HomeMy WebLinkAboutA121 - 1st Floor Electrical Plan RCPOFFICE
113
OFFICE
114
OFFICE
115
OFFICE
119
OFFICE
118
OFFICE
117
OPEN OFFICE
116
COMPETE
106
SERVER/STG
110
RESTROOM
112
WELCOME
101
TVCONFERENCE
103
CONFERENCE
107
OFFICE
109
DRINK +
GATHER
105 U.C.
REFRIG
U.C.
KEG TV321123OFFICE
108
OFFICE
102
OPEN OFFICE
104
+60"+60"+42"GFCI+44"GFCIJJJJJJ
+42"
GFCI
+60"
+60"DED+60"+60"+60"
+60"+60"
+60"+60"+60"+60"
+60"+60"
+60"
+60"
+60"
+60"
+60"
+60"
+60"
+44"GFCI
+72"
+72"
OFFICE
113
OFFICE
114
OFFICE
115
OFFICE
119
OFFICE
118
OFFICE
117
OPEN OFFICE
116
COMPETE
106
SERVER/STG
110
RESTROOM
112
WELCOME
101
TVCONFERENCE
103
CONFERENCE
107
OFFICE
109
DRINK +
GATHER
105 U.C.
REFRIG
U.C.
KEG TV321123OFFICE
108
OFFICE
102
OPEN OFFICE
104
+60"+60"+42"GFCI+44"GFCIJ JJJJJ
+42"
GFCI
+60"
+60"DED+60"+60"+60"
+60"+60"
+60" +60"+60"+60"
+60"+60"
+60"
+60"
+60"
+60"
+60"
+60"
+60"
+44"GFCI
+72"
+72"SN16'-0"
12'-0" TYP.8'-0"L; 8'-6" AFFELNELNELNELNELNELN
SNSNSNSNS N
SNSN3SNSNSNSNS NSNSN3
SNSN3SN3SN16'-0"
12'-0" TYP.8'-0"L; 8'-6" AFFELNELNELNELNELNELN
SNSNSNSNS N
SNSN3SNSNSNSNS NSNSN3
SNSN3SN38'-0"9'-0"REFLECTED
CEILING PLAN
A121
REFLECTED CEILING PLAN
DESCRIPTIONDATE
ISSUE
06.12.20 REVIEW SET
06.29.20 UPDATED SET
09.09.20 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
07.29.20 EH PLAN UPDATE
08.12.20 EH CLG UPDATES2
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER
DRAWN BYPROJ. MGR TRUEBLOODREALTYMIDTOWN EAST | SUITE 100571 MONON BLVD, CARMEL, IN 46032EHEH
2019.288
1ST FLOOR
N
1
0 2' 4' 8' 16'
AREA NOT IN CONTRACT
AREA OF WORK
AREA NOT IN CONTRACT
AREA OF WORK
ELECTRICAL PLAN NOTES
ELECTRICAL PLAN
DED
POWER OUTLET, DUPLEX
NEW CONSTRUCTION EXISTING TO REMAIN
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
POWER OUTLET, DUPLEX
POWER OUTLET,
QUADRUPLEX
JUNCTION BOX
BOX, BLANK COVER PLATE
BOX, OPEN
BOX, BLANK COVER PLATE
BOX, OPEN
POWER AND DATA POLE
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
FLOOR BOX WITH POWER
AND DATA, FLUSH
MOUNTED
FLOOR BOX WITH
JUNCTION BOX AND
DATA, FLUSH MOUNTED
DEDICATED CIRCUIT
DATA/COMMUNICATION
OUTLET (PROVIDE BOX
AND PULL STRING ONLY)
DATA/COMMUNICATION
OUTLET
GFCI GROUND FAULT CIRCUIT
INTERRUPT OUTLET
HEIGHT OF ELECTRICAL
OR DATA DEVICE
ELECTRICAL LEGEND
CEILING MOUNTED
JUNCTION BOX
CEILING MOUNTED
JUNCTION BOX
ELECTRICAL PLAN/
RCP PLAN NOTES GENERAL ELEC. NOTES
CONTROL WELCOME 101, OPEN OFFICE 104, COMPETE 106, OPEN
OFFICE 116 AREA LIGHTING WITH 3-WAY SWITCH AT THIS
LOCATION. PROVIDE MULTIPLE SWITCHES AS REQUIRED.
