HomeMy WebLinkAboutMI.0 MECHANICAL PLANFUTURE
FUTURE
102
DRIVE
THRU
101
POS
MAIN
103
METAL
PROGETTI
104
MANAGER
AREA
105
BREAK
ROOM
106
DELIVERY
107
EXIST.
RESTROOM
SCALE: 1/4" = 1'-0"
1
M1.0
MECHANICAL PLAN
SHEET KEYNOTES
1 TRANSITION LINED SUPPLY DUCT IN RISE TO FULL SIZE OF RTU SUPPLY OPENING. CONNECT TO FULL
SIZE OF RTU SUPPLY OPENING WITH FLEX CONNECTION BELOW ROOF DECK. PROVIDE RECTANGULAR
ELBOW WITH DOUBLE THICKNESS TURNING VANES IN TRANSITION TO HORIZONTAL. REFER TO RTU
SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
2 TRANSITION LINED RETURN DUCT IN RISE TO FULL SIZE OF RTU RETURN OPENING. CONNECT TO FULL
SIZE OF RTU RETURN OPENING WITH FLEX CONNECTION BELOW ROOF DECK. PROVIDE RECTANGULAR
ELBOW WITH DOUBLE THICKNESS TURNING VANES IN TRANSITION TO HORIZONTAL. REFER TO RTU
SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
3 30/20 RA OPENING IN TOP OF RETURN DUCT
4 WALL MOUNTED THERMOSTAT AT 60" AFF. COORDINATE EXACT LOCATION WITH FURNITURE LAYOUT AND
ARCHITECTURAL PLANS. INSULATED BACKING TO BE PROVIDED.
5 SMOKE DETECTOR MOUNTED IN RETURN DUCT. DETECTOR SHALL BE PROVIDED AND WIRED BY
ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR.
6 PROVIDE 24" X 24" INTAKE AIR DUCT BETWEEN ENCLOSED DRYER ROOM AND ROOF MOUNTED GRI.
PROVIDE MOTORIZED DAMPER AND DRYER POWER. UPON ANY DRYER BEING ENERGIZED, THE
MOTORIZED DAMPER SHALL OPEN. COORDINATE INTERLOCK WIRING CONNECTION WITH DRYER
REQUIREMENTS. COVER OPENING WITH 1/2" WIRE MESH SCREEN.
7 GREENHECK MODEL FGI 24x24, 24//24 THROAT SIZE, 4 SQ FT AREA, 0.61" ESP, 600 FPM) GRAVITY INTAKE
VENTILATOR. PROVIDE WITH HIGH WIND RATING. 12" ROOF CURB. BIRD SCREEN.
8 PROVIDE WATER HEATER FLUE AND COMBUSTION AIR INTAKE FROM WATER HEATER BELOW. PROVIDE
3" CPVC AND ROUTE/INSTALL PER MANUFACTURER'S RECOMMENDATIONS. TERMINATE THRU ROOF WITH
MANUFACTURER'S CONCENTRIC VENT KIT.
9 REMOVE EXISTING RTU AND CURB AND REPLACE WITH NEW CURB. COORDINATE WITH ROOFING
CONTRACTOR AND GC FOR FRAMING REVISIONS AND RE-ROOFING/FLASHING AROUND CURB.
10 PROVIDE DRYER VENT THRU ROOF WITH BACKDRAFT DAMPER, AND TERMINATE PER DETAIL ON SHEET
M0.1.
11 PROVIDE 16/10 TRANSFER DUCT WITH GRILLE
S1 8"Ø
150
S1 8"Ø
150
S3 12/6
170
(TYP. 3)
S2 10"Ø
210
(TYP. 4)
S1 12"Ø
400
14/12
R2 16/10
850
S1 10"Ø
200
GRI-1 ON
ROOF ABOVE
18/12
12/6
12/6
12/6
32/12L
R1 22/22
850
3
ETR EF
SD 5
GENERAL SHEET NOTES
1. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
2. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS
TO ADJACENT SPACES.
3. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE
AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE
REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN
CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS.
4. MECHANICAL SYSTEMS INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS
DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH
RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE W/ARCHITECTURAL PLANS AND GENERAL
CONTRACTOR.
5. LIMITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF MECHANICAL
WORK WITH ALL DUCTWORK, SPRINKLERS, LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES.
CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE.
6. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD APPROVED
ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ROOF PENETRATIONS AND
ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR.
7. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
STEEL WHICH EXISTS ABOVE THE SPACE.
8. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH STRUCTURAL ENGINEER. PROVIDE 10' CLEARANCE
FROM UNIT OUTSIDE AIR INTAKE TO ANY EXHAUST/VENTS ON ROOF.
9. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND
EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS.
10. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND
ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC CONTRACTOR,
MOUNT PER ADA REQUIREMENTS.
11. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE
ANGLE OF DIVERGENCE OF 15 DEGREE.
12. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE ALLOWANCE
FOR INTERNAL INSULATION.
13. ALL SUPPLY AIR DUCTWORK SHALL BE EXTERNALLY INSULATED.
14. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED
UNLESS NOTED OTHERWISE.
15. PROVIDE ACCESS HATCHES (24"x24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD
CEILING. COORDINATE W/ ARCHITECTURAL CEILING PLANS.
16. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL
WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH
PRE-MANUFACTURED PIPING CURB.
17. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN ROOFTOP UNITS WITH NEW CLEAN FILTERS BEFORE
AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT.
S4 6"Ø
50
STACKED DRYERS
(FURNISHED BY
OTHERS),
LOCATED WITHIN
ARCHITECTURAL
ENCLOSURE.
16/16 EA DOWN, W/ (2)
14" EA BRANCH DUCTS &
45° TAKE-OFF TO EACH
DRYER EXHAUST CONN.
20/20 EA
THRU ROOF
76
DUCT
12"
(MINIMUM)
DETAIL NOTES
1. HVAC CONTRACTOR TO COORDINATE INSTALLATION WITH LANDLORD APPROVED ROOFING CONTRACTOR
FOR PROPER SEQUENCE TO PERMIT FLASHING AND COUNTERFLASHING INSTALLATION.
SECURE CURB TO DECK
WITH SCREWS, 12" O.C.,
MINIMUM OF TWO PER SIDE
RELIEF/EXHAUST BASE
RESILIENT GASKET SEAL
BIRD SCREEN
ANGLE FRAMING PER
STRUCTURAL REQUIREMENTS
CONDUIT BY ELECTRICAL
CONTRACTOR
PRE FABRICATED CURB
MOTOR OPERATED
DAMPER
ALUMINUM OUTSIDE
AIR INTAKE VENTILATOR
DUCT INSULATION
SEE SPECIFICATION
METAL ROOF DECK
SCALE: NONE
2
M1.0
OUTSIDE AIR INTAKE DETAIL
SECURE VENTILATOR TO WOOD NAILING
STRIP WITH SCREWS, 12" O.C., MI, OR
TWO PER SIDE.
ROOF INSULATION
8
PROVIDE ROOF
INTAKE PER
DETAIL 2 ON M1.0
T
RTU-1
RTU-1 9
10
M
24"
(MINIMUM)
VENT
PVC VENT COMBUSTION AIR
PIPE CLAMP ATTACHED TO
STRUCTURE (FIELD SUPPLIED)
METAL DECK
ROOF INSULATION
DETAIL NOTES
1. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
ELBOW (FIELD SUPPLIED)
PATE PIPE SEAL
COMBUSTION AIR
SCALE: NONE
3
M1.0
CONCENTRIC ROOF VENT DEATIL
20/22 L
4
11
S1 10"Ø
200
1
1
20/2016/16 EA W/ 45
BRANCH DUCT
TAKE-OFF FROM
BOTTOM OF MAIN
CAPPED FOR
FUTURE CONN.
1
JEdwards 9/14/2020 10:23 AM M1.0 Mechanical Plan.dwg
MECHANICAL PLAN
DKK NDG
KEY PLAN
ISSUE DATE
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
COPYRIGHT 2020,CURRAN ARCHITECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NORTH
F :: 317 . 288 . 0753
O :: 317 . 288 . 0681
INDIANAPOLIS, IN 46216
5719 LAWTON LOOP E. DR. #212
N
T E S
E N G I N E E R I N G
Cleveland, OH 44145
25760 First Street
P 440 871 2410
F 440 871 7954
tesengineering.com
DRAWN BY: ________ CHECKED BY: ________
PROJECT NUMBER: 200079
TIDE CLEANERS
2801 E. 116TH STREET
CARMEL, INDIANA 46033
DROP STORE
OWNER CHANGE 09/11/2020
M1.0
06/04/2020
09/24/20