HomeMy WebLinkAboutEMG-001 - LIGHT FIXTURE SCHEDULE AND GENERAL NOTESREMARKSCATALOG NUMBERMOUNTINGTYPELAMPMANUFACTURERF1 JUNCTION BOXMOUNTTYPICAL LEVEL LIGHT FIXTURE. 3000K, U.L. LISTED FOR WET LOCATIONS, TAMPERPROOF, WITH OCCUPANCY/PHOTO SENSOR CONTROL PROVIDING DUAL LEVEL (50/100%) LIGHTING CONTROL, FUSED, 277V, (65W, 0.24A), COORDINATE COLOR WITH ARCHITECT. SEE NOTE 1 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS.LED3000KLIGHT FIXTURE SCHEDULEF2 POLE MOUNTF3WALL MOUNTTOP LEVEL LIGHT FIXTURE. 3000K, U.L. LISTED FOR WET LOCATIONS, 277V, FUSED, (225W, 0.83A), WITH OCCUPANCY/PHOTO SENSOR PROVIDING DUAL LEVEL (50/100%) LIGHTING CONTROL. 20'-0" MOUNTING HEIGHT, 16'-0" SQUARE STRAIGHT POLE MOUNTED ON 4'-0" COLUMN EXTENSION VALMONT DSS330-400Q160-GRAY OR KW SSP16-4.0-11-KZ41-DM10. POLES ARE TO BE INTERNALLY COATED. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 2 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS. STAIRTOWER/ENTRANCE LIGHT FIXTURE. 3000K, U.L. LISTED FOR WET LOCATIONS. 277V, (52W, 0.19A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT, WITH OCCUPANCY/PHOTO SENSOR PROVIDING DUAL LEVEL (50/100%) LIGHTING CONTROL, FUSED. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 2 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS.220-LED/25W-4K-120-BZ-5110ECLIPSEWALL MOUNTF8ELEVATOR SHAFT LIGHT FIXTURE. 120V, WITH BACK BOX. U.L. LISTED FOR WET LOCATIONS.GENERAL PURPOSE 8'-0" LENGTH UTILITY LIGHT FIXTURE. 277V, (104W, 0.38A), SUSPEND FIXTURE SO BOTTOM OF FIXTURE IS EVEN WITH BOTTOM OF TEE STEMS. U.L. LISTED.CEILINGF6MOUNTCEILINGF6ASURFACEMOUNTGENERAL PURPOSE 8'-0" LENGTH UTILITY LIGHT FIXTURE. 277V, (104W, 0.38A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT. SUSPEND FIXTURE SO BOTTOM OF FIXTURE IS EVEN WITH BOTTOM OF TEE STEMS. U.L. LISTED.SURFACECEILINGF7MOUNTCEILINGF7ASURFACEMOUNTSURFACEGENERAL PURPOSE 4'-0" LENGTH UTILITY LIGHT FIXTURE. 277V, (52W, 0.19A), SUSPEND FIXTURE SO BOTTOM OF FIXTURE IS EVEN WITH BOTTOM OF TEE STEMS. U.L. LISTED.GENERAL PURPOSE 4'-0" LENGTH UTILITY LIGHT FIXTURE. 