HomeMy WebLinkAboutC500 Sanitary PnP875
880
885
890
895
900
905
910
915
875
880
885
890
895
900
905
910
915FINISHED GRADE
EXISTING GRADE
GRANULAR BACKFILL
PROFILE LEGEND
NP = 898.83
2 YR = 899.05
EXISTING POND
TOP OF BANK = 900.1
SPILLWAY=899.7
10 YR = 899.25
100 YR = 899.60
STONE LAKEDRIVE65
WW 162
163
164
165 166 167
179180 181
178
177
176
175
182
183
184
168 169 170
171
172
173
174
STONE LAKEDRIVESTONE LAKEDRIVE185WWWWWWW
W
W
W
W
W
W
W W W W W W W W
W WWW WWW
W WWWWWW WDRY POND
SANITARY SEWER PIPE DATA TABLE
DOWNSTREAM
STRUCTURE
MH-WFW30
UPSTREAM
STRUCTURE
MH-WFW29
SIZE
8"
MATERIAL
PVC
LENGTH
283'
SLOPE
0.38%EX MH-WFW37
SANITARY SEWER STRUCTURE DATA TABLE
STRUCTURE NUMBER STRUCTURE TYPE TOP OF CASTING CASTING TYPE INVERT
EXISTING
MH-WFW50
MH-WFW51
MH-WFW49
MH-WFW50
8"
8"
PVC
PVC
154'
156'
0.45%
1.00%
MH-WFW31 MANHOLE 900.85 NEENAH R-1642 INV IN = 890.10(S)
INV OUT = 890.00(NE)
EXISTING
EXISTING
EX
ADJUSTED T.O.C. 904.22
MH-WFW37 MANHOLE 898.83 NEENAH R-1642
INV IN = 884.93(W)
INV IN = 884.93(NE)
INV OUT = 884.83(SE)
EXISTING
EXISTING
EX
ADJUSTED T.O.C. 904.51
MH-WFW49
MH-WFW50
MH-WFW51
MANHOLE
MANHOLE
MANHOLE
904.87
904.96
905.86
NEENAH R-1642
NEENAH R-1642
NEENAH R-1642
INV IN = 895.06(N)
INV OUT = 885.37(SW)
INV IN = 895.85(W)
INV OUT = 895.75(S)
INV OUT = 897.41(E)E N G I N E E R S317 | 846 - 6611800 | 452 - 6408317 | 843 - 0546 faxWEIHE Land Surveying | Civil Engi neeringLandscape ArchitectureALLAN H. WEIHE, P.E., L.S. - FOUNDER10505 N. College AvenueIndianapolis, Indiana 46280weihe.netWATERFRONT OF WEST CLAYSECTION FIVE "B"Know what'sbelow.
before you dig.Call
R
BENCHMARK INFORMATION
BM BOO 54 - A DNR DISK IS LOCATED 1.0 MILE NORTHEAST OF
ZIONSVILLE; 0.2 MILE EAST ALONG WEST 121ST STREET FROM ITS
JUNCTION WITH STATE ROAD 421, AT THE INTERSECTION OF
DAUGHERTY DRIVE AND WEST 121ST STREET, IN THE NORTHEAST 1/4
OF THE INTERSECTION, AT THE ENTRANCE TO THE EAGLE VILLAGE
SUBDIVISION; SET IN THE TOP OF A CONCRETE POST, LEVEL WITH
THE GROUND; A DEPARTMENT OF NATURAL RESOURCES BRASS
CONTROL STATION TABLET, STAMPED "BOO 54 1989".
ELEV.: 901.14 FEET (1929 DATUM)
ELEV.: 900.76 FEET (1988 DATUM)
THESE PLANS ARE BASED ON 1988 DATUM
CITY OF CARMEL COVER AND BACKFILL POLICY; 9-8-06
WATER AND SEWER UNDER PAVEMENT, SIDEWALK, PAVED AREAS AND WITHIN RIGHT-OF-WAY
BEDDING, HAUNCHING, INITIAL BACKFILL
BEDDING, HAUNCHING AND INITIAL BACKFILL REQUIREMENTS AND COMPACTION FOR WATER MAINS, WATER
SERVICE LATERALS, SANITARY MAINS AND SANITARY SERVICE LATERALS SHALL BE IN ACCORDANCE WITH THE
STANDARD PRACTICE OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION.
