTRIC CODE, B.O.C.A. AND O.S.H.A. LATEST EDITIONS,
AND ALL APPLICABLE LOCAL CODES.
6. ELECTRIC SERVICE SHALL BE COORDINATED WITH THE
UTILITY CO. CONTRACTOR SHALL PAY ANY FEES LEVIED FOR
SERVICE. PROVIDE METER CANS OR C/T CABINETS AS
REQUIRED.
7. CONTRACTOR SHALL OBTAIN AND PAY FOR BOTH ROUGH
AND FINAL UNDERWRITERS OR OTHER APPROVED
INSPECTION AGENCY CERTIFICATE OF "ELECTRICAL
INSPECTION". THESE CERTIFICATES SHALL BE PRESENTED
WITH REQUEST FOR FINAL PAYMENT.
8. SERVICE SHOWN AS BEING UNDERGROUND ON ELECTRICAL
RISER DIAGRAM, INCLUDE ANY CHANGES REQUIRED IN THE
ELECTRICAL PANELS, SWITCHES, MOTORS, WIRING, BREAKER
SIZES, AND EQUIPMENT NECESSARY TO ADAPT TO THE
SERVICE AVAILABLE, THE REQUIREMENTS OF THE UTILITY
COMPANY, LOCAL CODES OR THE SIZE OF HEATING,
VENTILATION AND AIR CONDITIONING EQUIPMENT SPECIFIED.
9. INSTALL CONCEALED TELEPHONE CONDUIT INCLUDING
NECESSARY PULL BOXES AND FISH WIRE IN ACCORDANCE
WITH LOCAL TELEPHONE COMPANY REQUIREMENTS TO
LOCATIONS INDICATED ON THE DRAWINGS. WHEN CALLED
FOR ON THE SITE DRAWING, ALSO PROVIDE NECESSARY
CONDUIT TO OUTSIDE TELEPHONE BOOTH.
10. CONTRACTOR SHALL COOPERATE WITH OTHER SECTIONS
FOR THE EXECUTION OF THIS WORK. SUPPLY AND
COOPERATE IN THE PLACEMENT OF INSERTS, SLEEVES AND
OTHER EQUIPMENT TO BE INSTALLED IN MASONRY.
CAREFULLY CUT NECESSARY HOLES FOR THE INSTALLATION
OF EQUIPMENT AND PATCH IN SUCH A MANNER AS TO MATCH
THE ORIGINAL WORK.
11. WHERE MOUNTING HEIGHTS ARE SHOWN ON THE DRAWINGS,
THE MEASUREMENT IS TO BE TAKEN FROM THE CENTERLINE
OF THE DEVICE.
12. ALL WIRING MUST BE INSTALLED IN CONDUIT. TYPICAL
CONDUIT SIZES ARE 1/2" EMT WITH 2#12, 1#12G. AWG UNLESS
OTHERWISE NOTED. IF REQUIRED BY LOCAL CODE, USE BX
ARMORED CABLE OR TYPE THHN WIRE ENCLOSED IN
APPROVED METAL RACEWAYS. ALUMINUM WIRE SHALL NOT
BE ALLOWED.
13. A #12 GROUND SHALL BE PROVIDED FOR ALL MECHANICAL
EQUIPMENT UNLESS NOTED OTHERWISE. ALL EQUIPMENT
SHALL BE GROUNDED AT THE PANEL THAT FEEDS THE
EQUIPMENT.
14. CONTRACTOR SHALL PROVIDE A TYPED PANEL SCHEDULE
DIRECTORY LOCATED ON THE INSIDE COVER OF THE
ELECTRICAL PANEL. ALL CIRCUITS, SPARES, AND SPACES
SHALL BE CORRECTLY AND CLEARLY LABELED. ALL CARDS
SHALL INDICATE AREAS AND DEVICES SERVED BY EACH
CIRCUIT.
15. ALL BRANCH CIRCUIT HOMERUN CONDUCTORS SHALL BE
PROVIDED WITH A SEPARATE INSULATED #12 AWG
EQUIPMENT GROUNDING CONDUCTOR.
