HomeMy WebLinkAboutIN-156701-Permitting Plan Set-Rev01_02162021CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING 02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
COVER PAGE
156701 : 33.75 kWp
J.P. MORGAN CHASE
13085 Pettigru Drive
CARMEL, IN 46032-4436
ASSESSOR'S #: 29-09-29-020-001.002-018
AUTHORITIES HAVING JURISDICTION
BUILDING: CITY OF CARMEL
ZONING: CITY OF CARMEL
UTILITY: DUKE ENERGY/1326
DESIGN SPECIFICATIONS
OCCUPANCY: B
CONSTRUCTION: COMMERCIAL / INDUSTRIAL
GROUND SNOW LOAD: 20 PSF
WIND SPEED: 106 MPH
DESIGN SPECIFICATIONS
RISK CATEGORY: II
SITE CLASS: D (DEFAULT)
SEISMIC IMPORTANCE FACTOR: 1.0
SEISMIC DESIGN CATEGORY: B
SS: 0.168
S1: 0.082
SDS: 0.18
SD1: 0.131
ANALYSIS PROCEDURE: NONSTRUCTURAL COMPONENTS
DESIGN CODES & STANDARDS
BUILDING: 2018 INTERNATIONAL BUILDING CODE (SEE NOTE 1)
ELECTRICAL: 2008 NEC
FIRE: 2018 INTERNATIONAL FIRE CODE (SEE NOTE 2)
PROJECT INFORMATION
IN-156701-G10
KPI KPI AT
AT
NRS NRS
DRAWING INDEX
DRAWING NUMBER SHEET TITLE
G10 COVER PAGE
G20 SITE PLAN
E10 ELECTRICAL ROOF PLAN
E20 THREE LINE DIAGRAM & BILL OF MATERIALS
E21 ONE LINE DIAGRAM
E30 PLACARDS
REQUIRED STANDARD DRAWING INDEX
DRAWING NUMBER SHEET TITLE
SG10 COVER PAGE
SG20 GENERAL NOTES
SG21 GENERAL NOTES
SS10 FLAT ROOF CONNECTION DETAILS
SE10 ELECTRICAL DETAILS
SE11 ELECTRICAL DETAILS NEC 2008
SE20 METERING AND SURGE PROTECTION DETAILS 3-PHASE
SR10 THREE PHASE SYSTEM CUTSHEETS
SR25 ELECTRICAL DATA CUTSHEETS
SR26 ELECTRICAL DATA CUTSHEETS
SR30 STRUCTURAL COMPONENT CUTSHEETS
01 AERIAL PHOTO
NOT TO SCALE
02 VICINITY MAP
NOT TO SCALE
INDIANA
CLB
CAMERON L. BRYANT
10505919
CLB
25/JUN/20
NOTE 1 : INTERNATIONAL BUILDING CODE 2018 REFERENCES THE MOST CURRENT DESIGN
PRACTICES RELATED TO STRUCTURAL ANALYSIS AND DESIGN OF ROOFTOP SOLAR
MODULE SYSTEMS. ANALYSIS AND DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS WAS
PERFORMED IN ACCORDANCE WITH INTERNATIONAL BUILDING CODE 2018 AND MEETS
2014 INDIANA BUILDING CODE REQUIREMENTS.
NOTE 2 : INTERNATIONAL FIRE CODE 2018 REFERENCES THE MOST CURRENT DESIGN
PRACTICES RELATED TO DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS. ANALYSIS AND
DESIGN OF ROOFTOP SOLAR MODULE SYSTEMS WAS PERFORMED IN ACCORDANCE WITH
INTERNATIONAL FIRE CODE 2018 AND MEETS 2014 INDIANA FIRE CODE REQUIREMENTS.
KPI AT NRS CLB CLB
11-Feb-2021
04/20/21
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING
02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
IN-156701-G20
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
SITE PLAN
LEGEND:
FLAT ROOF CLEARANCE AREA
PITCHED ROOF CLEARANCE AREA
(E) EXISTING
(E) PROPERTY LINE
NOTES:
1. CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND ROOF SLOPES
AND COORDINATE WITH ALL REFERENCE DRAWINGS AS REQUIRED. IF THE
CONTRACTOR ENCOUNTERS CONDITIONS OTHER THAN WHAT IS SHOWN ON
THE DRAWINGS, CONTRACTOR SHALL NOTIFY THE ENGINEER
OF RECORD PRIOR TO START OF CONSTRUCTION.
