HomeMy WebLinkAboutM3.0 MECHANICAL SPECIFICATIONSI. GENERAL PROVISIONS A.GENERAL CONDITIONS, CODES & STANDARDS 1. GENERAL CONDITIONS OF THE CONTRACT FOUND IN THE ARCHITECTURAL DRAWINGS, GENERAL AND SPECIAL CONDITIONS OF THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND ANY OF THE OWNER'S GENERAL REQUIREMENTS SHALL APPLY UNLESS NOTED OTHERWISE. 2. REFER TO THE GENERAL CONDITIONS ON THE ARCHITECTURAL DOCUMENTS AND THE GENERAL AND SPECIAL CONDITIONS OF THE AIA FOR ADDITIONAL REQUIREMENTS REGARDING; SAFETY, COORDINATION & COOPERATION, WORKMANSHIP, PROTECTION, CUTTING AND PATCHING, DAMAGE TO OTHER WORK, PRELIMINARY OPERATIONS, STORAGE, ADJUSTMENTS, CLEANING, ETC. 3. ALL WORK SHALL BE IN CONFORMANCE WITH ALL LOCALLY ENFORCED, FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES INCLUDING ANY SPECIAL THE OWNER REQUIREMENTS IN ADDITION TO THOSE SPECIFIED. 4. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS. B. SCOPE OF WORK 1. THIS CONTRACT SHALL INCLUDE THE FURNISHING, INSTALLING, CONNECTING, AND OPERATION OF ALL EQUIPMENT WHICH IS A PART OF THE MECHANICAL SYSTEMS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY SIMILAR INSTALLATIONS. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF A SIMILAR CHARACTER SHALL BE FURNISHED AND INSTALLED UNDER THIS CONTRACT AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS REQUIRED TO PROVIDE THE OWNER A COMPLETE, CODE APPROVED AND OPERATIONAL MECHANICAL SYSTEM. 2. CAREFULLY READ SPECIFICATION FOR ALL PARTS OF THE WORK SO AS TO BECOME FAMILIAR WITH ALL TRADES' WORK SCOPE. CONSULT WITH OTHER TRADES TO INSURE PROPER LOCATIONS AND AVOID INTERFERENCES. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER BEFORE WORK IS COMMENCED. 3. CONTRACTORS SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO COMPARE THEM WITH THE DRAWINGS AND SPECIFICATIONS, NOTE THE EXISTING CONDITIONS AND OTHER WORK THAT WILL BE REQUIRED, AND THE NATURE OF THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. NO ALLOWANCE SHALL BE MADE TO THE CONTRACTOR BY REASON OF THIS FAILURE TO HAVE MADE SUCH EXAMINATION OR OF ANY ERROR ON HIS PART. 4. ALL EXISTING UTILITY AND MECHANICAL SERVICES SHALL BE FIELD VERIFIED. CORRECTIONS TO THE DESIGN AND INSTALLATION SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER. 5. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF HVAC WORK. ALL CORE DRILLING OR CUTTING OF FIRE RATED FLOORS, SHAFTS, AND WALLS SHALL BE FIRESTOPPED PRIOR TO FINISH PATCHING. ALL PENETRATIONS SHALL BE FIRE SEALED TO MATCH THE FIRE RATING OF THE FLOORS, SHAFTS, AND WALLS PENETRATED. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE OPENINGS IN WALLS AND FLOORS WITH THE GENERAL TRADES CONTRACTOR. THE FINAL LOCATIONS AND SIZES OF ALL DUCT, PIPE AND LOUVER OPENINGS SHALL BE PROVIDED BY THIS CONTRACTOR. 