CLEAN ALL EXPOSED SURFACES; EXISTING SURFACES TO REMAIN
AS-IS. PROVIDE RIGID SPIRAL DUCT AND ROUND SUPPLY DIFFUSERS
AS REQUIRED IN THIS AREA.
INSTALL TENANT'S OVERHEAD PROJECTOR + AUTOMATIC
PROJECTOR SCREEN IN THIS AREA. ALL FINAL DETAILS AND
LOCATION TO BE COORDINATED WITH TENANT.
INSTALL FLOATING CLOUD WITH ARMSTRONG AXIOM TRIM
AROUND PERIMETER (6"; WHITE). GRID AND TILE TO BE 2'x2' SUITE
STANDARD (REFER TO GENERAL CEILING NOTE 1). HEIGHT TO
UNDERSIDE OF CEILING CLOUD TO BE AT 10'-0" AFF. FLOAT CLOUD
WITH ALL-THREAD INSTALLED 15" FROM EDGES. PAINT ALL THREAD
SAME COLOR AS CEILING DECK. INSTALL MINIMAL QUANTITY OF
ALL-THREAD SUPPORTS AS POSSIBLE AND MAKE ALL THREAD
SUPPORTS AS VISUALLY UNOBTRUSIVE AS POSSIBLE. CONSULT WITH
PHIL CAITO (317.519.2829) FOR FINAL SIZES, SPECIFICATIONS, ETC.
NOTE THAT SPRINKLERS MAY BE REQUIRED ABOVE AND BELOW
CLOUD. FIRE SPRINKLER CONTRACTOR TO PROVIDE SUBMITTAL OF
FINAL LAY-OUT FOR FINAL APPROVAL PRIOR TO INSTALLATION.
PROVIDE 4 78" WIDE BULKHEAD AT 8'-10" AFF AT THIS LOCATION.
BULKHEAD TO EXTEND TO DECK AND ALIGN WITH ADJACENT
WALLS AS SHOWN. INTENT IS FOR CEILING GRID AT 9'-0" TO DIE
INTO BULKHEAD AS SHOWN. ALL FACES OF BULKHEAD TO BE
PAINTED PT2; FLAT FINISH.
PROVIDE DRYWALL CEILING AT 10'-0" AFF THIS LOCATION WITH
ARMSTRONG AXIOM TRIM AROUND PERIMETER (6"; WHITE) - REFER
TO PLANS FOR DIMENSIONS. INTENT IS FOR DRYWALL CEILING TO
ALIGN WITH ADJACENT WALL AS SHOWN. UNDERSIDE OF
DRYWALL CEILING TO RECEIVE SPECIALTY FINISH - REFER TO FINISH
PLANS.
CLEAN ALL EXPOSED SURFACES AND PREPARE FOR DRYFALL PAINT
(PT6) AS NOTED ON PLAN PER MANUFACTURER'S
RECOMMENDATIONS. PAINT EXISTING EXPOSED STRUCTURAL
BEAMS AND CROSSBRACING IN ACCORDANCE WITH NFPA 13
6.3.8. ALL STRUCTURAL BEAMS INTENDED TO BE PAINTED ARE
CURRENTLY DARK GRAY; CONFIRM AREAS TO BE PAINTED WITH
SDI AS REQUIRED.
BASE BID: UNDERSIDE OF DECK TO REMAIN AS-IS AND BE CLEANED
AS NEEDED.
SEPARATE PRICE: ON UNDERSIDE OF DECK ONLY (NO OTHER
CEILING ELEMENTS), PROVIDE K13 ACOUSTICAL CEILING
TREATMENT IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND ALL STATE + LOCAL CODES. K13 TO BE
PAINTED WITH DRYFALL PAINT (PT5).
