07 9000 - JOINT SEALERS
A. SECTION INCLUDES: SEALANTS AND JOINT BACKING, PRE -COMPRESSED FOAM SEALERS, AND
HOLLOW GASKETS.
B. SUBMITTALS: PROVIDE PRODUCT DATA INDICATING SEALANT CHEMICAL CHARACTERISTICS AND
COLOR CHARTS OF MANUFACTURER'S STANDARD SELECTIONS.
C. FIELD CONDITIONS: MAINTAIN TEMPERATURE AND HUMIDITY RECOMMENDED BY THE SEALANT
MANUFACTURER DURING AND AFTER INSTALLATION.
D. WARRANTY: CORRECT DEFECTIVE WORK WITHIN 1 YEAR PERIOD AFTER DATE OF SUBSTANTIAL
COMPLETION. INCLUDE COVERAGE FOR INSTALLED SEALANTS AND ACCESSORIES WHICH FAIL TO
ACHIEVE AIRTIGHT SEAL, EXHIBIT LOSS OF ADHESION, OR DO NOT CURE.
E. MATERIALS: PROVIDE SEALANTS, FILLERS AND OTHER RELATED MATERIALS THAT ARE COMPATIBLE
WITH ONE ANOTHER AND WITH JOINT SUBSTRATES UNDER CONDITIONS OF SERVICE AND
APPLICATION, AS DEMONSTRATED BY SEALANT MANUFACTURER BASED ON TESTING AND FIELD
EXPERIENCE.
1. SEALANT BACKING: PROVIDE SEALANT BACKINGS OF MATERIAL AND TYPE WHICH ARE
NON -STAINING AND NON -ABSORBENT; CLOSED CELL; ARE COMPATIBLE WITH JOINT
SUBSTRATES, SEALANTS, PRIMERS AND OTHER JOINT FILLERS.
2. PLASTIC FOAM JOINT FILLERS: PREFORMED, COMPRESSIBLE, RESILIENT, NON -WAXING,
NON -EXTRUDING STRIPS OF FLEXIBLE, NON -GASSING PLASTIC FOAM; NONABSORBENT TO
WATER AND GAS; AND OF SIZE, SHAPE AND DENSITY TO CONTROL SEALANT DEPTH.
3. ELASTOMERIC TUBING JOINT FILLERS: NEOPRENE, BUTYL, EPDM, OR SILICONE TUBING
COMPLYING WITH ASTM D 1056, NONABSORBENT TO WATER AND GAS, CAPABLE OF REMAINING
RESILIENT AT TEMPERATURES DOWN TO -26 DEGREES F.
F. SEALANT SCHEDULE:
1. TYPE 1 - GENERAL PURPOSE EXTERIOR SEALANT: POLYURETHANE; ASTM C 920, GRADE NS,
CLASS 25, USES M, G, AND A; SINGLE COMPONENT. STANDARD COLORS AS SELECTED BY
ARCHITECT.
a. APPLICATION LOCATIONS:
1) JOINTS BETWEEN EXTERIOR METAL AND MASONRY, WINDOWS, FLASHING, COPING,
AND DIFFERING MATERIALS AT THE EXTERIOR.
2) INTERIOR EXPANSION AND CONTROL JOINTS.
3) SETTING BEDS FOR EXTERIOR THRESHOLDS, EXTERIOR JOINTS BETWEEN STEEL
LINTELS AND SUPPORTED MASONRY.
4) EXPOSED JOINTS BETWEEN MASONRY AND OVERHEAD CONSTRUCTION OR
ADJOINING STEEL FRAMING.
5) INTERIOR JOINT OF CONCRETE FLOOR SLAB AND EXTERIOR WALL.
6) EXPOSED CONCRETE FLOOR SLAB AND MASONRY EXPANSION AND CONTROL
JOINTS.
b. APPROVED PRODUCTS: TREMCO; DYMONIC FC, PECORA CORPORATION; DYNATROL I -XL,
SIKA CORPORATION; SIKAFLEX; 2C NS EZ, OR APPROVED EQUAL.
2. TYPE 2A - EXTERIOR EXPANSION JOINT SEALER: ASTM D 2628 MULTI -COMPONENT
POLYEPDXIDE URETHANE SEALANT, FS TT-S-00227E, TYPE II, CLASS A, 50% EXTENSION AND
COMPRESSION. STANDARD COLOR AS SELECTED BY ARCHITECT.
a. APPLICATION LOCATIONS: EXTERIOR WALL EXPANSION JOINTS AND COPING JOINTS.
b. APPROVED PRODUCTS: PECORA CORPORATION; DYNATROL II, TREMCO; DYMERIC 240 OR
APPROVED EQUAL.
3. TYPE 26 - EXTERIOR EXPANSION JOINT SEALER: ASTM C-920, SINGLE COMPONENT, LOW
MODULUS POLYURETHANE SEALANT, NS, CLASS 100/50. STANDARD COLOR AS SELECTED BY
ARCHITECT.
a. APPLICATION LOCATIONS: USE FOR EXTERIOR WALL EXPANSION JOINTS, EIFS JOINTS,
COPING JOINTS.
b. APPROVED PRODUCTS: SIKA CORPORATION, SIKAFLEX 15LM OR APPROVED EQUAL.
4. TYPE 2C - EXTERIOR EXPANSION JOINT SEALER: ASTM C-920, SELF LEVELING, SINGLE
COMPONENT OR MULTI -COMPONENT. STANDARD COLOR AS SELECTED BY ARCHITECT.
a. APPLICATION LOCATIONS: USE FOR EXTERIOR HORIZONTAL JOINTS.
b. APPROVED PRODUCTS: SIKA, SIKAFLEX SIKAFLEX; 1A, 1 C SL OR APPROVED EQUAL.
5. TYPE 3 - EXTERIOR METAL LAP JOINT SEALANT: BUTYL OR POLYISOBUTYLENE, NONDRYING,
NON -SKINNING, NON -CURING. STANDARD COLOR AS SELECTED BY ARCHITECT.
a. APPLICATION LOCATIONS: CONCEALED SEALANT BEAD IN SHEET METAL WORK, OR SIDING
OVERLAPS.
b. APPROVED PRODUCTS: TREMCO; BUTYL SEALANT OR APPROVED EQUAL.
6. TYPE 4 - GENERAL PURPOSE INTERIOR SEALANT: ACRYLIC EMULSION LATEX; ASTM C 834, TYPE
OP GRADE NF SINGLE COMPONENT PAINTABLE. STANDARD COLORS MATCHING FINISHED
SURFACES AS SELECTED BY THE ARCHITECT.
a. APPLICATION LOCATIONS: INTERIOR WALL AND CEILING CONTROL JOINTS, JOINTS
BETWEEN DOOR AND WINDOW FRAMES AND WALL SURFACES, AND OTHER INTERIOR
JOINTS FOR WHICH NO OTHER TYPE OF SEALANT IS INDICATED.
b. APPROVED PRODUCTS: TREMCO; TREMFLEX 834, PECORA; AC-20+, OR APPROVED EQUAL.