6. THIS CONTRACT SHALL ALSO INCLUDE ALL LABOR, MATERIALS AND MISCELLANEOUS EXPENSES REQUIRED FOR ALL REQUIRED MECHANICAL DEMOLITION OF THE EXISTING AREAS BEING RENOVATED. a. THE DEMOLITION SHALL CONSIST OF THE COMPLETE REMOVAL (PROPERLY DISPOSED OFF SITE UNLESS OTHERWISE NOTED) OF ALL MECHANICAL EQUIPMENT, PIPING, DUCTWORK, MATERIALS, ETC. NOT REQUIRED IN THE FINAL DESIGN AND INSTALLATION OF THE MECHANICAL HVAC SYSTEMS FOR THE NEW RENOVATED AREAS. b. ALL UNUSED SERVICES SHALL BE REMOVED BACK TO THEIR RESPECTIVE MAIN AND CAPPED OR IF THE MAIN IS NOT REQUIRED, THE MAIN SHALL BE REMOVED IN IT'S ENTIRETY. c. COORDINATE ALL DEMOLITION WITH THE ARCHITECTURAL DOCUMENTS AND THE ARCHITECT AND THE OWNER'S GENERAL REQUIREMENTS. 7. ALL WORK INCLUDING, BUT NOT LIMITED TO PARTS, MATERIAL, EQUIPMENT AND LABOR SHALL BE GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY THE ENGINEER AND OWNER. WHERE AN EQUIPMENT MANUFACTURER HAS A WARRANTY THAT EXCEEDS ONE YEAR, THAT WARRANTY PERIOD SHALL APPLY TO THIS PROJECT. C.DOCUMENTS 1. THE DRAWINGS ARE DIAGRAMMATIC, ALL WORK SHALL BE PERFORMED AS INDICATED ON THE DRAWINGS UNLESS EXISTING CONDITIONS OR COORDINATION ISSUES REQUIRE CHANGES. THESE CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER. 2. ANY INCIDENTAL ITEMS OR LABOR, ETC. NOT INCLUDED IN THE SPECIFICATIONS OR THE DRAWINGS BUT REASONABLY IMPLIED AS NECESSARY FOR THE COMPLETE INSTALLATION OF ALL APPARATUS SHALL BE INCLUDED IN BID. 3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NOT MENTIONED IN BOTH. 4. IF ERRORS ARE FOUND IN THE DRAWINGS OR SPECIFICATIONS OR DISCREPANCIES OCCUR BETWEEN THE SAME, OR BETWEEN THE FIGURES ON THE DRAWINGS, AND THE SCALE OF SAME OR BETWEEN THE LARGER AND SMALLER DRAWINGS, OR IN THE DESCRIPTIVE MATTER ON THE DRAWINGS SHALL BE REFERRED TO THE OWNER FOR REVIEW AND FINAL DECISION PRIOR TO THE BID DUE DATE. 5. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY AS SPECIFIED HEREIN. WHERE MORE THAN ONE MANUFACTURER IS MENTIONED ANY ONE MAY BE UTILIZED. SUBSTITUTE MANUFACTURERS MAY BE OFFERED ONLY AS AN ALTERNATE TO THE SPECIFIED EQUIPMENT AND MATERIAL AND MUST BE SUBMITTED AS SPECIFIED IN THE ARCHITECTURAL DOCUMENTS. 6. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN THESE SPECIFICATIONS. REFER TO EACH SECTION FOR ANY SPECIFIC REQUIREMENTS. D. COORDINATION 1. CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. 