2. SEE SHEET SG20 AND SG21 FOR GENERAL NOTES, LEGEND AND SYMBOLS.
4. OBSTRUCTIONS IN CLEARANCE AREA PATHWAYS SHALL BE KEPT TO A
MINIMUM.
5. SOLAR ASSEMBLY DOES NOT INCREASE EXISTING BUILDING HEIGHT FOR
PITCHED ROOFS. FOR FLAT ROOFS, SOLAR ASSEMBLY EXTENDS 11 3/8"
MAXIMUM ABOVE ROOF SURFACE WITH UNIRAC RMDT RACKING AND EXTENDS
1'-1 7/8" MAXIMUM ABOVE ROOF SURFACE WITH IRONRIDGE BX RACKING.
ROOF DESIGN CLEARANCE TABLE (SEE LEGEND FOR APPLICABLE HATCH)
ITEM MINIMUM CLEARANCE DIMENSIONS
FLAT ROOF 4'-0"
PITCHED ROOF:
ALONG RIDGE 6'-0" (3'-0" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG HIPS/VALLEY 3'-0" (18" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG EAVE/FREE EDGE 0'-10"
PITCHED ROOF:
OTHER CLEARANCE ON ROOF PLANE 3'-0"
ROOF CONNECTION DETAIL TABLE
DRAWING DETAIL ROOF SLOPE FRAMING TYPE ROOF TYPE CONNECTION LOCATION NOTES
SS10 1 FLAT ROOF DECK VARIES SEE SITE PLAN SEE RACKING SITE SPECIFIC DRAWING PACKAGE IF APPLICABLE.
SS10 2 FLAT ROOF DECK LOOSE GRAVEL
SS21 1 PITCHED WOOD MEMBERS ASPHALT SHINGLE SEE DRAWING SS20
SS21 2 PITCHED ROOF DECK SINGLE-PLY MEMBRANE SEE DRAWING SS20
SS21 3 PITCHED NA METAL STANDING SEAM SEE DRAWING SS20
SS21 4 PITCHED WOOD MEMBERS CORRUGATED METAL SEE DRAWING SS20
SS21 5 PITCHED STEEL MEMBERS ASPHALT SHINGLE SEE DRAWING SS20
SS22 1 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 2 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 3 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 4 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
SS22 5 PITCHED WOOD MEMBERS TILE SEE DRAWING SS20
NOTES:
1. ROOFS WITH SLOPE LESS THAN 7 DEGREES ARE CONSIDERED "FLAT". ROOFS WITH SLOPE GREATER THAN 7 DEGREES ARE CONSIDERED "PITCHED". REFER
TO SITE SPECIFIC DWG E10 FOR ROOF SLOPE.
2. FRAMING TYPE AND ROOF TYPE SHALL BE VERIFIED ON SITE PRIOR TO INSTALLATION.
3. EVEREST RACKING RAIL MAXIMUM ALLOWABLE SPAN
SHALL BE 4'-0" UNLESS NOTED OTHERWISE.
01 SITE PLAN
NOT TO SCALE
PARCEL DATA FROM LANDGRID.COM
KPI KPI AT
AT
NRS NRS
INDIANA
CLB
CAMERON L. BRYANT
10505919
CLB
25/JUN/20
ROOF MEMBRANE: BLACK RUBBER (EPDM)
ROOF DECK: METAL DECK
CONNECTION DETAIL: NONE. SEE DWG SS10 FOR BALLAST CRITERIA.
