HomeMy WebLinkAboutE9-3 - ELECTRICAL DETAILSTYPICAL GROUNDING DETAIL CU GRD. BAR RACKS #6 AWG INSULATED GROUND CONDUCTOR MDF & IDF'S G MAIN EQUIPMENT BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) TO MAIN SERVICE EQUIPMENT SWITCHBOARD OR PANELBOARD GROUND BUS AT SERVICE ENTRANCE N G PANELBOARD G DISTRIBUTION PANELBOARD N N G PANELBOARD EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS TRANSFORMER C N B A BONDING JUMPERS (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) N G COMMUNICATIONS SYSTEMS EQUIPMENT CABINET GROUND COMMUNICATIONS PLYWOOD BACKBOARD GROUND BAR TELEPHONE SERVICE DEMARK GROUND BAR 3/4"X10' CU GROUND ROD AS REQUIRED (SEE SECTION 260526) #3/0 CU BONDING JUMPER IF NOT FACTORY INSTALLED EQUIPMENT GROUND. SIZE AS SHOWN ON DRAWINGS EQUIPMENT GROUND - SIZE AS SHOWN ON DRAWINGS G NEUTRAL BUS GROUND BUS BUILDING STEEL (INDOOR) OR GROUND ROD (OUTDOOR) GENERATOR FRAME AND ENCLOSURE N C GENERATOR B A #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR #3/0 CU EQUIPMENT BONDING JUMPER BONDING BUSHING (TYPICAL) SERVICE EQUIPMENT ENCLOSURE (MAIN SWITCHBOARD) MAIN BONDING JUMPER (SIZE IN ACCORDANCE WITH NEC ARTICLE 250) PANELBOARD AUTOMATIC TRANSFER SWITCH ENCLOSURE (SWITCHED NTL) NOT TO SCALE BUILDING STEEL OR INTERIOR METAL WATER PIPE AND GROUND ROD IF STEEL IS NOT AVAILABLE #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR 3/4"X10' CU GROUND ROD BUILDING FOUNDATION REBAR #3/0 BARE CU GROUND RING INCOMING METAL WATER SERVICE BUILDING STEEL #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR 3/4"X10' CU GROUND ROD 3/4"X10' CU GROUND ROD INCOMING SERVICE METAL CONDUITS TRANSFORMER ENCLOSURE #3/0 BARE CU GROUNDING ELECTRODE CONDUCTOR IG IG IG TRANSFORMER C N B A NTL AS SHOWN ON DRAWINGS NO GROUND CABLE TO NTL UTILITY TRANSFORMER TO UTILITY TRANSFORMER ISOLATED GROUND- SIZE AS SHOWN ON DRAWINGS WHEN REQUIRED DOUBLE DUPLEX RECEPTACLE IN FLUSH MOUNTED 4" OR 4-11/16" SQUARE BOX WITH SINGLE-GANG PLASTER RING. MOUNT AT +20" AFF TO TOP. DUPLEX RECEPTACLE IN FLUSH MOUNTED 4" OR 4-11/16" SQUARE BOX WITH SINGLE-GANG PLASTER RING. MOUNT AT +20" AFF TO TOP. CONDUIT STUBBED TO NEAREST CABLE TRAY ON SAME FLOOR AS OUTLET. SEE OUTLET DETAILS ON E501 FOR CONDUIT SIZES. FACEPLATE. FLUSH MOUNTED, 3" DEEP, 4" OR 4-11/16" SQUARE BOX. PROVIDE WITH SINGLE-GANG PLASTER RING IN GYPSUM BOARD OR PLASTER FINISHED WALL. PROVIDE 3-1/2 INCH DEEP MASONRY BOX IN MASONRY WALL. 4" OCTAGONAL JUNCTION BOX (AT LEAST 1.5" DEEP). DO NOT INSTALL SENSOR WITHOUT JUNCTION BOX. CEILING DEPLUGGABLE TERMINAL SENSOR (2) MOUNTING SCREWS FRONT COVER SIDE BY SIDE JUNCTION BOXES STACKED JUNCTION BOXES JUNCTION BOXES HIGH VOLTAGE WIRING LOW VOLTAGE WIRING POWE R PACK POWE R PACK HIGH VOLTAGE WIRING JUNCTION BOX JUNCTION BOX EXTENSION BOX LOW VOLTAGE WIRING GENERAL NOTES: A. DO NOT INSTALL POWER PACKS CLOSER THAN 6-12 INCHES FROM SENSOR. DO NOT INSTALL POWER PACKS WITHOUT JUNCTION BOXES. PROJECT NUMBER DATE CERTIFIED BY: REVISIONS ISSUE DRAWING © 2019 Halstead Architects All Rights Reserved- - - - - - - 100% CONSTRUCTION DOCUMENTS E9.3 20015Owner 09/01/2020 ELECTRICAL DETAILSSitara Indian Restaurant13080 GRAND BOULEVARDCARMEL, IN 4603212" = 1'-0" TYPICAL FLUSH MOUNTED DOUBLE DUPLEX OUTLET DETAIL1 12" = 1'-0" TYPICAL FLUSH MOUNTED DUPLEX OUTLET DETAIL2 12" = 1'-0" TYPICAL FLUSH MOUNTED SYSTEMS OUTLET DETAIL4 12" = 1'-0" TYPICAL GROUNDING DETAIL3 12" = 1'-0" TYPICAL OCCUPANCY SENSOR MOUNTING DETAIL5 12" = 1'-0" TYPICAL OCCUPANCY SENSOR POWER PACK MOUNTING DETAIL6 10/20/20