HomeMy WebLinkAboutPlanset - DownerSHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
A0
PROJECT INFO
VICINITY MAP
PROJECT SITE
PROJECT SITE
OWNER: CHRISTOPHER DOWNER
ADDRESS:12925 HARRISON DR
CARMEL, IN 46033
PHONE: 317-371-3191
EMAIL: TITODOWNER@GMAIL.COM
APN:291028305013000018
(HAMILTON COUNTY)
CONSTRUCTION TYPE:VB
OCCUPANCY TYPE:R3- RESIDENTIAL
SHEET INDEX
A1 SITE PLAN, PROJECT INFO
A2 MOUNTING ROOF PLAN
E1 SINGLE LINE DIAGRAM
E2 ELECTRICAL CALCULATIONS
E3 REQUIRED SIGNAGE
E4 MODULE DATA SHEET
E5 OPTIMIZER DATA SHEET
E6 INVERTER DATA SHEET
S1 STANCHION DATA SHEET
S2 RACKING DATA SHEET
S3 RACKING ENGINEERING
S4 RACKING GROUNDING
S5 RACKING CERTIFICATION
13.135 DC kW SOLAR PV STRING INVERTER SYSTEM - ROOF MOUNT
DOWNER RESIDENCE
VICINITY MAP AERIAL VIEW
12925 HARRISON DR CARMEL, IN 46033
ARRAY AREA: 18.82 SQFT x 37 = 696.32 SQFT
PROJECT SCOPE
INSTALLATION OF ROOF MOUNT SOLAR PV SYSTEM
DERATE 200AMP MAIN BREAKER TO 175AMP
NEW
EQUIPMENT: 37 REC355AA BLK
REC SOLAR MODULES
37 P370 SOLAREDGE OPTIMIZERS
1 SE10000H-US (240V)
SOLAREDGE HD INVERTER
SYSTEM SIZE: 13.135 DC kW RATING
12.315 CEC AC RATING
SERVICE: EXISTING 200A MAIN SERVICE PANEL
APPLICABLE CODES
2014 IN BUILDING CODES
2020 IN RESIDENTIAL CODES
2012 IN PLUMBING CODES
2014 IN MECHANICAL CODES
2011 NEC (NFPA 70)
2012 INTERNATIONAL FIRE CODE
SOLAR PHOTOVOLTAIC SYSTEM NOTES
· ALL EQUIPMENT SHALL BE LISTED AND LABELED BY A RECOGNIZED TESTING LABORATORY AND INSTALLED PER
THE LISTING REQUIREMENTS AND THE MANUFACTURER’S INSTRUCINSTRUCTIONS, NEC 110.2, 110.3, 690.4(B)
AND 690.12(5).
· ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED IN ACCORDANCE WITH CEC ARTICLE 250.
· ALL PV CIRCUITS CONNECTED TO MORE THAN ONE SOURCE SHALL HAVE OVERCURRENT DEVICES LOCATED SO
AS TO PROVIDE OVERCURRENT PROTECTION FROM ALL SOURCES, NEC 690.9(A).
· ALL EQUIPMENT OF THE PV SYSTEM (INCLUDING RAPID SHUTDOWN INITIATION) SHALL BE LOCATED NEAR THE MAINELECTRICAL SERVICE EQUIPMENT, NEC 690.13, 690.15.
· RAPID SHUTDOWN EQUIPMENT TO PROVIDE CONTROLLED CONDUCTORS THAT ARE MORE THAN 5 FEET IN LENGTH
INSIDE A BUILDING OR MORE THAN 10 FEET FROM A PV ARRAY LIMITATION TO NOT MORE THAN 30 VOLTS AND 240
VOLT-AMPERES WITHIN 30 SECONDS OF RAPID SHUTDOWN INITIATION, NEC 690.12.
· THE UTILITY-INTERACTIVE INVERTERS SHALL AUTOMATICALLY DE-ENERGIZE ITS OUTPUT TO THE CONNECTEDELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK UPON LOSS OF VOLTAGE IN THE SYSTEM AND SHALL
REMAIN IN THAT STATE UNTIL THE ELECTRICAL PRODUCTION AND DISTRIBUTION NETWORK VOLTAGE HAS BEEN
RESTORED, NEC 690.61 & 705.40.
· DUE TO THE FACT THAT PV MODULES ARE ENERGIZED WHENEVER EXPOSED TO LIGHT, PV CONTRACTOR SHALL
DISABLE THE ARRAY DURING INSTALLATION AND SERVICE BY SHORT CIRCUITING, OPEN CIRCUITING, OR COVERING
THE ARRAY WITH OPAQUE COVERING,NEC 690.18.
· ALL CONDUCTOR EXPOSED TO WEATHER SHALL BE LISTED AND IDENTIFIED FOR USE IN DIRECT SUNLIGHT,
NEC310.10(D) AND 690.31(C) THROUGH (G).