277V, (52W, 0.19A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT. SUSPEND FIXTURE SO BOTTOM OF FIXTURE IS EVEN WITH BOTTOM OF TEE STEMS. U.L. LISTED.KENALLSPG18-QM-5S-SU-TA-MW-45L-30K8-DCC-DV-FS-TL50DM-TN05 + TL50-RC1TZL1N-L96-14000LM-FST-277-40K-80CRI-WHTZL1N-L96-14000LM-FST-277-40K-80CRI-E7W-WHLITHONIALITHONIAZL1N-L48-7000LM-FST-277-40K-80CRI-WHZL1N-L48-7000LM-FST-277-40K-80CRI-E7W-WHLITHONIALITHONIAORCOLUMBIALCL8-40K-HL-E-UORCOLUMBIALCL8-40K-HL-E-U-ELL14ORCOLUMBIA LCL4-40K-HL-E-UORCOLUMBIA LCL4-40K-HL-E-U-ELL14F4CEILINGSURFACEMOUNTMLHA8-48-F-MW-PP-45L35K-DCC-DV-LEL-FS-9500-TL50-TN05 + TL50-RC1ORKENALLLITHONIA STL4-48L-EZ1-LP830-LSXR1ANL-E10WLCP-SC2-(FUSED)STAIRTOWER/ELEVATOR LOBBY LIGHT FIXTURE. 3000K, VANDAL RESISTANT, FUSED, 277V, (50W, 0.18A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT, DIMMING POWER SUPPLY WITH OCCUPANCY/PHOTO CONTROL SENSOR. U.L. LISTED FOR WET LOCATIONS. PROVIDE (2) TAMPER-PROOF TOOLS. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 3 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS.LED3000KLED3000KLED3000KLED4000KLED4000KLED4000KLED4000KLED4000KORECLIPSE 574-SPL-277-50WLED-3K-WH-FUS-EL10W-CW-MSI3LITHONIAORVCPG-P3-30K-T5M-MVOLT-SRM-SF-NLTAIR2PIR-DWHXDORLEDPATHWAYLITHONIAWALL MOUNTF5JSLEX1R-WL-TP-277LV-S-WB-1-R-277-ELN-4XSINGLE FACE L.E.D. EXIT SIGN WITH SIDE CONDUIT ENTRY. 277V, WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT, VANDAL RESISTANT WITH TWO (2) TAMPERPROOF TOOLS W/ARROWS AS INDICATED ON DRAWINGS. U.L. LISTED FOR WET LOCATIONS.NOT USEDF5AORMULE LIGHTING WLPCX-1-R-WF1A JUNCTION BOXMOUNTTYPICAL LEVEL LIGHT FIXTURE. 3000K, U.L. LISTED FOR WET LOCATIONS, TAMPERPROOF, WITH OCCUPANCY/PHOTO SENSOR CONTROL PROVIDING DUAL LEVEL (50/100%) LIGHTING CONTROL, FUSED, 277V, (65W, 0.24A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 1 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS.LED3000KKENALL SPG18-QM-5S-HSS-SU-TA-MW-45L-30K8-DCC-DV-FS-CEL-TL50DM-TN05 + TL50-RC1LITHONIAORVCPG-P3-30K-T5M-MVOLT-SRM-SF-HS-E8WC-NLTAIR2PIR-DWHXDF3A WALL MOUNTVEHICULAR ENTRANCE LIGHT FIXTURE. 3000K, U.L. LISTED FOR WET LOCATIONS. 277V, (52W, 0.19A), WITH OCCUPANCY/PHOTO SENSOR PROVIDING DUAL LEVEL (50/100%) LIGHTING CONTROL, FUSED. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 2 FOR LIGHTING CONTROL REQUIREMENTS. PROVIDE CONFIGURATION REMOTES REQUIRED FOR ADJUSTING OCCUPANCY/PHOTO SENSORS.LED3000KHUBBELL LIGHTINGSRT2-65-3K7-5WQ-277-WHT-F-NXOS-12F-SRT-MB + SCP-REMOTEORHUBBELL LIGHTING SRT2-65-3K7-5WQ-277-WHT-F-EH-NXOS-12F-SRT-MB + SCP-REMOTEORLITHONIA WDGE3LED-P1-30K-70CRI-R2-MVOLT-SRM-E20WC-NLTAIR2PIR-DWHXDF4ARECESSEDCASSETTEMOUNTLTR-4RD-H-SL15L35K-8-MD-DM1-EM-FPRESCOLITETOP TIER ELEVATOR LOBBY LIGHT FIXTURE. 3500K, VANDAL RESISTANT, FUSED, 277V, (19W, 0.07A), WITH SELF CONTAINED BATTERY PACK RATED FOR BELOW 32 DEGREES FAHRENHEIT, DIMMING POWER SUPPLY. OPEN DOWNLIGHT, 4" DIAMETER APERTURE, CLEAR SPECULAR REFLECTOR, SELF FLANGED. U.L. LISTED FOR WET LOCATIONS. PROVIDE (2) TAMPER-PROOF TOOLS. COORDINATE COLOR WITH ARCHITECT. SEE NOTE 4 FOR LIGHTING CONTROL REQUIREMENTS. LED3500K222LITHONIA WDGE3LED-P1-30K-70CRI-R2-MVOLT-SRM-NLTAIR2PIR-DWHXD3EATONORTT-D4-830-U-WQ-NW-SG-TR-MS/DIM-L20 + FSIR-100EATONORTT-D4-830-U-WQ-NW-IBP-SG-TR-MS/DIM-L20 + FSIR-10044OREATON UX7-1-WH-SD W/ RED LETTERSOREATON B95-LD4-20W-40-CL-120-EDC1-F14OREATON 8TSNLED-LD5-170HL-SLW-UNV-L840-CD1-UOREATON 8TSNLED-LD5-170HL-SLW-UNV-EL14W-L840-CD1-UOREATON 4SNLED-LD5-69HL-SLW-UNV-L840-CD1-UOREATON 4SNLED-LD5-69HL-SLW-UNV-EL14W-L840-CD1-UOREATON FLD4BX15D010IEM14-FEU4B1/28035-F4LBXVM2LIEOREATON HVL12-4-LD4-2LO-30-277-O-EDD1-S-OS2-EL10WORHUBBEL LIGHTING TRP2-24L-70-3K-2-UNV-WHT-SCP-EH + SCP-REMOTEOREATON GWC-AF-02-LED-E1-T2-BZ-F-600-CWB-MS/DIM-L20-7030 + FSIR-100ORHUBBEL LIGHTING TRP2-24L-70-3K-2-UNV-WHT-SCP-EH + SCP-REMOTEOREATON GWC-AF-02-LED-E1-T2-BZ-F-600-MS/DIM-L20-7030 + FSIR-1005CREEMOUNT: OSQ-DA-BZ + LUMINAIRE: OSQ-A-5ME-U-30K-UL-BZ-F-PML2 + XA-SENSREMEATON GLEON-AF-04-LED-E1-5WQ-BZ-MS/DIM-L40W-8030-FUSING + FSIR-100ORLITHONIAORDSX2-LED-P2-30K-T5M-MVOLT-SPA-SF-PIRH-DDBXDHUBBELLORVPL-96L-220-3K7-5W-UNV-A-DBT-SCP/F + SCP-REMOTEORNEW STAR LIGHTING VIC-4-N-L2-30-2C-RW-XXV-WH-DM=PC/OC-EL1-FZX-THORBEGHELLI USA FTZ-SA-LR-U-U-BW-IHORNEW STAR LIGHTING 51CF2-L2-40K-UN-WLLIGHTING CONTROL NOTES1. THE F1 FIXTURES SHALL BE EQUIPPED WITH INDIVIDUAL OCCUPANCY SENSORS CONTROLLING DIMMING (100% HIGH/50% LOW) POWER SUPPLY. THE FIXTURES CONNECTED TO NL CIRCUITS SHALL BE PROGRAMMED TO SWITCH FROM HIGH MODE TO LOW MODE 15 MINUTES AFTER MOVEMENT IS NO LONGER DETECTED. THE FIXTURES CONNECTED TO NORMAL POWER CIRCUITS SHALL BE PROGRAMMED TO SWITCH FROM HIGH TO LOW MODE 5 MINUTES AFTER MOVEMENT IS NO LONGER DETECTED. UPON