HomeMy WebLinkAboutE100Service Disconnect and Meter
location. Service to be fed from
existing transformer. Confirm
exact location with Duke
Energy prior to rough-in.
EF-2
EWH-2
EWH-1
EF-1
EF-3
EWH-2
EWH-2 EWH-2
EWH-2
WH-1
Panel
'P1'P1-3
P1-4
P1-5
P1-6
P1-(7,9)
P1-(8,10)P1-(11,13)
P1-(12,14)P1-(15,17)
P1-(16,18)
P1-(19,21)P1-22
P1-3
Splash Pad
Control Panel
Location
2
P1-4WP
WPWire #8Wire #8
W1
W1
W1 W1
C2
L1
C1
L1
C2
C1
C1
C1
C1 C1
C1
C1
C1
C1
P1-1
P1-21
L1
A.All 120V., 20 Amp circuits over 60' in length shall be #10
AWG.
B.Contractor shall coordinate with all other trades to avoid
conflicts of space.
C.Contractor shall coordinate the exact location of all
devices with all other trades prior to rough-in. Exact
location to be determined in the field.
D.Contractor shall coordinate with the mechanical and
plumbing contractors for exact locations of equipment prior
to rough-in.
E.Refer to sheet E600 for light fixture and panel schedule.
F.Refer to sheet E700 for symbols and details.
G.Shared neutrals shall not be permitted.
H.Switches shall be a maximum 48" A.F.F. to the top of the
device.
I.Outlets above counters shall be a maximum of 46" A.F.F.
to the top of the device.
J.All receptacles and data outlets shall be installed 18"
A.F.F. to top of the device unless otherwise noted in the
plans.
)GPGTCN0QVGU
Circuit shall be controlled by photocell 1P and digital time
switch 1HH. Provide and install photocell on roof.
Provide connection for Sump Pump at storage tank
using 1/2” conduit. Circuit to P1-20. Confirm Sump Pump
location prior to rough-in.
2NCP0QVGU
1
2
10 9abcd 8 7 6efgh109876 REVISIONS AND ISSUES5 4 3 2 1 PREPARED FOR:PROJECT NO.
SHEET NO.abcd5 4 3 2
CHECKED BY:DRAWN BY:DESIGNED BY:DWG NAME:PROJECT NO.:DATEBYeDATE:1
ENGINEERS317 | 846 - 6611800 | 452 - 6408317 | 843 - 0546 faxWEIHELand Surveying | Civil EngineeringLandscape ArchitectureALLAN H. WEIHE, P.E., L.S. - FOUNDER10505 N. College AvenueIndianapolis, Indiana 46280weihe.netfhgSection 1, Township 17 North, Range 3 East, Clay Township, Hamilton County, IndianaW200371CARMEL, IN 46033W20062003/05/2021LAWRENCE W. INLOW PARKPHASE II IMPROVEMENTSPROF
E
SSIONA L E N G NIEERSA M U E L L.HU
R
TINDIA N A
0
N
EP1 6
.o
01087
ATS FOET
R E TEGIS
D
ER
Exp. 7.31.2022
Genesis Design, Inc.GNIBMULP·LACITCELE·LACINAHCEM R2410 Executive Drive - Suite 100
Indianapolis, Indiana 46241
317.636.3941
YYY6'%Ä/'2EQO
THEENGINEERINGC O L L A B OR
A
T
I
VEKnow what's below.
before you dig.Call
R SJWSLHSJW