· ALL CONDUCTORS TO BE OF MATERIAL APPROVED BY THE CODE AND THEIR INSULATIONS TO BE RATED TO NOT
LESS THAN 90OC 600-VOLTS MINIMUM
· INSULATION OF EXPOSED CONDUCTORS UNDER THE MODULES SHALL BE USE-2 OR PV-WIRE TYPE FOR GROUNDED
DC SYSTEMS,NEC 690.31(B); AND PV-WIRE TYPE FOR UNGROUNDED DC SYSTEMS, (AS IN TRANSFORMERLESS
INVERTERS OR MICROINVERTERS WITH ISOLATED GROUNDS), NEC 690.35(D).
· FINE-STRANDED CABLE CONNECTIONS MUST BE MADE IN LUGS AND TERMINALS LISTED AND MARKED FOR THE
USE, NEC 110.14 & 690.74(A).
· ALL PV CIRCUIT CONDUCTORS SHALL BE MARKED ON EACH END FOR UNIQUE IDENTIFICATION, NEC 690.31(B).
· ALL GROUNDED, (NEUTRAL), CONDUCTORS’ INSULATION SHALL BE SOLID WHITE, GRAY, OR WITH 3-WHITE
STRIPES, NEC 200.6, 200.7, & 400.22; AND ALL GROUNDING CONDUCTORS SHALL BE OF BARE WIRE WITHOUT
COVERING, OR WITH INSULATION OF GREEN OR GREEN WITH YELLOW STRIPES, NEC 250.119 & 400.23. THE COLOR
OF UNGROUNDED CONDUCTORS SHALL BE OTHER THAN FOR GROUNDED, (NEUTRAL)
· MAXIMUM CONDUCTOR LENGTH BETWEEN SUPPLY SIDE CONNECTION AND OVERCURRENT PROTECTION IS 10
FEET, NEC 705.31
· CONNECTIONS ON THE LOAD SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER SOURCE(S) AT ANY
DISTRIBUTION EQUIPMENT ON THE PREMISES SHALL MEET THE FOLLOWING, NEC 705.12(D).
· DC WIRING INSIDE A BUILDING MUST BE IN METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, OR
CABLE SHEATHINGS, NEC 690.31(G)
· RACEWAYS IN ENCLOSED PORTIONS OF THE BUILDING MUST RUN ALONG BOTTOM OF LOAD BEARING
MEMBERS,
· METALLIC TYPE RACEWAYS, CONDUITS, ENCLOSURES, AND CABLE SHEATHS CONTAINING CIRCUITS OVER
250-VOLTS TO GROUND MUST BE BONDED IN ACCORDANCE WITH NEC 250.97 & 290.92(B).
· FLEXIBLE, FINE-STRANDED CABLES SHALL BE TERMINATED ONLY WITH TERMINALS, LUGS, DEVICES OR
CONNECTOR THAT ARE IDENTIFIED AND LISTED FOR SUCH USE, NEC 690.31(H) & 110.14.
· CONNECTORS SHALL BE OF LATCHING OR LOCKING TYPE. CONNECTORS THAT ARE READILY
ACCESSIBLE AND OPERATING AT OVER 30 VOLTS SHALL REQUIRE TOOL TO OPEN ANDMARKED “DO NOT DISCONNECT UNDER LOAD” OR “NOT FOR CURRENT
INTERRUPTING”, NEC 690.33(C) & (E)(2).
· EQUIPMENT GROUNDING CONDUCTOR FOR PV MODULES SMALLER THAN 6 AWG SHALL BE
PROTECTED FROM PHYSICAL DAMAGE BY A RACEWAY OR CABLE ARMOR, NEC 690.46 & 250.120(C).
· THE INTERCONNECTION POINT SHALL BE ON THE LINE SIDE OF ALL GROUND-FAULT PROTECTION
EQUIPMENT, NEC 705.32.
· DC PV SOURCE OR DC PV OUTPUT CIRCUITS SHALL BE CONTAINED IN METAL RACEWAYS, TYPE MC
CABLE OR METALLIC ENCLOSURES WHEN INSIDE THE BUILDING, NEC 690.31(G).
· CABLES/WIRES THAT ARE SUBJECT TO PHYSICAL DAMAGE, SUCH AS THOSE NOT LOCATED UNDER
THE MODULES, MUST BE PROTECTED, NEC 300.4.
· PROPOSED LOCATIONS OF ELECTRICAL SERVICE REPLACEMENTS MUST ALSO BE APPROVED BYTHE ELECTRICAL UTILITY COMPANY.
· FOR ELECTRICAL SERVICE REPLACEMENTS, BONDING TO THE METAL PIPES OF NATURAL GAS, HOT
WATER, AND COLD WATER MUST BE PROVIDED, NEC 250.104.
· GROUNDING ROD ELECTRODES SHALL BE INSTALLED 8’ MINIMUM IN CONTACT WITH
SOIL, NEC 250.53(G).
· ALL EXTERIOR CONDUITS SHALL BE PAINTED TO MATCH THE COLOR OF THE SURROUNDING AREA
(ROOF, SIDING, AND STUCCO).