16. ELECTRICAL CONTRACTOR SHALL GUARANTEE ALL WORK
AND MATERIALS AGAINST ALL DEFECTS IN MATERIAL, DESIGN
AND WORKMANSHIP FOR ONE YEAR EFFECTIVE THE DAY THE
PROJECT IS ACCEPTED BY THE OWNER. FAILURE OF ANY
PART OR PARTS DURING GUARANTEE, OWING TO ABOVE
CAUSES, SHALL BE REPLACED PROMPTLY UPON NOTICE BY
ARCHITECT, WITHOUT CHARGE TO THE OWNER.
17. BUILDING CODE SECTION 705.4 SHALL BE MET WITH
ELECTRICAL DEVICES TO BE INSTALLED IN RATED WALLS.
18. ALL ELECTRICAL MATERIALS, DEVICES, AND EQUIPMENT
SHALL BE LISTED BY UL OR OTHER STATE APPROVED THIRD
PARTY TESTING AGENCY.
19. FIRE RATED SLEEVES SHALL BE PROVIDED AND ALL
FIRESTOPPING SHALL BE PROVIDED AS REQUIRED BY CODE
WHEN CABLING IS ROUTED THROUGH A FIRE RATED
PARTITION. BLANK COVERS SHALL BE INSTALLED ON RINGS.
20. MOUNT ALL DISCONNECT SWITCHES TO STRUCTURE.
DISCONNECTS SHALL NOT BE MOUNTED TO DUCTWORK OR
MECHANICAL EQUIPMENT.
21. ALL LIGHT FIXTURES SHALL BE CLEANED, AND FULLY
FUNCTIONAL AT MOVE-IN. THIS INCLUDES RE-LAMPING.
22. CONTRACTOR SHALL PROVIDE AND INSTALL PHENOLIC
LABELED NAMEPLATES FOR ALL RECEPTACLES AND
POWERED DEVICES (INCLUDING PANELBOARDS AND
DISCONNECTS). INFORMATION ON NAMEPLATE SHALL
INCLUDE ELECTRICAL PANEL AND CIRCUIT NUMBER FROM
WHICH DEVICE IS POWERED.
WHERE TWO SWITCHES OR MORE (INCLUDING DIMMERS) ARE
LOCATED NEXT TO EACH OTHER, CONTRACTOR SHALL
PROVIDE AND INSTALL A SINGLE SWITCH PLATE TO PROVIDE
A NEATER APPEARANCE.
ELECTRICAL SYMBOL AND ABBREVIATION
LEGEND
CONCEALED CONDUIT
CONCEALED CONDUIT IN FLOOR OR UNDERGROUND
CIRCUIT HOMERUN TO PANEL; EACH ARROWHEAD = 1 CIRCUIT
NO. OF CONDUCTORS IN CONDUIT (EACH CROSSHATCH = 1 WIRE) GROUND WIRE IS
NOT INDICATED WITHIN CROSSHATCH WIRES
ELECTRICAL PANELBOARD
FLUORESCENT OR LED LIGHT FIXTURE
INDUSTRIAL TURRET OR STRIP FIXTURE
TOGGLE LIGHT SWITCH
DOWN LIGHT
EXIT SIGN FIXTURE
EMERGENCY EGRESS LIGHT
EXIT SIGN EMERGENCY EGRESS LIGHT COMBO FIXTURE
FLUORSECENT OR LED LIGHT FIXTURE WITH 1400 LUMEN EMERGENCY BATTERY
BALLAST/PACK.
3 WAY AND 4 WAY TOGGLE SWITCHES
WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH (WATT STOPPER
MODEL DSW-301 OR APPROVED EQUAL)
CEILING MOUNTED OCCUPANCY SENSOR - DUAL TECHNOLOGY LINE VOLTAGE TYPE
(WATT STOPPER MODEL DT-355 OR APPROVED EQUAL)
DUPLEX RECEPTACLE (18"AFF UNO)
QUADRAPLEX RECEPTACLE (18" AFF UNO )
TELEPHONE/COMMUNICATIONS JACK (CONTRACTOR SHALL PROVIDE JUNCTION BOX
18" AFF UNO WITH 3/4" EMPTY CONDUIT WITH PULLSTRING TO UP ABOVE
ACCESSIBLE CEILING)
TELEPHONE BACKBOARD
DISCONNECT SWITCH (FRAME / FUSE / POLES / NEMA RATING)
MOTOR RATED SWITCH
JUNCTION BOX
JUNCTION BOX FOR TV CABLE
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER - EXACT LOCATION TO BE
COORDINATED WITH MILLWORK
30A/NF/3P/N1
SPECIAL PURPOSE RECEPTACLE. VOLTAGE, AMP RATING, AND NUMBER OF WIRES AS
INDICATED ON PLANS.