7. TYPE 5 - BATHTUB/TILE SEALANT: WHITE SILICONE; ASTM C 920, USES I, M AND A; SINGLE
COMPONENT, MILDEW RESISTANT.
a. APPLICATION LOCATIONS: JOINTS BETWEEN PLUMBING FIXTURES AND FLOOR AND WALL
SURFACES, KITCHEN AND BATH COUNTERTOPS AND WALL SURFACES, IN AND AROUND
WET AREA COUNTERTOPS OR LAVATORY VANITIES, AND AROUND TOILET ACCESSORIES.
b. APPROVED PRODUCTS: DOW CORNING; 786 SILICONE MILDEW RESISTANT SEALANT,
PECORA CORPORATION; 898, BASF CONSTRUCTION CHEMICALS -BUILDING SYSTEMS;
OMNIPLUS OR APPROVED EQUAL.
8. TYPE 6 - ACRYLIC SEALANT: ASTM C 920, GRADE NS, CLASS 12-1/2, USES NT, M, A, 0; SINGLE
COMPONENT, SOLVENT CURING, NON -STAINING, NON -BLEEDING, NON -SAGGING. STANDARD
COLORS AS SELECTED BY ARCHITECT. MOVEMENT CAPABILITY OF PLUS AND MINUS 12-1/2
PERCENT WITH A SERVICE TEMPERATURE RANGE: -13 TO 180 DEGREES F, AND A SHORE A
HARDNESS RANGE OF 25 TO 50.
a. APPROVED PRODUCTS: TREMCO; TREMFLEX 834, PECORA; AC-20+, OR APPROVED EQUAL.
9. TYPE 7 - SILICONE SEALANT: ASTM C 920, GRADE NS, CLASS 25, USES NT, A, G, M, 0; SINGLE
COMPONENT, SOLVENT CURING, NON -SAGGING, NON -STAINING, FUNGUS RESISTANT,
NON -BLEEDING. STANDARD COLORS MATCHING FINISHED SURFACES. WITH A MOVEMENT
CAPABILITY OF PLUS AND MINUS 25 PERCENT, A SERVICE TEMPERATURE RANGE OF -65 TO 180
DEGREES F, AND A SHORE A HARDNESS RANGE: 15 TO 35.
a. APPROVED PRODUCTS: PECORA; 846 NST OR APPROVED EQUAL.
G. ACCESSORIES:
1. PRIMER: NON -STAINING TYPE, RECOMMENDED BY SEALANT MANUFACTURER TO SUIT
APPLICATION.
2. JOINT CLEANER: NON -CORROSIVE AND NON -STAINING TYPE, RECOMMENDED BY SEALANT
MANUFACTURER; COMPATIBLE WITH JOINT FORMING MATERIALS.
3. JOINT BACKING: HOLLOW NEOPRENE (POLYCHLOROPRENE) COMPRESSION GASKET, ROUND
FOAM ROD COMPATIBLE WITH SEALANT; ASTM D 1667, CLOSED CELL; OVERSIZED 30 TO 50
PERCENT LARGER THAN JOINT WIDTH.
4. BOND BREAKER: POLYETHYLENE TAPE OR OTHER PLASTIC TAPE AS RECOMMENDED BY
SEALANT MANUFACTURER FOR PREVENTING SEALANT FROM ADHERING TO RIGID, INFLEXIBLE
JOINT FILLER MATERIALS OR JOINT SURFACES AT BACK OF JOINT WHERE SUCH ADHESION
WOULD RESULT IN SEALANT FAILURE. PROVIDE SELF-ADHESIVE TAPE WHERE APPLICABLE.
H. PREPARATION: REMOVE LOOSE MATERIALS AND FOREIGN MATTER THAT COULD IMPAIR ADHESION
OF SEALANT. CLEAN AND PRIME JOINTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
PERFORM PREPARATION IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND ASTM C 1193.
PROTECT ELEMENTS SURROUNDING THE WORK OF THIS SECTION FROM DAMAGE OR
DISFIGUREMENT.
I. INSTALLATION: PERFORM WORK IN ACCORDANCE WITH SEALANT MANUFACTURER'S REQUIREMENTS
FOR PREPARATION OF SURFACES AND MATERIAL INSTALLATION INSTRUCTIONS, AND IN
ACCORDANCE WITH ASTM C 1193.
1. MEASURE JOINT DIMENSIONS AND SIZE JOINT BACKERS TO ACHIEVE WIDTH -TO -DEPTH RATIO,
NECK DIMENSION, AND SURFACE BOND AREA AS RECOMMENDED BY MANUFACTURER.
2. INSTALL BOND BREAKER WHERE JOINT BACKING IS NOT USED.
3. INSTALL SEALANT FREE OF AIR POCKETS, FOREIGN EMBEDDED MATTER, RIDGES, AND SAGS.
4. APPLY SEALANT WITHIN RECOMMENDED APPLICATION TEMPERATURE RANGES.
5. TOOL JOINTS CONCAVE.
6. COMPRESSION GASKETS: AVOID JOINTS EXCEPT AT ENDS, CORNERS, AND INTERSECTIONS;
SEAL ALL JOINTS WITH ADHESIVE; INSTALL WITH FACE 1/8 TO 1/4 INCH BELOW ADJOINING
SURFACE.
J. CLEANING: CLEAN ADJACENT SOILED SURFACES.
K. PROTECTION: PROTECT SEALANTS UNTIL CURED.
08 1113 - HOLLOW METAL DOORS & FRAMES
A. SECTION INCLUDES: FIRE- RATED AND NON -FIRE -RATED STEEL DOORS AND FRAMES, STEEL FRAMES
FOR WOOD DOORS, THERMALLY AND ACOUSTICALLY INSULATED STEEL DOORS AND FRAMES, STEEL
GLAZING FRAMES AND ACCESSORIES, INCLUDING GLAZING, LOUVERS, AND MATCHING PANELS.
B. SUBMITTALS: SUBMIT PRODUCT DATA INDICATING MATERIALS AND DETAILS OF CONSTRUCTION,
HARDWARE LOCATIONS, AND FINISHES. ALSO SUBMIT SHOP DRAWINGS WITH DETAILS OF EACH
OPENING, SHOWING ELEVATIONS, GLAZING, AND FRAME PROFILES.
C. DELIVERY, STORAGE, AND HANDLING: STORE IN ACCORDANCE WITH NAAMM HMMA 840. PROTECT
WITH RESILIENT PACKAGING; AVOID HUMIDITY BUILD-UP UNDER COVERINGS; PREVENT CORROSION.
D. MANUFACTURERS: APPROVED DOOR AND FRAME MANUFACTURERS ARE CECO, CURRIES, REPUBLIC
DOORS; DM, DL OR DE SERIES, STEELCRAFT; L, SL AND/OR T SERIES OR APPROVED EQUAL.
