HomeMy WebLinkAboutEMG-410 - NORTH STAIR-ELEVATOR PLANSHSSSKSKTEUH-DHSTEUH-DHOCSTTG1GBG3G2GA.3F4F4F4F4 F4JJT.F.A.JT.F.A.JT.F.A.F5T.F.A.F4F4 F4F4F5F7ALP1-23PZ1-6ELEVATOR MACHINEROOMF8F8F8 F8F8F8JJPZ1-8PZ1-2PZ1-4TO PUMP CONTROL AND MONITORING ASSEMBLY IN PIT LP1-11RP1-17LP1-13LP1-11456141011121378PZ1691521AH-123PZ1-5/726MDP-4PZ1-1JRP1-21J27J28J29J28J3036201952G1GBG3G2GA.3F4F4F4 F4JJT.F.A.T.F.B.T.F.A.T.F.B.JT.F.A.T.F.B.F5F5T.F.A.T.F.B.F7ALP1-23RP1-31IT CLOSET1651021AH-223LP1-825RP1-23RP1-25DEDICATED DUPLEX RECEPTACLE MOUNTED 5'-0" A.F.FDEDICATED QUAD RECEPTACLE MOUNTED 5'-0" A.F.F24J28J29J30DATA OUTLET362019G1GBG3G2GA.3F4F4F3JT.F.B.JT.F.B.JT.F.B.F5F5JF4AF4AF4AF4AF7ASTORAGE ROOMLP1-23RP1-315105317T.F.B.201921AH-323J28J29F4AF4AJRP1-2727J27RP1-27J30J30RP1-29HVAC SERVICE RECEPTACLEEF-233343531GV-11822RP1-14/16HP-13636F335SHEET NOTES#1. CONNECT ALL LIGHT FIXTURES IN STAIR MAIN LANDINGS TO CIRCUIT LP1-11. CONNECT ALL FIXTURES IN STAIR INTERMEDIATE LANDINGS TO CIRCUIT LP1-13. CONNECT EXIT SIGN TO NEAREST STAIR CIRCUIT.2. SEAL ALL OPENINGS IN TOP OF ALL F4 LIGHT FIXTURES BEFORE MOUNTING IN PLACE.3. MOUNT F3 FIXTURES 10'-0" A.F.F. FIXTURES ARE TO BE FED THROUGH CONCRETE WITH EMBEDDED CONDUIT. COORDINATE WITH GENERAL CONTRACTOR.4. LOCATE LIGHTS, LIGHT SWITCH, AND G.F.C.I. RECEPTACLE IN ELEVATOR PIT. MOUNT LIGHT SWITCH AND RECEPTACLE ADJACENT TO ENTRANCE OR LADDER.5. WIRE SMOKE AND HEAT DETECTORS TO ELEVATOR RECALL AND SUPERVISORY PANEL IN ELECTRICAL ROOM. RUN CIRCUIT WITH DRY CONTACT OUTPUTS FROM ELEVATOR RECALL AND SUPERVISORY PANEL TO ELEVATOR SEQUENCING EQUIPMENT. COORDINATE INSTALLATION WITH ELEVATOR INSTALLER.6. 1" CONDUIT TO ELEVATOR RECALL AND SUPERVISORY PANEL IN ELECTRICAL ROOM.7. 30 AMP, 120 VOLT, FUSED DISCONNECT SWITCH. SQUARE D CATALOG No H221N (COORDINATE FUSE SIZE AND EXACT LOCATION OF DISCONNECT SWITCH WITH ELEVATOR MANUFACTURER). FOR 120V ELEVATOR CAR POWER. (ELEVATOR INSTALLER WILL CONTINUE CIRCUIT TO ELEVATOR CAR.8. 100 AMP, 3 PHASE, 480 VOLT, FUSED DISCONNECT SWITCH. SQUARE D CATALOG No H363N WITH AUXILIARY CONTACTS (COORDINATE FUSE SIZE AND EXACT LOCATION OF DISCONNECT WITH ELEVATOR MANUFACTURER). FOR 480V ELEVATOR POWER.9. 2-1" CONDUITS TO COMMUNICATIONS BACKBOARD IN ELECTRICAL ROOM.10. CONNECT F7A FIXTURES PER MANUFACTURERS INSTRUCTIONS SO IT IS SWITCHABLE BUT WILL AUTOMATICALLY TRANSFER TO BATTERY POWER UPON LOSS OF AC POWER. 