RACKING TYPE: UNIRAC RMDT
17'-8"
KPI ATNRS CLB CLB
THE PROVISIONS OF THE INTERNATIONAL FIRE CODE 2018, SEC. 1204.2.1
PERTAINING TO GROUP R-3 BUILDINGS (ONE OR TWO FAMILY DWELLINGS)
SPECIFIES SETBACKS AND PATHWAYS FOR PITCHED ROOFS. EXCEPTION TO
SEC. 1204.3 STATES THAT IF THE FIRE CODE OFFICIAL DETERMINES THAT THE
ROOF CONFIGURATION FOR A BUILDING OTHER THAN GROUP R-3 IS SIMILAR
TO THAT OF A GROUP R-3 OCCUPANCY, THE RESIDENTIAL ACCESS
REQUIREMENTS IN SEC. 1204.2.1 ARE A SUITABLE ALTERNATIVE. THEREFORE,
CONSIDERING FIREFIGHTING OPERATIONS, BUILDINGS WITH A PITCHED ROOF
HAVE BEEN CONSIDERED SIMILAR TO THAT OF A GROUP R-3 BUILDING AND
THE PROVISIONS OF SEC. 1204.2.1 WERE USED.
11-Feb-2021
04/20/21
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING 02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
IN-156701-E10
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
ELECTRICAL ROOF PLAN
LEGEND:
FLAT ROOF CLEARANCE AREA
PITCHED ROOF CLEARANCE AREA
(E) EXISTING
NOTES:
1. CONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS AND ROOF SLOPES
AND COORDINATE WITH ALL REFERENCE DRAWINGS AS REQUIRED. IF THE
CONTRACTOR ENCOUNTERS CONDITIONS OTHER THAN WHAT IS SHOWN ON
THE DRAWINGS, CONTRACTOR SHALL NOTIFY THE ENGINEER
OF RECORD PRIOR TO START OF CONSTRUCTION.
2. SEE SHEET SG20 AND SG21 FOR GENERAL NOTES, LEGEND AND SYMBOLS.
3. SEE SHEETS SE10 AND SE11 FOR ELECTRICAL DETAILS.
4. FOR THREE PHASE SYSTEMS, MODULES OF SIMILAR
ORIENTATION SHALL BE PAIRED WITH ONE OPTIMIZER
WHERE POSSIBLE.
5. OBSTRUCTIONS IN CLEARANCE AREA PATHWAYS SHALL BE KEPT TO A
MINIMUM. WHERE CONDUIT INTERSECTS CLEARANCE AREA PATHWAYS,
CONDUIT SHALL BE PLACED TRANSVERSE TO CLEARANCE AREA PATHWAYS.
6. SUBCONTRACTOR SHALL MAINTAIN MINIMUM 3' RADIAL CLEARANCE FROM
GAS RISER METER.
ROOF DESIGN CLEARANCE TABLE (SEE LEGEND FOR APPLICABLE HATCH)
ITEM MINIMUM CLEARANCE DIMENSIONS
FLAT ROOF 4'-0"
PITCHED ROOF:
ALONG RIDGE 6'-0" (3'-0" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG HIPS/VALLEY 3'-0" (18" MINIMUM EACH SIDE)
PITCHED ROOF:
ALONG EAVE/FREE EDGE 0'-10"
PITCHED ROOF:
OTHER CLEARANCE ON ROOF PLANE 3'-0"
01 ELECTRICAL ROOF PLAN
NOT TO SCALE
NRS NRS APN
APN
NRS NRS JDL
JASON D. LEIMBACK
11100106
INDIANA
JDL
25/JUN/20
INV1
PNL2
SW2
T
UDSM
(N) INVERTER
(N) METERING AND SURGE PROTECTION CABINET
(N) INVERTER FUSED DISCONNECT SWITCH
(N) TRANSFORMER
(N) GENERATOR DISCONNECT SWITCH
(E) UTILITY METER
1-1
1-1
1-2
1-2
1-3
1-3
ELECTRICAL ROOM WITH ELECTRICAL SERVICE PANEL