2. EACH CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGE TO OTHER WORK CAUSED BY HIS WORK OR THROUGH THE NEGLECT OF HIS, OR HIS SUB-TRADE'S PERSONNEL. ALL PATCHING, REPAIRING, REPLACEMENT AND PAINTING, ETC. SHALL BE DONE AS DIRECTED BY THE OWNER BY THE CRAFTSMEN OF THE TRADES INVOLVED. THE COSTS OF SUCH WORK SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. E. METHODS 1. EQUIPMENT, PIPING, DUCTWORK, ETC. SHALL NOT BE SUPPORTED FROM ANY CEILINGS, OTHER PIPING, CONDUIT OR DUCTWORK, ROOF DECK, OR JOIST BRIDGING. ITEMS SHALL BE SUPPORTED FROM ACCEPTABLE STRUCTURAL BUILDING COMPONENTS AS DETERMINED BY THE ARCHITECT AND STRUCTURAL ENGINEER. 2. ALL ROOF PENETRATIONS, FLASHINGS AND COUNTER FLASHINGS SHALL BE PERFORMED BY THE OWNER'S ROOFING CONTRACTOR AT THE REQUESTING CONTRACTOR'S COST. F. SUBMITTALS 1. SHOP DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT OF ALL EQUIPMENT AND ACCESSORIES PROVIDED FOR THE PROJECT WHETHER SPECIFIED HERE-IN OR ON THE DRAWINGS. REVIEW OF THE SHOP DRAWINGS SHALL BE FOR GENERAL DESIGN CONCEPT AND ADHERENCE WITH THE SPECIFICATIONS. QUANTITY OF SHOP DRAWINGS SUBMITTED SHALL BE AS SPECIFIED BY THE ARCHITECT. SHOP DRAWINGS SHALL BE PREPARED BY THE CONTRACTOR SHOWING LOCATIONS AND MEASUREMENTS FROM COLUMNS OF ALL CONCEALED AND EXPOSED PIPING, DUCTWORK, CONDUIT, EQUIPMENT, ACCESSORIES, ETC., AND SUBMITTED PRIOR TO INSTALLATION. THE OWNER MAY MAKE REPRODUCIBLE COPIES OF THEIR DRAWINGS AVAILABLE FOR USE IN PREPARATION OF SHOP DRAWINGS, HOWEVER THE OWNER SHALL NOT BE HELD RESPONSIBLE FOR NOT CONFIRMING ALL INFORMATION ON THE DRAWINGS PRIOR TO FABRICATION AND/OR INSTALLATION. 2. PROJECT RECORD DOCUMENTS - MAINTAIN AT THE JOBSITE ONE COPY OF ALL CONTRACT DOCUMENTS CLEARLY MARKED AS “PROJECT RECORD COPY”. THESE DRAWINGS ARE TO BE MAINTAINED IN GOOD CONDITION, UPDATED DAILY FOR CHANGES ENCOUNTERED AND AVAILABLE AT ALL TIMES FOR INSPECTION BY THE OWNER. DO NOT USE FOR FIELD CONSTRUCTION! PROJECT RECORD DOCUMENTS ARE TO BE KEPT CURRENT WITH EXACT DIMENSIONS OF ALL WORK, EQUIPMENT, PIPING, VALVES, DUCTWORK, ETC. MARK ALL INFORMATION IN RED LINES AND NOTES SO AS TO BE EASILY IDENTIFIED FROM THE BASE DRAWING. UPON COMPLETION OF THE WORK, ONE SET OF THESE DOCUMENTS SHALL BE TURNED OVER TO THE OWNER AS ONE QUALIFICATION FOR FINAL PAYMENT. 3. AFTER THE BALANCING AND ACCEPTANCE TESTS ARE COMPLETED AND ACCEPTED BY THE OWNER, THREE COMPLETE SETS OF AS-BUILT DOCUMENTATION SHALL BE PROVIDED. IT SHALL INCLUDE, BUT NOT BE LIMITED TO ACCURATE PLAN DRAWINGS, SYSTEM AND CONTROL SCHEMATICS, SEQUENCE OF OPERATION, WIRING DIAGRAMS AND OPERATION AND MAINTENANCE MANUALS. II. INSULATION A.GENERAL 1. INSTALLATION SHALL CONFORM TO THE MANUFACTURER'S RECOMMENDATIONS, AND IN ACCORDANCE WITH RECOGNIZED INDUSTRY PRACTICES. 2. CLEAN AND DRY SURFACES PRIOR TO INSULATING. 3. EXTEND INSULATION WITHOUT INTERRUPTION THROUGH WALLS, FLOORS, HANGERS AND SIMILAR PENETRATIONS. 4. INSULATION JACKET AND FITTING COVER MUST BE PLENUM RATED. 