HomeMy WebLinkAboutMI.0 MECHANICAL PLANFUTURE FUTURE 102 DRIVE THRU 101 POS MAIN 103 METAL PROGETTI 104 MANAGER AREA 105 BREAK ROOM 106 DELIVERY 107 EXIST. RESTROOM SCALE: 1/4" = 1'-0" 1 M1.0 MECHANICAL PLAN SHEET KEYNOTES 1 TRANSITION LINED SUPPLY DUCT IN RISE TO FULL SIZE OF RTU SUPPLY OPENING. CONNECT TO FULL SIZE OF RTU SUPPLY OPENING WITH FLEX CONNECTION BELOW ROOF DECK. PROVIDE RECTANGULAR ELBOW WITH DOUBLE THICKNESS TURNING VANES IN TRANSITION TO HORIZONTAL. REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION. 2 TRANSITION LINED RETURN DUCT IN RISE TO FULL SIZE OF RTU RETURN OPENING. CONNECT TO FULL SIZE OF RTU RETURN OPENING WITH FLEX CONNECTION BELOW ROOF DECK. PROVIDE RECTANGULAR ELBOW WITH DOUBLE THICKNESS TURNING VANES IN TRANSITION TO HORIZONTAL. REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION. 3 30/20 RA OPENING IN TOP OF RETURN DUCT 4 WALL MOUNTED THERMOSTAT AT 60" AFF. COORDINATE EXACT LOCATION WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. INSULATED BACKING TO BE PROVIDED. 5 SMOKE DETECTOR MOUNTED IN RETURN DUCT. DETECTOR SHALL BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. 6 PROVIDE 24" X 24" INTAKE AIR DUCT BETWEEN ENCLOSED DRYER ROOM AND ROOF MOUNTED GRI. PROVIDE MOTORIZED DAMPER AND DRYER POWER. UPON ANY DRYER BEING ENERGIZED, THE MOTORIZED DAMPER SHALL OPEN. COORDINATE INTERLOCK WIRING CONNECTION WITH DRYER REQUIREMENTS. COVER OPENING WITH 1/2" WIRE MESH SCREEN. 7 GREENHECK MODEL FGI 24x24, 24//24 THROAT SIZE, 4 SQ FT AREA, 0.61" ESP, 600 FPM) GRAVITY INTAKE VENTILATOR. PROVIDE WITH HIGH WIND RATING. 12" ROOF CURB. BIRD SCREEN. 8 PROVIDE WATER HEATER FLUE AND COMBUSTION AIR INTAKE FROM WATER HEATER BELOW. PROVIDE 3" CPVC AND ROUTE/INSTALL PER MANUFACTURER'S RECOMMENDATIONS. TERMINATE THRU ROOF WITH MANUFACTURER'S CONCENTRIC VENT KIT. 9 REMOVE EXISTING RTU AND CURB AND REPLACE WITH NEW CURB. COORDINATE WITH ROOFING CONTRACTOR AND GC FOR FRAMING REVISIONS AND RE-ROOFING/FLASHING AROUND CURB. 10 PROVIDE DRYER VENT THRU ROOF WITH BACKDRAFT DAMPER, AND TERMINATE PER DETAIL ON SHEET M0.1. 11 PROVIDE 16/10 TRANSFER DUCT WITH GRILLE S1 8"Ø 150 S1 8"Ø 150 S3 12/6 170 (TYP. 3) S2 10"Ø 210 (TYP. 4) S1 12"Ø 400 14/12 R2 16/10 850 S1 10"Ø 200 GRI-1 ON ROOF ABOVE 18/12 12/6 12/6 12/6 32/12L R1 22/22 850 3 ETR EF SD 5 GENERAL SHEET NOTES 1. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 2. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS TO ADJACENT SPACES. 3. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS. 4. MECHANICAL SYSTEMS INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE W/ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 5. LIMITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF MECHANICAL WORK WITH ALL DUCTWORK, SPRINKLERS, LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE. 6. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ROOF PENETRATIONS AND ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR. 7. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 8. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH STRUCTURAL ENGINEER. PROVIDE 10' CLEARANCE FROM UNIT OUTSIDE AIR INTAKE TO ANY EXHAUST/VENTS ON ROOF. 9. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS. 10. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC CONTRACTOR, MOUNT PER ADA REQUIREMENTS. 11. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE ANGLE OF DIVERGENCE OF 15 DEGREE. 12. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE ALLOWANCE FOR INTERNAL INSULATION. 13. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED. 14. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED UNLESS NOTED OTHERWISE. 15. PROVIDE ACCESS HATCHES (24"x24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD CEILING. COORDINATE W/ ARCHITECTURAL CEILING PLANS. 16. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH PRE-MANUFACTURED PIPING CURB. 17. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN ROOFTOP UNITS WITH NEW CLEAN FILTERS BEFORE AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT. S4 6"Ø 50 STACKED DRYERS (FURNISHED BY OTHERS), LOCATED WITHIN ARCHITECTURAL ENCLOSURE. 16/16 EA DOWN, W/ (2) 14" EA BRANCH DUCTS & 45° TAKE-OFF TO EACH DRYER EXHAUST CONN. 20/20 EA THRU ROOF 76 DUCT 12" (MINIMUM) DETAIL NOTES 1. HVAC CONTRACTOR TO COORDINATE INSTALLATION WITH LANDLORD APPROVED ROOFING CONTRACTOR FOR PROPER SEQUENCE TO PERMIT FLASHING AND COUNTERFLASHING INSTALLATION. SECURE CURB TO DECK WITH SCREWS, 12" O.C., MINIMUM OF TWO PER SIDE RELIEF/EXHAUST BASE RESILIENT GASKET SEAL BIRD SCREEN ANGLE FRAMING PER STRUCTURAL REQUIREMENTS CONDUIT BY ELECTRICAL CONTRACTOR PRE FABRICATED CURB MOTOR OPERATED DAMPER ALUMINUM OUTSIDE AIR INTAKE VENTILATOR DUCT INSULATION SEE SPECIFICATION METAL ROOF DECK SCALE: NONE 2 M1.0 OUTSIDE AIR INTAKE DETAIL SECURE VENTILATOR TO WOOD NAILING STRIP WITH SCREWS, 12" O.C., MI, OR TWO PER SIDE. ROOF INSULATION 8 PROVIDE ROOF INTAKE PER DETAIL 2 ON M1.0 T RTU-1 RTU-1 9 10 M 24" (MINIMUM) VENT PVC VENT COMBUSTION AIR PIPE CLAMP ATTACHED TO STRUCTURE (FIELD SUPPLIED) METAL DECK ROOF INSULATION DETAIL NOTES 1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. ELBOW (FIELD SUPPLIED) PATE PIPE SEAL COMBUSTION AIR SCALE: NONE 3 M1.0 CONCENTRIC ROOF VENT DEATIL 20/22 L 4 11 S1 10"Ø 200 1 1 20/2016/16 EA W/ 45 BRANCH DUCT TAKE-OFF FROM BOTTOM OF MAIN CAPPED FOR FUTURE CONN. 1 JEdwards 9/14/2020 10:23 AM M1.0 Mechanical Plan.dwg MECHANICAL PLAN DKK NDG KEY PLAN ISSUE DATE THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. COPYRIGHT 2020,CURRAN ARCHITECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NORTH F :: 317 . 288 . 0753 O :: 317 . 288 . 0681 INDIANAPOLIS, IN 46216 5719 LAWTON LOOP E. DR. #212 N T E S E N G I N E E R I N G Cleveland, OH 44145 25760 First Street P 440 871 2410 F 440 871 7954 tesengineering.com DRAWN BY: ________ CHECKED BY: ________ PROJECT NUMBER: 200079 TIDE CLEANERS 2801 E. 116TH STREET CARMEL, INDIANA 46033 DROP STORE OWNER CHANGE 09/11/2020 M1.0 06/04/2020 09/24/20