HomeMy WebLinkAboutPI.0 PLUMBING PLANSCA CWHWCWCW
HW
V
VSANEX SAN EX SAN
2 01
D
C8'-8"+/-
FUTURE
FUTURE
B
102
DRIVE
THRU
101
POS
MAIN
103
METAL
PROGETTI
104
MANAGER
AREA
105
BREAK
ROOM
106
DELIVERY107
EXIST.
RESTROOM
SCALE: 1/4" = 1'-0"
2
P1.0
PLUMBING DOMESTIC PLAN
SHEET KEYNOTES
1 EXTEND AND CONNECT 3" SANITARY PIPING TO EXISTING SANITARY PIPING. PLUMBING CONTRACTOR TO
VERIFY EXACT LOCATION, SIZE, INVERT, AND DIRECTION OF FLOW PRIOR TO STARTING WORK.
2 EXTEND AND CONNECT 2" SANITARY PIPING TO EXISTING SANITARY PIPING. PLUMBING CONTRACTOR TO
VERIFY EXACT LOCATION, SIZE, INVERT, AND DIRECTION OF FLOW PRIOR TO STARTING WORK.
3 EXTEND AND CONNECT 3" VENT PIPING TO EXISTING VENT PIPING. PLUMBING CONTRACTOR TO VERIFY
EXACT LOCATION AND SIZE PRIOR TO STARTING WORK.
4 2" CW FROM EXISTING WATER MAIN NEARBY. PLUMBING CONTRACTOR TO VERIFY EXACT LOCATION AND
SIZE PRIOR TO STARTING WORK.
5 2" CW AND HW DOWN TO F34.
6 3/4" CW AND HW DOWN IN WALL TO F32
7 1/2" CW AND HW DOWN IN WALL TO SK-1.
8 1-1/2" CW AND HW DOWN IN WALL TO WASHING MACHINE. PROVIDE WITH AMERICAN GRANDY FLOW
CONTROL VALVE GP15. VERIFY FINAL LOCATION PRIOR TO INSTALL WITH TDC.
9 1/2" COMPRESSED AIR DOWN TO EQ-1B
10 1/2" COMPRESSED AIR TO STORAGE CONVEYOR. VERIFY FINAL LOCATION PRIOR TO INSTALL WITH TIDE
DRY CLEANING.
11 EXTEND AND CONNECT 4" SANITARY PIPING TO EXISTING SANITARY PIPING. PLUMBING CONTRACTOR TO
VERIFY EXACT LOCATION, SIZE, INVERT, AND DIRECTION OF FLOW PRIOR TO STARTING WORK.
12 CONTRACTOR TO COORDINATE NEW PIPING WITH EXISTING PIPING AND FIXTURE SUPPORTS.
13 EXTEND T&P RELIEF TO OVER TOP OF MOP BASIN AND TERMINATE WITH 2" AIR GAP ABOVE FLOOD RIM
LEVEL OF FIXTURE
14 PLUMBING CONTRACTOR TO PROVIDE ROUGH IN CONNECTIONS WITH SHUT OFF VALVES AND CAP FOR
FUTURE CONNECTION.
2 01
D
C8'-8"+/-FUTURE
FUTURE
B
102
DRIVE
THRU
101
POS
MAIN
103
METAL
PROGETTI
104
MANAGER
AREA
105
BREAK
ROOM
106
DELIVERY107
EXIST.
RESTROOM
SCALE: 1/4" = 1'-0"
1
P1.0
PLUMBING SANITARY PLAN
GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD
WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY.
CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR
INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS.
2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
4. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR
DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND
QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS
WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS.
5. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
6 PROVIDE STOP VALVES AT EVERY FIXTURE ON BOTH HOT AND COLD WATER SUPPLY LINES. VALVES,
ESCUTCHEONS, FITTINGS, ETC. MUST BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS
TO BE USED.
7. ALL SANITARY PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 1% SLOPE EXCEPT FOR 2" LINES
WHICH SHALL BE PITCHED AT 2% SLOPE.
8. ALL OVERHEAD PIPING IS TO BE ROUTED TIGHT TO BUILDING STRUCTURE.
9. PIPING IS NOT PERMITTED IN DEMISING WALLS.
10. ALL EXPOSED, EXTERIOR PIPING SHALL BE PAINTED WITH RUST INHIBITIVE PRIMER, COLOR CODED
FINISH, AND IDENTIFICATION LABELS.
11. VERIFY NATURAL GAS AVAILABILITY AND CAPACITY. COORDINATE PRESSURE, SERVICE CONNECTION,
AND METER INSTALLATION WITH THE LANDLORD AND LOCAL UTILITY COMPANY.
12. PROVIDE GAS PIPE SUPPORTS ON ROOF. PROVIDE 10'-0" ON CENTER AND AT ALL CHANGES OF
DIRECTION.
13. DO NOT ROUTE ANY WATER CONVEYING PIPING OVER ELECTRICAL EQUIPMENT.
14. ALL ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH BOTTOM CLEANOUT PLUGS.
15. INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING SERVING HANDICAPPED LAVATORIES.
16. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN LEAK PROOF AND FREE FROM DEFECTS PRIOR
TO CONCEALMENT.
SK-1
F32
F34
TD-1
1
11
2
3
EX CO
SAN
4
5
6
7
8
8
9
10
SK-1
F34
F32
2" O/H
1/2" O/H
2" O/H
3/4" O/H
2" O/H
1-1/2" O/H
1-1/2" O/H
1/2" O/H
12
EQ 1A
1313
TMV-1
14
3/4" O/H
PLUMBING PLANS
MMD DLJ
KEY PLAN
ISSUE DATE
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
COPYRIGHT 2020, CURRAN ARCHITECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NORTH
F :: 317 . 288 . 0753
O :: 317 . 288 . 0681
INDIANAPOLIS, IN 46216
5719 LAWTON LOOP E. DR. #212
N
T E S
E N G I N E E R I N G
Cleveland, OH 44145
25760 First Street
P 440 871 2410
F 440 871 7954
tesengineering.com
DRAWN BY: ________ CHECKED BY: ________
PROJECT NUMBER: 200079
TIDE CLEANERS
2801 E. 116TH STREET
CARMEL, INDIANA 46033
DROP STORE
P1.0
06/04/2020
09/24/20