5. IT IS ESSENTIAL THAT THE INTEGRITY OF THE VAPOR-BARRIER BE MAINTAINED. SEAL ALL PENETRATIONS OF THE VAPOR BARRIER BY STAPLES, HANGERS OR WHERE OTHERWISE DAMAGED. 6. MAINTAIN ACCESS TO BALANCING DAMPERS AND VALVES. 7. INSULATION SHALL BE BY OWENS-CORNING, KNAUF, OR MANVILLE. B. HVAC DUCTWORK 1. INTERNALLY INSULATE WITH 1 INCH THICK, 1-1/2# DENSITY ACOUSTICAL INSULATION (AIR SIDE BLACK COATED TO MEET NFPA) ALL DUCTWORK NOTED AS REQUIRING SUCH. INTERNAL INSULATION SHALL BE INSTALLED PER THE REQUIREMENTS OF THE SMACNA GUIDE AND THE MANUFACTURER'S RECOMMENDATIONS. DUCT SIZES NOTED ON DRAWING ARE SHEET METAL DIMENSIONS. 2. ALL SUPPLY AND OUTSIDE AIR DUCTWORK SHALL BE WRAPPED WITH 1-1/2 INCH OF 0.75 LB/CU.FT. FIBERGLASS, FOIL BACKED DUCT WRAPPING. III. HVAC A.PIPING 1. OUTDOOR CONDENSATE PIPING SHALL BE TYPE “L” COPPER CONDENSATE DRAIN FOR THE ROOFTOP MOUNTED AIR CONDITIONING UNIT, INSTALLED PER THE MANUFACTURERS REQUIREMENTS AND DETAILS. DRAIN SHALL DISCHARGE INTO A ROOF DRAIN. 2. ALL PIPING SHALL BE SUPPORTED ON A MAXIMUM OF 10' CENTERS EXCEPT COPPER PIPING 1-1/4" AND SMALLER SHALL BE SUPPORTED ON A MAXIMUM OF 6' CENTERS. B. DUCTWORK AND AIR DISTRIBUTION 1. DUCTWORK (ROUND OR RECTANGULAR OR SPIRAL) SHALL BE OF GALVANIZED STEEL CONSTRUCTION AND SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA “HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE” MANUAL AND THE FOLLOWING PRESSURE / SEAL SCHEDULE: a. SUPPLY AIR DUCTWORK - 2" W.G. POSITIVE PRESSURE, SEAL CLASS B. b. RETURN DUCTWORK - 2" W.G. NEGATIVE PRESSURE, SEAL CLASS B. c. EXHAUST DUCTWORK - 2” W.G. NEGATIVE PRESSURE, SEAL CLASS A. 2. ROUND DUCT ELBOWS SHALL BE LONG SWEEP, 1-1/2 TIMES THE CENTERLINE RADIUS UNLESS CLEARANCE IS NOT AVAILABLE AT WHICH TIME MITERED ELBOWS WITH TURNING VANES SHALL BE UTILIZED. 3. SPIRAL DUCT AND FITTINGS SHALL BE MANUFACTURED FROM G-60 GALVANIZED STEEL MEETING ASTM-A924 AND A653 REQUIREMENTS. a. CONSTRUCTION (1)BRANCH CONNECTIONS SHALL BE MADE WITH 90 CONICAL AND 45 STRAIGHT TAPS AS SHOWN ON THE DRAWINGS. BRANCH CONNECTIONS SHALL BE MADE AS A SEPARATE FITTING. FACTORY OR FIELD INSTALLATION OF TAPS INTO SPIRAL DUCT SHALL NOT BE ALLOWED WITHOUT WRITTEN APPROVAL OF THE ENGINEER. (2)ELBOWS SHALL BE FABRICATED WITH A CENTERLINE RADIUS OF 1.5 TIMES THE DIAMETER. 90 AND 45 ELBOWS IN DIAMETERS 3 INCH ROUND THROUGH 12 INCH ROUND SHALL BE STAMPED OR PLEATED ELBOWS. OTHER ELBOWS SHALL BE OF THE GORED TYPE. CIRCUMFERENTIAL AND LONGITUDINAL SEAMS OF ALL FITTINGS SHALL BE A CONTINUOUS WELD OR SPOT WELDED AND SEALED WITH MASTIC. ALL WELDS SHALL BE PAINTED TO PREVENT CORROSION. (3)FIELD JOINTS FOR ROUND DUCTS UP TO AND INCLUDING 36 INCH DIAMETER AND OVAL DUCTS UP TO AND INCLUDING 41 INCH MAJOR AXIS SHALL BE MADE WITH A 2 INCH