Loading...
HomeMy WebLinkAboutE101NO. REVISIONS DATE DESCRIPTION ISSUE REVIEW BIDDING PERMIT CONSTRUCTION HAMILTON COUNTYMILLER AUTO CAREB. Dodd PROJECT NUMBER SCALE DRWN BY DATE AS NOTED 1609 5/1/2020 SHEET TITLE Engineering & Contractors, Inc Design & Build Electrical NEW CONSTRUCTION FOR:985 N. RANGELINE ROADCARMEL, INDIANA 46032CLAY TOWNSHIP5/1/2020 E101 ELECTRICAL SCHEDULES & DETAILS ELECTRICAL SYMBOL SCHEDULE ELECTRICAL SPECIFICATION: GENERAL REQUIREMENTS THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS, FEEDER CONNECTION POINTS, AND EQUIPMENT REQUIREMENTS FOR EQUIPMENT PROVIDED BY OTHERS BY VISITING THE JOB SITE AND EXAMINING THE INSTALLATION DOCUMENTS, AND IS TO REPORT ANY DISCREPANCIES TO THE ENGINEER PRIOR TO BIDDING. ELECTRICAL CONTRACTOR SHALL VERIFY FINAL EQUIPMENT REQUIREMENTS AND LOCATION PRIOR TO ROUGH-IN. ANY MATERIAL OR LABOR WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AS DESCRIBED IN THESE DRAWINGS SHALL BE PROVIDED AS PART OF THIS CONTRACT. ALL EQUIPMENT DEVICES AND ELECTRICAL SUPPLIES SHALL BE LISTED IN A MANNER RECOGNIZED BY THE NATIONAL ELECTRIC CODE WHERE APPLICABLE. MANUFACTURER AND NEC REQUIRED CLEARANCES SHALL BE MAINTAINED AROUND EQUIPMENT. THESE CLEARANCES SHALL BE CONFIRMED BEFORE INSTALLATION. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH ALL LOCAL CODES, OBTAINING NECESSARY PERMITS, PAYING REQUIRED FEES, AND MAKING ALL ARRANGEMENTS FOR NECESSARY INSPECTIONS, TESTS, ETC. ALL WORK SHALL COMPLY WITH OSHA STANDARDS AS WELL AS COMPLY WITH LOCAL REGULATIONS. COORDINATE INSTALLING OF ELECTRICAL MATERIALS WITH GENERAL CONSTRUCTION WORK. PROVIDE FIRESTOPPING TO CABLE AND RACEWAY PENETRATIONS OF FIRE-RATED FLOORS AND WALLS TO MAINTAIN FIRE RATING. ALL CONDUIT PENETRATIONS SHALL BE SEALED WITH APPROPRIATE CONDUIT SEALING MATERIAL. INSTALL EQUIPMENT IDENTIFICATION LABELS ON EACH UNIT OF EQUIPMENT IN POWER, LIGHTING, COMMUNICATION, SIGNAL, AND ALARM SYSTEMS, INCLUDING THE MAIN UNIT OF EACH SYSTEM. USING ½” HIGH WHITE LETTERS ON BLACK ENGRAVED PLASTIC LAMINATE, PROVIDE A 1 ½” HIGH LABEL FOR ONE LINE OF TEXT OR A 2” HIGH LABEL FOR TWO LINES. PROVIDE CIRCUIT IDENTIFICATION ON EACH POWER OR COMMUNICATION CIRCUIT IN EACH VAULT, PULL, AND JUNCTION BOX AND SWITCHBOARD OR PANEL. PROVIDE CIRCUIT IDENTIFICATION ON BACK OF EACH DEVICE PLATE OR ON NON-VISIBLE (COVERED BY PLATE) PORTION OF DEVICE (SWITCH OR RECEPTACLE) WITH PERMANENT INK INSTALL ENGRAVED PLASTIC-LAMINATED INSTRUCTION SIGNS WITH APPROVED LEGEND WHERE INSTRUCTIONS ARE NEEDED FOR SYSTEM OR EQUIPMENT OPERATION. ANY DEVIATION FROM SPECIFIED PRODUCT MANUFACTURER MUST BE APPROVED IN WRITING BY THE ENGINEER PRIOR TO BIDDING. ALL EQUIPMENT IN OUTDOOR LOCATIONS SHALL BE WEATHERPROOF. ALL WORK SHALL BE DONE IN A NEAT AND PROFESSIONAL MANNER. ANY UNSATISFACTORY WORKMANSHIP SHALL BE REMOVED AND REPLACED BY AND AT THE EXPENSE OF THE ELECTRICAL CONTRACTOR. INSPECT FINISHED WORK. CUT, PATCH, REFINISH, CLEAN AND TOUCH-UP AS NEEDED. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE TESTED AND DEFECTS CORRECTED. THE CONTRACTOR SHALL GUARANTEE FOR ONE YEAR THAT ALL WORK IS FREE OF DEFECTS AND SHALL CORRECT ANY DEFECTIVE WORK FOUND DURING THAT PERIOD, AS WELL AS ANY DAMAGE RESULTING FROM SAID DEFECT. SUBMITTALS PROVIDE MANUFACTURER'S LITERATURE ON ALL ELECTRICAL EQUIPMENT. THE FOLLOWING SHALL BE INCLUDED WHERE APPLICABLE: 1.STANDARD SCHEMATIC DRAWINGS, MODIFIED FOR SPECIFIC MODEL AND ACCESSORIES PROVIDED. 2.CUT SHEETS IDENTIFYING PERTINENT MATERIALS AND PRODUCTS REQUIRED. 3.EQUIPMENT DIMENSIONS, SHIPPING SPLITS, AND CONSTRUCTION CLEARANCES. 4.MAINTENANCE REQUIREMENTS. 5.PERFORMANCE SPECIFICATIONS. 6.WIRING AND CONTROL DIAGRAMS. 7.SAFETY INSTRUCTIONS. 8.THE FULL MANUFACTURER'S MODEL NUMBER SHALL BE CLEARLY SHOWN ON THE TOP OF THE FIRST AND THE BOTTOM OF THE LAST PAGE. 9.IDENTIFICATION OF COLOR OR FINISHES. 10.THE CONTRACTOR'S STAMP, SIGNATURE, AND CONTACT DATA SHALL BE AFFIXED TO EACH SUBMITTAL. 11.WARRANTY INFORMATION AND SERIAL NUMBER. AN OPERATIONS MANUAL CONTAINING EQUIPMENT DRAWINGS AND RELATED INFORMATION, INCLUDING THE DATA LISTED ABOVE, SHALL BE SUBMITTED TO THE OWNER AFTER PROJECT COMPLETION. RECORD DRAWINGS, OR “AS BUILTS”, SHALL BE PROVIDED WITH THE OPERATIONS MANUAL. THE MANUAL SHALL BE LABELED WITH THE PROJECT NAME AND LOCATION AND SHALL CONTAIN THE NAMES AND ADDRESSES OF THE OWNER, ENGINEER, AND CONTRACTOR. CONDUITS AND WIRING ALL CONDUIT SHALL BE 1/2” MINIMUM RIGID GALVANIZED STEEL OR ELECTRIC METALLIC TUBING. RIGID CONDUIT OR SCHEDULE 40 PVC SHALL BE USED UNDER SLAB. FLEXIBLE STEEL CONDUIT SHALL BE USED FOR CONNECTIONS TO LIGHTING FIXTURES AND WHERE SHORT CONNECTIONS MAKE RIGID CONDUIT IMPRACTICAL. GALVANIZED STEEL CONDUIT SHALL USE THREADED FITTINGS. EMT FITTINGS SHALL BE COMPRESSION TYPE. ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. SUPPORT CONDUIT AT NOT MORE THAN 5' CENTERS. HANGERS AND SUPPORTS LISTED FOR THE PURPOSE SHALL BE USED TO SUPPORT ELECTRICAL DEVICES. THESE SHALL BE FASTENED TO THE BUILDING STEEL, CONCRETE OR MASONRY. HANGERS SHALL NOT INTERFERE WITH ACCESS TO EQUIPMENT. ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL COMPLY WITH THE NEC. ALL CONNECTIONS TO EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE LIQUID TIGHT FLEXIBLE METAL CONDUIT, NOT LESS THAN 12” IN LENGTH, NOR GREATER THAN 36” IN LENGTH. CONDUCTORS SHALL BE COPPER THWN #12 MINIMUM CONDUCTORS FOR FEEDERS OF 100 AMPS OR GREATER MAY BE ALUMINUM. THHN MAY BE USED ABOVE GRADE IN INTERIOR LOCATIONS ONLY. HVAC CONTROL WIRING FURNISHED AND INSTALLED BY DIVISION 15. WIRE OUTLETS WITH AT LEAST 6 INCHES OF SLACK. OUTLET BOXES SHALL BE A MINIMUM OF 4” x 2 1/8” x 2 1/8” FOR SINGLE GANG AND 4” x 4” x 2 1/8” FOR TWO GANG. ALL CIRCUITS SHALL HAVE AN INSULATED EQUIPMENT GROUND CONDUCTOR, IN ADDITION TO GROUND CONTINUITY OF THE CONDUIT SYSTEM. RECEPTACLES SHALL BE INDUSTRIAL SPECIFICATION GRADE RATED 20A UNLESS OTHERWISE INDICATED. JUNCTION AND PULL BOXES SHALL BE RIGIDLY SUPPORTED FROM THE BUILDING STRUCTURE, SUPPORTED INDEPENDENTLY FROM THE CONDUIT SYSTEM, AND SHALL BE LABELED WITH CIRCUIT NUMBER AND SYSTEM TYPE ON COVER. ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. EMPTY CONDUITS SHALL BE TERMINATED WITH A SUITABLE CAP. ALL CONDUIT CONNECTIONS TO OTHER CONDUITS, BOXES AND EQUIPMENT SHALL BE PROVIDED WITH APPROPRIATE FITTINGS. PROVIDE PULL WIRE IN ALL CONDUITS. PANELBOARDS AND CIRCUIT BREAKERS EXISTING - PROVIDE NEW CIRCUIT BREAKER BY SAME MANUFACTURER AS EXISTING PANEL. FUSES AND DISCONNECTS DISCONNECTS SHALL BE EXTERNALLY OPERATED, HEAVY-DUTY METAL ENCLOSED, AND SIZED TO PROTECT THE DESIGNATED LOAD. EACH FUSED DISCONNECT SHALL BE PROVIDED WITH A COMPLETE SET OF UL CLASS RK5 DUAL ELEMENT FUSES FOR MOTOR LOADS AND UL CLASS RK1 FOR RESISTIVE LOADS. PROVIDE SPARE FUSES OF EACH SIZE AND TYPE. MOTORS ALL MOTORS SHALL BE PROVIDED WITH INTEGRAL OVERLOAD PROTECTION. GROUNDING PROVIDE A COMPLETE GROUNDING CONDUCTOR SYSTEM AS REQUIRED BY THE NEC AND LOCAL CODES. ALL CONDUIT SHALL BE GROUNDED WITH A GREEN GROUNDING CONDUCTOR. PROVIDE BONDING JUMPERS WITH PLUMBING SYSTEM, COORDINATING WITH PLUMBING CONTRACTOR. ALL DEVICES SHALL BE BONDED TO THE CONDUIT SYSTEM. ALL JUNCTION BOXES, OUTLET BOXES, AND PULL BOXES SHALL BE BONDED TO THE CONDUIT SYSTEM. OUTLET BOXES SHALL BE BONDED WITH A BONDING JUMPER. ALL ENCLOSURES AND NON-CURRENT-CARRYING METAL PARTS ARE TO BE GROUNDED. CONDUITS ARE TO BE ELECTRICALLY CONTINUOUS. LOCK NUTS MUST CUT THROUGH ENAMELED OR PAINTED SURFACES. GROUND WIRES SHALL BE PROTECTED FROM MECHANICAL INJURY. LIGHTING LIGHTING SHALL BE EXACT MODEL NUMBERS AS SHOWN ON THE SCHEDULE UNLESS A COMPLETE ALTERNATE PACKAGE IS SUBMITTED AND APPROVED BEFORE BIDDING. PROVIDE AUXILIARY SUPPORTS AS REQUIRED BY LOCAL CODES. COMPLY WITH LOCAL SEISMIC REQUIREMENTS. PROVIDE FIRE RATED DRYWALL BOXES IN FIRE RATED CEILINGS. FIELD COORDINATE FIXTURES WITH OTHER SYSTEMS TO AVOID CONFLICT. COMPLY WITH LOCAL ENERGY CODES. PROVIDE SPECIAL HOUSINGS WHERE REQUIRED TO COMPLY WITH APPLICABLE CODE REQUIREMENTS. FIRE ALARM EXISTING SPRINKLER SUPERVISION SYSTEM SHALL REMAIN.