11. SUPPLY WEATHERPROOF KEY OPERATED SWITCH FOR OIL DETECTION CONTROL PANEL, MOUNTED NEXT TO OIL DETECTION CONTROL PANEL IN A JUNCTION BOX. HARDWIRE PANEL TO SWITCH. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.12. SUPPLY WEATHERPROOF KEY OPERATED SWITCHES FOR SUMP PUMP AND HEAT TRACING, MOUNT SWITCHES 1'-0" ABOVE PIT COVER IN A JUNCTION BOX. HARDWIRE SUMP PUMP AND HEAT TRACE TO SWITCHES. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.13. OIL DETECTION CONTROL PANEL. MOUNT TOP OF PANEL 6" BELOW CEILING ABOVE. ROUTE ONE 3/4" CONDUIT TO KEY OPERATED SWITCH FOR POWER, ONE 3/4" CONDUIT TO PUMP CONTROL/MONITORING ASSEMBLY IN SUMP PIT AND ONE 3/4" CONDUIT TO WEATHERPROOF SIMPLEX RECEPTACLE IN ELEVATOR PIT. SEE PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.14. HORN/STROBE. MOUNT HORN/STROBE 80" A.F.F. DO NOT ROUTE CONDUIT RISERS IN EXPANSION JOINT. SEE ELEVATOR RECALL RISER DIAGRAM ON SHEET E-601 FOR ADDITIONAL INFORMATION.15. AH-1 DUCT FREE SPLIT SYSTEM HEAT PUMP, 18,000 BTU COOLING, 19,000 BTU HEATING, 208V, SINGLE PHASE, WITH CONDENSATE PUMP, HARD WIRED THERMOSTAT. FRIEDRICH HIGH WALL MOUNT UNIT INDOOR MODEL NO. FPHFW18A3A WITH HARD WIRED CONTROLS. PROVIDE ALL NECESSARY ACCESSORIES REQUIRED TO INSTALL FAN COIL UNIT AT LOCATION SHOWN ABOVE DOOR. PROVIDE ALL SUPPORT AND MOUNTING HARDWARE REQUIRED.16. AH-2 DUCT FREE SPLIT SYSTEM HEAT PUMP, 7,000 BTU COOLING, 8,000 BTU HEATING, 208V, SINGLE PHASE, WITH CONDENSATE PUMP, HARD WIRED THERMOSTAT. FRIEDRICH HIGH WALL MOUNT UNIT INDOOR MODEL NO. FPHMW07A3A WITH HARD WIRED CONTROLS. PROVIDE ALL NECESSARY ACCESSORIES REQUIRED TO INSTALL FAN COIL UNIT AT LOCATION SHOWN ABOVE DOOR. PROVIDE ALL SUPPORT AND MOUNTING HARDWARE REQUIRED.17. AH-3 DUCT FREE SPLIT SYSTEM HEAT PUMP, 18,000 BTU COOLING, 20,400 BTU HEATING, 208V, SINGLE PHASE, WITH CONDENSATE PUMP, HARD WIRED THERMOSTAT. FRIEDRICH RECESSED CASSETTE MOUNT UNIT INDOOR MODEL NO. FPHFC18A3A WITH HARD WIRED CONTROLS. PROVIDE ALL NECESSARY ACCESSORIES REQUIRED TO INSTALL FAN COIL UNIT AT LOCATION SHOWN. PROVIDE ALL SUPPORT AND MOUNTING HARDWARE REQUIRED.18. HP-1 DUCT FREE SPLIT SYSTEM HEAT PUMP OUTDOOR UNIT, 208V, SINGLE PHASE, MOUNT OUTDOOR UNIT ON ICE AND SNOW STAND. FRIEDRICH OUTDOOR UNIT MODEL FPHMR36A3A. COORDINATE WITH GENERAL CONTRACTOR AND HVAC INSTALLER. 