SLIP-FIT OR SLIP COUPLING. DIAMETERS 38 INCH ROUND AND LARGER SHALL BE PROVIDED WITH A FLANGED CONNECTION. FLANGED CONNECTIONS MAY ALSO BE USED IN LIEU OF SLIP CONNECTIONS ON SMALLER SIZES. ACCESS DOORS SHALL BE SUPPLIED BY THE DUCT MANUFACTURER AT ALL FIRE AND/OR SMOKE DAMPERS. ALL FLANGES AND ACCESS DOORS SHALL BE FACTORY INSTALLED. SHIPMENTS OF LOOSE FLANGES, ACCESS DOORS, OR TAPS FOR FIELD INSTALLATION INTO SPIRAL DUCT WILL NOT BE ALLOWED. (4)FLAT OVAL DUCT SHALL BE REINFORCED WITH TRAPEZE TYPE REINFORCEMENT, AS RECOMMENDED BY THE MANUFACTURER, TO LIMIT WALL DEFLECTION TO 3/4" AND REINFORCEMENT DEFLECTION TO 1/4". 4. DOUBLE WALL DUCT a. WHERE INDICATED ON THE DRAWINGS, DOUBLE WALL, ACOUSTICALLY INSULATED ROUND DUCT SHALL BE SUPPLIED. DOUBLE WALL DUCT SHALL BE CONSTRUCTED OF AN OUTER SHELL, A 1 INCH THICK LAYER OF FIBERGLASS INSULATION, AND AN INNER METAL LINER. INSULATION SHALL HAVE A THERMAL CONDUCTIVITY "K" FACTOR OF .26 BTU/HR/SQ. FT. / OR LESS. THE INNER METAL LINER FOR ALL SPIRAL AND LONGITUDINAL SEAM DUCT SHALL BE PERFORATED METAL. ALL FITTINGS FROM FAN DISCHARGE TO A POINT WHERE 35 LINEAL FEET OF SPIRAL DUCT HAS BEEN USED SHALL HAVE A PERFORATED METAL LINER. ALL OTHER FITTINGS SHALL HAVE A SOLID METAL LINER WHICH MAY BE ONE EVEN GAUGE LIGHTER THAN THAT SHOWN FOR PERFORATED LINERS. 5. RECTANGULAR ELBOWS SHALL BE FURNISHED WITH DOUBLE THICKNESS TURNING VANES. TURNING VANES SHALL BE FASTENED WITH A DOUBLE ROW OF SCREWS. 6. FLEXIBLE CONNECTIONS AT THE INLET AND OUTLET OF EQUIPMENT. INSTALL FLEXIBLE CONNECTIONS WITH 3" WIDE DOUBLE NEOPRENE COATED FLAME RETARDANT, NFPA 90A APPROVED, FIBERGLASS FLEXIBLE CONNECTION. FLEXIBLE CONNECTION TO HAVE A MINIMUM OF 24 GAGE, 3" WIDE SHEET METAL COLLARS PERMANENTLY ATTACHED TO EACH SIDE. 7. MITERED OFFSETS GREATER THAN 30 DEGREES IN EITHER DIRECTION SHALL NOT BE PERMITTED. 8. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE ANGLE OF DIVERGENCE OF 15DEGREES. 9. RECTANGULAR BALANCING DAMPERS - RUSKIN MD25 SHALL BE SINGLE BLADE UP TO 6" IN HEIGHT AND 36" IN WIDTH, AND RUSKIN MD35 MULTI-BLADE FOR LARGER SIZES. ALL ROUND BALANCING DAMPERS SHALL BE COMMERCIAL GRADE SINGLE BLADE UP TO 16" IN DIAMETER SHALL INCORPORATE LOCKING TYPE INDICATING ADJUSTMENT. BALANCING DAMPERS SHALL BE INSTALLED IN ALL BRANCH DUCTS OFF MAIN AND ON ALL TAPS OFF DUCTS TO DIFFUSERS UNLESS OTHERWISE NOTED ON DRAWINGS. 10. FINAL CONNECTIONS TO DIFFUSERS MAY BE MADE WITH FLEXIBLE AIR DUCTWORK BUT ITS USE IS LIMITED TO STRAIGHT HORIZONTAL OR VERTICAL RUNS. ALL CHANGES OF DIRECTION IN A DUCT SYSTEM (GALVANIZED OR FLEXIBLE) SHALL BE MADE WITH AN APPROPRIATE GALVANIZED ELBOW. MAXIMUM LENGTH OF ANY FLEXIBLE AIR DUCT IS 5'-0". 