· EXISTING PLUMBING VENTS, SKYLIGHTS, EXHAUST OUTLETS, & VENTILATIONS INTAKE AIR OPENINGS
SHALL NOT BE COVERED OR BLOCKED BY THE SOLAR PHOTOVOLTAIC SYSTEM.
· EXISTING DWV PLUMBING VENT TERMINATIONS THAT ARE HORIZONTALLY LOCATED CLOSER
THAN 12” FROM THE PROPOSED MODULES, MUST BE REROUTED, OR MUST BE EXTENDED A
MINIMUM OF 6” ABOVE THE SURFACE OF THE MODULES
· EXISTING B-VENT TERMINATIONS, FOR FUEL BURNING APPLIANCES, WHERE ADJACENT TO THE
PROPOSED MODULES, MUST BE EXTENDED 12” ABOVE THE MODULES’ TOP
SURFACE
· THE MARKINGS, “WARNING: PHOTOVOLTAIC POWER SOURCE”, FOR DC RACEWAYS AND CABLE
ASSEMBLIES MUST BE AT 10’ O.C.; AND BENDS, ABOVE OR BELOW PENETRATIONS OF
ROOFS, CEILINGS, WALLS, OR BARRIERS, NEC 690.31(G)(4).
· PV COMBINER PANELBOARDS MUST HAVE PERMANENT MARKINGS INDICATING THAT THEY ARE
DEDICATED FOR PV CIRCUITS ONLY NO LOADS ARE TO BE CONNECTED.
· WORKING CLEARANCES TO BE PROVIDED AT NEW AND EXISTING ELECTRICAL EQUIPMENT, NEC
110.26.
· RESIDENTIAL TYPE PV CIRCUITS OVER 150-VOLTS TO GROUND MUST NOT BE ACCESSIBLE TO
OTHER THAN QUALIFIED PERSONS WHILE ENERGIZED, NEC 690.7(D).
· A LADDER MUST BE PROVIDED FOR INSPECTIONS IN ACCORDANCE WITH CAL-OSHA REGULATIONS.
· ALL OF THE REQUIRED MARKINGS, SIGNS, AND LABELS MUST BE INSTALLED ON ALL EQUIPMENT
PRIOR TO ANY INSPECTIONS.
· LABELS SHALL BE REFLECTIVE, AND ALL LETTERS SHALL BE CAPITALIZED AND SHALL BE A
MINIMUM HEIGHT OF 3/8’’ IN WHITE ON A RED BACKGROUND.
· WHEN THE MAIN CIRCUIT BREAKER IS DERATED, A PERMANENT MARKING MUST BE PROVIDED ON
THE PANELBOARD TO INDICATE THAT THE MAIN CIRCUIT BREAKER HAS BEEN DOWNSIZED TO_______AMPS, DO NOT UPSIZE IT.
· GROUND-MOUNTED PV SYSTEMS MUST HAVE A CLEAR, BRUSH-FREE AREA OF 10-FEET AND A FIRE
SEPARATION DISTANCE OF 5-FEET MINIMUM TO OTHER STRUCTURES AND PROPERTY LINES
GENERAL NOTES
1. WORKING CLEARANCES AROUND ALL ELECTRICAL EQUIPMENT SHALL BE MAINTAINED IN ACCORDANCE
WITH CEC 110.26.
2. PV EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL ONLY BE INSTALLED BY
QUALIFIED PERSONS. CEC 690.4 (E)
3. ROOFTOP MOUNTED PV SYSTEM PANELS AND MODULES SHALL MEET A MINIMUM FIRE CLASSIFICATION AS
REQUIRED BY R902.4 AND CBC 1505.9.
4. ROOF ACCESS POINTS. ROOF ACCESS POINTS SHALL BE LOCATED IN AREAS THAT DO NOT REQUIRE THE
PLACEMENT OF GROUND LADDERS OVER OPENINGS SUCH AS WINDOWS OR DOORS, AND LOCATED AT
STRONG POINTS OF BUILDING CONSTRUCTION IN LOCATIONS WHERE THE ACCESS DOES NOT CONFLICT
WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES OR SIGNS (R331.4.1).LADDERS SHALL BE
OSHA APPROVED AND SECURED TO THE STRUCTURE FOR INSPECTION PURPOSES.CONTRACTORS ARE
REQUIRED TO BE PRESENT FOR THE FIRST AND/OR FINAL INSPECTIONS.