E. DOORS AND FRAMES: REQUIREMENTS FOR ALL DOORS AND FRAMES SHALL BE:
1. ACCESSIBILITY: COMPLY WITH ANSI/ICC Al17.1.
2. DOOR TOP CLOSURES: FLUSH WITH TOP OF FACES AND EDGES.
3. DOOR EDGE PROFILE: BEVELED ON BOTH EDGES.
4. DOOR TEXTURE: SMOOTH FACES.
5. GLAZED LIGHTS: NON -REMOVABLE STOPS ON NON -SECURE SIDE; SIZES AND CONFIGURATIONS
AS INDICATED ON DRAWINGS.
6. HARDWARE PREPARATION: IN ACCORDANCE WITH BHMA A156.115, WITH REINFORCEMENT
WELDED IN PLACE, IN ADDITION TO OTHER REQUIREMENTS SPECIFIED IN DOOR GRADE
STANDARD.
7. FINISH: FACTORY PRIMED, FOR FIELD FINISHING.
F. EXTERIOR STEEL DOORS:
1. GRADE: ANSI A250.8 LEVEL 3, PHYSICAL PERFORMANCE LEVEL A, MODEL 2, SEAMLESS
2. CORE: POLYSTYRENE FOAM FOR AN INSULATION U-VALUE OF 0.50 WHEN TESTED IN
ACCORDANCE WITH ASTM C 1363.
3. ALL COMPONENTS ARE TO BE HOT -DIPPED ZINC -IRON ALLOY -COATED (GALVANNEALED) IN
ACCORDANCE WITH ASTM A 653/A 653M, WITH MANUFACTURER'S STANDARD COATING
THICKNESS.
G. INTERIOR STEEL DOORS (NON -FIRE -RATED):
1. GRADE: ANSI A250.8 LEVEL 1, PHYSICAL PERFORMANCE LEVEL C, MODEL 1, FULL FLUSH.
2. DOOR: THICKNESS OF 1-3/4 INCHES WITH A CARDBOARD HONEYCOMB CORE.
I. STEEL FRAMES: COMPLY WITH THE REQUIREMENTS OF GRADE SPECIFIED FOR CORRESPONDING
DOORS.
1. FRAMES FOR WOOD DOORS: COMPLY WITH FRAME REQUIREMENTS SPECIFIED IN ANSI A250.8
FOR LEVEL 1, 18 GAGE.
2. FRAMES FOR SOUND -RATED WOOD DOORS: COMPLY WITH FRAME REQUIREMENTS SPECIFIED
IN ANSI A250.8 FOR LEVEL 1, 16 GAGE.
3. FINISH: FACTORY PRIMED, FINISH PAINTED IN FIELD PER.
4. PROVIDE MORTAR GUARD BOXES FOR HARDWARE CUT-OUTS IN FRAMES TO BE INSTALLED IN
MASONRY OR TO BE GROUTED.
5. FRAMES IN MASONRY WALLS: SIZE TO SUIT MASONRY COURSING WITH HEAD MEMBER 4
INCHES HIGH TO FILL OPENING WITHOUT CUTTING MASONRY UNITS.
6. FRAMES WIDER THAN 48 INCHES: REINFORCE WITH STEEL CHANNEL FITTED TIGHTLY INTO
FRAME HEAD, FLUSH WITH TOP.
7. FRAMES INSTALLED BACK-TO-BACK: REINFORCE WITH STEEL CHANNELS ANCHORED TO FLOOR
AND OVERHEAD STRUCTURE.
K. EXTERIOR DOOR FRAMES: FACE WELDED SEAMLESS WITH JOINTS FILLED. GALVANIZE ALL
COMPONENTS WITH HOT -DIPPED ZINC -IRON ALLOY -COATED (GALVANNEALED) IN ACCORDANCE WITH
ASTM A 653/A 653M, WITH MANUFACTURER'S STANDARD COATING THICKNESS. WEATHERSTRIPPING
AS SPECIFIED IN ANOTHER SECTION.
L. INTERIOR DOOR FRAMES (NON -FIRE -RATED): FACE WELDED, SEAMLESS WITH JOINTS FILLED.
M. MULLIONS FOR PAIRS OF DOORS: FIXED, OF PROFILE SIMILAR TO JAMBS.
N. FRAMES FOR INTERIOR GLAZING OR BORROWED LIGHTS: CONSTRUCTION AND FACE DIMENSIONS
TO MATCH DOOR FRAMES, AND AS INDICATED ON DRAWINGS.
0. ACCESSORY MATERIALS:
1. LOUVERS: ROLL FORMED STEEL WITH OVERLAPPING FRAME; FACTORY -PAINTED FINISH, COLOR
AS SELECTED; FACTORY -INSTALLED. IN FIRE -RATED DOORS PROVIDE AN UL-LISTED FUSIBLE
0
LINK LOUVER, SAME RATING AS DOOR. STANDARD STRAIGHT SLAT BLADE STYLE WITH 70 /a
FREE AREA AND CONCEALED FASTENERS.
2. GLAZING: AS SPECIFIED IN SECTION 08 8000, FACTORY INSTALLED.
3. REMOVABLE STOPS: FORMED SHEET STEEL, SHAPE AS INDICATED ON DRAWINGS, MITERED OR
BUTTED CORNERS; PREPARED FOR COUNTERSINK STYLE TAMPER PROOF SCREWS.
4. GROUT FOR FRAMES: PORTLAND CEMENT GROUT OF MAXIMUM 4-INCH SLUMP FOR HAND
TROWELING; THINNER PUMPABLE GROUT IS PROHIBITED.
5. SILENCERS: RESILIENT RUBBER, FITTED INTO DRILLED HOLE; 3 ON STRIKE SIDE OF SINGLE
DOOR, 3 ON CENTER MULLION OF PAIRS, AND 2 ON HEAD OF PAIRS WITHOUT CENTER
MULLIONS.
6. TEMPORARY FRAME SPREADERS: PROVIDE FOR ALL FACTORY- OR SHOP -ASSEMBLED FRAMES.
Q. FINISH MATERIALS:
1. PRIMER: RUST -INHIBITING, COMPLYING WITH ANSI A250.10, DOOR MANUFACTURER'S
STANDARD.
2. BITUMINOUS COATING: ASPHALT EMULSION OR OTHER HIGH -BUILD, WATER-RESISTANT,
RESILIENT COATING.
R. PREPARATION: COAT INSIDE OF FRAMES TO BE INSTALLED IN MASONRY OR TO BE GROUTED, WITH
BITUMINOUS COATING, PRIOR TO INSTALLATION.
S. INSTALLATION:
1. INSTALL IN ACCORDANCE WITH THE REQUIREMENTS OF THE SPECIFIED DOOR GRADE
STANDARD AND NAAMM HMMA 840.
