HomeMy WebLinkAboutA010.1REFLECTED
CEILING PLAN
A121
CONTROL COPY 208, OPEN OFFICE 209, AND COPY 214 LIGHTING
WITH 3-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE
SWITCHES AS REQUIRED.
CONTROL EXEC ENTRY 219 AND COPY/COFFEE 220 LIGHTING
WITH 3-WAY SWITCH AT THIS LOCATION. PROVIDE MULTIPLE
SWITCHES AS REQUIRED.
ACOUSTICAL CEILING (TILES AND GRID) IN ENTRY 201 TO BE
PAINTED PT3. REFER TO FINISH LEGEND FOR ADDITIONAL
INFORMATION.
IN AREA TO BE EXPOSED TO DECK, REPLACE LOW PRESSURE
SUPPLY BRANCH LINE DUCT AND WITH NEW RIGID SPIRAL DUCT
AND RECTANGULAR SUPPLY DIFFUSERS AS REQUIRED. CLEAN AND
PREPARE FOR DRYFALL PAINT (PT4). AS SPECIFIED, PAINT EXISTING
EXPOSED CEILING DECK, EXPOSED DUCTWORK, SPRINKLER PIPING,
JUNCTION BOXES, CONDUIT, STRUCTURAL BEAMS FIREPROOFING,
ETC. IN ACCORDANCE WITH NFPA 13 6.3.8.
CEILING CLOUD TO BE INSTALLED AT 10'-0". AT PERIMETER,
PROVIDE 4" AXIOM TRIM (WHITE).
CLOUD TO BE INSTALLED AT 9'-0". CONFIRM HEIGHT WITH TENANT.
DRYWALL BULKHEAD TO ALIGN WITH CORNER IN THIS LOCATION.
BOTTOM OF BULKHEAD TO BE AT 8'-0".
TRANSITION FROM CEILING GRID TO EXPOSED CEILING TO BE A
DRYWALL BULKHEAD EXTENDING FROM 1" BELOW ACOUSTICAL
CEILING TO DECK. TRANSITION TO BE A CLEAN VERTICAL
BULKHEAD, FINISHED SUCH THAT CONTRASTING PAINT COLORS
CAN EASILY AND CLEANLY CUT AT WALL TO CEILING LINE.
VERTICAL FACE OF DRYWALL TO BE PAINTED COLOR OF
ADJACENT WALL.
CONFIRM INSTALLATION LOCATION AND MOUNTING HEIGHTS
WITH TENANT IN FIELD.
PROVIDE UNDER CABINET LIGHT FIXTURES AT FULL LENGTH OF
UPPER CABINETS, CONTROLLED WITH SEPARATE SWITCH. SEE
ELEVATION FOR MORE INFORMATION.
LIT MIRROR TO BE ON SAME CIRCUIT AS CAN LIGHTS. CONFIRM
WITH TENANT.
PROVIDE DRYWALL BULKHEAD AT THIS LOCATION AS REQUIRED
FOR DHIVE WALL SYSTEM. COORDINATE WITH MANUFACTURER AS
REQUIRED.
ABOVE COUNTER SWITCH TO BE INSTALLED HORIZONTALLY.