5. APPROVED SMOKE AND CARBON MONOXIDE ALARMS ARE REQUIRED WITHIN THE DWELLING UNIT AND
SHALL BE FIELD VERIFIED EITHER THROUGH FINAL BUILDING INSPECTION. SMOKE ALARMS ARE REQUIRED
TO BE INSTALLED IN ALL BEDROOMS, OUTSIDE EACH BEDROOM, AND AT LEAST ONE ON EACH FLOOR OF
THE HOUSE. CARBON MONOXIDE ALARMS ARE REQUIRED OUTSIDE EACH BEDROOM AND AT LEAST ONE
ON EACH FLOOR OF THE HOUSE. R314.1, R315.1
6. NOTIFY SERVING UTILITY BEFORE ACTIVATION OF PV SYSTEM.
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
A1
SITE PLAN
LEGEND:
(E) - EXISTING
(N) - NEW
SITE PLAN
SCALE: 1/16" = 1'
(E) 1 - STORY
4075 SQFT
N
S
EW
H A R R I SO N
D R
(E) DRIVEWAY
INSIDE HOUSE
(E) 200A MAIN SERVICE PANEL
(N) SE10000H-US (240V)
SOLAREDGE HD INVERTER
(N) 60A AC DISCONNECT
(N) 37 - REC355AA BLK
REC SOLAR MODULES WITH P370
SOLAREDGE OPTIMIZERS
P
R
O
P
E
R
TY
LI
N
E
(E) UTILITY METER
P
R
O
P
E
R
T
Y
L
I
N
E
PROPERTY LINE04/02/21
MSPMIN
V
D
JB
3'18"3'4'3'3' 3'±41116"2.5"MIN2.5"MIN±4916"A2
MOUNTING
PLAN
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
MOUNTING PLAN
SCALE: 3/32" = 1'-0"
LEGEND
(E) EXISTING
(N) NEW
CONDUIT RUN
VIF VERIFY IN FIELD
JUNCTION BOX
MAIN SERVICE PANEL
SUBPANEL
INVERTER
UTILITY METER
AC DISCONNECT
MSP
JB
N
S
EW
SUB
INV
66 TOTAL
ATTACHMENTS @
4FT OC MAX
D
M
ROOF INFO
COMP SHINGLE ROOF 1 - LAYER
2 X 6 RAFTERS
16 " ON CENTER
72 "ATTACHMENT MAX SPACING
ON CENTER
MODULES COVER 28% OF THE ROOF
AREA LESS THAN 33% (CRC 324.6.2)
3/4" EMT CONDUIT RUN
WIRING/CONDUIT RUN
7/8'' MINIMUM ABOVE THE
ROOF
FIRE ACCESS POINT
(NOT TO BE OVER ANY
DOORS, WINDOWS OR
OTHER OBSTRUCTIONS)
STRING A OF 13 MODULES
STRING B OF 12 MODULES
STRING C OF 12 MODULES
3' FIRE
PATHWAY PER
R324.6.1
(N) 37 - REC355AA BLK
REC SOLAR MODULES WITH P370
SOLAREDGE OPTIMIZERS
125.96° AZIMUTH
33° SLOPE
A FIRE SETBACK
SOLAR PANEL DEAD WEIGHT CALCULATION
RACKING
MANUFACTURER IRONRIDGE FLUSH MOUNT AND XR100 RAILS
MODULE REC ALPHA SERIES MODULE
TOTAL # OF
MODULES 37 MOUNTING SYSTEM WEIGHT 203.38 LBS
MODULE WEIGHT 48.5 LBS TOTAL SOLAR MODULE WEIGHT 1794.50 LBS
MODULE LENGTH 67.75 INCHES TOTAL PANEL WEIGHT CALCULATION 1997.88 LBS
MODULE WIDTH 40.00 INCHES POINT LOAD CALCULATION 30.27 LBS
MODULE AREA 18.82 SQFT TOTAL SOLAR MODULE AREA 696.32 LBS
TOTAL# OF
ATTACHMENTS 66 DISTRIBUTED LOAD CALCULATION
THE POINT LOADING AND DISTRIBUTED LOADING SHOULD BE
MAX 5 LBS/FT2
2.87 PSF
RACKING WEIGHT .68 LBS / LN FT
ROOF COVERAGE
TOTAL MODULE AREA 696.32 27.9% </= 50% = OK
ROOF FACE AREA 2492
ROOF COVERAGE (%) 27.9
INSIDE HOUSE
(E) 200A MAIN SERVICE PANEL
(N) SE10000H-US (240V)
SOLAREDGE HD INVERTER
(N) 60A AC DISCONNECT
(E) UTILITY METER
3' FIRE
PATHWAY PER
R324.6.1