11. FLEXIBLE AIR DUCTS TO DIFFUSERS SHALL BE ATCO RUBBER PRODUCTS, INC. MODEL UPC #070, INSULATED (R=4.2), U.L. 181 RATED AND CLASS 1 AIR CONNECTOR. MAXIMUM LENGTH OF FLEXIBLE AIR DUCT TO DIFFUSER TO BE 5'-0". 12. FLEXIBLE CONNECTOR DUCTS AT THE INLETS OF THE NEW VAV BOXES SHALL BE ATCO RUBBER PRODUCTS, INC. MODEL UPC #050, UN-INSULATED, U.L. 181 RATED AND CLASS 1 AIR CONNECTOR. MAXIMUM LENGTH OF FLEXIBLE DUCT AT BOX INLET TO BE 3'-0". 13. FIRE DAMPERS SHALL BE RUSKIN AND SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS AND SMACNA REQUIREMENTS FOR A U.L. APPROVED INSTALLATION. FIRE DAMPERS SHALL BE TYPE "B" (BLADES AND FRAME COMPLETELY OUT OF THE AIRSTREAM) FOR ALL WALL ASSEMBLIES AND SHALL BE INSTALLED WITH THE APPROPRIATE WALL SLEEVE AND ANGLES PER UL 555. FIRE DAMPERS SHALL BE INSTALLED IN ALL FIRE RATED WALLS. VERIFY FIRE RATED WALL LOCATIONS AND RATINGS ON THE ARCHITECTURAL DOCUMENTS. FOR ALL FLOOR PENETRATIONS PROVIDE RUSKIN TYPE “LR” FIRE DAMPERS. SEE DETAILS ON DRAWINGS FOR ADDITIONAL INSTALLATION REQUIREMENTS. 14. DOUBLE THICKNESS INSULATED ACCESS DOORS SHALL BE PROVIDED AT ALL FIRE DAMPERS FOR ACCESS TO FUSIBLE LINK. DOOR SHALL BE SIZED TO ALLOW FOR EASY SERVICE AND ACCESSIBILITY. ACCESS DOORS SHALL BE A MINIMUM OF 24" IN THE LONGEST DIMENSION. 15. PROVIDE 3"x3"x1/4" ANGLE FRAMING AROUND THE ROOF OPENINGS FOR THE SUPPLY AND RETURN AIR DUCTWORK. 16. SUPPORT ALL SHEET METAL AND EQUIPMENT FROM ANGLE IRON CONNECTED TO STRUCTURAL STEEL. DO NOT SUSPEND DUCT OR EQUIPMENT FROM METAL DECK OR JOIST BRIDGING. 17. WATER HEATER FLUE AND FITTINGS SHALL BE METALBESTOS MODEL DF, COMMERCIAL/ INDUSTRIAL TYPE "B" GAS VENT. a. TESTED AND LISTED AS “BUILDING HEATING APPLIANCE CHIMNEY” IN ACCORDANCE WITH U.L. STANDARD 103. b. DOUBLE WALL CONSTRUCTION WITH AN OUTER JACKET OF ALUMINIZED COATED STEEL AND AN INNER LINER OF TYPE 430 STAINLESS STEEL SEPARATED BY A 1/2" AIR SPACE. a. c. CONTRACTOR SHALL INSTALL TOPS A MINIMUM OF 2'-0" ABOVE ROOF OR HIGHER IF REQUIRED BY CODE. CONTRACTOR TO PROVIDE ROOF FLASHING CONE AND MISCELLANEOUS EQUIPMENT OR COMPONENTS REQUIRED FOR A COMPLETE INSTALLATION. IV. HVAC EQUIPMENT A.GENERAL 1. INSTALLATION OF ALL EQUIPMENT SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION INFORMATION AND INSTRUCTIONS, REQUIREMENTS AND ANY ADDITIONAL GUIDELINES. CONTRACTOR SHALL PROVIDE ALL ADDITIONAL REQUIRED ACCESSORIES REQUIRED TO COMPLETE THE INSTALLATIONS. 2. HVAC EQUIPMENT SHALL BE "STARTED UP" BY A FACTORY TRAINED AND AUTHORIZED SERVICE TECHNICIAN. 3. ALL FACTORY STARTUP FORMS SHALL BE COMPLETED AND TURNED OVER TO THE OWNER WITH ALL COMPLETED WARRANTY CARDS PRIOR TO FINAL APPROVAL. B. PACKAGE ROOFTOP HEATING AND AIR-CONDITIONING UNITS 1. SEE DRAWING FOR INDIVIDUAL UNIT PERFORMANCE REQUIREMENTS. 