HomeMy WebLinkAboutEP102 FIRST FLOOR POWER & SYSTEMS PLANWater Main Electrical T-4L3030#1806611 & 12 ga SteelHA-1,3,5 HA-7,9,11 HA-10,12,14 EX. PUH-4 EX. PUH-2EX. PUH-1 EX. (4) 4" C FOR TELECOM EX. STUB 2" CONDUIT EX. STUB 2" CONDUIT EX. STUB 2" CONDUIT EX. STUB 2" CONDUIT EX. PANEL HA EX. PANEL DP PANEL LA PANEL LB LA-13,15 LA-30 LA-29,31,33 LA-8,10,12 LE-8,10 PANEL LE LE-1 LE-3 LE-5 LE-2 LE-4 LE-6LE-7 LE-9 LE-11 LB-21,23 LE-27,29 LA-14,16 LA-32, 34,36 LA-5,7 LE-19 LE-48 LE-18 LE-22 LE-25LB-10LB-10 LB-10 LB-10 LB-10 LB-11 LB-11 LB-11 LB-11 LB-11 LB-12 LE-12 LA-2,4,6 LB-17,19 LB-18,20 LB-13,15 LB-14,16 VESTIBULE 101 LAB 102 UNISEXRESTROOM 104 UNISEXRESTROOM 105 JANITOR'SCLOSET 107 DATAROOM 108 CONFERENCEROOM 103 ELECTRONIC'SLAB 109 RALPH'SGARAGE 110 LIFTDEVELOPMENT AREA 111 AC-3A LE-12 LE-12 LE-12 LE-13 LE-13 LE-13 LE-13 LE-13 LE-14LE-14 LE-14 LE-14 TRANS. A TRANS. B TRANS. E LB-12 LB-12 LB-12 LB-12 LB-25 LB-27 N3 LE-15,17 N21 N2 N18 N2 N18 N3 N13N4 N17 N16 N9 N19 N19 N9 N19 N8N9 N14A N6 N7 N5 N12 N11 N20 N10A N22 HA-4,6,8 RELOCATED PUH-3 N15 PANEL LC TRANS. C N23 LA-2 LB-25 LB-25 LB-25 LA-1N14B N19 N19 N19 N19 N19 HA-13,15,17 DP-7 AC-3B AC-1 AC-2 ECH-1ECH-2 N19 N10B N10C N10D LC-1,3,5 LC-2,4,6 LC-7,9,11 LC-8,10,12 LC-13,15,17 LE-18 LE-18 LE-20 LE-23 LE-22LE-22 LE-24 LE-24 LE-24 LE-24 LE-24 LE-21 LE-25 LE-25 LE-25 LE-26,28 LE-21 LE-30 LE-32,34 LE-31,33LE-35,37 FACP RA LE-39,41 LB-5,7 LB-6,8 LB-22,24 LB-2,4 LB-1,3 OVERHEAD DOOR LB-12 LE-25 LE-25 LE-43LE-43 LE-43 LE-43 LB-26 LB-26 LB-26 LB-26 LE-18 LE-44,46 DWH-1 LE-45 DHWRP-1 LE-47 S WD-1 LE-16 LB-27 LB-27 LE-50 SCALE: FIRST FLOOR POWER & SYSTEMS PLAN 3/32" = 1'-0" 1 N 0 24'16'8' CIRCLE DESIGN GROUPA. SEE SHEET E-000 FOR ELECTRICAL SYMBOLS AND ABBREVIATIONS. B. WIRING SYSTEM SHALL BE CONDUIT AND CONDUCTOR. MINIMUM WIRE SIZE SHALL BE #12 AWG. USE SOLID CONDUCTOR #10 AWG AND SMALLER, USE STRANDED IN LARGER SIZES. C. ALL COVER PLATES FOR ELECTRICAL DEVICES SHALL BE OF A COLOR TO MATCH THE AREA COLOR SCHEME AS DIRECTED BY THE ARCHITECT. D. FURNISH AND INSTALL ALL INTERCONNECT WIRING FOR MECHANICAL AND PLUMBING EQUIPMENT FURNISHED BY OTHERS E. TELE/DATA, AV AND ALL LOW VOLTAGE SYSTEMS ARE ROUGH IN ONLY. PROVIDE ROUGH IN AND CONDUIT/ RACEWAY. F. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS, ROOM AND AREA FINISHES, CEILING PLANS, DOOR SWINGS, FIRE RATED PARTITIONS, CABINET AND CASEWORK DETAILS. G. PROVIDE BRANCH CIRCUIT WIRING AS REQUIRED FOR ALL EQUIPMENT FURNISHED BY OTHERS. H. FINAL DETERMINATION OF FIRE AND/OR SMOKE STOPPING REQUIREMENTS SHALL BE BASED ON LOCAL CODE REQUIREMENTS. SEE COVER SHEET FOR ADDITIONAL INFORMATION. I. ALL WORK SHALL COMPLY WITH NATIONAL, STATE AND LOCAL CODES AND ORDINANCES PERTAINING TO THE WORK IN THIS PROJECT. J. EXPOSED CONDUIT SHALL BE RUN PARALLEL TO AND AT RIGHT ANGLES TO THE BUILDING LINES. K. PROVIDE A TYPED UPDATED SCHEDULE TO BE INSTALLED IN THE PANEL AND INCLUDED IN THE AS BUILT DRAWINGS. L. RECEPTACLES SHALL BE A MAXIMUM OF +18" ABOVE FINISHED FLOOR TO THE CENTER OF THE DEVICE. UNLESS NOTED OTHERWISE. M. REFER TO ELECTRICAL CONNECTION TO MECHANICAL EQUIPMENT SCHEDULE FOR DISCONNECT SWITCH REQUIREMENTS. N. ALL EXTERIOR EQUIPMENT AND DEVICES SHALL BE WEATHER PROOF AND RAIN TIGHT. O. ALL DEVICES AND EQUIPMENT MARKED "EX." ARE EXISTING TO REMAIN. PROTECT DURING CONSTRUCTION. P. FOR DEVICES MARKED WITH " N# " SQUARE CALLOUTS REFER TO ELECTRICAL CONNECTION TO TENANT EQUIPMENT SCHEDULE. COORDINATE EXACT LOCATION OF ELECTRICAL CONNECTION WITH EQUIPMENT PROVIDER. Q. CONDUIT SHALL BE IMC ABOVE GROUND. INSTALL TIGHT TO STRUCTURE. R. COORDINATE 'RALPH'S GARAGE' DEVICE MOUNTING HEIGHT AND LOCATION WITH OWNER. S. ROUTE ALL CONDUIT TO TURN OUT AT TOP OF STRUCTURE. T. TELE / DATA AND ACCESS CONTROL SYSTEM ARE ROUGH IN ONLY. 1 GENERAL SHEET NOTES SHEET PLAN NOTES 1. SUSPENDED TRANSFORMER MOUNTED TO WALL. 2. MOUNT CENTER OF DEVICE +48" ABOVE FINISHED FLOOR (A.F.F) 3. MOUNT CENTER OF DEVICE +6" ABOVE COUNTERTOP BACK SPLASH 4. MOUNT CENTER OF DEVICE +60" A.F.F FOR MONITOR. COORDINATE EXACT LOCATION WITH ARCHITECT. 5. RELOCATED 'PUH-3'. EXTEND AND RELANR EXISTING ELECTRICAL FEEDER. 6. SWITCHED GFI DUPLEX RECEPTACLE FOR GARBAGE DISPOSAL. GARBAGE DISPOSAL SWITCH TO BE MOUNTED +6" ABOVE COUNTERTOP BACK SPLASH. 7. OVER HEAD DOOR MOTOR. CONFIRM EXACT ELECTRICAL REQUIREMENT AND MOTOR HORSE POWER SIZE WITH ARCHITECT. PROVIDE PUSH BUTTON FOR DOOR OPERATION IN LINE WITH MOTOR AND MOUNTED AT +48" A.F.F COORDINATE EXACT LOCATION WITH ARCHITECT. 8. INDOOR UNIT POWER FED FROM OUTDOOR UNIT. 9. FM200 FIRE SUPPRESSION SYSTEM CONTROL PANEL. 10. RE LABEL EXISTING PANEL "HA" 11. POWER CONNECTION FOR (2) FIRE SMOKE DAMPERS SERVING DATA ROOM. COORDINATE WITH HVAC DRAWINGS. 1 1 2 2 2 2 2 2 3 3 4 5 7 8 8 8 8 RTL BKS FIRST FLOOR POWER & SYSTEMS PLAN EP102 6 9 10 11 P:\2018\18183 Lakeside ATAPCO Braunability CSO\Tenant\Dwgs\Elec\EP101.dwg, 6/17/2020 3:05:43 PM, rlamb11/04/20