DETECTING MOVEMENT, FIXTURES ARE TO IMMEDIATELY SWITCH TO HIGH MODE. THE FIXTURES SHALL TURN OFF COMPLETELY WHEN THE LIGHT LEVEL INCREASES TO 20 FOOT CANDLES AND BACK ON (OCCUPANCY SENSOR CONTROLLING FIXTURES) WHEN THE LIGHT LEVEL IS LESS THAN 10 FOOT CANDLES. ADDITIONAL FIXTURES AT VEHICULAR ENTRIES ARE TO BE FULLY ON DURING THE DAY AND OFF FROM DUSK TO DAWN, SEE GROUND TIER PLAN FOR NOTED FIXTURES.2. THE F2, F3 & F3A FIXTURES SHALL BE EQUIPPED WITH INDIVIDUAL OCCUPANCY/PHOTO CONTROL SENSORS CONTROLLING DIMMING (100% HIGH/50% LOW) POWER SUPPLY. THE FIXTURES SHALL BE PROGRAMMED TO SWITCH FROM HIGH MODE TO LOW MODE 15 MINUTES AFTER MOVEMENT IS NO LONGER DETECTED. UPON DETECTING MOVEMENT, FIXTURES ARE TO IMMEDIATELY SWITCH TO HIGH MODE. THE FIXTURES SHALL TURN OFF COMPLETELY WHEN THE LIGHT LEVEL INCREASES TO 10 FOOT CANDLES AND BACK ON (OCCUPANCY SENSOR CONTROLLING FIXTURES) WHEN THE LIGHT LEVEL IS LESS THAN 5 FOOT CANDLES. 3. THE F4 FIXTURES SHALL BE EQUIPPED WITH INDIVIDUAL OCCUPANCY SENSORS CONTROLLING DIMMING (100% HIGH/50% LOW) POWER SUPPLY. THE FIXTURES SHALL BE PROGRAMMED TO SWITCH FROM HIGH TO LOW MODE 5 MINUTES AFTER MOVEMENT IS NO LONGER DETECTED. UPON DETECTING MOVEMENT, FIXTURES ARE TO IMMEDIATELY SWITCH TO HIGH MODE. 4. THE F4A FIXTURES SHALL BE CONTROLLED BY EXTERNAL OCCUPANCY CONTROL SENSOR CONTROLLING DIMMING (100% HIGH/50% LOW) POWER SUPPLY. THE FIXTURES SHALL BE PROGRAMMED TO SWITCH FROM HIGH TO LOW MODE 5 MINUTES AFTER MOVEMENT IS NO LONGER DETECTED. UPON DETECTING MOVEMENT, FIXTURES ARE TO IMMEDIATELY SWITCH TO HIGH MODE.5GENERAL NOTES1. ALL FIXTURES ARE TYPE F1 UNLESS NOTED OTHERWISE. SEE FIXTURE MOUNTING DETAIL 1/EMG-501. SEE LIGHT FIXTURE SCHEDULE ON THIS SHEET.2. LIGHT FIXTURES AND CONDUIT ARE SHOWN IN REFLECTED CEILING ORIENTATION.3. ALL CONDUITS SHALL CONTAIN A GREEN COLORED EQUIPMENT GROUNDING CONDUCTOR PROVIDING CONTINUITY TO ALL BOXES, DEVICES AND FIXTURES. LIGHT FIXTURE CONDUCTORS SHALL BE NO.10 THWN UNLESS NOTED OTHERWISE. ALL HOMERUN CONDUCTOR SIZES SHALL BE AS NOTED ON THE PANEL SCHEDULES. CONDUIT SIZING SHALL BE BASED ON USE OF THWN INSULATION AND NEC REQUIREMENTS.4. ALL ABOVE GROUND CONDUIT SHALL BE SURFACE MOUNTED RIGID HOT DIPPED GALVANIZED STEEL WITH THREADED FITTINGS UTILIZING HOT