215.68° AZIMUTH
33° SLOPE
FIRE SETBACKFI
R
E
SE
T
B
A
C
K
FI
R
E
SE
T
BA
C
K
FIRE SETBACKA
A
A
A
A
A
A
A
A
A
A
A
B
B
B
B
B
B
B
B
B
B
B
B
C
C
C
C
C
C
C
C
C
C
C
C
MODULE
FLASHFOOT
IRONRIDGE
XR100 RAILS
ALUMINUM
FLASHING
WITH 3-COURSE
APPLICATION
EXISTING
RAFTERS
ROOF ATTACHMENT DETAIL
SCALE: 1-1/2" = 1'-0"
FRONT VIEW
SIDE VIEW
EXISTING
RAFTERS
MODULE
FLASHFOOT
IRONRIDGE
XR100 RAILS
ALUMINUM
FLASHING
WITH 3-COURSE
APPLICATION
5/16" Ø SS LAG BOLT
1 LAG PER ATTACHMENT
2.5" MIN EMBEDMENT
5/16" Ø SS LAG BOLT
1 LAG PER ATTACHMENT
2.5" MIN EMBEDMENT
NOTE:
MODULES WILL BE INSTALLED
FLUSHED TO EXISTING ROOF SLOPE
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAGcadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E1
ELECTRICAL
LINE DIAGRAM
SERVICE LOAD CALCULATIONS @ MSP
BACKFED 120% RULE - PER 705.12 (D)
BUS RATING SIZE MUTIPLIER (120%) RESULT
200 1.20 240.00
MCB INVERTER AC
OUTPUT +125%RESULT
175 52.50 227.50
240A >/= 227.50A = OK
125% OF TOTAL INVERTER MAX AC OUTPUT
MAX AC
OUTPUT
(AMPS)
125%RESULT
(AMPS)OCPD SIZE
42 1.25 40.00 60A
WIRE/CONDUIT SCHEDULE
TAG DESCRIPTION CONDUCTOR TYPE/SIZE/QUANTITY CONDUIT
SIZE/TYPE
A ARRAY TO JUNCTION BOX (6) #10 AWG PV WIRE & #6 AWG SOLID COPPER (G) FREE AIR
B JBOX TO INVERTER (6) #10 AWG THWN-2 (3+& 3-) & (1) #8 AWG THWN-2 (G) 3/4" EMT
C INVERTER TO AC DISCONNECT (3) # 6 AWG THWN-2 (L1, L2 & N) & (1) #8 AWG THWN-2 (G) 3/4" EMT
D AC DISCONNECT TO MAIN
SERVICE PANEL (3) # 6 AWG THWN-2 (L1, L2 & N) & (1) #8 AWG THWN-2 (G) 3/4" EMT
INVERTER SPECIFICATION
INVERTER MAKE SOLAREDGE
INVERTER MODEL NO. SE10000H-US (240V)
MAX INPUT VOLTAGE 480 V
MAX INPUT CURRENT 27 A
NOMIMAL AC VOLTAGE 240 V
MAX AC CURRENT 42A
(N)JB
BNEMA 3R
DC AC...
A
WITH INTEGRATED DC
DISCONNECT AND
AUTOMATIC RAPID
SHUTDOWN UPON
AC GRID DISCONNECT
(N) 37 - REC355AA BLK
REC SOLAR MODULES
WITH P370 SOLAREDGE
OPTIMIZERS
13
12
DC/DC CONVERTER/OPTIMIZER VOLTAGE CALCULATION
LARGEST MODULE VOC FOR SINGLE-MODULE DC/DC CONVERTER CONFIGURATIONS (WITH 80V AFCI CAP) (CEC 690.7 and 690.11)
MODULE VOC ____ X # OF MODULES PER CONVERTER ___X CF = V
MODULE VOC MODULES PER INVERTER TL IS GREATER THAN OR EQUAL TO
-5°C, CF VOLTS
43.60 1.00 1.12 48.83
60V > 48.83V = OK THE VALUE CALCULATED MUST BE LESS THAN
OPTIMIZERS MAX DC INPUT VOLTAGE
(N) SE10000H-US (240V)
SOLAREDGE HD INVERTER
MAX AC OUTPUT = 42A
NEC 705.12(D)(2)(3)(B)
WHERE TWO SOURCES, ONE A UTILITY AND THE OTHER AN
INVERTER, ARE LOCATED AT OPPOSITE ENDS OF A BUSBAR
THAT CONTAINS LOADS, THE SUM OF 125% OF THE
INVERTER(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF
THE OVERCURRENT DEVICE PROTECTING THE BUSBAR
SHALL NOT EXCEED 120% OF THE AMPACITY OF THE
BUSBAR.