FINAL BACKFILL
FINAL BACKFILL FOR WATER MAINS, WATER SERVICE LATERALS, SANITARY MAINS AND SANITARY SERVICE
LATERALS UNDER AND WITHIN 5-FEET OF PAVEMENT OR SIDEWALK OR OTHER PAVED AREAS AND FOR ALL
INSTALLATIONS WITHIN CITY RIGHT-OF-WAY SHALL BE B-BORROW FOR STRUCTURE BACKFILL MEETING THE
MATERIAL REQUIREMENTS OF THE INDOT. THE MATERIAL SHALL BE APPROVED BY THE CITY OF CARMEL
DEPARTMENT OF ENGINEERING AT TIME OF INSTALLATION. FINAL BACKFILL SHALL BE COMPACTED IN 6-INCH
MAXIMUM LIFTS TO NOT LESS THAN 95% STANDARD PROCTOR DENSITY FOR THE ENTIRE DEPTH OF THE
MATERIAL PLACED. THE BACKFILL FOR THE TOP 6-INCHES OF THE EXCAVATION BELOW THE START OF THE
AGGREGATE SUB-BASE OF THE PAVEMENT SHALL BE NO. 53 STONE MEETING THE MATERIAL REQUIREMENT OF
THE INDOT AND SHALL BE COMPACTED TO NOT LESS THAN 95% STANDARD PROCTOR DENSITY. IF THE
STANDARD PRACTICE OF THE UTILITY THAT HAS JURISDICTION OVER THE INSTALLATION HAS A MORE STRINGENT
BACKFILL REQUIREMENT, THE MORE STRINGENT REQUIREMENT SHALL GOVERN.
MINIMUM COVER FOR PIPE CROSSINGS WITHIN CITY RIGHT-OF-WAY
FOR INSTALLATION OF STORM MAINS, WATER MAINS, SANITARY MAINS, WATER SERVICE LATERALS, SANITARY
SERVICE LATERALS UNDER CITY STREETS, REGARDLESS OF JURISDICTION OF THE UTILITY, THE MINIMUM COVER
FROM THE TOP OF THE INSTALLED PAVEMENT TO THE TOP OF THE INSTALLED PIPE SHALL BE THE PAVEMENT
SECTION THICKNESS (ALL BITUMINOUS AND AGGREGATE MATERIAL ABOVE THE SUBGRADE) PLUS 1-0", BUT
UNDER NO CIRCUMSTANCES SHALL THE COVER ALONG ANY PART OF THE PIPE FROM THE FINAL PAVEMENT
ELEVATION TO THE TOP OF THE PIPE BE LESS THAN 2.5-FEET. IF THE STANDARD PRACTICE OF THE UTILITY THAT
HAS JURISDICTION OVER THE INSTALLATION HAS A MORE STRINGENT COVER REQUIREMENT, THE MORE
STRINGENT REQUIREMENT SHALL GOVERN.
COVER HEIGHTS FOR REINFORCED CONCRETE PIPE STORM SEWER THAT ARE LESS THAN THOSE REQUIRED
WILL BE EVALUATED ON A CASE BY CASE CONDITION AND APPROVED ONLY WITH WRITTEN PERMISSION BY THE
CITY ENGINEER.
SANITARY SEWER NOTES
1. THE CONTRACTOR SHALL CONTACT APPLICABLE UNDERGROUND-PLANT
PROTECTION/LOCATION SERVICE AT LEAST 72 HOURS PRIOR TO ANY WORK.
2. THE CONTRACTOR SHALL CONTACT THE OWNER AND/OR ENGINEER IF UTILITIES
APPEAR TO BE IN CONFLICT WITH THE PROPOSED IMPROVEMENTS. IT SHALL
BE THE RESPONSIBILITY OF THE CONTRACTOR TO RELOCATE ALL EXISTING
UTILITIES WHICH CONFLICT WITH THE PROPOSED IMPROVEMENTS SHOWN ON
THE PLANS.
