HomeMy WebLinkAboutM2.0 MECHANICAL SCHEDULEROOFTOP HVAC UNIT SCHEDULE TAG MFR MODEL No.NOMINAL TONS EER MIN OA (CFM) SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS NOTES/ACCESSORIESAIR FLOW (CFM) ESP (IN WC) MOTOR (HP) FAN (RPM) EAT °DB/°WB (°F) LAT °DB/°WB (°F) SENSIBLE (MBH) TOTAL (MBH) COOLING STAGES EAT/LAT (°F) INPUT (MBH) OUTPUT (MBH) HEATING STAGES VOLTAGE (V-ɸ-Hz)UNIT MCA UNIT MOCP OPERATING WEIGHT (LBS) RTU-1 TRANE YHC074 6 13.1 300 2400 1.00 2.75 1093 74.8/62.7 53.7/52.9 57.1 70.1 1 61.7/81.7 80.0 64.8 1 208-3-60 37 50 1600 1-18 NOTES/ACCESSORIES 1. 95° CONDENSING TEMPERATURE 2. REFRIGERANT - R410A 3. REFERENCE ENTHALPY ECONOMIZER 4. BAROMETRIC RELIEF 5. 14" INSULATED ROOF CURB 6. UNIT MOUNTED NON FUSED DISCONNECT 7. UNPOWERED GFCI RECEPTACLE 8. SUPPLY FAN WITH SINGLE ZONE VAV CONTROLLER 9. THROUGH THE BASE ELECTRICAL 10. HAIL GUARD - WITH TOOL LESS REMOVAL 11. PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT 12. HINGED ACCESS DOORS 13. ONCE THE RTU’S ARE OPERATIONAL - PROVIDE 2” MERV 8 FILTERS. INSPECT FILTERS DAILY. REPLACE AS NEEDED BUT NOT LONGER THAN 7 DAYS UNTIL UNIT IS ADJUSTED BY BALANCE CONTRACTOR. AT THE DISCRETION OF THE TENANT CONSTRUCTION REPRESENTATIVE THIS FILTER REPLACEMENT CAN BE EXTENDED PAST THE 7 DAY LIMIT. ALL UN-USED FILTERS TO REMAIN ON SITE FOR FUTURE USE BY TENANT. NEVER OPERATE THE RTU(S) IN COOLING DURING ANY SANDING OR DEMOLITION OR IF ANY TYPE OF FINE PARTICULATE COULD BE AIR BORNE. ALL RETURN AIR GRILLES OPENING IN RETURN AIR DUCTWORK SHALL BE COVERED WITH CHEESE CLOTH OR A THROW AWAY FILTER (CHEAP CUT TO FIT FILTER ROLL) UNTIL UNITS ARE ADJUSTED BY THE BALANCING CONTRACTOR. REMOVE THIS CHEESE CLOTH FILTER UPON TESTING BY BALANCE CONTRACTOR. 14. MICRO-PROCESSOR CONTROLS 15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY 16. STAINLESS STEEL HEAT EXCHANGER WITH STAGED HEAT 17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER 18. APPROVED ALTERNATES: CARRIER, AAON, YORK/JOHNSON CONTROLS, AND LENNOX OUTSIDE AIR SCHEDULE ZONE DATA SYSTEM DATA ZONE NAME FLOOR AREA (SF) REQUIRED OUTSIDE AIR (CFM/SF) OCCUPANCY REQUIRED OUTSIDE AIR (CFM/PERSON) BREATHING ZONE OUTSIDE AIR (CFM) ZONE AIR DISTRIBUTION EFFECTIVENESS REQUIRED OUTSIDE AIR (CFM) SUPPLY AIR (CFM) OUTDOOR AIR FRACTION SYSTEM NAME SYSTEM VENTILATION EFFICIENCY REQUIRED OUTSIDE AIR (CFM) DELIVERED OUTSIDE AIR (CFM) BREAK 85 0.06 1 5 10 0.8 13 150 0.087 RTU-1 0.950 245 300 LAUNDRY 451 0.12 8 7.5 114 0.8 143 700 0.204 LOBBY 350 0.06 6 5 51 0.8 64 850 0.075 MANAGER 125 0.06 1 5 13 0.8 17 150 0.113 METAL PROGRETTI 367 0.12 0 0 44 0.8 55 450 0.122 NOTES 1. SPACE OUTSIDE AIR REQUIREMENTS BASED ON IMC 2012 AIR DISTRIBUTION SCHEDULE TAG SERVICE MOUNTING MFR MODEL No.MODULE/ DIFFUSER SIZE NOTES/ACESSORIES S1 SUPPLY DUCT TITUS TMSA 24" X 24" 1 S2 SUPPLY CEILING TITUS TMSA 24" X 24" 1,2 S3 SUPPLY WALL TITUS 300FL SIZE ON PLAN +2" 1 S4 SUPPLY CEILING TITUS TMSA 12" X 12" 1,3 R1 RETURN CEILING TITUS 350FL 24" X 24" 1 R2 RETURN WALL TITUS 350FL SIZE ON PLAN +2" 1 NOTES/ACCESSORIES 1. FINISH - WHITE POWDER COAT 2. RAPID MOUNT FRAME 3. FIELD VERIFY EXISTING CEILING AND SELECT DIFFUSER FRAMING INSTALLATION TO MATCH MECHANICAL SCHEDULES DKK NDG ISSUE DATE THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. COPYRIGHT 2020, CURRAN ARCHITECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES F :: 317 . 288 . 0753 O :: 317 . 288 . 0681 INDIANAPOLIS, IN 46216 5719 LAWTON LOOP E. DR. #212 T E S E N G I N E E R I N G Cleveland, OH 44145 25760 First Street P 440 871 2410 F 440 871 7954 tesengineering.com DRAWN BY: ________ CHECKED BY: ________ PROJECT NUMBER: 200079 TIDE CLEANERS 2801 E. 116TH STREET CARMEL, INDIANA 46033 DROP STORE M2.0 06/04/2020 09/24/20