HomeMy WebLinkAboutTaylor Ortiz1925 St. Clair Ave NE
Cleveland, Ohio 44114
Phone: 216-333-1364
www.yellowlite.com
PV Layout
8.58 kW Solar Photovoltaic
Project: 1306 – TO
Silfab
SIL-330 NL
66.9 x 39.4 x 1.5 in
Taylor Ortiz
3837 Penzance Place
Carmel, IN 46032
PH: (312) 523-9581
System Details:
· Residential 8.58 kW grid tied (photovoltaic) system
· This system has been designed in accordance with all current and applicable
NEC, OBC, and RCO codes
· Height of the Array: 3-4in above the roof, parallel to the roof
· Weight of the Array: Less than 4lbs/ft^2
· Total Area of Array: 5.6ft x 3.3ft x 26= 481 sq. ft.
· Weight of the Array on Roof: 41.4lbs x 26= 1076.4 lbs
· Stress of Array on entire roof : 1076.4 lbs./481 sq.ft.= 2.24 lbs/sq. ft.
· No fencing or trenching would be needed with this project
SYSTEM: 26 x Silfab SIL-330 NL @ 330W – 8.58 kW • AZIMUTH: R1,R2: 191º • PITCH: R1,R2: 32º
Legend
Utility Meter &
AC Disconnect
N
S
EW
Customer Signature
Inspection Notes for Crew
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
Roof 1: South
24 x Modules
1
60'12'’24'12'
36"36'’1414'’12'’
Roof 2: South
02 x Modules
2
12/17/20
1925 St. Clair Ave NE
Cleveland, Ohio 44114
Phone: 216-333-1364
www.yellowlite.com
N
S
EW
Property Details
Total Land Area in Sq. ft.: 22,539.44
Total Area in Acreage: 0.52
Depth(ft.): 219
Frontage(ft.): 104
Right Setback(ft.): 09
Left Setback(ft.): 38
Front Setback(ft.): 34
Rear Setback(ft.): 109
Total Buildings in Property: 1
Building Height (Story): 2
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
SITE PLAN
1306 – TO
ADDRESS: 3837 Penzance Place Carmel, IN 46032
OWNER: Taylor Ortiz PH: (312) 523-9581
SYSTEM: 26 x Silfab SIL-330 NL @ 330W – 8.58 kW • AZIMUTH: R1,R2: 191º • PITCH: R1,R2: 32º
116'196'219'34'109'38'
9'
Penzance P
l
Penzance P
l
Penzance P
l
104'
Legend
Setbacks
Inverter, Solar Meter, Utility
Meter & AC Disconnect
(Outside house)
Main Service Panel
(Inside Garage)
AC Disco
n
n
e
c
t
Utility M
e
t
e
r
Inverter &
S
o
l
a
r
M
e
t
e
r
Main Ser
v
i
c
e
P
a
n
e
l
12/17/20
Confidential Information: The contents of this document are subject to Non-Disclosure Agreement and shall not be disclosed.
1925 St Claire Ave NE
Cleveland, Ohio 44114
Phone: 216-333-1364
www.yellowlite.com
Module Specifications:
Model: Silfab SIL-330 NL Mono
Module Power (Pmax): 330W
Maximum Power Voltage (Vpmax): 33.33V
Maximum Power Current (Ipmax): 9.92A
Open Circuit Voltage (Voc): 40.5V
Short Circuit Current (Isc): 10.42A
Module efficiency (%): 19.4
Max Series Fuse Rating: 20A
Power Tolerance: 0 / +10W
Cell Type: Mono-crystalline
Number of cells: 60
Weight of Module: 19kg
Dimensions (L x W x H mm): 1700 ˣ 1000 ˣ 38
Listing: ULC ORD C1703, UL1703, IEC 61215,
IEC 61730-1 & IEC 61730-2 Certified, CEC
Listed. UL Fire Rating: Type 2.
Inverter Specifications:
Model: SolarEdge SE7600H-US
Rated AC Power Output : 7600VA
Max. AC Output Power: 7600VA
Nom. AC Frequency: 60Hz
Nom. AC Voltage: 240Vac
Max. Continuous Output Current: 32A
Maximum DC Power (STC): 11800W
Max. Input Voltage: 480V
Nom. DC Input Voltage: 400 @ 240V
Max. Input Current: 20A @ 240V
Max. Input Short Circuit Current: 45A
Maximum Inverter Efficiency: 99.2%
Dimensions H / W / D: 17.7 / 14.6 / 6.8 inches
Weight: 25.3lb / 11.5kg
Listing: UL1741, UL1741 SA, UL1699B, CSA C22.2
Safety: NEMA3R / IP14,
Grid Connection Standards: IEEE1547, Rule 21, Rule 14 (HI)
Emissions: FCC Part 15 Class B
System Specifications:
System Type: Grid-Tied
Mounting Method: Roof-Top
Total DC rating of panels: 8.58 kW
Total AC rating of inverter: 7.6 kVA
Number of panels: 26
Number of inverters: 01
Online Monitoring: Cellular card
AC Disconnect:
Model: Eaton DG222NRB, 2-Pole, NEMA 3R
Rating: 60A, 240 VAC
Type: Fusible, Fuse Rating: 40A
Dimensions: H: 14.38", W: 8.69", D: 4.21".