2. UNIT SHALL BE OF ONE-PIECE PACKAGED CONSTRUCTION COMPLETELY ASSEMBLED, WIRED AND FACTORY TESTED. 3. WIRING SHALL COMPLY WITH LATEST EDITION OF THE NEC AND SHALL INCORPORATE 3-LEG OVERLOAD PROTECTION FOR THE COMPRESSOR(S). 4. UNIT SHALL BE COMPLETE WITH PRESSURE SAFETY CONTROLS, ANTI-SHORT CYCLE PROTECTION AND CONTROLS (WHEN SPECIFICALLY NOTED ON THE DRAWINGS). VI. CONTROLS A.CONTROL WIRING SHALL BE PLENUM RATED CABLE WITH COLOR CODED 18 AWG WIRES (MINIMUM). B. CONTRACTOR SHALL PROVIDE ALL WIRING BETWEEN THERMOSTAT AND EQUIPMENT (AIR HANDLER, ROOFTOP UNIT, CONDENSING UNIT, ETC.). C. DUCT MOUNTED PHOTOELECTRIC SMOKE DETECTORS SHALL BE WIRED, BY THE ELECTRICAL CONTRACTOR, TO SHUT DOWN UNIT UPON ACTIVATION. D.LOCAL CONTROL PANELS SHALL BE PROVIDED FOR ALL RELAYS, TRANSDUCERS, AND OTHER FIELD INTERFACE DEVICES. 1. PANELS SHALL BE NEMA TYPE SUITABLE FOR EACH APPLICATION. 2. ALL WIRING IN PANEL SHALL BE ROUTED IN WIRING TRAYS. 3. PROVIDE FINAL, AS-BUILT CONTROL DRAWING MOUNTED INSIDE THE PANEL. 4. CONTRACTOR SHALL PROVIDE ALL WIRING AND/OR TUBING BETWEEN CONTROL PANEL(S) AND REMOTE CONTROL DEVICES. E. THERMOSTATS 1. FURNISH AND INSTALL A HONEYWELL 7 DAY PROGRAMMABLE HEATING/COOLING THERMOSTAT AND CLEAR LOCKABLE COVER WITH APPROPRIATE CONTROL WIRING BETWEEN THERMOSTAT AND ROOFTOP UNIT AS REQUIRED TO PROVIDE A COMPLETE OPERATING SYSTEM. WIRING SHALL BE MINIMUM 18 AWG. 2. THERMOSTATS SHALL BE MOUNTED WHERE INDICATED ON THE DOCUMENTS. 3. CONTRACTOR SHALL PROGRAM THERMOSTAT PER THE OWNER'S REQUIREMENTS AND TRAIN OWNER'S PERSONNEL IN THE OPERATION AND PROGRAMMING OF THE THERMOSTAT AND SYSTEM. VII. TESTING AND BALANCING A. TESTING AND BALANCING SHALL NOT BEGIN UNTIL THE SYSTEM HAS BEEN COMPLETED, IS IN FULL WORKING ORDER AND ALL EQUIPMENT START-UP HAS BEEN COMPLETED. ALL HVAC SYSTEMS AND EQUIPMENT SHALL BE PUT INTO FULL OPERATION AND THE OPERATION OF SAME CONTINUED DURING EACH WORKING DAY OF THE TESTING AND BALANCING. B. AN INDEPENDENT "AABC" OR "NEBB" CERTIFIED AIR AND WATER BALANCE CONTRACTOR SHALL TEST AND BALANCE THE SYSTEM AND REPORT RESULTS TO THE ENGINEER AND THE OWNER. 1. ALL WORK SHALL BE DONE UNDER DIRECT SUPERVISION OF THE CERTIFIED BALANCING ENGINEER AND BY QUALIFIED BALANCING TECHNICIANS. 2. METHODS AND FORMS SHALL BE IN ACCORDANCE WITH THE CERTIFICATION AGENCIES RECOMMENDATIONS AND REQUIREMENTS. 3. COMPLY WITH ASHRAE RECOMMENDATIONS PERTAINING TO MEASUREMENTS, INSTRUMENTS, TESTING, ADJUSTING AND BALANCING. 4. ALL QUANTITIES SHALL BE WITHIN 10% OF THE DESIGN VALUES. 