19. TWO 3/4" CONDUITS. ONE CONDUIT ROUTE 5-#10 FOR CONTROL WIRING AND ONE CONDUIT FOR THERMISTOR CABLES. INSTALL EXPANSION LOOP WHERE LINE CROSSES BUILDING EXPANSION JOINT. COORDINATE REQUIREMENTS WITH HVAC INSTALLER.20. REFRIGERANT TUBING. ROUTE REFRIGERANT TUBING IN A PVC CONDUIT, FOR PROTECTION OF TUBING, FROM THE INDOOR UNIT TO THE OUTDOOR UNIT. COORDINATE SIZE OF CONDUIT WITH HVAC INSTALLER.21. ROUTE CONDENSATE 1" PVC DRAIN LINE ALONG CEILING THEN DOWN WALL AND TERMINATE 6" ABOVE FLOOR.22. 60 AMP, 240V, NEMA 3R FUSED DISCONNECT SWITCH FOR HVAC OUTDOOR UNIT WITH 50A FUSE. SQUARE D CATALOG NO.H222NRB. COORDINATE FUSE SIZE AND EXACT LOCATION OF DISCONNECT SWITCH WITH HVAC INSTALLER. FOR HVAC 208V POWER. 23. 30 AMP, 240V, FUSED DISCONNECT SWITCH FOR HVAC INDOOR UNIT. SQUARE D CATALOG NO.H221N. COORDINATE WITH HVAC INSTALLER. 24. ONE 4" CONDUIT FROM IT CLOSET TO STUB LOCATION LOCATED AT BRIDGE CEILING PER LIBRARY PER DRAWINGS T300 AND T301 FOR COMMUNICATIONS. COORDINATE EXACT CONNECTION POINT WITH TECHNOLOGY DRAWINGS.25. EUH CHROMALOX UNIT HEATER, 2.6 KW, 277V, SINGLE PHASE, WITH INTEGRAL THERMOSTAT/DISCONNECT SWITCH. CATALOG No. LUH-02-71-35. MOUNT NEAR CEILING. SET THERMOSTAT AT 50°F.26. EUH CHROMALOX UNIT HEATER, 2.6 KW, 208V, SINGLE PHASE, WITH INTEGRAL THERMOSTAT/DISCONNECT SWITCH. CATALOG No. LUH-02-81-35. MOUNT NEAR CEILING. SET THERMOSTAT AT 50°F.27. JUNCTION BOX AND CONDUIT FOR DOOR OPERATOR POWER. COORDINATE WITH ARCHITECT AND DOOR INSTALLER.28. CAMERA LOCATION. PROVIDE JUNCTION BOX AND ROUTE ONE 1" CONDUIT TO SECRUITY EQUIPMENT IN IT CLOSET ON SECOND TIER. COORDINATE EXACT LOCATION AND DETAILS WITH CAMERA INSTALLER. CAMERA AND COMMUNICATION CABLING BY OTHERS. SEE TECHNOLOGY DRAWINGS FOR EXACT EQUIPMENT LOCATIONS AND ADDITIONAL INFORMATION.29. EMERGENCY SPEAKER PHONE LOCATION. PROVIDE JUNCTION BOX AND ROUTE ONE 1" CONDUIT TO SECURITY EQUIPMENT IN THE IT CLOSET ON SECOND TIER. COORDINATE EXACT LOCATION AND DETAILS WITH PHONE INSTALLER. PHONE AND COMMUNICATION CABLING BY OTHERS. SEE TECHNOLOGY DRAWINGS FOR ADDITIONAL INFORMATION.30. CARD READER LOCATION. PROVIDE JUNCTION BOX AND ROUTE ONE 1" CONDUIT TO SECRUITY EQUIPMENT IN IT CLOSET ON SECOND TIER. COORDINATE EXACT LOCATION AND DETAILS WITH CARD READER INSTALLER. CARD READER AND COMMUNICATION CABLING BY OTHERS. SEE TECHNOLOGY DRAWINGS FOR EXACT EQUIPMENT LOCATIONS AND ADDITIONAL INFORMATION.31. 