HomeMy WebLinkAboutM2.0 MECHANICAL SCHEDULEROOFTOP HVAC UNIT SCHEDULE
TAG MFR MODEL No.NOMINAL
TONS
EER MIN OA
(CFM)
SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS
NOTES/ACCESSORIESAIR FLOW
(CFM)
ESP
(IN WC)
MOTOR
(HP)
FAN
(RPM)
EAT °DB/°WB
(°F)
LAT °DB/°WB
(°F)
SENSIBLE
(MBH)
TOTAL
(MBH)
COOLING
STAGES
EAT/LAT
(°F)
INPUT
(MBH)
OUTPUT
(MBH)
HEATING
STAGES
VOLTAGE
(V-ɸ-Hz)UNIT MCA UNIT MOCP
OPERATING
WEIGHT
(LBS)
RTU-1 TRANE YHC074 6 13.1 300 2400 1.00 2.75 1093 74.8/62.7 53.7/52.9 57.1 70.1 1 61.7/81.7 80.0 64.8 1 208-3-60 37 50 1600 1-18
NOTES/ACCESSORIES
1. 95° CONDENSING TEMPERATURE
2. REFRIGERANT - R410A
3. REFERENCE ENTHALPY ECONOMIZER
4. BAROMETRIC RELIEF
5. 14" INSULATED ROOF CURB
6. UNIT MOUNTED NON FUSED DISCONNECT
7. UNPOWERED GFCI RECEPTACLE
8. SUPPLY FAN WITH SINGLE ZONE VAV CONTROLLER
9. THROUGH THE BASE ELECTRICAL
10. HAIL GUARD - WITH TOOL LESS REMOVAL
11. PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT
12. HINGED ACCESS DOORS
13. ONCE THE RTU’S ARE OPERATIONAL - PROVIDE 2” MERV 8 FILTERS. INSPECT FILTERS DAILY. REPLACE AS NEEDED BUT NOT LONGER THAN 7 DAYS UNTIL UNIT IS ADJUSTED BY BALANCE CONTRACTOR. AT THE DISCRETION OF THE TENANT CONSTRUCTION REPRESENTATIVE THIS FILTER REPLACEMENT CAN BE EXTENDED PAST THE 7 DAY LIMIT. ALL UN-USED FILTERS
TO REMAIN ON SITE FOR FUTURE USE BY TENANT. NEVER OPERATE THE RTU(S) IN COOLING DURING ANY SANDING OR DEMOLITION OR IF ANY TYPE OF FINE PARTICULATE COULD BE AIR BORNE. ALL RETURN AIR GRILLES OPENING IN RETURN AIR DUCTWORK SHALL BE COVERED WITH CHEESE CLOTH OR A THROW AWAY FILTER (CHEAP CUT TO FIT FILTER ROLL) UNTIL
UNITS ARE ADJUSTED BY THE BALANCING CONTRACTOR. REMOVE THIS CHEESE CLOTH FILTER UPON TESTING BY BALANCE CONTRACTOR.
14. MICRO-PROCESSOR CONTROLS
15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY
16. STAINLESS STEEL HEAT EXCHANGER WITH STAGED HEAT
17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER
18. APPROVED ALTERNATES: CARRIER, AAON, YORK/JOHNSON CONTROLS, AND LENNOX
OUTSIDE AIR SCHEDULE
ZONE DATA SYSTEM DATA
ZONE NAME
FLOOR
AREA
(SF)
REQUIRED
OUTSIDE AIR
(CFM/SF)
OCCUPANCY
REQUIRED
OUTSIDE AIR
(CFM/PERSON)
BREATHING ZONE
OUTSIDE AIR
(CFM)
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
REQUIRED
OUTSIDE AIR
(CFM)
SUPPLY
AIR
(CFM)
OUTDOOR AIR
FRACTION SYSTEM NAME
SYSTEM
VENTILATION
EFFICIENCY
REQUIRED
OUTSIDE AIR
(CFM)
DELIVERED
OUTSIDE AIR
(CFM)
BREAK 85 0.06 1 5 10 0.8 13 150 0.087
RTU-1 0.950 245 300
LAUNDRY 451 0.12 8 7.5 114 0.8 143 700 0.204
LOBBY 350 0.06 6 5 51 0.8 64 850 0.075
MANAGER 125 0.06 1 5 13 0.8 17 150 0.113
METAL PROGRETTI 367 0.12 0 0 44 0.8 55 450 0.122
NOTES
1. SPACE OUTSIDE AIR REQUIREMENTS BASED ON IMC 2012
AIR DISTRIBUTION SCHEDULE
TAG SERVICE MOUNTING MFR MODEL No.MODULE/ DIFFUSER
SIZE NOTES/ACESSORIES
S1 SUPPLY DUCT TITUS TMSA 24" X 24" 1
S2 SUPPLY CEILING TITUS TMSA 24" X 24"
1,2
S3 SUPPLY WALL TITUS 300FL SIZE ON PLAN +2" 1
S4 SUPPLY CEILING TITUS TMSA 12" X 12"
1,3
R1 RETURN CEILING TITUS 350FL 24" X 24" 1
R2 RETURN WALL TITUS 350FL SIZE ON PLAN +2" 1
NOTES/ACCESSORIES
1. FINISH - WHITE POWDER COAT
2. RAPID MOUNT FRAME
3. FIELD VERIFY EXISTING CEILING AND SELECT DIFFUSER FRAMING INSTALLATION TO MATCH
MECHANICAL
SCHEDULES
DKK NDG
ISSUE DATE
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
COPYRIGHT 2020, CURRAN ARCHITECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
F :: 317 . 288 . 0753
O :: 317 . 288 . 0681
INDIANAPOLIS, IN 46216
5719 LAWTON LOOP E. DR. #212
T E S
E N G I N E E R I N G
Cleveland, OH 44145
25760 First Street
P 440 871 2410
F 440 871 7954
tesengineering.com
DRAWN BY: ________ CHECKED BY: ________
PROJECT NUMBER: 200079
TIDE CLEANERS
2801 E. 116TH STREET
CARMEL, INDIANA 46033
DROP STORE
M2.0
06/04/2020
09/24/20