Compliant with 690.13(B) & (C) and 690.15(A) & (B)
The load center/disconnect will be visible, lockable, accessible to utility linesmen and will be properly labeled as
per NEC requirements. It will be located on the exterior wall of the building, next to the utility meter.
Optimizer Specifications:
Model: SolarEdge Optimizer P340
Rated Input DC Power: 340W
Absolute Maximum Input Voltage: 48V
MPPT Operating Range: 8-48V
Maximum Short Circuit Current: 11A
Maximum efficiency (%): 99.5
Maximum Output Current: 15A
Maximum Output Voltage 60V
Safety Output Voltage per Optimizer: 1V
Dimensions (W x L x H) in: 5.1 x 6 x 1.1
Weight: 1.4 lbs.
Connector Type: MC4 Compatible
Protection Rating: IP68 / NEMA6P
Listing: FCC Part15 Class B, IEC61000-6-2,
IEC61000-6-3, IEC62109-1 (class II safety), UL1741
Rapid shut down is included in Inverter and Optimizers. See the attached files
Grounding will be done via IronRidge Grounding Mid-clamps and WEEB
Bonding Jumpers so the rail and panels will be continuously grounded.
L1
L2
02 x Strings of 13 Modules
AC Disconnect
Fuse Rating: 40A
Location: Next
to Utility Meter
Main Service Panel
240V/200A 1 ɸ service
Location: Inside Garage
AC ELECTRIC
UTILITY GRID
Utility Meter
Location: Eastern
wall of house
N
Inverter : SolarEdge SE7600H-US
Location: Next to Utility Meter
DC
Disconnect
M
Solar Meter
Location: Next
to Utility Meter
N
G
N
L2
L1
AC
Disconnect
M
Irreversible Splice to
Existing EGC
Voltage = 240 Vac
Max AC Output Current = 32A x 1.25 = 40A
Minimum Wire Size: #8 AWG THWN Cu
NEC 2017 [Table 310.15 (B)(16)]
EGC: #06 THHN AWG Copper
[NEC 2017 690.45]
[NEC 2017 Table 250.122]
Line Side
Connection in MSP
EGC: #6 AWG Bare Cu
[NEC 2017 690.45]
[NEC 2017 Table 250.122]
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
SolarEdge
Optimizer P340
Three Line Diagram
8.58 kW Solar Photovoltaic
Project: 1306 – TO
Taylor Ortiz
3837 Penzance Place
Carmel, IN 46032
String Current = 10.72A
String MPP Voltage = 30.77 Vdc x 13 = 400Vdc
Voc = 1Vdc x 13 = 13Vdc
Max. Current = 15A x 1.56 = 24A
Max. Voltage = 480Vdc
Wire Size: #10 AWG USE-2 Cu 1000V Black PV Wire
(UL 4703 rated photovoltaic wire, single insulated)
NEC 2017 [Table 310.15(B)(16)]
EGC: #06 AWG THHN Cu
[NEC 2017 690.45]
[NEC 2017 Table 250.122]
12/17/20
PV Array
Junction Box
Inverter AC Disconnect
Main Service
PanelSolar MeterDC Disconnect
Label #4, #11,
#5, #10, #12
Label
#6
Label
#4, #9, #10
Label
#1
Label
#1
Label
#1
Label
#1
Label
#1
Label
#1
Label
#2, #3 Label
#4, #5, #6, #7, #8
DC JUNCTION BOX
SOLAR CIRCUIT
#2
#1
#3
#4
#5
#6
#7
#8
#9
#10
#11
#12
LABELS
1925 St Claire Ave NE
Cleveland, Ohio 44114
Phone: 216-333-1364
www.yellowlite.comConfidential Information: The contents of this document are subject to Non-Disclosure Agreement and shall not be disclosed.
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
Three Line Diagram
8.58 kW Solar Photovoltaic
Project: 1306 – TO
Taylor Ortiz
3837 Penzance Place
Carmel, IN 46032
12/17/20
Customer Signature
N
Page 1 of 2
Legend
Utility meter & AC Disconnect
Wiring Diagram
1306 – TO
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
String Configuration
Inverter:
SolarEdge
SE7600H-US
SYSTEM: 26 x Silfab SIL-330 NL @ 330W – 8.58 kW • AZIMUTH: R1,R2: 191º • PITCH: R1,R2: 32º
ADDRESS: 3837 Penzance Place Carmel, IN 46032
OWNER: Taylor Ortiz PH: (312) 523-9581
1 x String of 13Modules
Use two Soladecks to run DC conduit internally via attic
1 x String of 13 Modules
Soladeck
1
Soladeck
2
12/17/20
Customer Signature
Page 2 of 2
Wiring Diagram
1306 – TO
Project Manager: Jesse Varner
PH: 440 935 5505
Email: jesse.varner@yellowlite.com
SYSTEM: 26 x Silfab SIL-330 NL @ 330W – 8.58 kW • AZIMUTH: R1,R2: 191º • PITCH: R1,R2: 32º
ADDRESS: 3837 Penzance Place Carmel, IN 46032
OWNER: Taylor Ortiz PH: (312) 523-9581
DC conduit run
AC conduit run
Legend
AC
Disconnect
Utility
Meter
Inverter Solar
Meter
Lineside tap connection to be done in 200A Main Service Panel
Use cellular card for the online monitoring
Eastern wall Garage
200A Main
Service Panel
Penetrate into the Main Service Panel rear
12/17/20