PLAN NOTES
LIGHT CIRCUIT
LIGHT SWITCH, DIMMER
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
ND
N
N3
D
3
EXIT LIGHT FIXTURE -
LED EDGE LIT
LIGHT FIXTURE,
PENDANT (PROVIDED
BY TENANT)
RECESSED LIGHT
FIXTURE, LED
LIGHT FIXTURE, 2'x2',
BUILDING STANDARD LED
LIGHT FIXTURE, 2'x4',
BUILDING STANDARD LED
RELOCATED DIFFUSER,
LAY-IN, 2'x2'
CEILING GRID,
SUSPENDED, 2'x2' -
ARMSTRONG - LYRA -
GRID TO BE 9/16 IN SILVER,
TILES TO MATCH PT3
NEW OR RELOCATED EXISTING TO REMAIN
WALL SCONCE LIGHT
FIXTURE (PROVIDED BY
TENANT)
EXIT LIGHT FIXTURE
LIGHT CIRCUIT
LIGHT SWITCH, DIMMER
LIGHT SWITCH, 3-WAY
LIGHT SWITCH
CEILING GRID,
SUSPENDED, 2'x2'
DIFFUSER,
LAY-IN, 2'x2'
CEILING GRID,
SUSPENDED, 4'x4' -
ARMSTRONG LYRA
CONCEALED
CEILING GRID,
SUSPENDED, 4'x4'
GYPSUM BOARD CEILING
LEGEND
REFLECTED CEILING PLAN
RECESSED LIGHT
FIXTURE, LED
WALL SCONCE LIGHT
FIXTURE
DESCRIPTIONDATE
ISSUE
08.31.20 75% REVIEW SET
09.02.20 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700PROJECT NUMBER
DRAWN BYPROJ. MGR STERLING INVESTORSLIFE INSURANCEMERIDIAN TOWER - SUITE 24010201 N. ILLINOIS ST, INDIANAPOLIS, IN 46290MSSDH/MS
2020.162
2ND FLOOR
N
0 2'4' 8' 16'
EMERGENCY LIGHT FIXTURE EMERGENCY LIGHT FIXTURE
MECHANICAL DIFFUSER RELOCATION
A121
1
*REFER TO MECHANICAL NOTES FOR FURTHER INFORMATION
EXISTING VAV BOXES OR
HEAT PUMP AND MAIN SUPPLY
DUCTS TO REMAIN
RELOCATE DIFFUSERS &
FLEXDUCT IF REQUIRED
VAV /
HEAT PUMP
EXHAUST FAN, 2'x2' EXHAUST FAN,
2'x2'
SWITCH, GARBAGE
DISPOSAL (ABOVE
COUNTERTOP)
NG G SWITCH, GARBAGE
DISPOSAL
EXPOSED TO DECK
A121
1
SWITCH, EXHAUST FAN NE E SWITCH, EXHAUST FAN
1. PROVIDE NEW CEILING GRID AND TILE THROUGHOUT. GRID TO BE
10'-0" A.F.F. REFER TO PLAN AND LEGEND FOR MORE INFORMATION.
2. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY. IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN
SUITE, ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI
OR TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT
IN CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. LAYOUT SHOWN IS INTENDED TO MEET ASHRAE 90.1 STANDARDS.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR COMPLIANT
INSTALLATION. IF ADJUSTMENT IS REQUIRED TO MEET ASHRAE 90.1,
CONTRACTOR MUST NOTIFY SDI.
4. ALL NEW SWITCHES TO BE OCCUPANCY SENSORS; PROVIDE COMBO
UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY WITH A
ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE
LOCATED SUCH THAT OCCUPANCY WITHIN ANY PORTION OF
INCLUDED AREA IS DETECTED. PROVIDE CEILING MOUNTED
OCCUPANCY SENSORS IN OPEN AREAS AS REQUIRED.
5. ALL NEW AND EXISTING FACE PLATES TO BE WHITE. WHERE POSSIBLE,
GANG MULTIPLE SWITCHES TO ACCOMMODATE MULTI-SWITCH PLATE
WHEN SWITCHES ARE SHOWN ADJACENT ON PLAN.
6. ELECTRICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS.¬ ALL ELECTRICAL WORK IS LIMITED TO
ADDITIONS OR RELOCATIONS OF ELECTRICAL OUTLET DEVICES AND
LIGHTING THAT DO NOT EXCEED THE CAPACITY OF THE EXISTING
ELECTRICAL SERVICE IN THE BUILDING. ELECTRICAL CONTRACTOR IS
TO NOTIFY APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED
SO THAT ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH
ALL APPLICABLE CODES.
4. CONFIRM INSTALLATION LOCATIONS OF ALL LIGHTING FIXTURES ON
SITE WITH TENANT.