ARRAY 2 - 32.25 kW
[x43] (N) MODULES EAST
AZIMUTH: 90 DEGREES
[x43] (N) MODULES WEST
AZIMUTH: 270 DEGREES
ROOF PITCH: 0:12
ARRAY 1 - 1.50 kW
[x2] (N) MODULES EAST
AZIMUTH: 90 DEGREES
[x2] (N) MODULES WEST
AZIMUTH: 270 DEGREES
ROOF PITCH: 0:12
NRS APN NRS JDL JDL
(E) GAS RISER METER
NOTE 6
G
(N) METERING AND SURGE PROTECTION CABINET
(N) TRANSFORMER
(N) INVERTER FUSED DISCONNECT SWITCH
(N) INVERTER
02 ELEVATION 1
NOT TO SCALE
(N) GENERATOR DISCONNECT SWITCH
03 ELEVATION 2
NOT TO SCALE
11-FEB-2021
04/20/21
L1L2L3G
G
N
02
(N) MODULESPM
IN
STRING
IN
STRING
IN
STRING
OPT
(N) DC OPTIMIZERS
INV1
(N) INVERTER
(N) AC SURGE PROTECTOR
NOTE 2SP1
01 01 01
G
(N) ( KVA) 480/277V - 208V
TRANSFORMER
TR1
45
NAWG GEC TIED TO BLDG/SITE
GROUNDING ELECTRODE SYSTEM
6
04
30 30 30
G
(N) GENERATOR DISCONNECT
SWITCH
NOTE 5 & 7 SW1
F1
RGM
(N) OWNER REVENUE GRADE METER
NOTES 2, 4 & 6
(10 FEET OR LESS)
OUTSIDE
INSIDE
05
G
SW2
F2
03
N
(N) INVERTER FUSED
DISCONNECT SWITCH
G
N
(E) LOADS
(E) ELECTRICAL SERVICE PANEL
208/120V, 3 PHASE, 4 WIRE
MAIN BUS: 225A
MAIN BREAKER: 225A
(E) GROUNDING
ELECTRODE
L1
L2L3
L2
TO UTILITY
GRID
(E)
BI-DIRECTIONAL
UTILITY METER
(E) MAIN
AWG GEC TIED TO BLDG/SITE
GROUNDING ELECTRODE SYSTEM
6 S/NLEGEND
(N) -NEW EQUIPMENT
(E) -EXISTING EQUIPMENT
NOTES:
1. THIS CABLE SIZE AND INSTALLATION ALSO APPLIES TO THE
CABLE INTERCONNECTING MODULES IN THE SAME STRING
WHERE IT IS NOT PROTECTED UNDERNEATH THE PV ARRAY.
THE CONDUIT SIZE IS CALCULATED BASED ON THE MAXIMUM
SET OF STRINGS ROUTED TO A SINGLE INVERTER.
2. AC SURGE PROTECTOR (SP1) AND OWNER REVENUE GRADE
METER (RGM) SHOWN ON THE THREE LINE DIAGRAM ARE
INSTALLED IN PNL2. REFER TO SE20 FOR TYPICAL WIRING
DIAGRAM DETAILS.
3. SUBCONTRACTOR SHALL REPLACE EXISTING LOAD SIDE
METER LUGS WITH A DUAL LUGGED CONNECTOR TO ACCEPT
WIRING. IF CORRECT CONNECTORS ARE NOT AVAILABLE,
SUBCONTRACTOR SHALL REPLACE METER SOCKET OR
PURCHASE AND INSTALL LOCKABLE NEMA 3R WIREWAY
BELOW METER BASE AND INTERCONNECT USING POLARIS
CONNECTORS OR ENGINEER APPROVED EQUIVALENT.
PLEASE REFER TO DUKE ENERGY GOLD BOOK FIG 142A.
4. REFER TO ELECTRICAL DETAILS DRAWING SE10 FOR THE
COMMUNICATION DETAIL.
5. NEW PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
TO BE LOCATED CLOSE TO EXISTING METER PER UTILITY
REQUIREMENTS.
6. SUBCONTRACTOR SHALL USE LOCK PROVIDED BY
DISTRIBUTOR TO LOCK THE METERING AND SURGE
PROTECTION CABINET, INVERTER DISCONNECT SWITCH AND
GENERATOR DISCONNECT SWITCH.