0 2' 4' 8' 16'
1. TENANT'S FURNITURE VENDOR IS RESPONSIBLE FOR INSTALLATION OF FURNITURE AND FIELD VERIFICATION OF ALL CRITICAL DIMENSIONS.
2. ALL OUTLETS ARE TO BE INSTALLED 18" MIN. A.F.F. TO THE CENTER OF THE DEVICE PER ADA GUIDELINES UNLESS NOTED OTHERWISE. ALL
EXISTING AND NEW DEVICES + FACE PLATES TO BE WHITE; REPLACE AS REQUIRED.
3. REFER TO DOOR SCHEDULE AND COORDINATE WITH TENANT/OWNER REGARDING POWER LOCATIONS TO ACCOMMODATE ELECTRIC
STRIKES, CARD READERS AND/OR MAG-LOCKS. CARD READERS ARE TYPICALLY INSTALLED BY THE TENANT'S SECURITY CONTRACTOR
AND NOT SPECIFIED BY SDI.
4. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH ALL APPLICABLE CODES.
J
J
B
O
J
+42"
PROVIDE POWER AS REQUIRED AT DOOR FOR CARD READER
(CARD READER BY TENANT). COORDINATE WITH TENANT'S
SECURITY CONTRACTOR. SEE DOOR SCHEDULE FOR MORE
DETAILS.
COORDINATE POWER REQUIREMENTS IN THIS ROOM WITH
TENANT. PROVIDE DEDICATED RECEPTACLES AS REQUIRED.
PROVIDE JUNCTION BOX AND DATA FOR TENANT'S FURNITURE
SYSTEM. COORDINATE EXACT LOCATION WITH TENANT'S
FURNITURE VENDOR.
COORDINATE COPIER RECEPTACLE WITH TENANT. PROVIDE
DEDICATED RECEPTACLE AS REQUIRED.
PROVIDE POWER AND DATA FOR TENANT'S WALL MOUNTED
TELEVISION AT HEIGHT NOTED ON PLAN. COORDINATE EXACT
LOCATION WITH TENANT.
PROVIDE POWER FOR TENANT'S UNDERCOUNTER
REFRIGERATOR AND/OR KEG.
PROVIDE POWER FOR TENANT'S OVERHEAD PROJECTOR +
AUTOMATIC PROJECTOR SCREEN IN THIS AREA. FINAL DETAILS
AND LOCATION TO BE COORDINATED WITH TENANT.
PROVIDE DIRECT HDMI/VGA CONDUIT CONNECTION FROM
FLOOR CORE POKE THRU DEVICE TO WALL MOUNTED
MONITOR(S).
PROVIDE FLUSH MOUNT FLOOR CORE WITH POKE THRU DEVICE
FOR ELECTRICAL AND/OR JUNCTION BOX + DATA.
COORDINATE WITH TENANTS FURNITURE VENDOR ON EXACT
LOCATION. PROVIDE POKE THRU DEVICE SUBMITTAL TO
TENANT FOR APPROVAL PRIOR TO ORDERING.
OUTLETS AT THIS LOCATION TO BE INSTALLED HORIZONTALLY.
ALL ABOVE COUNTER OUTLETS ARE FOR DEDICATED
APPLIANCE USE ONLY. CONVENIENCE OUTLETS ARE LOCATED
ELSEWHERE IN ROOM.
PROVIDE JUNCTION BOX
ABOVE CEILING FOR
POWER POLE
CONNECTION. POWER
POLE BY OTHERS.
