HomeMy WebLinkAboutP001 - Water Entrance Riser DiagramPLUMBING GENERAL NOTES
1. INSTALLATION OF PLUMBING FIXTURES AND ACCESSORIES, INCLUDING FLUSH CONTROL VALVES INTENDED FOR
PEOPLE WITH DISABILITIES, SHALL BE IN ACCORDANCE WITH ADA REQUIREMENTS.
2. INSTALLATION OF PLUMBING PIPING SHALL BE FULLY COORDINATED WITH STRUCTURAL, ARCHITECTURAL,
ELECTRICAL, AND HVAC DRAWINGS TO AVOID CONFLICT.
3. NO PLUMBING (WATER, DRAINS, VENT, OR GAS PIPING) SHALL BE INSTALLED DIRECTLY ABOVE ANY ELECTRICAL
PANELS. COORDINATE WITH OTHER DIVISIONS BEFORE PROCEEDING WITH INSTALLATION.
4. IF NON DESIGN BASE EQUIPMENT IS SELECTED, CONTRACTOR SHALL BEAR ADDITIONAL COSTS FOR MODIFICATIONS
TO THE ORIGINAL SYSTEM(S).
5. PROVIDE WATER HAMMER ARRESTERS AT PLUMBING FIXTURES AND GROUPS OF PLUMBING FIXTURES THAT ARE
SUBJECT TO WATER HAMMER. SELECT ARRESTERS IN ACCORDANCE WITH THE PLUMBING AND DRAINAGE INSTITUTE
STANDARD.
6. CONTRACTOR SHALL FURNISH AND INSTALL ALL MATERIALS, LABOR AND EQUIPMENT PERMIT FEES, REQUIRED FOR,
OR INCIDENTAL TO THE INSTALLATION OF A COMPLETE AND OPERATIONAL PLUMBING SYSTEM AS INDICATED IN THE
CONTRACT DOCUMENTS INCLUDING SPECIFICATIONS.
7. ALL PLUMBING SERVICES GOING INTO THE BUILDING AND LEAVING THE BUILDING SHALL BE CONNECTED TO THE SITE
UTILITIES, COORDINATE WITH SITE UTILITIES DWGS. COORDINATE ALL EXTERIOR UNDERGROUND PLUMBING WORK
WITH THE SITE UTILITIES BEFORE COMMENCING WORK. COORDINATE ALL UNDERGROUND PIPING WITH FOUNDATION
DRAWINGS.
8. ALL PLUMBING WORK SHALL BE IN CONFORMANCE WITH THE INTERNATIONAL PLUMBING CODE, LATEST EDITION
ADOPTED BY THE STATE OF INDIANA WITH INDIANA AMENDMENTS, MUNICIPAL OR CITY CODES, AND THE AUTHORITY
HAVING JURISDICTION.
9. INSTALL BALL VALVE CLOSE TO WATER MAIN ON EACH BRANCH AND RISER SERVING PLUMBING EQUIPMENT AND
FIXTURES.
10. CONTRACTOR SHALL PROVIDE ACCESS DOORS, WHETHER SPECIFICALLY IDENTIFIED ON THE SHEETS OR NOT, IN ALL
WALL AND CEILINGS WHERE SERVICE OR ADJUSTMENT TO PLUMBING ITEMS MAY BE REQUIRED. ACCESS DOORS
SHALL BE OF AN APPROPRIATE SIZE REQUIRED FOR EACH APPLICATION. WHERE APPLICABLE, ACCESS DOORS
SHALL MATCH THE FIRE RATING OF THE WALL / CEILING ASSEMBLY.
11. REFER TO DIVISION 23 SPECIFICATIONS FOR FACILITY NATURAL GAS REQUIREMENTS.
12. REFER TO ARCHITECTURAL ROOF DRAWINGS FOR ROOF DIMENSIONS.
13. PROVIDE SIZES TO FIXTURES AS INDICATED ON PLANS, RISERS AND SECTIONS. IF SIZE NOT INDICATED, PROVIDE
SIZE SHOWN ON PLUMBING FIXTURE SCHEDULE.
14. COORDINATE SLEEVING REQUIREMENTS WITH PAN JOISTS WHERE REQUIRED WITH STRUCTURAL DRAWINGS.
15. REFERENCE SECTIONS AND RISER / ISOMETRICS FOR ADDITIONAL INFORMATION ON PIPE SIZES NOT SHOWN IN PLAN
VIEWS.
16. ALL SHUT-OFF VALVES LOCATED ABOVE THE CEILING THROUGHOUT THE BUILDING SHALL BE WITHIN 24" OF THE
CEILING.
17. INSTALLATION OF EQUIPMENT SHALL BE AS PER MANUFACTURER'S WRITTEN RECOMMENDATIONS. IF PLANS OR
DETAILS DIFFER FROM THOSE RECOMMENDATIONS, REQUEST DIRECTION FROM THE ARCHITECT BEFORE
CONTINUING.
COLD WATER
GAS -5,085 CFH
-323 WSFU'S
SANITARY
STORM (ROOF)-26,730 S.F.