NOTE 3
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING 02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
IN-156701-E20
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
THREE LINE DIAGRAM AND BILL OF MATERIALS
MODULE
MAKE
MISSION
SOLAR
MODEL MSE375SQ9S
POWER OUTPUT 375 W
SHORT CIRCUIT Isc 9.83 A
OPEN CIRCUIT VOLTAGE Voc 48.16 V
RATED CURRENT Imp 9.43 A
RATED VOLTAGE Vmp 39.76 V
TEMPERATURE COEFFICIENT OF Voc -0.28%/C
TEMPERATURE COEFFICIENT OF Isc 0.046%/C
OPTIMIZER
MAKE SOLAR EDGE
MODEL P850
RATED INPUT DC POWER 850 W
MAXIMUM SYSTEM VOLTAGE 1000 V
MAXIMUM OUTPUT CURRENT 18.0 A
MAXIMUM OUTPUT VOLTAGE 85 V
MAXIMUM INPUT VOLTAGE 120 V
MAXIMUM SHORT CIRCUIT CURRENT 12.5 A
MINIMUM MODULES IN SERIES 27
MAXIMUM MODULES IN SERIES 40
CONDITIONS OF USE CONDUCTOR EGC CONDUIT CIRCUIT INFORMATION
CIRCUIT
ID DESCRIPTION
NUMBER OF TYPICAL
CIRCUITS
INSULATION
TEMP. RATING
RACEWAY
LOCATION
MODIFIED
AMBIENT
TEMPERATURE
# CURRENT
CARRYING
CONDUCTORS
CONDUIT FILL
DERATE
FACTOR
TEMPERATURE
DERATE
FACTOR MINIMUM SPECIFICATION MINIMUM SPECIFICATION MIN SIZE
# OF
CONDUCTORS # OF EGC
CONDUIT FILL
%
CONDUCTOR
AMPACITY
CONDUCTOR
DERATED
AMPACITY
CONT.
CURRENT
MAXIMUM
CURRENT OCPD
ESTIMATED
CIRCUIT LENGTH
% VOLTAGE
DROP
% AVERAGE
LOSSES
01 STRING TO INVERTER (NOTE 1) 3 90 °C > 3.5" & < 12" 49 °C 2 0.8 0.82 8 AWG, COPPER, PV WIRE 10 AWG, COPPER, RHW-2 1.25", EMT 6 1 33% 55 A 36 A 18.0A 22.5A 25 278 FT 0.69% 0.69%
02 33.3KW INVERTER TO INVERTER DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 8 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75", EMT 4 1 31% 55 A 53 A 40.0A 50.0A 50 10 FT 0.11% 0.11%
03 INVERTER DS TO TRANSFORMER 1 90 °C UNDER ROOF 32 °C 3 1 0.96 8 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 0.75", EMT 4 1 34% 55 A 53 A 40.0A 50.0A 50 10 FT 0.11% 0.11%
04 TRANSFORMER TO UTILITY DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1 AWG, COPPER, THWN-2 6 AWG, COPPER, THWN-2 1.5", EMT 3 1 26% 145 A 139 A 92.3A 115.4A 125 20 FT 0.25% 0.25%
05 UTILITY DS TO POI 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1 AWG, COPPER, THWN-2 NA 1.5", RMC 4 0 30% 145 A 139 A 92.3A 115.4A 125 10 FT 0.12% 0.12%
TOTAL 1.36% 1.36%
SYSTEM INFORMATION DC WIRING LOSSES AT STC
STRING
INPUTS
MODULES IN
SERIES
DC POWER
(STC)
TOTAL DC
POWER (STC)
INVERTER
AC POWER ILR
INVERTER
OUTPUT
CURRENT
ESTIMATED
CIRCUIT
LENGTH
% VOLTAGE
DROP % STC LOSS
INVERTER-1 STRING 1-1 30 11,250 W 33,750 W 33,300 W 1.01 40.0A 265 0.66% 0.66%
STRING 1-2 30 11,250 W 230 0.57% 0.57%
STRING 1-3 30 11,250 W 340 0.84% 0.84%
WEIGHTED AVERAGE 0.69% 0.69%
DESIGN PARAMETERS