2. INSTALL FIRE RATED UNITS IN ACCORDANCE WITH NFPA 80.
3. COORDINATE FRAME ANCHOR PLACEMENT WITH WALL CONSTRUCTION.
4. GROUT FRAMES IN MASONRY CONSTRUCTION, USING HAND TROWEL METHODS; BRACE
FRAMES SO THAT PRESSURE OF GROUT BEFORE SETTING WILL NOT DEFORM FRAMES.
5. COORDINATE INSTALLATION OF HARDWARE, GLAZING, AND ELECTRICAL CONNECTIONS TO
ELECTRICAL HARDWARE ITEMS.
6. TOUCH UP DAMAGED FACTORY FINISHES.
T. TOLERANCES: CLEARANCES BETWEEN DOOR AND FRAME SHALL BE AS SPECIFIED IN ANSI A250.8,
WITH A MAXIMUM DIAGONAL DISTORTION OF 1/16 INCH, CORNER TO CORNER.
U. ADJUSTING: ADJUST FOR SMOOTH AND BALANCED DOOR MOVEMENT.
081416 - FLUSH WOOD DOORS
A. SECTION INCLUDES: FLUSH WOOD DOORS; FLUSH CONFIGURATION; NON -RATED.
B. SUBMITTALS: PROVIDE PRODUCT DATA INDICATING DOOR CORE MATERIALS AND CONSTRUCTION;
VENEER SPECIES, TYPE AND CHARACTERISTICS. SUBMIT SHOP DRAWINGS THAT ILLUSTRATE DOOR
ELEVATIONS, SIZES, TYPES, SWINGS, UNDERCUTS REQUIRED, SPECIAL BEVELING, SPECIAL
BLOCKING FOR HARDWARE, FACTORY MACHINING CRITERIA, FACTORY FINISHING CRITERIA, AND
IDENTIFY CUTOUTS FOR GLAZING. SUBMIT TWO SAMPLES OF DOOR VENEER, 4"X 4" IN SIZE
ILLUSTRATING WOOD GRAIN, STAIN COLOR, AND SHEEN.
C. DELIVERY, STORAGE, AND HANDLING: PACKAGE, DELIVER AND STORE DOORS IN ACCORDANCE WITH
SPECIFIED QUALITY STANDARD. INSPECT FOR DAMAGE. PROTECT DOORS WITH RESILIENT
PACKAGING SEALED WITH HEAT SHRUNK PLASTIC. DO NOT STORE IN DAMP OR WET AREAS; OR IN
AREAS WHERE SUNLIGHT MIGHT BLEACH VENEER. SEAL TOP AND BOTTOM EDGES WITH TINTED
SEALER IF STORED MORE THAN ONE WEEK. BREAK SEAL ON SITE TO PERMIT VENTILATION.
D. WARRANTY: PROVIDE MANUFACTURER'S WARRANTY FOR THE LIFE OF THE INSTALLATION THAT
INCLUDES COVERAGE FOR DELAMINATION OF VENEER, WARPING BEYOND SPECIFIED INSTALLATION
TOLERANCES, DEFECTIVE MATERIALS, AND TELEGRAPHING CORE CONSTRUCTION.
E. MANUFACTURERS: ACCEPTED MANUFACTURERS INCLUDE: GRAHAM WOOD DOORS: CUSTOM GRADE,
EGGERS INDUSTRIES, MARSHFIELD DOOR SYSTEMS: SIGNATURE SERIES, VT INDUSTRIES, MOHAWK,
OR APPROVED EQUAL.
08 1416 - FLUSH WOOD DOORS (CONT.)
1. SPECIES AND CONFIGURATION: PLAIN SLICED WHITE OAK, BOOK MATCH
2. COLOR: AS SELECTED BY ARCHITECT FROM MANUFACTURERS STANDARD COLORS
G. DOORS AND PANELS:
1. QUALITY LEVEL: CUSTOM GRADE, EXTRA HEAVY DUTY PERFORMANCE, IN ACCORDANCE WITH
WDMA I.S.1-A.
2. WOOD VENEER FACED DOORS: 5-PLY, 1 3/4" THICK.
3. INTERIOR DOORS: FLUSH SOLID CORE CONSTRUCTION 1 114 INCHES THICK.
4. FACING: WOOD VENEER WITH FACTORY TRANSPARENT FINISH.
G. DOOR AND PANEL CORES:
1. NON -RATED SOLID CORE DOORS: TYPE PARTICLEBOARD CORE, PLIES AND FACES AS
INDICATED ABOVE. GRADE M-2 PARTICLEBOARD, MINIMUM, WITH NO SEAMS ON FACES; EDGES
REINFORCED AS REQUIRED TO PASS WDMA PERFORMANCE GRADE SPECIFIED.
H. DOOR FACINGS:
1. WOOD VENEER FACING FOR TRANSPARENT FINISH: SPECIES AS SPECIFIED ABOVE, VENEER
GRADE AS SPECIFIED BY QUALITY STANDARD, PLAIN SLICED, BOOK VENEER MATCH, RUNNING
ASSEMBLY MATCH.
2. VERTICAL EDGES: SAME SPECIES AS FACE VENEER.
3. PAIRS: MATCH EACH PAIR; SET MATCH PAIRS WITHIN 10 FEET OF EACH OTHER WHEN DOORS
ARE CLOSED.
I. ACCESSORIES:
1. WOOD LOUVERS: FLUSH LOUVER, WITH MATERIAL AND FINISH TO MATCH DOOR.
2. GLAZING STOPS: WOOD OF SAME SPECIES AS DOOR FACING BUTTED CORNERS.
3. ASTRAGALS: STEEL, T SHAPED, OVERLAPPING AND RECESSED AT FACE EDGE.
J. DOOR CONSTRUCTION:
1. FABRICATE DOORS IN ACCORDANCE WITH DOOR QUALITY STANDARD SPECIFIED.
2. CORES CONSTRUCTED WITH STILES AND RAILS PROVIDING SOLID BLOCKS AT LOCK EDGE FOR
HARDWARE REINFORCEMENT.
3. PROVIDE SOLID BLOCKING FOR OTHER THROUGH -BOLTED HARDWARE.
4. FACTORY MACHINE DOORS FOR HARDWARE OTHER THAN SURFACE -MOUNTED HARDWARE, IN
ACCORDANCE WITH HARDWARE REQUIREMENTS AND DIMENSIONS.
5. PROVIDE EDGE CLEARANCES IN ACCORDANCE WITH AWI QUALITY STANDARDS ILLUSTRATED
SECTION 1700.
K. FACTORY FINISHING (WOOD VENEER DOORS):
1. TRANSPARENT FINISH: TRANSPARENT CONVERSION VARNISH, PREMIUM QUALITY.
2. FACTORY FINISH ALL DOORS IN ACCORDANCE WITH APPROVED SAMPLE.
3. SEAL DOOR TOP EDGE WITH COLOR SEALER TO MATCH DOOR FACING.
L. INSTALLATION:
1. INSTALL DOORS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND SPECIFIED
QUALITY STANDARD.