AFC
AFF
BFC
E EX /
EXTG
EC
EWC
FPMR
GFI
NF
NIC
WP
XFMR
UNO
ABOVE FINISHED CEILING OR AVAILABLE FAULT CURRENT
ABOVE FINISHED FLOOR
BELOW FINISHED CEILING
EXISTING
ELECTRICAL CONTRACTOR
ELECTRIC WATER COOLER
FUSE PER MANUFACTURER'S RECOMMENDATIONS
GROUND FAULT CIRCUIT INTERRUPTION
NON-FUSED or NOT FUSED
NOT IN CONTRACT
WEATHERPROOF
TRANSFORMER
UNLESS NOTED OTHERWISE
PHOTOCELL (WATT STOPPER MODEL ''EM-24' OR APPROVED EQUAL)
EQUIPMENT TAG
STRUCTURE
SUSPENDED CEILING
DISCONNECT, MOTOR
RATED SWITCH, OR
RECEPTACLE
UNISTRUT SUPPORT ANCHORED
TO STRUCTURAL SUPPORT ABOVE
CEILING WITH HARDWARE AS
REQUIRED.
FLOOR
24. PROVIDE "FLASH HAZARD" WARNING LABELS ON ALL
ELECTRICAL PANELS, AS PER NEC REQUIREMENTS.
25. ALL ELECTRICAL PERMITS AND INSPECTION FEES SHALL BE
OBTAINED AND PAID FOR BY THE ELECTRICAL CONTRACTOR.
26. ALL WIRING SHALL BE INSTALLED IN GALVANIZED RIGID
CONDUIT, INTERMEDIATE METAL CONDUIT, OR EMT. EMT
SHALL NOT BE USED IN OR UNDER CONCRETE SLABS, OR IN
MASONRY WALLS. USE SCHEDULE 40 PVC BELOW FLOOR
SLAB OR OUTDOORS WHERE NOT SUBJECT TO PHYSICAL
DAMAGE.
27. CONDUCTORS SHALL BE COPPER RATED AT NOT LESS THAN
600 VOLTS.
28. ALL CONDUCTORS SHALL BE COPPER WITH TYPE "THHN" OR
"THW" INSULATION. USE "THHN" FOR #10 OR SMALLER
CONDUCTORS. USE "THW" FOR CONDUCTORS #8 OR LARGER.
29. THE MINIMUM WIRE SIZE SHALL BE #12 A.W.G. WITH A 75°
DEGREE TEMPERATURE RATING.
30. FUSES 0 - 600 AMPS SHALL BE UL CLASS "RK-1" LOW PEAK
DUAL ELEMENT TIME DELAY WITH 200,000 AMPERE
INTERRUPTING RATING AS MANUFACTURED BY BUSSMAN,
UNLESS OTHERWISE NOTED.
31. INSTALL ALL ELECTRICAL OUTLET BOXES HORIZONTAL AND
FLUSH IN WALLS WHERE POSSIBLE. PROVIDE APPROPRIATE
FLUSH MOUNTING RECEPTACLE BOXES AND CONDUIT AS
REQUIRED FOR MOUNTING OF OUTLETS ON CONCRETE
WALLS.
32. ALL TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL
BE IDENTIFIED FOR USE WITH THE MATERIAL (CU/AL) OF THE
CONDUCTOR AND SHALL BE PROPERLY INSTALLED. ALL
TERMINALS, SPLICING CONNECTORS, LUGS, ETC. SHALL BE
IDENTIFIED FOR USE WITH 75° RATED CONDUCTORS.
33. ALL 15 AND 20 AMP, 125 VOLT RECEPTACLES LOCATED IN THE
KITCHEN AND BREAK AREA SHALL BE GFCI PROTECTED.