PV BREAKER MUST BE
INSTALLED AT THE
FARTHEST OPPOSITE END
OF THE MAIN BREAKER
MODULE SPECIFICATION
MANUFACTURER REC SOLAR
MODEL NO. REC355AA BLK
PEAK POWER 355W
RATED VOLTAGE (Vmp) 36.4 V
RATED CURRENT (Imp) 9.77 A
OPEN CIRCUIT VOLTAGE (Voc) 43.6 V
SHORT CIRCUIT CURRENT (Isc) 10.47 A
(N)175A
MCB
DERATE M
(N)60A
(E) 200A MAIN
SERVICE PANEL
G
N
EXISTING
WIRES &
CONDUCTORS
(E) UTILITY
METER
PV OCPD
(N) 60A AC
DISCONNECT
D
SOLAR GROUND TYING
INTO THE EXISTING
UFER GROUND POINT
C
INSIDE HOUSE
(E) EARTH
GROUND
12
INVERTER DC INPUT CURRENT IS REGULATED BY
SOLAREDGE OPTIMIZER, MAX STRING CURRENT IS
4615= 11.54 AMPS400
INVERTER DC INPUT VOLTAGE IS REGULATED BY SOLAREDGE OPTIMIZER
MAX # OF MODULES IN A STRING X MODULE WATTAGE
NOMIMAL DC INPUT VOLTAGE OF INVERTER
11.54 AMPS </= 15 AMPS = OK
13 X 355 W
400 V =
WITH A MAXIMUM SHORT CIRCUIT OF 15A (OPTIMIZER MAX
OUTPUT CURRENT) [CEC 690.8]
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E2
ELECTRICAL
CALCULATIONS
DC CONDUCTOR AMPACITY CALCULATIONS
ARRAY TO JUNCTION BOX (CEC ART 310.15)
A EXPECTED WIRE TEMPERATURE (FREE AIR) 35 CELSIUS
B ADD 22°C OR 4O°F FOR CONDUITS EXPOSED TO
SUNLIGHT ON OR ABOVE ROOF 57 CELSIUS
TEMPERATURE CORRECTION FACTOR
CEC TABLE 310.15 (B)(2)(A)0.71
C # OF CURRENT CARRYING CONDUCTORS 6 (UP TO 8 CONDUCTORS IN ROOF MOUNTED CONDUITS EXPOSED TO SUNLIGHT)
D CONDUIT FILL CORRECTION 0.80 .80 (FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00 (FOR 3 OR LESS CONDUCTORS IN CONDUIT)
CEC TABLE 310.15 (B)(3)(A)
E CIRCUIT CONDUCTOR SIZE #10 AWG MINIMUM #10 AWG CU, 90°C WET (USE-2, PV WIRE, THWN-2, RHW-2)
F CIRCUIT CONDUCTOR AMPACITY 40 AMPS CEC TABLE 310.15 (B)(16)
G REQUIRED CIRCUIT CONDUCTOR AMPACITY 18 AMPS OPTIMIZER ISC
H DERATED AMPACITY OF CIRCUIT CONDUCTOR 22.72 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY
CEC TABLE 310.15 (B)(2)(A)
NOTE: "H" MUST BE LARGER THAN "G" 22.72A > 18.00A = OK
DC CONDUCTOR AMPACITY CALCULATIONS
FROM JUNCTION BOX TO INVERTER
A AMBIENT TEMPERATURE ADJUSTMENT
EXPOSED CONDUIT 57 CELSIUS
(ADD 22° OR 4O° FOR CONDUITS EXPOSED TO SUNLIGHT ON OR ABOVE ROOF)
CEC TABLE 310.15 (B)(2)(A) & CEC TABLE 310.15 (B)(2)(C)
EXPECTED WIRE TEMPERATURE
TEMPERATURE CORRECTION FACTOR 0.71 CEC TABLE 310.15 (B)(2)(A)
# OF CURRENT CARRYING CONDUCTORS 6 (UP TO 8 CONDUCTORS IN ROOF MOUNTED CONDUITS EXPOSED TO SUNLIGHT)
CONDUIT FILL CORRECTION 0.80 .80 (FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00 (FOR 3 OR LESS CONDUCTORS IN CONDUIT)
CEC TABLE 310.15 (B)(3)(A)
CIRCUIT CONDUCTOR SIZE #10 AWG MINIMUM #10 AWG CU, 90°C WET (USE-2, PV WIRE, THWN-2, RHW-2)
CIRCUIT CONDUCTOR AMPACITY 40 AMPS CEC TABLE 310.15 (B)(16)
B REQUIRED CIRCUIT CONDUCTOR AMPACITY 18 AMPS OPTIMIZER ISC
C DERATED AMPACITY OF CIRCUIT CONDUCTOR 22.72 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY
CEC TABLE 310.15 (B)(2)(A)
NOTE: "C" MUST BE LARGER THAN "B" 22.72A > 18.00A = OK
AC CONDUCTOR AMPACITY CALCULATIONS
BETWEEN INVERTER TO MAIN SERVICE
A AMBIENT TEMPERATURE ADJUSTMENT
EXPOSED CONDUIT 57 CELSIUS
(ADD 22° OR 4O° FOR CONDUITS EXPOSED TO SUNLIGHT ON OR ABOVE ROOF)
CEC TABLE 310.15 (B)(2)(A) & CEC TABLE 310.15 (B)(2)(C)
