HomeMy WebLinkAboutLSDWx
OFFICE
204
11'-0"8'-6"
x
SERVER
227
8'-3"4'-10"
x
STG/
FILES
216
12'-2"19'-6"
CFO
OFFICE
225
430 SF
x
OFFICE
206
11'-0"8'-6"
x
CONFERENCE
202
23'-9"16'-0"
ENTRY
201
x
OFFICE
211
9'-8"12'-6"
x
OFFICE
212
10'-1"12'-8"
COPY
208
OPEN OFFICE
209
x
OFFICE
205
11'-0"8'-6"
x
CONFERENCE
213
10'-0"11'-0"
x
OFFICE
203
11'-0"8'-4"
DW
x
OFFICE
215
9'-9"12'-7"
x
BREAK
210
27'-5"13'-0"
x
CONFERENCE
224
14'-7"15'-5"
CEO
OFFICE
222
443 SF
x
EXEC
OFFICE
221
11'-0"15'-10"
x
CONFERENCE
207
13'-11"12'-10"
x
RR
226
6'-7"8'-2"COPY/
COFFEE
220
EXEC
ENTRY
219
COPY
214
RR
228
43 SF
x
OFFICE
217
14'-9"13'-0"
x
EXEC
OFFICE
218
18'-2"13'-11"FEFEICENLEL
NLEL
NLEL
NLEL
NLEL
NLELFE
LIFE SAFETY
PLAN
L100LIFE SAFETY PLAN
DESCRIPTIONDATE
ISSUE
08.31.20 75% REVIEW SET
09.02.20 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700PROJECT NUMBER
DRAWN BYPROJ. MGR STERLING INVESTORSLIFE INSURANCEMERIDIAN TOWER - SUITE 24010201 N. ILLINOIS ST, INDIANAPOLIS, IN 46290MSSDH/MS
2020.162
2ND FLOOR
N
4. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
5. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
L1. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DETAILS.
L2. EXISTING EXIT SIGNS, FIRE PULLS, FIRE EXTINGUISHERS, ALARM
NOTIFICATION APPLIANCES TO REMAIN. RELOCATE EXISTING EXIT
SIGNS, FIRE PULLS, FIRE EXTINGUISHERS AND ALARM NOTIFICATIONS AS
REQUIRED TO MEET ALL LOCAL AND STATE CODES.
GENERAL NOTES
0 8'16'4'
EXISTING ELECTRICAL PANEL LOCATION
EXISTING EXIT
EP
EX
LEGEND
FIRE EXTINGUISHER
EXIT SIGN
FE FE
- BUILDING STAIR LOCATION
AREA NOT IN CONTRACT
AREA OF WORK
TRAVEL DISTANCE
SCOPE OF WORK OFFICE REMODEL OF PREVIOUSLY BUILT-OUT OFFICE SPACE
TOTAL BUILDING AREA
TOTAL PROJECT AREA
CHANGE OF OCCUPANCY CLASS?
OCCUPANCY CALCULATIONS SPACE TYPE AREA SF PER OCCUPANT OCCUP LOAD
NO
OCCUPANCY CLASSIFICATION B(USINESS)
GEN. OFFICE SF 100
NUMBER OF EXITS REQUIRED: 2 PROVIDED: 2
SPRINKLER SYSTEM (YES/NO) YES - EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES 0
TOTAL AREA ON THE FLOOR
SF
SF/FLOOR X STORIES SF
SF
SF
ACCESSORY AREA EXCEEDS 10% NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
N/A
=
TOTAL OCCUPANTS IN PROJECT AREA 72
CODE SUMMARY
PREVIOUS USE OF SPACE B(USINESS)
ASHRAE 90.1 SUMMARY REQUIREMENTS WILL BE MET (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 1978? NO
7,132
7,132
72
- LED EDGE LIT
BUILDING CONSTRUCTION TYPE
1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
LIFE SAFETY NOTES
BUSINESS
(OPEN TO BELOW)
BUSINESS
BUSINESS
TRAVEL DISTANCE = 159'
22,357
22,357 6 134,142
II-A
EX
EX
EP
EP
NIGHT LIGHT/EMERGENCY LIGHTING NLEL
10/02/20