34. ALL CONDUIT SHALL BE ZINC-COATED EMT EXCEPT IN WET,
DAMP, OR UNDERGROUND LOCATIONS, WHERE ZINC-COATED
RIGID STEEL SHALL BE USED. EMT FITTING SHALL BE STEEL
SET-SCREW TYPES. ALL FITTINGS SHALL BE U.L. LISTED FOR
CONCRETE TIGHT AND RAIN TIGHT CONSTRUCTION. ALL EMT
ENTRANCE FITTINGS SHALL BE PROVIDED WITH INSULATED
THROATS. KEEP ALL RACEWAYS A MINIMUM OF 6 INCHES
AWAY FROM ALL PARALLEL RUNS OF FLUES, STEAM PIPES,
AND HOT WATER PIPES.
35. RACEWAY AND OUTLET PENETRATIONS THROUGH SLABS
AND FIRE RATED WALLS SHALL BE SEALED WITH IMPERVIOUS
NON COMBUSTIBLE MATERIALS IN SUCH A MANNER AS TO
RESTORE THE ORIGINAL FIRE RATING. MANUFACTURED
MATERIALS SHALL BE EQUAL TO 3M AND SHALL BE UL LISTED.
36. WIRING DEVICES SHALL BE HUBBELL, LEVITON, OR EQUAL.
PLATE AND DEVICES SHALL BE WHITE.
37. ALL ELECTRICAL CONDUCTORS SHALL BE TESTED FOR
CONTINUITY AND GROUNDS BEFORE BEING ENERGIZED. ALL
FAULTY CONDUCTORS SHALL BE REPLACED.
38. THE ELECTRICAL CONTRACTOR SHALL CONNECT ALL
EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS, EXCEPT
CONTROL WIRING PROVIDED BY OTHERS. #14 AWG SHALL BE
MINIMUM SIZE FOR CONTROL CONDUCTORS PROVIDED BY
ELECTRICAL CONTRACTOR.
39. CONNECTIONS TO MOTORS SHALL BE THROUGH FLEXIBLE
METALLIC CONDUIT. WHERE EXTERIOR, MATERIALS SHALL BE
NEOPRENE JACKETED WITH WATERTIGHT CONNECTIONS. A
SEPARATE GREEN INSULATED GROUNDING CONDUCTOR
SIZED PER NEC SHALL BE PROVIDED IN EACH NEW FEEDER
CONDUIT AND EACH NEW BRANCH CIRCUIT WIRING CONDUIT.
PROVIDE CONNECTIONS FOR PANEL BACKBOXES,
RECEPTACLES, MOTOR FRAMES, AND OTHER DEVICES.
40. SAFETY SWITCHES SHALL BE FUSIBLE WITH AN EXTERNAL
LEVER OR HANDLE FOR MANUAL OPERATION WITH
INTERLOCKING COVER. OF THE SIZE AND FUSING INDICATED
ON THE DRAWINGS. PROVIDE NEMA 1 ENCLOSURE FOR
INDOOR SWITCHES AND NEMA 3R ENCLOSURE FOR
OUTDOOR SWITCHES. FUSES SHALL BE DUAL ELEMENT, TIME
DELAY TYPE.
41. MANUAL MOTOR STARTERS TO BE PROVIDED ELECTRICAL
CONTRACTOR SHALL BE MOTOR SENTINEL TYPE WITH
PROPERLY SIZED OVERLOAD HEATERS, MOUNTED IN NEMA 1
OR NEMA 3R ENCLOSURE AS REQUIRED. ELECTRICAL
CONTRACTOR SHALL PROVIDE WHERE NOT SPECIFIED
UNDER DIVISION PROVIDING EQUIPMENT.
42. ALL FLUORESCENT FIXTURES SHALL BE ELECTRONIC, UL AND
CBM LISTED, ETL APPROVED, HAVING "A" SOUND RATING. PL
LAMPS SHALL BE SP-35 TYPE.
43. PROVIDE LATERAL BRACING FOR CONDUIT, TRANSFORMERS
AND OTHER FLOOR MOUNTED ELECTRICAL EQUIPMENT AS
REQUIRED BY LOCAL CODE (AS APPLICABLE).
44. ROOFTOP MECHANICAL UNITS SHALL HAVE A GFCI WP
OUTLET.