EXPECTED WIRE TEMPERATURE
TEMPERATURE CORRECTION FACTOR 0.96 CEC TABLE 310.15 (B)(2)(A)
# OF CURRENT CARRYING CONDUCTORS 2 (UP TO 8 CONDUCTORS IN ROOF MOUNTED CONDUITS EXPOSED TO SUNLIGHT)
CONDUIT FILL CORRECTION 1.00 .80 (FOR 4 TO 6 CONDUCTORS IN CONDUIT) OR 1.00 (FOR 3 OR LESS CONDUCTORS IN CONDUIT)
CEC TABLE 310.15 (B)(3)(A)
CIRCUIT CONDUCTOR SIZE #6 AWG MINIMUM #10 AWG CU, 90°C WET (USE-2, PV WIRE, THWN-2, RHW-2)
CIRCUIT CONDUCTOR AMPACITY @ 90° 75 AMPS CEC TABLE 310.15 (B)(16)
INVERTER'S MAXIMUM AC OUTPUT CURRENT 42 AMPS INVERTER MANUFACTURER SPECIFICATIONS
B REQUIRED AC CONDUCTOR AMPACITY 40.00 AMPS REQUIRED AC CONDUCTOR AMPACITY =1.25 X MAXIMUM INVERTER'S OUTPUT CURRENT (AMPS)
C DERATED AMPACITY OF CIRCUIT CONDUCTORS 72.00 AMPS TEMPERATURE CORRECTION X CONDUIT FILL CORRECTION X CIRCUIT CONDUCTOR AMPACITY
CEC TABLE 310.15 (B)(2)(A)
NOTE: "C" MUST BE GREATER THAN "B" 72.00A > 52.50A = OK
OPTIMIZERS SPECIFICATION
MAKE SOLAREDGE P370
MAXIMUM INPUT DC POWER 370
ABSOLUTE MAX INPUT VOLTAGE (VOC)60 VDC
MAX SHORT CIRCUIT CURRENT (ISC)11 ADC
MAX DC INPUT CURRENT 13.75 ADC
MAX OUTPUT CURRENT 15 ADC
MAX OUTPUT VOLTAGE 60 ADC
LOCATION INFORMATION
HIGH TEMP 35°
LOW TEMP -22°
VOLTAGE CORRECTION FACTOR 1.12
ROOF TEMP + 22° 57°
TEMP CORRECTION FACTOR (EXPOSED) 0.71
TEMP CORRECTION FACTOR (CONDUIT) 0.96
INVERTER SPECIFICATION
INVERTER MAKE SOLAREDGE
INVERTER MODEL NO. SE10000H-US (240V)
MAX INPUT VOLTAGE 480 V
MAX INPUT CURRENT 27 A
NOMIMAL AC VOLTAGE 240 V
MAX AC CURRENT 42A
MODULE SPECIFICATION
MANUFACTURER REC SOLAR
MODEL NO. REC355AA BLK
PEAK POWER 355W
RATED VOLTAGE (Vmp) 36.4 V
RATED CURRENT (Imp) 9.77 A
OPEN CIRCUIT VOLTAGE (Voc) 43.6 V
SHORT CIRCUIT CURRENT (Isc) 10.47 A
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E3
REQUIRED
SIGNAGE
DIRECTORY PLACARD
NEC 705.10 & NEC 690.56(B) REQUIRES A PERMANENT PLAQUE OR DIRECTORY
DENOTING ALL ELECTRIC POWER SOURCE ON OR IN THE PREMISES OR RAPID FIRE
SHUTDOWN EQUIPMENT; INSTALL AT MAIN SERVICE PANEL
· ALL INTERIOR AND EXTERIOR DC CONDUIT, ENCLOSURES, RACEWAYS, CABLE ASSEMBLIES,
JUNCTION BOXES, COMBINER BOXES AND DISCONNECTS ARE MARKED. (CFC 605.11.1, CEC
690.31[E], 690.17 & 690.53 & CRC R324)
· THE MARKINGS ON THE CONDUITS, RACEWAYS AND CABLE ASSEMBLIES ARE EVERY 10 FEET,
WITHIN ONE FOOT OF ALL TURNS OR BENDS AND WITHIN ONE FOOT ABOVE AND BELOW ALL
PENETRATIONS OF ROOF/CEILING ASSEMBLIES, WALLS AND BARRIERS. (CFC 605.11.1.4, CEC
690.31[E])
· MARKING IS PLACED ADJACENT TO THE MAIN SERVICE DISCONNECT IN A LOCATION CLEARLY
VISIBLE FROM WHERE THE DISCONNECT IS OPERATED. (CFC 605.11.1.3 & CRC R324)
· THE MARKINGS SAY WARNING: PHOTOVOLTAIC POWER SOURCE
AND HAVE 3/8-INCH (9.5 MM) MINIMUM-SIZED WHITE LETTERS ON A RED BACKGROUND. THE
SIGNS ARE MADE OF REFLECTIVE WEATHER RESISTANT MATERIAL. (CFC 605.11.1.1, 605.11.1.2 &
CRC R324 & CEC 690.31)
· WHERE PV CIRCUITS ARE EMBEDDED IN BUILT-UP, LAMINATE OR MEMBRANE ROOFING
MATERIALS IN ROOF AREAS NOT COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT, THE
LOCATION OF CIRCUITS SHALL BE CLEARLY MARKED. (CEC 690.4)
· REQUIRED LABELS SHALL BE PERMANENT AND SUITABLE FOR THE ENVIRONMENT.