ASHRAE EXTREME LOW -23.8 °C
ASHRAE 2% HIGH 32.4 °C
SERVICE VOLTAGE 208V, 3Ф
UTILITY DUKE ENERGY
ELECTRICAL CODE NEC 2008
DISTRIBUTOR BILL OF MATERIAL
REF CATEGORY MAKE MODEL QTY UNIT DESCRIPTION
PM MODULE
MISSION
SOLAR MSE375SQ9S 90 EA 375WP, 72 CELL SOLAR MODULE (PROVIDED BY JPMC)
OPT DC OPTIMIZER SOLAREDGE P850 45 EA SOLAREDGE POWER OPTIMIZER
INV1 33.3KW INVERTER SOLAREDGE SE33.3KUS 1 EA
UTILITY INTERACTIVE DC-TO-AC INVERTER: 3-PHASE, 4-WIRE,
480/277VAC, NEMA 3R, NEC 2014 and 2017 RAPID
SHUTDOWN COMPLIANT
CELL1 CELLULAR CDMA KIT SOLAREDGE SE-CELL-B-R05-S-S4 1 EA CDMA MODEM W/SIM, INV≤33.3KVA, 5YRS, HB 15MIN
PNL2
METERING AND SURGE
PROTECTION CABINET VARIES DETAIL 01 1 EA REFER TO DRAWING SE20 FOR CABINET DESIGN AND BOM
TR1 TRANSFORMER HPS 226427 1 EA
TRANSFORMER 45kVA, 480/277 WYE-GND/208VAC DELTA,
NEMA 3R
SW1 UTILITY DISCONNECT EATON DG324NRK 1 EA
240VAC, 200A, 3 POLE GENERAL-DUTY,FUSIBLE,
SINGLE-THROW DISCONNECT SWITCH, NEMA 3R
F1 UTILITY DISCONNECT FUSE BUSSMANN FRN-R-125 3 EA FUSE, 125A, 250VAC, SCCR 200 kA
SW2 INVERTER DISCONNECT EATON DH362NRK 1 EA
600VAC 60A, 3 POLE, HEAVY-DUTY, FUSIBLE, SINGLE-THROW
DISCONNECT SWITCH, NEMA 3R
F2 INVERTER DISCONNECT FUSE BUSSMANN FRS-R-50 3 EA FUSE, 50A, 600VAC, SCCR 200 kA
INVERTER
MAKE SOLAREDGE
MODEL SE33.3KUS
MAXIMUM AC POWER OUTPUT 33,300 W
AC RATED VOLTAGE 480Y/277 V
MAX CONTINUOUS OUTPUT CURRENT 40.0 A
RATED INPUT VOLTAGE 840 V
MAXIMUM INPUT CURRENT 40.0 A
MAXIMUM SHORT CIRCUIT CURRENT 45.0 A
MAXIMUM INPUT VOLTAGE 980 V
TRANSFORMER-LESS, UNGROUNDED YES
SYSTEM SUMMARY
TOTAL DC POWER 33,750 W
TOTAL AC POWER 33,300 W
WEIGHTED ILR 1.01
INVERTER OUTPUT RATED VOLTAGE 480 V
MAX AC CURRENT (480 V) 40.0A
TRANSFORMATION VOLTAGE 208 V
MAX AC CURRENT (208 V) 92.3A
NRS NRS APN
APN
NRS NRS
01 THREE LINE DIAGRAM
NOT TO SCALE
JDL
JASON D. LEIMBACK
11100106
INDIANA
JDL 25/JUN/20
NRS APN NRS JDL JDL
11-FEB-2021
04/20/21
(N) ( KVA)
480/277V - 208V
TRANSFORMER TR1
45
INV1
(N) INVERTER
04
(N) AC SURGE PROTECTORSP1
LEGEND
(N) - NEW EQUIPMENT
(E) - EXISTING EQUIPMENT
02
01
PHOTOVOLTAIC
STRINGS
PM
OPT
20 12 9
# REFER TO E30 FOR PLACARD LABELING
7
(N) GENERATOR DISCONNECT
SWITCH
SW1
F1
RGM
(N) OWNER REVENUE
GRADE METER
05
7
8 6 117 11
5
(N) INVERTER FUSED
DISCONNECT SWITCH
SW2
F2
03
21 6 2
(E) MAIN
TO UTILITY
GRID
(E)
BI-DIRECTIONAL
UTILITY METER
15 4 3
13
(E) LOADS
(10 FEET OR LESS)
(E) ELECTRICAL SERVICE PANEL
208/120V, 3 PHASE, 4 WIRE
MAIN BUS: 225A
MAIN BREAKER: 225A
NOTES:
1. THIS CABLE SIZE AND INSTALLATION ALSO APPLIES TO THE
CABLE INTERCONNECTING MODULES IN THE SAME STRING
WHERE IT IS NOT PROTECTED UNDERNEATH THE PV ARRAY.