45. ALL RECEPTACLES AND DATA/COMM. DEVICES SHALL BE
MOUNTED AT 18"AFF, UNLESS OTHERWISE NOTED.
46. WHERE FLUORESCENT LIGHT FIXTURES ARE INSTALLED IN
SUSPENDED CEILINGS, THEY ARE TO BE INDEPENDENTLY
SUPPORTED AND SECURED TO THE BUILDING STRUCTURE BY
WIRES ON OPPOSING CORNERS.
47. CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO ALL
LESSEE'S OR FRANCHISE OWNER'S SIGNS AND EQUIPMENT
AND FURNISH AND INSTALL FITTINGS OR INCIDENTAL
ACCESSORIES THAT MAY BE NECESSARY OR THAT MAY BE
REQUIRED BY LOCAL CODES FOR COMPLETING FINAL
CONNECTIONS AND MAKING EQUIPMENT READY FOR
OPERATION.
48. CONTRACTOR SHALL COORDINATE WITH THE APPROVED
SIGN INSTALLATION COMPANY AND, IN CONJUNCTION WITH
THE SIGN COMPANY, MAKE FINAL CONNECTIONS TO SIGNS
AT THE TIME OF INSTALLATION.
49. UNDERGROUND CONDUITS FOR PYLON SIGN AND AREA
LIGHTING SHALL BE HEAVY WALL, SCHEDULE 40 PVC.
CONDUIT SHALL BE CAPPED DURING CONSTRUCTION TO
PREVENT ENTRANCE OF FOREIGN MATTER. IF THE USE OF
PVC IS NOT PERMITTED BY LOCAL CODES, ALL
UNDERGROUND CONDUIT SHALL BE RIGID STEEL, HEAVY
WALL GALVANIZED. CONDUIT FITTINGS EXPOSED TO
WEATHER SHALL BE OF A TYPE APPROVED FOR SUCH USE
AND SHALL BE PROVIDED WITH GASKETS OR OTHER MEANS
OF EXCLUDING MOISTURE.
50. "SWAB" CONDUIT DRY BEFORE PULLING WIRES. THREADS
SHALL BE PROTECTED. UNDERGROUND CONDUIT IN YARD
RUNS SHALL BE LAID WITH 2FT. MINIMUM COVER OF SAND OR
AS REQUIRED BY LOCAL CODE. WHERE REQUIRED BY LOCAL
CODE, USE RIGID STEEL CONDUIT, HEAVY WALL GALVANIZED
FOR ALL WORK WITHIN BUILDING. OTHERWISE, WHERE
RACEWAYS ARE REQUIRED USE THIN WALL ELECTRIC
METALLIC TUBING.
51. SEALTITE CONDUIT AND FITTINGS SHALL BE USED FOR FINAL
MOTOR CONNECTIONS. SMALLEST SIZE CONDUIT FOR
BRANCH CIRCUIT WIRING SHALL BE 1/2 INCH CONDUIT,
UNLESS OTHERWISE NOTED.
52. ALL TOGGLE SWITCHES AND RECEPTACLES SHALL BE FLUSH
MOUNTED WITH THE FINISHED WALL, UNLESS SPECIFICALLY
NOTED OTHERWISE.
53. INTERIOR FLUSH BOXES SHALL BE CODE GRADE STEEL,
SECURELY FASTENED WITH APPROVED DEVICES TO STUDS
OR MASONRY AND SHALL BE AS MANUFACTURED BY RACO,
OR APPROVED EQUAL.
54. TOGGLE SWITCHES SHALL BE TYPE 54521-2-I (WHITE) AS
MANUFACTURED BY LEVITON, INC., AND SHALL BE TUMBLER
TYPE 20 AMP, QUIET TYPE.
55. ALL INDOOR CONVENIENCE OUTLETS SHALL BE TYPE CR-15
AS MANUFACTURED BY LEVITON. ALL OUTLET COVERPLATES
SHALL BE WHITE.
56. LAMPS SHALL BE MANUFACTURED BY SYLVANIA,
WESTINGHOUSE, GENERAL ELECTRIC, OR APPROVED EQUAL.