SIGNAGE NOTES:H ARRISON DRDRIVEWAY MAIN SERVICE
PANEL
INVERTER
AC DISCO
SOLAR
ARRAYS 6"5"
UTILITY
METER
CAUTION
POWER TO THIS BUILDING ALSO SUPPLIED
FROM THE FOLLOWING SOURCES WITH
DISCONNECTS AS SHOWN
G
F
SIGNS AND LABEL - CENTRAL/STRING INVERTER SYSTEMS
NEC ARTICLES 690 AND 705 REQUIRE THE FOLLOWING LABELS OR MARKINGS BE INSTALLED AT
THESE COMPONENTS OF THE PHOTOVOLTAIC SYSTEM:
WARNING: PHOTOVOLTAIC
POWER SOURCE
NEC 690.31(G)(3)(4)
ON ALL INTERIOR AND EXTERIOR PV CONDUIT,
RACEWAYS, ENCLOSURES, CABLE ASSEMBLIES
AND JUNCTION BOXES PROVIDE A SIGN WITH THE
FOLLOWING WORDING:
H
CAUTION:
SOLAR ELECTRIC SYSTEM CONNECTED
WARNING
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINAL. TERMINAL ON
BOTH LINE AND LOAD SIDE MAY BE
ENERGIZED IN THE OPEN POSITION
NEC 690.17
AT THE MAIN SERVICE DISCONNECT PROVIDE A
SIGN WITH THE FOLLOWING WORDING:
WARNING
INVERTER CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
PER NEC 690.64 AND 705.12(D)(4) EQUIPMENT
CONTAINING OVERCURRENT DEVICES IN CIRCUITS
SUPPLYING POWER TO A BUSBAR FROM MULTIPLE
SOURCES SHALL BE MARKED TO INDICATE THE
PRESENCE OF ALL SOURCES. LOCATED AT
BACKFED BREAKER
PHOTOVOLTAIC POWER SOURCE SHALL BE LABELED WITH THE
FOLLOWING WARNING AT EACH JUNCTION BOX, COMBINER
BOX, DISCONNECT, AND DEVICE WHERE ENERGIZED,
UNGROUNDED CIRCUITS MAY BE EXPOSED DURING SERVICE
PER NEC690.35(F)
WARNING
ELECTRIC SHOCK HAZARD
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE
UNGROUNDED AND MAY BE ENERGIZED
LABEL FOR SOLAR AC DISCONNECT:
SOLAR AC DISCONNECT
PROVIDE WARNING LABEL AT THE UTILITY
INTERACTIVE INVERTER OR GROUND FAULT
INDICATOR STATING:
WARNING
ELECTRIC SHOCK HAZARD
IF THE GROUND FAULT IS INDICATED,
NORMALLY GROUNDED CONDUCTORS MAY
BE UNGROUNDED AND ENERGIZED.
PLAQUE TO BE INSTALLED ON FACE OF THE
UTILITY AC DISCONNECT:
PV SYSTEM DISCONNECT
FOR UTILITY OPERATION
TO BE INSTALLED ON THE FACE OF THE
SERVICE METER PANEL:
CAUTION
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECT LOCATED
AS SHOWN
LABEL FOR SOLAR DC DISCONNECT:
SOLAR DC DISCONNECT
PLAQUE TO BE INSTALLED AT ELECTRIC SERVICE:
PHOTOVOLTAIC SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
LABEL FOR SOLAR DC DISCONNECT:
OPERATING CURRENT
OPERATING VOLTAGE
MAXIMUM SYSTEM VOLTAGE
MAXIMUM SYSTEM CURRENT
MAXIMUM INVERTER OUTPUT
11.54 A
400.00 A
480.00 V
15.00 A
42 A
A
E
B
C
D
I
J
K
L
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E4
MODULE
DATA SHEET
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E5
OPTIMIZER
DATA SHEET
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
E6
INVERTER
DATA SHEET
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
S1
STANCHION
DATA SHEET
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
S2
RACKING
DATA SHEET
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
S3
RACKING
ENGINEERING
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
S3.1
RACKING
ENGINEERING
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
S3.2
RACKING
ENGINEERING
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
GROUNDING
DATA SHEET
S4
04/02/21
SHEET TITLE
SHEET NUMBER
REVISION
OWNER
PROJECT TITLE
JOBSITE ADDRESS
DOWNER
RESIDENCE
12925
HARRISON DR
CARMEL, IN
46033
13.135 DC kW
12.315 kW CEC-AC Rating
STRING INVERTER SYSTEM
DATE DESCRIPTION
DATE
DRAWN02-18-21 DESIGN
REVISION
DESIGN BY:
CONTRACTOR
SIGNATURE OF LICENSE HOLDER
LG/SC
SHELLEY V CALUAG
cadforcali@gmail.com
323-698-4207
CAD
FOR CALI I NC.
3911 N. COLLEGE AVE,
SUITE B.
INDIANAPOLIS,
IN 46205
PHONE: 855.573.2843
RACKING
CERTIFICATION
S5
04/02/21