5. TENANT TO CONFIRM ALL DIMMING REQUIREMENTS.
6. PROVIDE SUBMITTALS/SHOP DRAWINGS FOR ALL CEILINGS AND
LIGHTING FIXTURES TO TENANT FOR APPROVAL.
GENERAL NOTES
1. MECHANICAL WORK IS LIMITED TO A DESIGN-BUILD SCOPE AND IS
OUTLINED IN THESE DRAWINGS.¬NO NEW MAIN MECHANICAL
APPLIANCES OR MAIN EQUIPMENT ARE BEING PROVIDED.¬ ALL
MECHANICAL WORK IS LIMITED TO RELOCATION OF DIFFUSERS AND
FLEX DUCT PER NEW WALL LAYOUT. IF IN GOOD CONDITION, EXISTING
H.V.A.C. DIFFUSERS SALVAGED FROM DECONSTRUCTION MAY BE
SUBSTITUTED FOR NEW. NO NEW HARD DUCTWORK OR EQUIPMENT IS
BEING ADDED;¬ MECHANICAL CONTRACTOR IS TO NOTIFY
APPLICABLE PARTIES IF ADDITIONAL WORK IS REQUIRED SO THAT
ADDITIONAL PLANS CAN BE FILED AND MUST COMPLY WITH THE
INDIANA MECHANICAL CODE AND ALL OTHER APPLICABLE CODES.
MECHANICAL NOTES
AREA NOT IN CONTRACT
AREA OF WORK
LIGHT FIXTURE, 2'x2',
BUILDING STANDARD LED
LIGHT FIXTURE, 2'x4',
BUILDING STANDARD LED
LIGHT FIXTURE,
PENDANT (PROVIDED BY
TENANT)
LIGHT FIXTURE,
PENDANT
LIGHT FIXTURE,
PENDANT (PROVIDED
BY TENANT)
LIGHT FIXTURE,
PENDANT (PROVIDED
BY TENANT)
LIGHT FIXTURE,
PENDANT - AXIS - STENCIL -
4'-0" - BLACK (OR EQUAL)
A
LIGHT FIXTURE,
PENDANT - AXIS - BEAM 2 -
8'-0" - WHITE (OR EQUAL)
B
LIGHT FIXTURE,
PENDANT - AXIS - STENCIL -
8'-0" - BLACK (OR EQUAL)
C
LIGHT FIXTURE,
PENDANT - AXIS - STENCIL -
6'-0" - BLACK (OR EQUAL)
D
LIGHT FIXTURE,
PENDANT - AXIS - STENCIL -
LENGTHS VARY - BLACK
(OR EQUAL)
E
SUSPENDED CLOUD -
ARMSTRONG
SOUNDSCAPES -
HEXAGON - 48" - WHITE
LIGHT FIXTURE,
RECESSED - AXIS - BEAM 2
- 6'-0" (OR EQUAL)
F
LIGHT FIXTURE,
RECESSED - AXIS - BEAM 2
- 8'-0" (OR EQUAL)
G
LIGHT FIXTURE,
RECESSED - AXIS - BEAM 2
- 16'-0" (OR EQUAL)
H
A
B
C
D
LIGHT FIXTURE,
PENDANT - AXIS - BEAM 4 -
8'-0" BLACK (OR EQUAL)
J
LIGHT FIXTURE,
RECESSED - AXIS - BEAM 2
- 4'-0" (OR EQUAL)
K
LIGHT FIXTURE,
RECESSED - AXIS - PERFEKT
WALL WASHER - 8'-0" (OR
EQUAL)
L
LIGHT FIXTURE,
RECESSED - AXIS - PERFEKT
WALL WASHER - 4'-0" (OR
EQUAL)
M
A
WALL SCONCE LIGHT
FIXTURE (PROVIDED BY
TENANT)
B
CEILING FAN, CRAFTMADE -
MONDO - 72" - CONFIRM
FINISH WITH TENANT
CONTACT GINA WILLIAMS AT ESL SPECTRUM FOR MORE INFORMATION AND
PRICING ON AXIS FIXTURES - 317-223-2614
10/02/20