5. CONTRACTOR SHALL PROVIDE ANY SHEAVE CHANGES REQUIRED ON THE HVAC UNIT. C. ACCEPTANCE AND CHECK-OUT - CONTRACTOR SHALL PROVIDE QUALIFIED PERSONNEL, AT NO ADDITIONAL COST TO THE OWNER, AS MAY BE REQUIRED BY THE ENGINEER FOR THE PURPOSE OF VERIFYING PROPER OPERATION AND INSTALLATION OF THEIR WORK AT THE TIME OF REQUEST FOR ACCEPTANCE. VIII. LABELING A.SUMMARY 1. SECTION INCLUDES NAMEPLATES, TAGS, STENCILS AND PIPE MARKERS. B. REFERENCES 1. ASME A13.1 (AMERICAN SOCIETY OF MECHANICAL ENGINEERS) - SCHEME FOR THE IDENTIFICATION OF PIPING SYSTEMS. C.NAMEPLATES 1. PRODUCT DESCRIPTION: LAMINATED THREE-LAYER PLASTIC WITH ENGRAVED BLACK LETTERS ON LIGHT CONTRASTING BACKGROUND COLOR. D. TAGS 1. METAL TAGS: a. BRASS WITH STAMPED LETTERS; TAG SIZE MINIMUM 1-1/2 INCHES DIAMETER. 2. INFORMATION TAGS: a. CLEAR PLASTIC WITH PRINTED "DANGER," "CAUTION," OR "WARNING" AND MESSAGE; SIZE 3-1/4 X 5-5/8 INCHES WITH GROMMET AND SELF-LOCKING NYLON TIES. 3. TAG CHART: TYPEWRITTEN LETTER SIZE LIST OF APPLIED TAGS AND LOCATION IN ANODIZED ALUMINUM FRAME. E. STENCILS 1. STENCILS: WITH CLEAN CUT SYMBOLS AND LETTERS OF FOLLOWING SIZE: a. DUCTWORK 1-3/4 INCHES HIGH LETTERS. 2. STENCIL PAINT: SEMI-GLOSS ENAMEL, COLORS AND LETTERING SIZE CONFORMING TO ASME A13.1. F. PIPE MARKERS 1. COLOR AND LETTERING: CONFORM TO ASME A13.1. 2. PLASTIC PIPE MARKERS: a. FACTORY FABRICATED, FLEXIBLE, SEMI-RIGID PLASTIC, PREFORMED TO FIT AROUND PIPE OR PIPE COVERING. LARGER SIZES MAY HAVE MAXIMUM SHEET SIZE WITH SPRING FASTENER. G.LABELS 1. DESCRIPTION: POLYESTER OR LAMINATED MYLAR, SIZE 1.9 X 0.75 INCHES, ADHESIVE BACKED WITH PRINTED IDENTIFICATION. 2. CONTRACTOR TO PROVIDE LABELS AT EACH ENTRANCE DOOR TO CHILLER ROOM - “DO NOT ENTER ROOM WHEN BEACON IS FLASHING” H.PREPARATION 1. DEGREASE AND CLEAN SURFACES TO RECEIVE ADHESIVE FOR IDENTIFICATION MATERIALS. I. INSTALLATION 1. INSTALL IDENTIFYING DEVICES AFTER COMPLETION OF COVERINGS AND PAINTING. 2. INSTALL PLASTIC NAMEPLATES WITH CORROSIVE-RESISTANT MECHANICAL FASTENERS, OR ADHESIVE. 3. INSTALL LABELS WITH SUFFICIENT ADHESIVE TO ENSURE PERMANENT ADHESION AND SEAL WITH CLEAR LACQUER. FOR UNFINISHED CANVAS COVERING, APPLY PAINT PRIMER BEFORE APPLYING LABELS. 4. INSTALL TAGS USING CORROSION RESISTANT CHAIN. NUMBER TAGS CONSECUTIVELY BY LOCATION. 5. IDENTIFY EQUIPMENT WITH PLASTIC NAMEPLATES. 6. TAG AUTOMATIC CONTROLS, INSTRUMENTS, AND RELAYS. KEY TO CONTROL SCHEMATIC. MECHANICAL SPECIFICATIONS DKK NDG ISSUE DATE THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. COPYRIGHT 2020, CURRAN ARCHITECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES F :: 317 . 288 . 0753 O :: 317 . 288 . 0681 INDIANAPOLIS, IN 46216 5719 LAWTON LOOP E. DR. #212 T E S E N G I N E E R I N G Cleveland, OH 44145 25760 First Street P 440 871 2410 F 440 871 7954 tesengineering.com DRAWN BY: ________ CHECKED BY: ________ PROJECT NUMBER: 200079 TIDE CLEANERS 2801 E. 116TH STREET CARMEL, INDIANA 46033 DROP STORE M3.0 09/24/20