Mark Area
Served Model Airflow
(CFM)
Static Pressure
(in. w.g.)
Electrical Connection
Weight
(lbs)Remarks
Voltage
(V)
Phase
(Ø)
Power
(HP)Disconnect
EF-1 Equipment
Room
Greenheck
SQ-95-G 300 0.4 120 1 0.05 MFR 41 1,2,3
EF-2 Various SQ-80-D 200 0.4 120 1 0.05 MFR 41 1,2,4,5
EF-3 Various Greenheck
SQ-95-G 375 0.4 120 1 0.05 MFR 41 2,4
Notes:
1.Inlet Guard screen by MFR.
2.Direct drive with solid state speed controller.
3.Fan shall run from T-stat in space. See Sequence of operations for more information.
4.Fan shall operate from disconnect.
5.Fan and all components need to be Hi-Pro Polyester coated for corrosion resistance.
'NGEVTKE9CNN*GCVGT5EJGFWNG
Mark Area
Served Raywall Model Type
Electrical Connection
Disconnect Remarks
Power (Watts)Voltage
(V)MCA (A)
EWH-1 Family Rest
Room (003)
Raywall
AFA Series Wall Heater 1500 240 6.2 MFR 1,2,3
EWH-2 Various Raywall
AFC/AFH Wall Heater 2000 240 8.3 MFR 1,3,4
Notes:
1.Fan forced heater.
2.Integral Tamper proof T-Stat to prevent adjustment by unauthorized personnel.
3.Recessed.
4.Provide Tamper proof T-stat. Thermostat control knob shall be covered by a 16 gauge tamper-proof access plate to
prevent adjustment by unauthorized personnel.
6GTOKPCN1WVNGVU
Mark Function Price
Model
Airflow
Range
(CFM)
Face Size
(in.)
Neck Size
(in.)Color Remarks
ER-1 Exhaust Register 530 0-100 7 3 4 x 7 3 4 6 x 6 By Architect 1,2,3
Notes:
1.Provide factory extended panel for any diffuser which is smaller than the grid in which it is installed.
2.Sound baffle by Sheet Metal Contractor.
3.Provide plaster frame for diffusers, registers and grilles installed in gypsum board.
Exhaust Fans:
EF-1: Exhaust fan shall run from Temperature sensor (see M100 for
location). EF shall operate when Temp goes above 85°F[adj] and shall
operate until temperature in space is 75°F[adj].
EF-2: Exhaust fan shall run continuously.
EF-3: Exhaust Fan shall run continuously when the restrooms are open for
public use.
5GSWGPEGQH1RGTCVKQPU
.QWXGTU
Mark Function Greenheck
Model
Air
Volume
(CFM)
Static
Pressure
(in w.c.)
Size Type Remarks
LVR-1 Exhaust EDJ-401 200 0.08 12 x 12 Wall 1,2,3,4
LVR-2 Exhaust EDJ-401 1400 0.08 30 x 24 Wall 1,2,3,4
LVR-3 Intake EDJ-401 1100 0.08 24 x 24 Wall 1,2,3,5
Notes:
1.Color selected by architect. Provide Insect screen.
2.Maintain at least 10'-0" between intakes and exhausts and
all other flues or vents.
3.All Sheet-metal transitions shall be provided by the
contractor.
4.Louvers must be Kynar coated for corrosion resistance.
5.Back Draft Damper. Field verify size prior to ordering. See
Plans for more information.
10 9abcd 8 7 6efgh109876 REVISIONS AND ISSUES5 4 3 2 1 PREPARED FOR:PROJECT NO.
SHEET NO.abcd5 4 3 2
CHECKED BY:DRAWN BY:DESIGNED BY:DWG NAME:PROJECT NO.:DATEBYeDATE:1
ENGINEERS317 | 846 - 6611800 | 452 - 6408317 | 843 - 0546 faxWEIHELand Surveying | Civil EngineeringLandscape ArchitectureALLAN H. WEIHE, P.E., L.S. - FOUNDER10505 N. College AvenueIndianapolis, Indiana 46280weihe.netfhgSection 1, Township 17 North, Range 3 East, Clay Township, Hamilton County, IndianaW200371CARMEL, IN 46033W20062003/05/2021LAWRENCE W. INLOW PARKPHASE II IMPROVEMENTSPROF
E
SSIONA L E N G NIEERSA M U E L L.HU
R
TINDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
Exp. 7.31.2022
Genesis Design, Inc.GNIBMULP·LACITCELE·LACINAHCEM R2410 Executive Drive - Suite 100
Indianapolis, Indiana 46241
317.636.3941
YYY6'%Ä/'2EQO
THEENGINEERINGC O L L A B OR
A
T
I
VEKnow what's below.
before you dig.Call
R AKSLHAK