DIPPED GALVANIZED, CAST, OR MALLEABLE IRON THREADED JUNCTION BOXES AND COVERS. ALL UNDERGROUND CONDUIT SHALL BE PVC MINIMUM CONDUIT SIZE IS 3/4" UNLESS NOTED OTHERWISE. USE SEAL TIGHT FLEXIBLE CONDUIT IN LENGTHS NO GREATER THAN 2'-0" TO CONNECT MOTORS, TRANSFORMERS AND FOR WHIPS CONNECTING TRUNNION MOUNTED FIXTURES TO JUNCTION BOXES. DO NOT INSTALL FLEXIBLE CONDUIT AT OTHER LOCATIONS WITHOUT WRITTEN APPROVAL OF ENGINEER.5. ALL HORIZONTAL CONDUIT RUNS ARE TO BE ROUTED EXPOSED ALONG THE CEILING THRU BLOCK-OUTS IN TEE STEMS AND BEAMS. COORDINATE REQUIRED BLOCK-OUTS IN TEE STEMS AND BEAMS WITH STRUCTURAL ENGINEER. ALL VERTICAL CONDUIT RUNS SHALL BE ROUTED EXPOSED ALONG COLUMNS/WALLS IN PARKING AREAS. HOMERUNS TO ELECTRICAL ROOM ARE TO BE ROUTED DOWN ADJACENT COLUMNS THEN UNDERGROUND TO THE ELECTRICAL ROOM. ALL EXPOSED CONDUIT MUST BE ROUTED UP TIGHT AGAINST THE CEILING, COLUMNS, TEES OR WALLS. NO GAPS WILL BE PERMITTED. (USING BLOCKOUTS OR OTHER STRUCTURAL MEMBERS AS A SOURCE OF SUPPORT IS PROHIBITED. ROUTING CONDUIT UNDER BEAMS WILL NOT BE PERMITTED.) CONDUIT SHALL NOT BE ROUTED BEHIND SIGNS, OR LOCATED SUCH A WAY THAT IT OBSTRUCTS THE OPERATION OF A DEVICE OR RESTRICTS OPENING AN ACCESS POINT, ENCLOSURE DOOR OR ANY OTHER PIECE OF EQUIPMENT.6. AT STAIRS AND ELEVATOR TOWERS RUN CONDUITS BELOW SLAB AND FROM BOTTOM UP AND DO NOT CROSS EXPANSION JOINTS AT SUPPORTED TIERS UNLESS NOTED OTHERWISE. DO NOT ROUTE VERTICAL CONDUIT RISERS THROUGH EXPANSION JOINTS.7. PROVIDE CONDUIT EXPANSION FITTINGS FOR ALL CONDUIT THAT CROSS EXPANSION JOINT AT LOCATIONS REQUIRED.8. DO NOT ENCASE CONDUIT IN SLAB ON GRADE. INSTALL BELOW SLAB ON GRADE AND GRADE BEAMS. 9. THE USE OF POWDER PROPELLED FASTENERS FOR MOUNTING CONDUIT, SUPPORTS, JUNCTION BOXES, FIXTURES OR OTHER EQUIPMENT IS PROHIBITED. 10. PROVIDE APPROVED, HOT DIPPED GALVANIZED STEEL GUARDS AROUND JUNCTION BOXES, CONDUITS AND OTHER EQUIPMENT WHICH MAY BE EXPOSED TO POSSIBLE BUMPER DAMAGE. SEE STRUCTURAL DRAWINGS.11. ALL RECEPTACLES SHALL BE G.F.C.I. TYPE. ALL RECEPTACLES EXCEPT THOSE IN ENCLOSED ROOMS SHALL HAVE WEATHERPROOF COVERS.12. CONDUITS ARE TO BE LOCATED IN THE GARAGE INTERIOR TO MINIMIZE VISUAL IMPACT. DO NOT ROUTE CONDUITS ON THE EXTERIOR OF ANY PART OF THE STRUCTURE. FIXTURES