2. FACTORY -FINISHED DOORS: DO NOT FIELD CUT OR TRIM; IF FIT OR CLEARANCE IS NOT
CORRECT, REPLACE DOOR.
3. USE MACHINE TOOLS TO CUT OR DRILL FOR HARDWARE.
4. COORDINATE WITH INSTALLATION OF FRAMES, HARDWARE AND GLAZING.
5. FITTING CLEARANCES (NON -RATED DOORS):
a. JAMBS, HEADS AND BOTTOM OF DOORS TO FLOOR FINISH: 1/8"
b. AT MEETING STILES FOR PAIRS OF DOORS; 1/16" PER LEAF
c. AT THRESHOLDS: 1/4" CLEARANCE FROM BOTTOM OF DOOR TO TOP OF THRESHOLD.
d. ROOMS WITH CONDITIONED AIR SUPPLY BUT NO AIR RETURN: 1/2" FROM FLOOR FINISH.
M. TOLERANCES: CONFORM TO SPECIFIED QUALITY STANDARD FOR FIT AND CLEARANCE TOLERANCES
AND FOR MAXIMUM DIAGONAL DISTORTION.
N. ADJUSTING: ADJUST DOORS FOR SMOOTH AND BALANCED DOOR MOVEMENT. ADJUST CLOSERS
FOR FULL CLOSURE.
08 3100 - ACCESS DOORS
A. SECTION INCLUDES: ACCESS DOOR AND FRAME UNITS FOR NON -RATED IN -WALL LOCATIONS
(COORDINATE WITH DESIGN -BUILD MECHANICAL ELECTRICAL AND PLUMBING SPECIFICATIONS BY
OTHERS)
B. SUBMITTALS: PROVIDE PRODUCT DATA INDICATING SIZES, TYPES, FINISHES, HARDWARE, AND SHOP
DRAWINGS INDICATING EXACT POSITION OF ALL ACCESS DOOR UNITS.
C. MANUFACTURERS: APPROVED MANUFACTURERS INCLUDE: ACUDOR PRODUCTS INC., MILCOR INC.,
WILLIAMS BROTHERS CORPORATION OR APPROVED EQUAL.
D. ACCESS DOORS AND PANELS: FACTORY FABRICATED, FULLY ASSEMBLED UNITS WITH CORNER
JOINTS WELDED, FILLED, AND GROUND FLUSH; SQUARE AND WITHOUT RACK OR WARP.
1. FLOOR UNITS: DESIGN TO SUPPORT LIVE LOAD OF 100 LB/SQ FT WITH DEFLECTION NOT TO
EXCEED 1/180 OF SPAN.
2. PROVIDE PRODUCTS LISTED AND LABELED BY UL AS SUITABLE FOR THE PURPOSE SPECIFIED
AND INDICATED.
E. WALL AND CEILING UNITS: FORMED STEEL DOOR AND FRAME UNITS IN SIZES INDICATED.
1. FRAMES AND FLANGES: 0.058 INCH STEEL.
2. DOOR PANELS: 0.070 INCH SINGLE THICKNESS STEEL SHEET.
3. HARDWARE: 175 DEGREE STAINLESS STEEL PIANO HINGE WITH REMOVABLE PIN, IN
GALVANIZED, HOT DIPPED FINISH AND A PRIME COAT WITH ALKYD PRIMER.
4. FINISH: ONE COAT BAKED ENAMEL IN COLOR AS SELECTED FROM MANUFACTURER'S
STANDARD SELECTION.
F. EXAMINATION: VERIFY THAT ROUGH OPENINGS ARE CORRECTLY SIZED AND LOCATED.
G. INSTALLATION: INSTALL UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. INSTALL
FRAMES PLUMB AND LEVEL IN OPENINGS. SECURE RIGIDLY IN PLACE. POSITION UNITS TO PROVIDE
CONVENIENT ACCESS TO THE CONCEALED WORK REQUIRING ACCESS.
08 3323 - OVERHEAD DOORS
A. SECTION INCLUDES: OVERHEAD SECTIONAL DOORS, OPERATING HARDWARE, NON -FIRE -RATED,
INSULATED AND ELECTRIC OPERATION.
B. SUBMITTALS: PROVIDE GENERAL CONSTRUCTION, COMPONENT CONNECTIONS AND DETAILS, AND
ELECTRICAL EQUIPMENT. SUBMIT SHOP DRAWINGS THE INCLUDE DIMENSIONING, ANCHORAGE
METHODS, HARDWARE LOCATIONS, AND INSTALLATION DETAILS.
C. MANUFACTURERS: APPROVED MANUFACTURERS INCLUDE: OVERHEAD DOOR COMPANY, CORNELL
IRON WORKS, INC., THE COOKSON COMPANY, WAYNE-DALTON CORPORATION, CHI OVERHEAD
DOORS, OR APPROVED EQUAL.
D. INSULATED STEEL SECTION OVERHEAD DOORS: BASIS OF DESIGN IS THERMACORE MODEL 592
INSULATED STEEL DOORS BY OVERHEAD DOOR CORPORATION. UNITS SHALL HAVE THE FOLLOWING
CHARACTERISTICS:
1. DOOR ASSEMBLY: METAL/FOAM/METAL SANDWICH PANEL CONSTRUCTION, WITH PVC THERMAL BREAK
AND WEATHER -TIGHT SHIP -LAP DESIGN MEETING JOINTS.
a. PANEL THICKNESS: 2 INCHES (51 MM).
b. EXTERIOR SURFACE: FLUSH, TEXTURED.
C. EXTERIOR STEEL:.015 INCH (.38 MM), HOT -DIPPED GALVANIZED.
d. END STILES: 16 GAUGE WITH THERMAL BREAK.
e. SPRING COUNTERBALANCE: SIZED TO WEIGHT OF THE DOOR, WITH A HELICALLY WOUND, OIL
TEMPERED TORSION SPRING MOUNTED ON A STEEL SHAFT; CABLE DRUM OF DIECAST ALUMINUM
WITH HIGH STRENGTH GALVANIZED AIRCRAFT CABLE. SIZED WITH A MINIMUM 7 TO 1 SAFETY
FACTOR.
1) HIGH CYCLE SPRING: 100,000 CYCLES.
f. INSULATION: CFC-FREE AND HCFC-FREE POLYURETHANE, FULLY ENCAPSULATED.
g. THERMAL VALUES: R-VALUE OF 17.50; U-VALUE OF 0.057.
h. AIR INFILTRATION: 0.08 CFM AT 15 MPH; 0.08 CFM AT 25 MPH.
i. HIGH -USAGE PACKAGE: PROVIDE WITH OPTIONAL HIGH -USAGE PACKAGE.
j. GLAZING: PARTIAL 1/2" INSULATED GLAZING WITH FULL VIEW SASH ACROSS ENTIRE PANEL WIDTH
AS SHOWN ON THE ELEVATIONS.
