HomeMy WebLinkAboutE (1)UM ACMSPINV
WARNING PLACARD
ADDRESS:1215 E 105TH
ST,INDIANAPOLIS,IN 46280
39.939739, -86.138523
APN:291-312-107-002-000-018
CUSTOMER INFORMATION
NAME:JEFF YEGERLEHNER
DATE:10/8/2020
SCALE:AS NOTED REV:A
AHJ:IN- CITY OF CARMEL
PRN NUMBER: GRN-014487
DESIGNER /CHECKED
BY: SRI/BH PAPER SIZE:17"X11"
UTILITY:DUKE ENERGY
WARNING PLACARDS
PL-1
!
A
V
15
480
400RATED MAXIMUM POWER-
POINT VOLTAGE(Vmp)
MAXIMUM SYSTEM
VOLTAGE(Voc)
MAXIMUM CIRCUIT
CURRENT(Isc)
RATED MAXIMUM POWER-
POINT CURRENT(Imp)
INVERTER 1
WARNING
CAUTION: SOLAR CIRCUIT
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION
POINT OF INTERCONNECTION
(PER CODE: NEC 705.12(D)(7)
[ Not Required if Panel board is rated not less than sum of ampere
ratings of all overcurrent devices supplying it]
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS PHOTOVOLTAIC
SYSTEM ARE UNGROUNDED AND MAY BE
ENERGIZED
LABEL LOCATION
DC DISCONNECT,INVERTER
[PER CODE: NEC 690.35(F)]
[To be used when inverter is ungrounded]
WARNING:PHOTOVOLTAIC
POWER SOURCE
LABEL LOCATION
CONDUIT, COMBINER BOX
[PER CODE: NEC690.31(G)(3)(4) & NEC
690.13(G)(4)]
WARNING-Electric Shock Hazard
No User Serviceable Parts inside
Contact authorized service provide
for assistance
LABEL LOCATION
INVERTER, JUNCTION BOXES(ROOF),
AC DISCONNECT
[PER CODE: NEC 690.13.G.3 & NEC 690.13.G.4]
LABEL LOCATION
DISCONNECT, POINT OF INTERCONNECTION
[PER CODE: NEC690.13(B)]
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
[PER CODE: NEC 690.54]
LABEL LOCATION
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR DC CONDUIT,
RACEWAYS, ENCLOSURES AND CABLE ASSEMBLES AT LEAST EVERY
10 FT, AT TURNS AND ABOVE/BELOW PENETRATIONS AND ALL
COMBINER/JUNCTION BOXES.
(PER CODE: IFC605.11.1.4)
LABEL LOCATION
POINT OF INTERCONNECTION
[PER CODE: NEC705.12(D)(4)]
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.17(E)]
DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR
MODULES ARE EXPOSED TO SUNLIGHT
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.17(E)]
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE ADHESDIVE,
UL969 AS STANDARD TO WEATHER RATING (UL LISTING
OF MARKINGS NOT REQUIRED), MIN 38" LETTER HEIGHT
ARIAL OR SIMILAR FONT NON-BOLD,PLACED WITHIN
THE MAIN SERVICE DISCONNECT,PLACED ON THE
OUTSIDE OF THE COVER WHEN DISCONNECT IS
OPERATED WITH THE SERVICE PANEL CLOSED.
(PWER CODE: NEC690.15 ,690.13(B))
WARNING
DUAL POWER SOURCE SECOND
SOURCE IS PHOTOVOLTAIC
SYSTEM
!
!
! SOLAR DISCONNECT
V
A
9.60
LABEL LOCATION
DC DISCONNECT[PER CODE: NEC690.14(C)(2)]
WARNING!
WARNING
INVERTER OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVER-CURRENT DEVICE
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
32.00
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
LABEL LOCATION
AC DISCONNECT , DC DISCONNECT,POINT OF
INTERCONNECTION
(PER CODE: NEC690.56(C))
!
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
!WARNING:
(E) MAIN SERVICE
PANEL(INTERIOR)
SOLAR PHOTOVOLTAIC
ARRAYS ON ROOF
(E) UTILITY METER(EXTERIOR)
ALL PLACARDS SHALL BE OF WEATHER PROOF CONSTRUCTION, BACKGROUND ON ALL PLACARDS SHALL BE
RED WITH WHITE LETTERING U.O.N.
PLACARD SHALL BE MOUNTED DIRECTLY ON THE EXISTING UTILITY ELECTRICAL SERVICE.
FASTENERS APPROVED BY THE LOCAL JURISDICTION
(N) PV INVERTER (EXTERIOR)
(N) AC DISCONNECT (EXTERIOR)
HOUSE-2
HOUSE-1
10/21/20