-160.5 DFU'S
PLUMBING BASIS OF DESIGN
HOT WATER -65.5 WSFU'S
PLUMBING SYMBOLS
HW
SAN
SAN
DOMESTIC HOT WATER
SANITARY ABOVE GROUND
SANITARY BELOW GROUND
STM
V
STORM ABOVE GROUND
ABOVE GROUND VENT
CW DOMESTIC COLD WATER
SHUT-OFF VALVE (SEE SPECIFICATIONS)
CALIBRATED BALANCING VALVE
CHECK VALVE
V BELOW GROUND VENT
A COMPRESSED AIR
HWR DOMESTIC HOT WATER RETURN
G NATURAL GAS
SINGLE LINE - PIPE DROP
SINGLE LINE - PIPE RISE
SINGLE LINE - PIPE RISE TEE
SINGLE LINE - PIPE DROP TEE
TWO LINE - PIPE DROP
TWO LINE - PIPE RISE
STM STORM BELOW GROUND
HW-140 DOMESTIC HOT WATER (140)
SCW DOMESTIC SOFT COLD WATER
HWR BALANCING VALVE
OR
EQUIPMENT ABBREVIATIONS
AD
CB
DF
DWBP
EWC
FCO
FD
FS
GI
HB
LAV
MS
OI
ORD
RD
RCP
SH
S
TD
TMV
UR
WH
WC
WH
WTS
AREA DRAIN
CATCH BASIN
DRINKING FOUNTAIN
DOMESTIC WATER BOOSTER PUMP
ELECTRIC WATER COOLER
FLOOR CLEAN OUT
FLOOR DRAIN
FLOOR SINK
GREASE INTERCEPTOR
HOSE BIBB
LAVATORY
MOP SINK
OIL INTERCEPTOR
OVERFLOW ROOF DRAIN
ROOF DRAIN
RECIRCULATING PUMP
SHOWER
SINK
TRENCH DRAIN
THERMOSTATIC MIXING VALVE
URINAL
WALL HYDRANT
WATER CLOSET
WATER HEATER
WATER TREATMENT SYSTEM
PLUMBING ABBREVIATIONS
AFF
AFG
BT
BV
CONT
CW
DN
DWG.
ELEV.
FBG
FFA
FFB
G
GPM
HW
HWR
IE
LKW
MAX
MIN
OS&Y
PHE
SAN
STM
SF
TS
TBG
TFA
TFB
TYP
V
VTR
W
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
BRINE TANK
BALANCING VALVE
CONTINUATION
COLD WATER
DOWN
DRAWING
ELEVATION
FROM BELOW GRADE
FROM FLOOR ABOVE
FROM FLOOR BELOW
NATURAL GAS
GALLONS PER MINUTE
HOT WATER
HOT WATER RETURN
INVERT ELEVATION
LAVATORY KITCHEN WASTE
MAXIMUM
MINIMUM
OUTSIDE SCREW & YOKE
PLATE HEAT EXCHANGER
SANITARY
STORM
SQUARE FEET
TEMPERATURE SENSOR
TO BELOW GRADE
TO FLOOR ABOVE
TO FLOOR BELOW
TYPICAL
VENT
VENT THROUGH ROOF
WASTE
REFER TO P2.1
FOR CONTINUATION.
DWBP-2
DWBP-1 4" CW4" CW4" CW
4" CW
4" CW4 " C W
4" OS&Y SHUT-OFF VALVE.
WATER METER PROVIDED BY LOCAL UTILITY COMPANY.
COORDINATE REQUIRED LENGTH NEEDED BETWEEN
SHUTOFF VALVE AND BACKFLOW PREVENTER DEVICE.
Y-STRAINER
RPZ-1
WTS-1
WTS-2
NOTE:
PIPING ISOMETRIC FOR DIAGRAMATIC
PURPOSES ONLY.
PIPE PER MANUFACTURER RECOMMENDATIONS.
BY-PASS LINE FOR DOMESTIC
WATER BOOSTER PUMPS WITH
SHUT-OFF VALVE.
CW LINE TO
TPM-1.
REFER TO P2.1 FOR
CONTINUATION.
4" OS&Y SHUT-OFF VALVE
FOR WATER MAIN AFTER
DWBP (TYP. 2)DLZ INDIANA, LLCDRAWING NUMBERPROJECT NUMBERDATE:APPRV'D:DESIGNED:DRAWN:CHK'D:8/20/2020 2:00:08 PMC:\RevitBackups\2020\1963-1025-90_AdminBldg_MEP_sbhat6T6FS.rvtP0.1COMMUNITY BUILDINGCARMEL CLAY1963-1025-90SSBESAESAJULY 28, 2020SSBGENERAL NOTES, SYMBOLS, AND ABBREVIATIONSPLUMBINGCARMELINDIANABID PACKAGE 2BACKFLOW PREVENTER SCHEDULE
TAG
DESCRIPTION BASIS OF DESIGN NOTES
RPZ 1 REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER: ASSE 1013 APPROVED. MAIN BODY
AND ACCESS COVER SHALL BE EPOXY COATED DUCTILE IRON (ASTM A 536 GRADE 4). THE
SEAT RING AND CHECK VALVE SHALL BE NORYL, THE STEM SHALL BE STAINLESS STEEL
(ASTM A 276) AND THE SEAT DISC ELASTOMERS SHALL BE EPDM.
ZURN WILKINS MODEL
375ADA-4" OR EQUIVALENT.
INSTALL PER MFGR AND WATER
UTILITY REQUIREMENTS
RPZ 2 REDUCED PRESSURE BACKFLOW PREVENTER ASSEMBLY: ASSE 1013 APPROVED. INCLUDES
METERED BY-PASS TO DETECT LEAKS AND UNAUTHORIZED WATER USE. MAIN BODY AND
ACCESS COVER SHALL BE EPOXY COATED DUCTILE IRON (ASTM A 536 GRADE 4). THE SEAT
RING AND CHECK VALVE SHALL BE NORYL, THE STEM SHALL BE STAINLESS STEEL (ASTM A
276) AND THE SEAT DISC ELASTOMERS SHALL BE EPDM.
ZURN WILKINS MODEL
375ADA-2" OR EQUIVALENT
INSTALL PER MFGR
REQUIREMENTS.(10 PSI)
SCALE: NTSP0.1
1 DOMESTIC WATER ENTRANCE RISER DIAGRAM
NO.REVISIONDATE