2. FINISH AND COLOR: TWO COAT BAKED -ON POLYESTER.
a. INTERIOR COLOR: AS SELECTED BY ARCHITECT FROM MFR STANDARD COLOR PALETTE.
b. EXTERIOR COLOR: AS SELECTED BY ARCHITECT FROM MFR STANDARD COLOR PALETTE.
E. HARDWARE: GALVANIZED STEEL HINGES AND FIXTURES. BALL BEARING ROLLERS WITH HARDENED STEEL
RACES.
08 3323 - OVERHEAD DOORS (CONT.)
F. LOCK
1. KEYED LOCK WITH INTERLOCK SWITCH FOR AUTOMATIC OPERATOR.
2. LOCKING MECHANISM DESIGNED TO MAINTAIN SECURITY FOR EXTERIOR WHILE PERMITTING BREAK OUT
WHEN IMPACTED FROM THE INSIDE.
G. WEATHERSTRIPPING:
1. EPDM BULB -TYPE STRIP AT BOTTOM SECTION.
2. FLEXIBLE JAMB SEALS.
3. FLEXIBLE HEADER SEAL.
H. TRACK: PROVIDE TRACK AS RECOMMENDED BY MANUFACTURER TO SUIT LOADING REQUIRED AND
CLEARANCES AVAILABLE.
1. SIZE: 3 INCH (76 MM).
2. TYPE: OVERHEAD LIFT.
I. ELECTRIC MOTOR OPERATION: PROVIDE UL LISTED ELECTRIC OPERATOR, SIZE AND TYPE AS RECOMMENDED
BY MANUFACTURER TO MOVE DOOR IN EITHER DIRECTION AT NOT LESS THAN 2/3 FOOT NOR MORE THAN 1
FOOT PER SECOND. OPERATOR SHALL MEET UL325/2010 REQUIREMENTS FOR CONTINUOUS MONITORING OF
SAFETY DEVICES.
1. ENTRAPMENT PROTECTION: REQUIRED FOR MOMENTARY CONTACT, INCLUDES RADIO CONTROL
OPERATION.
a. PHOTOELECTRIC SENSORS MONITORED TO MEET UL 325/2010.
b.
2. OPERATOR CONTROLS:
a. PUSH-BUTTON OPERATED CONTROL STATIONS WITH OPEN, CLOSE, AND STOP BUTTONS.
b. SURFACE MOUNTING.
C. INTERIOR LOCATION.
J. INSTALLATION:
1. INSTALL UNITS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
2. USE ANCHORAGE DEVICES TO SECURELY FASTEN ASSEMBLY TO WALL CONSTRUCTION AND
BUILDING FRAMING WITHOUT DISTORTION OR STRESS.
3. SECURELY AND RIGIDLY BRACE COMPONENTS SUSPENDED FROM STRUCTURE. SECURE
GUIDES TO STRUCTURAL MEMBERS ONLY.
4. FIT AND ALIGN ASSEMBLY INCLUDING HARDWARE; LEVEL AND PLUMB, TO PROVIDE SMOOTH
OPERATION.
5. COORDINATE INSTALLATION OF ELECTRICAL SERVICE AND COMPLETE WIRING FROM
DISCONNECT TO UNIT COMPONENTS.
6. COMPLETE WIRING FROM FIRE ALARM SYSTEM.
7. COORDINATE INSTALLATION OF SEALANTS AND BACKING MATERIALS AT FRAME PERIMETER.
8. INSTALL PERIMETER TRIM, AND CLOSURES.
K. CLEANING: CLEAN INSTALLED COMPONENTS. REMOVE LABELS AND VISIBLE MARKINGS.
08 4313 - ALUMINUM FRAMED STOREFRONTS
A. SECTION INCLUDES: ALUMINUM -FRAMED STOREFRONT, WITH VISION GLASS, INFILL PANELS OF
METAL AND GLASS, AND ALUMINUM DOORS AND FRAMES.
B. SUBMITTALS: PROVIDE SHOP DRAWINGS THAT INDICATE SYSTEM DIMENSIONS, FRAMED OPENING
REQUIREMENTS AND TOLERANCES, ANCHORAGE AND FASTENERS, EXPANSION AND CONTRACTION
JOINT LOCATION AND DETAILS, DOOR HARDWARE, AND FIELD WELDING REQUIRED.
C. DELIVERY, STORAGE, AND HANDLING: HANDLE PRODUCTS OF THIS SECTION IN ACCORDANCE WITH
AAMA CW-10. PROTECT FINISHED ALUMINUM SURFACES WITH WRAPPING.
D. WARRANTY: PROVIDE FIVE YEAR MANUFACTURER WARRANTY AGAINST FAILURE OF GLASS SEAL ON
INSULATING GLASS UNITS. PROVIDE FIVE YEAR MANUFACTURER WARRANTY AGAINST EXCESSIVE
DEGRADATION OF EXTERIOR FINISH. INCLUDE PROVISION FOR REPLACEMENT OF FAILED UNITS.
E. MANUFACTURERS: APPROVED MANUFACTURERS INCLUDE; KAWNEER NORTH AMERICA; 451T
MANKO; 2450 SERIES, US ALUMINUM; IT 451, YKK AP AMERICA; YES 45 TU OR APPROVED EQUAL.
F. ALUMINUM -FRAMED STOREFRONT: FACTORY FABRICATED, FACTORY FINISHED ALUMINUM FRAMING
MEMBERS WITH INFILL, AND RELATED FLASHINGS, ANCHORAGE AND ATTACHMENT DEVICES.
1. FINISH: CLASS I NATURAL ANODIZED.
2. FRAMING MEMBERS: TUBULAR ALUMINUM SECTIONS, THERMALLY BROKEN WITH INTERIOR
SECTION INSULATED FROM EXTERIOR, DRAINAGE HOLES AND INTERNAL WEEP DRAINAGE
SYSTEM.
3. GLAZING STOPS: FLUSH.
4. STRUCTURALLY REINFORCED MEMBERS: EXTRUDED ALUMINUM WITH INTERNAL
REINFORCEMENT OF STRUCTURAL STEEL MEMBER.
5. DOORS: GLAZED ALUMINUM 1-3/4 INCHES WITH THE TOP RAIL 4"WIDE, VERTICAL STILES 4-1/2"
WIDE AND THE BOTTOM RAIL 6" WIDE WITH SQUARE GLAZING STOPS, ALL IN A FINISH MATCHING
THE STOREFRONT SYSTEM.
G. MATERIALS:
1. EXTRUDED ALUMINUM: ASTM B 221.
2. SHEET ALUMINUM: ASTM B 209.
3. FASTENERS: STAINLESS STEEL.
4. GLAZING GASKETS: TYPE TO SUIT APPLICATION TO ACHIEVE WEATHER, MOISTURE, AND AIR
INFILTRATION REQUIREMENTS.