30"x30" GRAVITY VENT AT ROOF. CARNES MODEL GL. COORDINATE EXACT LOCATION WITH ARCHITECT.32. JUNCTION BOX AND CONDUIT FOR DOOR OPERATOR POWER. WALL MOUNT PUSH BUTTONS TO MULLIONS OR WALL CONCEAL CONDUIT IN STOREFRONT WHERE APPLICABLE. COORDINATE PUSH BUTTON MOUNTING LOCATIONS AND ALL OTHER REQUIREMENTS WITH ARCHITECT AND DOOR INSTALLER.33. EXHAUST FAN WITH BACK GUARD AND MOTOR OPERATED SHUTTER, WITH INSECT SCREEN. 220 CFM @ 0.25 S.P., 120V, 1 PHASE, 60HZ. MOUNT 6" BELOW BOTTOM OF CEILING. GREENHECK MODEL NO. SE1 WITH NO. EB SHUTTER. CONTROLLED BY THERMOSTAT. 34. SQUARE D CATALOG NO. FG-1 MOTOR STARTER SWITCH. 35. THERMOSTAT, LINE VOLTAGE, TWO STAGE. HONEYWELL CATALOG NO. T6052A1015. STAGE ONE SHALL OPEN FAN SHUTTER AT 60°F. STAGE TWO SHALL START EXHAUST FAN AT 80°F. 36. ROUTE 1" CONDUIT WITH CONTROL WIRING FROM HVAC EQUIPMENT TO DATA CLOSET ON SECOND TIER FOR BAS MONITORING. COORDINATE INTERFACE WITH LIBRARY MECHANICAL.25SHEET TITLESHEET NUMBERCARMEL CLAY PUBLIC LIBRARY55 4th Ave. SECarmel, IN 46032317-814-3900OwnerRATIO Architects, Inc.101 South Pennsylvania StreetIndianapolis, Indiana 46204317-633-4040ArchitectCE Solutions, Inc.Structural EngineerMechanical / Electrical EngineerCivil Engineer10 Shoshone DriveCarmel, IN 46032317-818-1912KBSO Consulting, LLC1344 South Rangeline, Suite 202Carmel, IN 46032317-344-8044Civil & Environmental Consultants, Inc.530 E. Ohio Street, Suite GIndianapolis, IN 46204317-655-7777PROJECT NO.COPYRIGHT NOTICE: THIS ARCHITECTURAL AND ENGINEERING DRAWING IS GIVEN IN CONFIDENCE AND SHALL BE USED ONLY PURSUANT TO THE AGREEMENT WITH RATIO ARCHITECTS, INC. NO OTHER USE, DISSEMINATION OR DUPLICATION MAY BE MADE WITHOUT PRIOR WRITTEN CONSENT OF RATIO ARCHITECTS, INC. ALL COMMON LAW RIGHTS OF COPYRIGHT AND OTHERWISE ARE HEREBY SPECIFICALLY RESERVED.SHEET ISSUESEAL | DATE Technology DesignDesign 271650 East 49th StreetIndianapolis, IN 46205317-536-8000Garage ConsultantWalker Consultants6602 East 75th Street, Suite 210Indianapolis, IN 46250317-842-68908/20/2020 8:44:19 AMEMG-410NORTHSTAIR/ELEVATORPLANS13-3431.00CARMEL CLAYPUBLIC LIBRARYRENOVATION55 4th Ave SECarmel, IN 46032NS WE1/4" = 1'-0"1NORTH STAIR/ELEVATOR GROUND TIERPLAN1/4" = 1'-0"2NORTH STAIR/ELEVATOR SECOND TIERPLAN1/4" = 1'-0"3NORTH STAIR/ELEVATOR TOP TIERPLAN121212311 100% CONSTRUCTION DOCUMENTS 7/14/20202 STATE SUBMISSION SET 7/17/20205 ADDENDUM 5 8/20/2020