57. FLUORESCENT FIXTURE BALLASTS SHALL BE "P" RATED, WITH
POWER FACTOR, CBM-ETL CERTIFIED AND LISTED BY THE
UNDERWRITER'S LABORATORIES. ALL BALLASTS TO HAVE
INTEGRAL THERMAL PROTECTION WITH AUTOMATIC RESET,
UNIVERSAL OR APPROVED EQUAL.
58. ALL PANELBOARDS SHALL BE DEAD-FRONT, SAFETY-TYPE
EQUIPPED WITH SINGLE OR MULTI-POLE CIRCUIT BREAKERS,
SPECIFIED IN THIS SECTION AND AS SCHEDULED ON THE
DRAWINGS.
59. ALL CIRCUIT BREAKERS SHALL BE BOLTED-TYPE,
QUICK-MADE AND QUICK-BREAK TYPE OF MANUAL
OPERATION, TRIP FEE, AND WITH INVERSE TIME
CHARACTERISTICS SECURED THROUGH THE USE OF
BIMETALLIC THERMAL-MAGNETIC TRIPPING ELEMENTS. ALL
MULTI-POLE BREAKERS SHALL HAVE A SIMULTANEOUS TRIP.
60. SINGLE POLE, DOUBLE AND THREE-POLE CIRCUIT BREAKERS
FOR LIGHTING AND POWER PANELBOARDS SHALL BE 240
VOLT, TYPE THQB FROM 15 AMPS THROUGH 100 AMPS,
HAVING NEMA INTERRUPTING CAPACITY NOT LESS THAN
10,000 AMPERES A.C. AT 240 VOLTS OR LESS.
61. PANELBOARDS SHALL BE TYPE AQ PANEL BOARDS
MANUFACTURED BY GE, SQUARE 'D', SIEMENS,
WESTINGHOUSE OR PETERSON.
62. CIRCUIT BREAKERS IN LIGHTING PANEL SHALL BE APPROVED
"SWITCHING TYPE" CIRCUIT BREAKERS.
63. NEUTRAL CONDUCTORS SHALL BE SOLID THROUGHOUT
SAFETY SWITCHES AND FUSES. SAFETY SWITCHES SHALL BE
TYPE TH AS MANUFACTURED BY GE, SQUARE D, ITE, OR
WESTINGHOUSE. ALL FUSES INSTALLED IN SAFETY
SWITCHES THROUGHOUT THE CONTRACT SHALL BE
NON-RENEWABLE DUAL ELEMENT TYPE. FUSES.
64. INSTALL CONCEALED TELEPHONE CONDUIT INCLUDING
NECESSARY PULL BOXES AND FISH WIRE IN ACCORDANCE
WITH LOCAL TELEPHONE COMPANY REQUIREMENTS TO
LOCATIONS INDICATED ON THE DRAWINGS. WHEN CALLED
FOR ON THE SITE DRAWING, ALSO PROVIDE NECESSARY
CONDUIT TO OUTSIDE TELEPHONE BOOTH.
65. AT CASH REGISTERS, PROVIDE CAT6 10BASE-T AND RJ45
TERMINATION POINTS AS INDICATED ON DRAWINGS. PULL
WIRE TO EACH TERMINAL, USING EQUAL LENGTHS OF CABLE
FROM MIDDLE OF FRONT COUNTER. NETWORK HUB IS
LOCATED AT FRONT LINE. PROVIDE ISOLATED SECOND
GROUND FOR EACH CASH REGISTER.
ELECTRICAL SPECIFICATIONS
SCALE: NONE
1
E0.1
UNISTRUT MOUNTING RACK
ELECTRICAL LEGENDS,
ABBREVIATIONS &
SPECIFICATIONS
JDJ EJR
ISSUE DATE
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
F :: 317 . 288 . 0753
O :: 317 . 288 . 0681
INDIANAPOLIS, IN 46216
5719 LAWTON LOOP E. DR. #212
T E S
E N G I N E E R I N G
Cleveland, OH 44145
25760 First Street
P 440 871 2410
F 440 871 7954
tesengineering.com
DRAWN BY: ________ CHECKED BY: ________
PROJECT NUMBER: 200079
TIDE CLEANERS
2801 E. 116TH STREET
CARMEL, INDIANA 46033
DROP STORE
E0.1
06/04/2020
09/24/20