LOCATED ON THE EXTERIOR OF THE STRUCTURE ARE TO BE FED FROM BEHIND WITH NO CONDUIT VISIBLE FROM THE OUTSIDE. FIXTURES LOCATED ON BRICK (INSIDE OR OUTSIDE THE STRUCTURE) ARE TO BE FED FROM BEHIND WITH NO CONDUIT VISIBLE.13. IN LOCATIONS WHERE LIGHT FIXTURES, EXIT SIGNS, FIRE ALARM STROBES OR OTHER PIECES OF EQUIPMENT NEED TO BE MOUNTED TO A COLUMN OR WALL OVER PIPING OR OTHER OBSTACLES, PROVIDE EXTENSION BRACKETS MADE OUT OF 1/4" HOT DIPPED GALVANIZED STEEL PLATES AS REQUIRED.14. PARKING STRUCTURE IS DESIGNED FOR A ONE BAY HORIZONTAL EXPANSION TO THE EAST. PROVIDE ALL ELECTRICAL PROVISIONS FOR FUTURE EXPANSION.15. NOT USED.16. ALL EQUIPMENT SELECTIONS THROUGHOUT ARE BASED ON ROOMS, CONTAINING EITHER HEATING OR COOLING EQUIPMENT, THAT HAVE A THERMAL ENVELOPE IN ACCORDANCE WITH THE INDIANA ENERGY CONSERVATION CODE 2010 (VIA ASHRAE 90.1-2007); CLIMATE ZONE 5A.THE ARCHITECT/ENGINEER OF RECORD SHALL BE NOTIFIED AS SOON AS POSSIBLE IF THE FOLLOWING MINIMUM INSULATION REQUIREMENTS ARE NOT MET:A. ROOF, INSULATION ENTIRELY ABOVE DECK -R-20 CONTINUOUS INSULATIONB. MASS WALL, ABOVE GRADE -R-11.4 CONTINUOUS INSULATIONC. STEEL-FRAMED WALL, ABOVE GRADE -R-13 BETWEEN STUDS PLUS R-7.5 CONTINUOUS INSULATIOND. WALL, BELOW GRADE –7.5 CONTINUOUS INSULATIONE. MASS FLOOR/CEILING -R-10.4 CONTINUOUS INSULATIONF. SWINGING DOORS -U-0.70G. FENESTRATION:a. METAL FRAMING, FIXED:• U-0.45• MAX SHGC -0.40• MIN VT/SHGC -1.10b. METAL FRAMING, ENTRANCE DOOR:• U-0.80• MAX SHGC -0.40• MIN VT/SHGC -1.10244HIGH REACTANCE HIGH POWER FACTOR BALLASTCONSTANT WATTAGE AUTO-TRANSFORMERA OR AMPAMPEREHX-HPFGRDAFFBBCKT/CCIPCARCHCWAEJDIADETCONCGFCICOMMJBHPHZPCKWKVAINCANDGT, T2GROUNDCAST IN PLACECONDUCTORBACKBOARDCONDUITCIRCUITGROUND FAULTCONCRETEDIAMETERDETAILJUNCTION BOXINCANDESCENTHORSEPOWERHERTZKILOWATTTIER DESIGNATION: GROUNDPHOTOELECTRIC CONTROLKILOVOLT-AMPERETIER, 2ND TIER, ETC.CIRCUIT INTERRUPTERABOVE FINISHED FLOORARCHITECT (ARCHITECTURAL)EXPANSION JOINTCOMMUNICATIONSPARCS PARKING ACCESS & REVENUE CONTROL SYSTEMW/PHPNLSIMRCSHTRECEPTSPSWSTRUCTTFBSOGTFATYPULWVTRANSUNOWPWITHSIMILARPHASEPANELSHEETRECEPTACLEWATTTYPICALTRANSFORMERVOLTSWITCHSTRUCTURALWEATHERPROOFUNLESS NOTED OTHERWISEUNDERWRITER'S LABORATORIESRIGID METAL CONDUITSLAB ON GRADESTATIC PRESSURETO FLOOR ABOVETO