LIGHT CIRCUIT
LIGHT SWITCH, 3-WAY
DIMMER
LIGHT SWITCH, DIMMERN
N3 3
EXIT LIGHT FIXTURE
CEILING GRID,
SUSPENDED, 2'x2'
NEW OR RELOCATED EXISTING TO REMAIN
LIGHT FIXTURE,
PENDANT
LIGHT FIXTURE, 1'x4',
FLUORESCENT, INDIRECT
EXIT LIGHT FIXTURE
LIGHT CIRCUIT
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
GYPSUM BOARD CEILING
LIGHT FIXTURE, 2'x2',
FLUORESCENT, PARABOLIC
LIGHT FIXTURE, 2'x4',
FLUORESCENT, PARABOLIC
RCP LEGEND
RECESSED LIGHT
FIXTURE
EMERGENCY LIGHT FIXTURE EMERGENCY LIGHT FIXTURE
EXHAUST FAN, 2'x2'
EXPOSED TO DECK
1. WHERE SHOWN, PROVIDE NEW 2'x2' 916" CEILING GRID AND 2'x2' FINE
FISSURED REVEAL EDGE CEILING TILE (ARMSTRONG DUNE, OR
SIMILAR). GRID TO BE INSTALLED AT 9'-0" AFF.
2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI
OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT
IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI.
4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS; PROVIDE COMBO
UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A
ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE
LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF
INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED
OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
5. EXISTING AND NEW DEVICES AND FACE PLATES TO BE WHITE;
REPLACE AS REQUIRED. WHERE POSSIBLE, GANG MULTIPLE SWITCHES
TO ACCOMMODATE MULTI-SWITCH PLATE WHEN SWITCHES ARE
SHOWN ADJACENT ON PLAN.
6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS. ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND
LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH
ALL APPLICABLE CODES.
7. PROVIDE SOUND DAMPERS IN HVAC SYSTEM SUCH THAT SOUND
TRANSMISSION BETWEEN ROOMS IS REDUCED.
8. EXHAUST FAN IN RESTROOM TO BE TIED INTO SWITCH FOR LIGHT
FIXTURE SUCH THAT SWITCH CONTROLS BOTH. SPECIFICATION FOR
EXHAUST FAN MUST BE APPROVED BY TENANT PRIOR TO ORDERING.
9. PROVIDE SEPARATE PRICE FOR (25) ARMSTRONG TECTUM
DIRECT-ATTACH ACOUSTICAL CEILING PANELS; 24X48, VERTICAL LINE
DESIGN, WHITE. IF SEPARATE PRICE IS ACCEPTED, COORDINATE WITH
SDI ON INSTALLATION LOCATIONS.
GENERAL NOTES
LIGHT FIXTURE, LED
PENDANT - KUZCO
LIGHTING MONAE -
MEDIUM SIZE. MOUNT AT
8'-0" TO BOTTOM OF
FIXTURE.
LIGHT FIXTURE, 2'x4', LED,
COLUMBIA LIGHTING
LCAT, 3500K (OR EQUAL)
LIGHT FIXTURE,
FINELITE HP-2 I/D (OR
EQUAL),
MOUNT AT 9'-0" AFF TO
BOTTOM OF FIXTURE. SEE
LENGTH OF FIXTURE AS
NOTED ON PLAN.
LIGHT FIXTURE, 6" LED CAN
LIGHT; 3500K
PROVIDE FLUSH MOUNT FLOOR CORE WITH POKE THRU DEVICE
FOR ELECTRICAL AND/OR JUNCTION BOX + DATA. INTENT IS
FOR POKE THRU DEVICE AT THIS LOCATION TO BE COMPLETELY
FLUSH WITH ADJACENT FLOOR AND CONCEAL POWER AND
DATA BELOW. COORDINATE WITH TENANT + TENANT'S
FURNITURE VENDOR ON EXACT LOCATION. PROVIDE POKE
THRU DEVICE SUBMITTAL TO TENANT FOR APPROVAL PRIOR TO
ORDERING.
AT EXISTING STEEL COLUMN, COORDINATE WITH TENANT ON
EXACT TV SPECIFICATIONS AND PROVIDE APPROPRIATE
POWER + DATA, CONDUIT, AND J-BOX AS REQUIRED FOR
TELEVISION. COORDINATE MOUNTING HEIGHT WITH TENANT.
PROVIDE POWER AS REQURED FOR TENANT'S WATER MACHINE
AND UNDERCOUNTER REFRIGERATOR AT THIS LOCATION.
1
1
2