3. THE PLANS SHOW THE LOCATION OF ALL KNOWN UTILITIES LOCATED WITHIN
THE LIMITS OF CONSTRUCTION ACCORDING TO INFORMATION PROVIDED BY
THE VARIOUS UTILITY COMPANIES, PREVIOUS CONSTRUCTION PLANS AND AS
EVIDENCED BY OBSERVATION OF ABOVE GROUND CONDITIONS BY THE
SURVEYOR. THE ACCURACY OF THIS INFORMATION IS NOT GUARANTEED.
4. THE LOCATION AND PROTECTION OF UTILITY STRUCTURES, THEIR SUPPORT
AND MAINTENANCE DURING CONSTRUCTION (IN COOPERATION WITH
APPLICABLE UTILITY COMPANY) IS THE EXPRESS RESPONSIBILITY OF THE
CONTRACTOR.
5. THE CONTRACTOR SHALL CONTACT ALL APPLICABLE UTILITY OWNERS TO
VERIFY ANY AND ALL FEES ASSOCIATED WITH THE INSTALLATION OF UTILITIES.
6. ALL CONSTRUCTION ON THIS SITE TO BE PERFORMED IN COMPLIANCE WITH
O.S.H.A. STANDARDS FOR WORKER SAFETY.
7. ANY PART OF SANITARY TRENCHES RUNNING UNDER OR WITHIN 5' OF
PAVEMENT TO BE BACKFILLED WITH GRANULAR MATERIAL.
8. IT IS THE CONTRACTORS RESPONSIBILITY TO VERIFY LOCATION, SIZE, AND
ELEVATION OF EXISTING UTILITIES, STRUCTURES, PIPES, PAVEMENTS, ETC. AS
RELATED TO THEIR WORK. NOTIFY ENGINEER OF ANY CONFLICT AND/OR
DISCREPANCIES IN THE CONSTRUCTION DOCUMENTS.
9. CLEARANCE BETWEEN STORM / SANITARY SEWER SYSTEMS AND
DOMESTIC/FIRE LINE SERVICE, SHALL MAINTAIN 10' HORIZONTAL AND 18"
VERTICAL.
10. CONTRACTOR TO INSTALL CONCRETE CRADLES AT PIPE CROSSING WHEN THE
VERTICAL SEPARATION (AS MEASURED FROM THE EXTERIOR OF THE PIPES)
BETWEEN SANITARY SEWERS, WATER MAINS AND STORM SEWERS IS 18" OR
LESS.
11. SANITARY SEWER LINE IN PROXIMITY OF WATER LINE SHALL BE C900 WATER
MAIN GRADE PVC.
12. IF ANY EXISTING STRUCTURES TO REMAIN ARE DAMAGED DURING
CONSTRUCTION, IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REPAIR
AND/OR REPLACE THE EXISTING STRUCTURE AS NECESSARY TO RETURN IT TO
IT'S CONDITION PRIOR TO CONSTRUCTION.
13. WHEN PERFORMING EXCAVATIONS DURING PERIODS OF WET WEATHER,
PROVIDE ADEQUATE DEWATERING, DRAINAGE AND GROUND WATER
MANAGEMENT TO CONTROL MOISTURE OF SOILS.
14. COMPACTED "B" BORROW BACK FILL REQUIRED OVER ALL UTILITIES IN PAVED
AREAS.
15. ALL UTILITY STRUCTURES IN PAVED AREAS SHALL BE FLUSH WITH PAVEMENT
AND SHALL HAVE TRAFFIC BEARING RINGS AND COVERS RATED FOR H20
LOADING.
16. FOLLOW ALL LOCAL AND STATE CODES IN REFERENCE TO SANITARY SEWER
INSTALLATION.
17. SANITARY SEWER LATERALS SHALL BE BACKFILLED WITH GRANULAR MATERIAL
FOR THE ENTIRE LENGTH OF THE PIPE.
18. ALL EXISTING MANHOLES SHALL BE ADJUSTED TO NEW FINISH GRADE
ELEVATIONS.
19. SEE SHEETS C501-C502 FOR SANITARY SEWER DETAILS AND SPECIFICATIONS.
W
S
N
E
C500SAINTARY PLAN AND PROFILE11/16/20