5. TOUCH-UP PRIMER FOR GALVANIZED STEEL SURFACES: SSPC-PAINT 20, ZINC RICH.
H. FINISHES: CLASS I ANODIZED FINISH: AAMA 611 AA-M12C22A42 DARK BRONZE ANODIC COATING NOT
LESS THAN 0.7 MILS THICK.
I. HARDWARE:
1. DOOR HARDWARE: AS SPECIFIED IN THE DOOR HARDWARE SPECIFICATION.
2. WEATHERSTRIPPING: WOOL PILE, CONTINUOUS AND REPLACEABLE; PROVIDE ON ALL DOORS.
3. SILL SWEEP STRIPS: RESILIENT SEAL TYPE, RETRACTING, OF NEOPRENE; PROVIDE ON ALL
DOORS.
4. THRESHOLD: EXTRUDED ALUMINUM, ONE PIECE PER DOOR OPENING, RIBBED SURFACE;
PROVIDE ON ALL DOORS.
J. FABRICATION:
1. FABRICATE COMPONENTS WITH MINIMUM CLEARANCES AND SHIM SPACING AROUND
PERIMETER OF ASSEMBLY, YET ENABLING INSTALLATION AND DYNAMIC MOVEMENT OF
PERIMETER SEAL. ACCURATELY FIT AND SECURE JOINTS AND CORNERS. MAKE JOINTS FLUSH,
HAIRLINE, AND WEATHERPROOF.
2. PREPARE COMPONENTS TO RECEIVE ANCHOR DEVICES.
3. COAT CONCEALED METAL SURFACES THAT WILL BE IN CONTACT WITH CEMENTITIOUS
MATERIALS OR DISSIMILAR METALS WITH BITUMINOUS PAINT.
4. ARRANGE FASTENERS AND ATTACHMENTS TO CONCEAL FROM VIEW. REINFORCE
COMPONENTS INTERNALLY FOR DOOR HARDWARE AND DOOR OPERATORS.
5. FINISHING: APPLY FACTORY FINISH TO ALL SURFACES THAT WILL BE EXPOSED IN COMPLETED
ASSEMBLIES.
6. TOUCH-UP SURFACES CUT DURING FABRICATION SO THAT NO NATURAL ALUMINUM IS VISIBLE IN
COMPLETED ASSEMBLIES, INCLUDING JOINT EDGES.
K. INSTALLATION: INSTALL ALUMINUM STOREFRONT SYSTEM IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS AND APPROVED SHOP DRAWINGS.
1. ATTACH TO STRUCTURE TO PERMIT SUFFICIENT ADJUSTMENT TO ACCOMMODATE
CONSTRUCTION TOLERANCES AND OTHER IRREGULARITIES.
2. ALIGN ASSEMBLY PLUMB AND LEVEL, FREE OF WARP OR TWIST. MAINTAIN ASSEMBLY
DIMENSIONAL TOLERANCES, ALIGNING WITH ADJACENT WORK.
3. INSTALL SILL FLASHINGS. TURN UP ENDS AND EDGES; SEAL TO ADJACENT WORK TO FORM
WATER TIGHT DAM. COORDINATE ATTACHMENT AND SEAL OF PERIMETER AIR AND VAPOR
BARRIER MATERIALS.
4. PACK FIBROUS INSULATION IN SHIM SPACES AT PERIMETER OF ASSEMBLY TO MAINTAIN
CONTINUITY OF THERMAL BARRIER.
5. SET THRESHOLDS IN BED OF MASTIC AND SECURE.
6. TOUCH-UP MINOR DAMAGE TO FACTORY APPLIED FINISH; REPLACE COMPONENTS THAT
CANNOT BE SATISFACTORILY REPAIRED.
L. TOLERANCES: MAXIMUM VARIATION FROM PLUMB SHALL BE 0.06 INCHES EVERY 3 FT
NON -CUMULATIVE OR 1/16" PER 10 FT, WHICHEVER IS LESS. THE MAXIMUM MISALIGNMENT OF TWO
ADJOINING MEMBERS ABUTTING IN PLANE SHALL BE 1/32".
M. ADJUSTING: ADJUST OPERATING HARDWARE AND SASH FOR SMOOTH OPERATION.
N. CLEANING: REMOVE PROTECTIVE MATERIAL FROM PRE -FINISHED ALUMINUM SURFACES. WASH
DOWN SURFACES WITH A SOLUTION OF MILD DETERGENT IN WARM WATER, APPLIED WITH SOFT,
CLEAN WIPING CLOTHS. TAKE CARE TO REMOVE DIRT FROM CORNERS. REMOVE EXCESS SEALANT
BY METHOD ACCEPTABLE TO SEALANT MANUFACTURER.
08 7100 - DOOR HARDWARE
A. SECTION INCLUDES: HARDWARE FOR WOOD, HOLLOW STEEL, AND ALUMINUM DOORS, FIRE -RATED
DOORS, ELECTRICALLY OPERATED AND CONTROLLED HARDWARE. THRESHOLDS,
WEATHERSTRIPPING, SEALS AND DOOR GASKETS.
B. SUBMITTALS: PROVIDE SHOP DRAWINGS THAT INDICATE LOCATIONS AND MOUNTING HEIGHTS OF
EACH TYPE OF HARDWARE, SCHEDULES, CATALOG CUTS, ELECTRICAL CHARACTERISTICS AND
CONNECTION REQUIREMENTS.
C. DELIVERY, STORAGE, AND HANDLING: PACKAGE HARDWARE ITEMS INDIVIDUALLY; LABEL AND
IDENTIFY EACH PACKAGE WITH DOOR OPENING CODE TO MATCH HARDWARE SCHEDULE.
D. WARRANTY: AS PART OF RESPECTIVE MANUFACTURERS' REGULAR TERMS OF SALE, PROVIDE
MANUFACTURERS' WARRANTIES AS FOLLOWS:
1. LOCKSETS: GRADE 1 - FIVE (5) YEARS.
2. EXIT DEVICES: THREE (3) YEARS MECHANICAL, ONE (1) YEAR ELECTRICAL.
3. CLOSERS: TEN (10) YEARS MECHANICAL, TWO (2) YEARS ELECTRICAL.
4. OTHER HARDWARE: ONE (1) YEAR.
E. MANUFACTURERS: THE APPROVED MANUFACTURERS FOR EACH ITEM ARE AS FOLLOWS:
1. HINGES: ASSAABLOY MCKINNEY, BOMMER INDUSTRIES, INC., HAGER COMPANIES, STANLEY
HARDWARE OR APPROVED EQUAL.
2. PIVOTS: ASSA ABLOY; MCKINNEY OR RIXSON, DORMA GROUP NORTH AMERICA,
GLYNN-JOHNSON OR APPROVED EQUAL.
3. LOCK AND LATCH SETS: ASSA ABLOY; CORBIN/RUSSWIN, SARGENT, OR YALE, BEST ACCESS
SYSTEMS, SCHLAGE, HAGER OR APPROVED EQUAL.
