HomeMy WebLinkAboutSU3 - Sanitary Sewer DetailsHYDRAULIC SEALING FLANGE
GRINDER PUMP STATION - SECTION
NOT TO SCALE
NOTES: 1. SHOP WELD ALL ANGLES
C OF PANELL
2. ALL MATERIAL TO BE
STAINLESS STEEL
TO BE MIN. 3" OR REQ'D
TO PROVIDE RIGID SUPPORT
3. ALL ANGLES AND SUPPORTS
4. ALL FASTENERS TO BE
ALUMINUM
AND SUPPORTS
CONTROL PANEL SUPPORT DETAIL
NOT TO SCALE
5"x3/8" STN. STL.
EXPANSION BOLTS,
AS REQ'D.
3"x3"x1/4" MIN.
ALUMINUM ANGLE, TYP.
3"x1/4" MIN. ALUMINUM
SUPPORT PLATE
TOP OF LIFT STATION
STRUCTURE
1/4" ALUMINUM PLATE
AS REQ'D. TO SUPPORT
EQUIPMENT
(SIZE AS REQUIRED)
4" X 4" TREATED
WOOD POSTS
PRESSURE TREATED
5/8" CDX PLYWOOD
ELECTRICAL SERVICE SCHEMATIC
3-#8 & 1#12 GROUND WIRE IN 1" RIGID STEEL CONDUIT
COPPER
CONCRETE
18"Ø
NOT TO SCALE
WIRE
1/0
2
3
4
BURIED ELECTRIC SERVICE FROM NEW BUILDING POWER PANEL, 40A @ 480/277V, 3
PHASE, USE RIGID CONDUIT ABOVE GRADE
10' COPPER
GROUNDING ROD
40 AMP SERVICE RATED DOUBLE DISCONNECT
T.O.S. = 783.50
B.O.S. = 772.00
2nd PUMP
PUMP ALARM
1st PUMP
"ON" EL. 775.00
PUMPS "OFF" EL. 774.00
"ON" EL. 776.00
EL. 777.00
8" PVC GRAVITY SEWER
INV.=777.00
4" PVC AIR VENT W/
CORROSION PROOF
INSECT SCREEN
CONNECT NEW
DISCHARGE PIPING TO
EX. 2" PVC FORCE MAIN
EX. 8" PVC GRAVITY
SEWER INV=777.00±
NEW 8" PVC GRAVITY
SEWER INV=778.24
GRINDER PUMP STATION - PLAN
NOT TO SCALE
SUBMERSIBLE
LEVEL SENSOR
ANTI-FLOTATION
FLANGE
2" PVC FORCE MAIN PIPING
(CONNECT TO EXISTING)
4' DIA. FRP BASIN
STRUCTURE
LIFT STATION CONTROL
PANEL (SEE SPEC.
SECTION 11310)
VISUAL ALARM LIGHT
RGS CONDUIT FOR POWER
& CONTROL WIRING
6'x4'x4" CONCRETE PAD
AT CONTROL PANEL
BURIED POWER CONDUIT & WIRING FROM
ELECTRICAL SERVICE (SEE DETAIL THIS
SHEET).
2" PVC CHECK VALVE
(TYP. OF 2)
2" PVC PLUG VALVE
(TYP. OF 2)
ALUMINUM STATION COVER (1
4" THICK
MIN.) WIH INTEGRAL HATCH, HINGES,
AND RECESSED PADLOCK HASP.
STAINLESS STEEL
PUMP GUIDE RAILS
W/ BRACKETS
STAINLESS STEEL
PUMP LIFTING CHAIN
SEAL CABLE ENTRANCES
FOR PUMP AND LEVEL
SENSOR WIRING
SUBMERSIBLE GRINDER
PUMPS (DUPLEX) REFER TO
SPECIFICATIONS
SUBMERSIBLE GRINDER
PUMPS (DUPLEX) REFER TO
SPECIFICATIONS
2" PVC FITTINGS
AS REQUIRED
CABLE RACK
CONDUIT TO
CONTROL PANEL
NEMA 4X JUNCTION BOX
8" PVC GRAVITY SEWER
INV.=778.24
SUBMERSIBLE GRINDER PUMPS
TO BE FLYGT MODEL 3102 OR
EQUAL, SIZED FOR 60 GPM @100'
TDH, 3600 RPM MAX.
3-#8 & 1#12 GROUND WIRE IN 1" RIGID STEEL CONDUIT
4
COPYRIGHT 2019 BY FANNING/HOWEY ASSOCIATES, INC.
WWW.FHAI.COM
ARCHITECT
CONSULTANT
6/13/2019 3:21:38 PM\\data1\citrixprofiles$\amiller\My Documents\218052.00_ARCH_amiller.rvtPROJECT NUMBER: 2019199.00
INDOOR FACILITY
AT BADGER
FIELDS
CLAY TOWNSHIP
5459 E MAIN STREET
CARMEL, INDIANA
PROJECT ISSUE DATE: August 23, 2019
DRAWN BY: MTP
REV.
NO.DESCRIPTION DATE
11300453
SOI
STATE OF
ORPF
E
S NEER N LA E N GIANAINIDER DAHC I
IG S
No.
TERE
D
A
CNIK.N
DTAC COMMENTS 09/06/20191
UTILITY DETAILS
SU3.1