HomeMy WebLinkAboutE-601 ELECTRICAL DETAILSCIRCLE DESIGN GROUPRTL BKS
ELECTRICAL
DETAILS
E-601
SCALE: NONE
"EWC" WIRING DETAIL
VERIFY ROUGH-IN-HEIGHT
WITH APPROVED MFG. SHOP
DWG. CONTRACTOR TO USE
DUPLEX RECEPTACLE.
DRINKING WATER
COOLER BY OTHER
DIVISION.
FLOOR
1 1/2 " CONDUIT TO IDF
ON SAME FLOOR AS OUTLET
FACEPLATE.
FLUSH MOUNTED, 3" DEEP, 4" OR 4-11/16"
SQUARE BOX. PROVIDE WITHSINGLE-GANG PLASTER RING IN GYPSUM
BOARD OR PLASTER FINISHED WALL.PROVIDE 3-1/2 INCH DEEP MASONRY BOX
IN MASONRY WALL.
SCALE: NONE
TYPICAL FLUSH MOUNTED
SYSTEMS OUTLET
DUPLEX RECEPTACLE IN
FLUSH MOUNTED 4"
OR 4-11/16" SQUARE
BOX WITH SINGLE-GANG
PLASTER RING. MOUNT
AT +20" AFF TO TOP.
SCALE: NONE
TYPICAL FLUSH MOUNTED
DUPLEX OUTLET
DOUBLE DUPLEX
RECEPTACLE IN FLUSH
MOUNTED 4" OR 4-11/16"
SQUARE BOX WITH
SINGLE-GANG PLASTER
RING. MOUNT AT +20"
AFF TO TOP.
SCALE: NONE
TYPICAL FLUSH MOUNTED
DOUBLE DUPLEX OUTLET
BUILDING
STRUCTURE
J
BRANCH CIRCUIT CONDUIT
DOWN TO OUTLET
WALL
OUTLET
LAY-IN
TYPE
CEILING
BRANCHCIRCUIT
CONDUIT
JUNCTION
BOX
SCALE: NONE
OVERHEAD FEED TO INTERIOR WALL
SCALE: NONE
COLUMN GROUNDING
WITHOUT SLEEVE
BONDING PLATE OR
EXOTHERMIC WELD
TO STEEL COLUMN
EXOTHERMIC CONNECTION
TO GROUND ROD
CLASS II COPPER
GROUNDING CONDUCTOR
3/4" x 10'-0" COPPER CLAD
STEEL GROUND ROD
7
SupportStructure
Conduit
Beam Clamp
Beam
Clamp
Conduit
Clamps
Slotted Channel
to Support 400%of Conduit Weight
SCALE: NONE
1.5 INCH AND SMALLER
CONDUIT SUPPORT
SlottedChannelto Support 400%of ConduitWeight.
Double NutTop andBottom
Beam
Clamp
Threaded
Rod
Conduit
Clamps
SCALE: NONE
2 INCH AND LARGER
CONDUIT SUPPORT
TYPICAL GROUNDING DETAIL12
1
2
3 5
6 8 9
EXIT
NOTES:
1. EQUIPMENT MOUNTING HEIGHTS SHALL BE INDICATED UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THE SPECIFICATIONS.
2. CONCEAL RECEPTACLE BEHIND WATER COOLER. VERIFY EXACT MOUNTING HEIGHTS.3. WHERE DEVICES ARE LOCATED IN MASONRY WALLS LOCATE DEVICE WITHIN COARSING SO THAT MOUNTING INDICATED HERE IN IS NOT EXCEEDED.
4. ALL RECEPTACLES ABOVE KITCHEN COUNTER AND NEAR BATH VANITIES SHALL BE INSTALLED HORIZONTALLY AT +44" AFF TO TOP OF THE BOX.
CEILING
F
H
S
F STV
VC IC F96"96"48"48"72"48"36"20"20"20"NOTE 220"20"96"96"72"96"48"20"48"48"84"SYMBOLS:
FLOOR
W
WC
J C S M
D
M
ELECTRICAL ELEVATION
SCALE: NONE11
SCALE: NONE
EF-1 AND PF-1 WIRING
DIAGRAM
10
P:\2018\18183 Lakeside ATAPCO Braunability CSO\Tenant\Dwgs\Elec\E-601.dwg, 6/17/2020 3:05:33 PM, rlamb11/04/20