4. PUSH/PULLS: ASSA ABLOY, ROCKWOOD, MCKINNEY, HAGER COMPANIES OR APPROVED EQUAL.
5. CYLINDRICAL LOCKSETS: ASSA ABLOY; CORBIN/RUSSWIN SARGENT OR YALE BEST ACCESS
SYSTEMS, SCHLAGE OR APPROVED EQUAL.
6. MORTISE LOCKSETS: ASSA ABLOY; CORBIN/RUSSWIN, SARGENT, OR YALE, BEST ACCESS
SYSTEMS, SCHLAGE OR APPROVED EQUAL.
7. ELECTRIFIED LOCKSETS: ASSA ABLOY; CORBIN/RUSSWIN, SARGENT, OR YALE, BEST ACCESS
SYSTEMS, KABA ILCO INC. OR APPROVED EQUAL.
8. MAGNETIC LOCKS: ASSA ABLOY SECURITRON OR APPROVED EQUAL.
9. ELECTRIC STRIKES: ASSA ABLOY; FOLGER, ADAM, EDC, HES OR SECURITRON, OR APPROVED
EQUAL.
10. EXIT DEVICES: ASSA ABLOY; CORBIN/RUSSWIN, SARGENT, OR YALE, VON DUPRIN, DORMA
GROUP NORTH AMERICA OR APPROVED EQUAL.
11. CLOSERS: ASSA ABLOY CORBIN RUSSWIN, HAGER, NORTON, RIXSON, SARGENT, OR YALE, LCN,
DORMA OR APPROVED EQUAL.
12. WALL AND FLOOR STOPSMOLDERS: ASSA ABLOY MCKINNEY, ROCKWOOD, HAGER COMPANIES,
IVES DOOR HARDWARE OR APPROVED EQUAL.
13. MANUAL AND AUTOMATIC BOLTS: ASSA ABLOY MCKINNEY, GLYNN-JOHNSON, HAGER
COMPANIES, IVES DOOR HARDWARE OR APPROVED EQUAL.
14. GASKETING AND THRESHOLDS: ASSA ABLOY MCKINNEY, NATIONAL GUARD PRODUCTS, INC,
PEMKO MANUFACTURING CO. OR APPROVED EQUAL.
15. SLIDING DOOR HARDWARE: HAGER COMPANIES, JOHNSON HARDWARE, STANLEY HARDWARE
OR APPROVED EQUAL.
16. BI-FOLDING DOOR HARDWARE: HAGER COMPANIES, JOHNSON HARDWARE, STANLEY
HARDWARE OR APPROVED EQUAL.
17. PROTECTION PLATES: ASSA ABLOY; MCKINNEY, ROCKWOOD, HAGER COMPANIES, IVES DOOR
HARDWARE OR APPROVED EQUAL.
F. GENERAL REQUIREMENTS FOR DOOR HARDWARE PRODUCTS: PROVIDE PRODUCTS THAT COMPLY
WITH THE FOLLOWING:
1. APPLICABLE PROVISIONS OF FEDERAL, STATE, AND LOCAL CODES.
2. ANSI/ICC Al17.1, AMERICAN NATIONAL STANDARD FOR ACCESSIBLE AND USABLE BUILDINGS
AND FACILITIES.
3. APPLICABLE PROVISIONS OF NFPA 101, LIFE SAFETY CODE.
4. FIRE -RATED DOORS: NFPA 80.
5. ALL HARDWARE ON FIRE -RATED DOORS: LISTED AND CLASSIFIED BY UL AS SUITABLE FOR THE
PURPOSE SPECIFIED AND INDICATED.
6. PRODUCTS REQUIRING ELECTRICAL CONNECTION: LISTED AND CLASSIFIED BY UL AS SUITABLE
FOR THE PURPOSE SPECIFIED AND INDICATED.
G. KEYING: DOOR LOCKS SHALL BE GRAND MASTER KEYED. INCLUDE CONSTRUCTION KEYING. WHERE
EXISTING CONDITIONS ARE PRESENT, KEY TO EXISTING KEYING SYSTEM.
H. KEY CABINET: PROVIDE A KEY CABINET SIZED FOR PROJECT KEYS PLUS 10 PERCENT GROWTH. THE
CABINET CONSTRUCTION SHALL BE SHEET STEEL WITH A PIANO HINGED DOOR AND A LOCK MASTER
KEYED TO BUILDING SYSTEM. PROVIDE HORIZONTAL METAL STRIPS FOR KEY HOOK LABELING WITH
CLEAR PLASTIC STRIP COVER OVER LABELS. THE FINISH SHALL BE BAKED ENAMEL, COLOR AS
SELECTED BY ARCHITECT.
I. FIRE DEPARTMENT KEY BOX: KNOX COMPANY'S KNOX BOX 3200 SERIES, HINGED DOOR MODEL, WITH
RECESSED MOUNTING KIT - INSTALLED ACCORDING TO LOCAL FIRE MARSHAL REQUIREMENTS.
J. EXAMINATION: VERIFY THAT DOORS AND FRAMES ARE READY TO RECEIVE WORK AND DIMENSIONS
ARE AS INDICATED ON SHOP DRAWINGS. VERIFY THAT ELECTRIC POWER IS AVAILABLE TO POWER
OPERATED DEVICES AND OF THE CORRECT CHARACTERISTICS.
K. INSTALLATION:
1. INSTALL HARDWARE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE
CODES.
2. USE TEMPLATES PROVIDED BY HARDWARE ITEM MANUFACTURER.
3. INSTALL HARDWARE ON FIRE -RATED DOORS AND FRAMES IN ACCORDANCE WITH CODE AND
NFPA 80.
4. MOUNTING HEIGHTS FOR HARDWARE FROM FINISHED FLOOR TO CENTER LINE OF HARDWARE
ITEM: AS LISTED IN SCHEDULE.
K. ADJUSTING: ADJUST HARDWARE FOR SMOOTH OPERATION.
L. SCHEDULE: SEE DOOR SCHEDULE ON DRAWINGS
CERTIFIED BY:
i,
SrER s�
� •� �� No. FO•.�o
= 0 900019 0 =
STATE OF
OF
i
Lu
Q N
Q M
Q0 O
O O
LL V
z W Q
o O z
Z
J Z =
C)0 Z
� W Q oZ
Z
0 �
0
(D
Z z o
V) J
-
Q
z Q �J
O J ="
U
W
3: LU z
W J �
z Q
J 0)U
DRAWING
ARCHITECTURAL
SPECIFICATIONS
ISSUE
100% CONST. DOCUMENTS - 05/15/2020
90% CONST. DOCUMENTS - 04/01/2020
DESIGN DEVELOPMENT SET-01/16/2020
REVISIONS
Al -
2 -
3 -
4 -
PROJECT NUMBER 1832
DATE MAY 15, 2020