FLOOR BELOWELECTRICAL ABBREVIATIONSELECTRICAL SYMBOLSLIGHT FIXTURE (NL) CONNECTED TO EMERGENCY POWERLINEAR LED FIXTURE (NL) CONNECTED TO EMERGENCY POWERSTRIP LED FIXTUREWALL MOUNTED FIXTUREPOLE MOUNTED FIXTURE EMERGENCY LIGHT CONNECTED TO EMERGENCY POWEREXIT SIGN CONNECTED TO EMERGENCY POWERPHONEDISCONNECT SWITCHFUSED DISCONNECT SWITCHLIGHT FIXTUREF1, F2, ETC. = FIXTURE TYPEC, D, NL, ETC. = SWITCHINGMOUNT SO TOP OF UNIT IS 6" BELOW BOTTOM OF TEE STEMS BUT NEVER HIGHER THAN 9'-0" A.F.F.DATA OUTLETELECTRIC UNIT HEATEREXHAUST FANINTAKE LOUVEREMERGENCY PHONECCTV FIXEDCCTV PTZEFEUH-A/C UNITELECTRICAL SYMBOLSFIRE ALARM PULL STATIONINDICATES DIRECTION OF AIR FLOWJUNCTION BOXQUAZITE JUNCTION BOXMOTORSTARTERKEY OPERATED SWITCHPHOTOELECTRIC CONTROLSMOKE DETECTORHEAT DETECTORCARBON MONOXIDE DETECTORTHERMOSTAT20 AMP DUPLEX RECEPTACLEMOUNT 18" A.F.F. EXCEPT IN PARKING AREAS MOUNT 36" A.F.F.GROUND RODELECTRICAL PANELVERTICAL CONDUITEXPOSED CONDUITCONCEALED CONDUITOCCUPANCY SENSORFIRE ALARM HORN/STROBEPSHJSKOCJDTCOMSS3LIGHT SWITCH3 WAY LIGHT SWITCHSHEET TITLESHEET NUMBERCARMEL CLAY PUBLIC LIBRARY55 4th Ave. SECarmel, IN 46032317-814-3900OwnerRATIO Architects, Inc.101 South Pennsylvania StreetIndianapolis, Indiana 46204317-633-4040ArchitectCE Solutions, Inc.Structural EngineerMechanical / Electrical EngineerCivil Engineer10 Shoshone DriveCarmel, IN 46032317-818-1912KBSO Consulting, LLC1344 South Rangeline, Suite 202Carmel, IN 46032317-344-8044Civil & Environmental Consultants, Inc.530 E. Ohio Street, Suite GIndianapolis, IN 46204317-655-7777PROJECT NO.COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO ARCHITECTS, INC. NO OTHER USE, DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO ARCHITECTS, INC. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.SHEET ISSUESEAL | DATE Technology DesignDesign 271650 East 49th StreetIndianapolis, IN 46205317-536-8000Garage ConsultantWalker Consultants6602 East 75th Street, Suite 210Indianapolis, IN 46250317-842-68908/20/2020 9:03:37 AMEMG-001LIGHT FIXTURESCHEDULE ANDGENERAL NOTES13-3431.00CARMEL CLAYPUBLIC LIBRARYRENOVATION55 4th Ave SECarmel, IN 460321 100% CONSTRUCTION DOCUMENTS 7/14/20202 STATE SUBMISSION SET 7/17/20203 ADDENDUM 1 8/3/20204 ADDENDUM 2 8/11/20205 ADDENDUM 5 8/20/2020