LIFE SAFETY
L100LIFE SAFETY PLAN
DESCRIPTIONDATE
ISSUE
08.11.20 REVIEW SET
08.11.20 PERMIT SET
REVISIONS
DESCRIPTIONMARK DATE DB
THIS DRAWING, AND THE IDEAS,
DESIGNS AND CONCEPTS CONTAINED
HEREIN, ARE THE EXCLUSIVE
INTELLECTUAL PROPERTY OF SCHOTT
DESIGN, INC., AND ARE NOT TO BE
USED OR REPRODUCED IN WHOLE, OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF SCHOTT DESIGN.450 E. 96th StreetIndianapolis, IN 46240p: 317.387.1700www.schottdesign.comPROJECT NUMBER
DRAWN BYPROJ. MGR COMMONAREA REMODELTWO PENN MARK - 4TH FLOOR11555 N. MERIDIAN ST. CARMEL, IN 46032EHEH
2020.203
4TH FLOOR
N0 8' 16'4'
AREA NOT IN CONTRACT
AREA OF WORK
LIFE SAFETY NOTES GENERAL NOTES
SCOPE OF WORK REMODEL OF EXISTING COMMON CORRIDOR & RESTROOMS
TOTAL BUILDING AREA
TOTAL PROJECT AREA
CHANGE OF OCCUPANCY CLASS?
OCCUPANCY CALCULATIONS SPACE TYPE AREA SF PER OCCUPANT OCCUP LOAD
NO
OCCUPANCY CLASSIFICATION B(USINESS)
COMMON
CORRIDOR &
RESTROOMS
SF 100
SPRINKLER SYSTEM (YES/NO) YES - EXISTING TO REMAIN
TOTAL AREA OF ACCESSORY USES 0
TOTAL AREA ON THE FLOOR
SF
SF/FLOOR X STORIES SF
SF
19,568 SF
ACCESSORY AREA EXCEEDS 10% NO
FIRE WALLS, AND/OR OCCUPANCY
SEPARATIONS (IF REQUIRED)
N/A
=
TOTAL OCCUPANTS IN PROJECT AREA 13
CODE SUMMARY
PREVIOUS USE OF SPACE B(USINESS)
ASHRAE 90.1 SUMMARY REQUIREMENTS WILL BE MET (SEE REFLECTED CEILING PLAN)
BUILT BEFORE 1978? NO
1,205
1,205
19,568 5 97,840
13
BUILDING CONSTRUCTION TYPE II-B
1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER
NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE REQUIRED IF
THE SPACE CONTAINS 50 PERSONS OR MORE. FIXTURES SHOWN ON
PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND ANY
OTHER REQUIRED ALARM & DETECTION SYSTEMS AS NECESSARY TO
MEET ALL APPLICABLE CODES (INTERNATIONAL BUILDING CODE,
INTERNATIONAL FIRE CODE, NFPA). IN RECEPTION AREAS,
CONFERENCE ROOMS AND OTHER HIGH PROFILE AREAS WITHIN SUITE,
ALL LOCATIONS OF SUCH DEVICES MUST BE APPROVED BY SDI OR
TENANT PRIOR TO INSTALLATION. FAILURE TO DO SO MAY RESULT IN
CONTRACTOR RELOCATING THESE ITEMS AT THEIR EXPENSE.
3. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A COMPLETE,
WORKING SYSTEM. SCHOTT DESIGN, INC., IS NOT RESPONSIBLE FOR
THE DESIGN, INSTALLATION, OR RENOVATION OF THE FIRE SPRINKLER
SYSTEM.
4. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND RELATED
DOCUMENTS, WITH THE STATE AND LOCAL AUTHORITIES HAVING
JURISDICTION OVER THE PROJECT.
5. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA
10. COORDINATE WITH OWNER/LANDLORD ON EXTINGUISHER TYPE
AND HOUSING. MAXIMUM TRAVEL DISTANCE OF 75 FEET FROM ANY
POINT TO A VISIBLE EXTINGUISHER.
L1. REFER TO ARCHITECTURAL PLAN FOR WALL TYPE AND CONSTRUCTION
DETAILS.
L2. EXISTING FIRE PULLS, FIRE EXTINGUISHERS AND ALARM NOTIFICATION
APPLIANCES TO REMAIN. RELOCATE EXISTING FIRE PULLS, FIRE
EXTINGUISHERS AND ALARM NOTIFICATIONS AS REQUIRED TO MEET
ALL LOCAL AND STATE CODES. NEW LED EDGE LIT EXIT SIGNS ARE TO
MEET ALL LOCAL AND STATE CODES.
EXISTING ELECTRICAL PANEL LOCATION
EXISTING EXIT
EP
EX
LEGEND
FIRE EXTINGUISHER
EXIT SIGN
FE
EMERGENCY LIGHT
FE
- BUILDING STAIR LOCATION
TRAVEL DISTANCE
NUMBER OF EXITS REQUIRED: 2 PROVIDED: 2
- LED EDGE LIT
BUSINESS
TRAVEL DISTANCE = 75'-0"
EP
EX
EX
BUSINESS
BUSINESS
10/13/20