THE CONDUIT SIZE IS CALCULATED BASED ON THE MAXIMUM
SET OF STRINGS ROUTED TO A SINGLE INVERTER.
2. AC SURGE PROTECTOR (SP1) AND OWNER REVENUE GRADE
METER (RGM) SHOWN ON THE THREE LINE DIAGRAM ARE
INSTALLED IN PNL2. REFER TO SE20 FOR TYPICAL WIRING
DIAGRAM DETAILS.
3. SUBCONTRACTOR SHALL REPLACE EXISTING LOAD SIDE
METER LUGS WITH A DUAL LUGGED CONNECTOR TO ACCEPT
WIRING. IF CORRECT CONNECTORS ARE NOT AVAILABLE,
SUBCONTRACTOR SHALL REPLACE METER SOCKET OR
PURCHASE AND INSTALL LOCKABLE NEMA 3R WIREWAY
BELOW METER BASE AND INTERCONNECT USING POLARIS
CONNECTORS OR ENGINEER APPROVED EQUIVALENT.
PLEASE REFER TO DUKE ENERGY GOLD BOOK FIG 142A.
4. REFER TO ELECTRICAL DETAILS DRAWING SE10 FOR THE
COMMUNICATION DETAIL.
5. NEW PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH
TO BE LOCATED CLOSE TO EXISTING METER PER UTILITY
REQUIREMENTS.
6. SUBCONTRACTOR SHALL USE LOCK PROVIDED BY
DISTRIBUTOR TO LOCK THE METERING AND SURGE
PROTECTION CABINET, INVERTER DISCONNECT SWITCH AND
GENERATOR DISCONNECT SWITCH.
NOTE 3
23
23
22
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING 02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
IN-156701-E21
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
ONE LINE DIAGRAMNRS NRS APN
APN
NRS NRS
MODULE
MAKE
MISSION
SOLAR
MODEL MSE375SQ9S
POWER OUTPUT 375 W
SHORT CIRCUIT Isc 9.83 A
OPEN CIRCUIT VOLTAGE Voc 48.16 V
RATED CURRENT Imp 9.43 A
RATED VOLTAGE Vmp 39.76 V
TEMPERATURE COEFFICIENT OF Voc -0.28%/C
TEMPERATURE COEFFICIENT OF Isc 0.046%/C
OPTIMIZER
MAKE SOLAR EDGE
MODEL P850
RATED INPUT DC POWER 850 W
MAXIMUM SYSTEM VOLTAGE 1000 V
MAXIMUM OUTPUT CURRENT 18.0 A
MAXIMUM OUTPUT VOLTAGE 85 V
MAXIMUM INPUT VOLTAGE 120 V
MAXIMUM SHORT CIRCUIT CURRENT 12.5 A
MINIMUM MODULES IN SERIES 27
MAXIMUM MODULES IN SERIES 40
SYSTEM INFORMATION DC WIRING LOSSES AT STC
STRING
INPUTS
MODULES IN
SERIES
DC POWER
(STC)
TOTAL DC
POWER (STC)
INVERTER
AC POWER ILR
INVERTER
OUTPUT
CURRENT
ESTIMATED
CIRCUIT
LENGTH
% VOLTAGE
DROP % STC LOSS
INVERTER-1 STRING 1-1 30 11,250 W 33,750 W 33,300 W 1.01 40.0A 265 0.66% 0.66%
STRING 1-2 30 11,250 W 230 0.57% 0.57%
STRING 1-3 30 11,250 W 340 0.84% 0.84%
WEIGHTED AVERAGE 0.69% 0.69%
DESIGN PARAMETERS
ASHRAE EXTREME LOW -23.8 °C
ASHRAE 2% HIGH 32.4 °C
SERVICE VOLTAGE 208V, 3Ф
UTILITY DUKE ENERGY
ELECTRICAL CODE NEC 2008
DISTRIBUTOR BILL OF MATERIAL
REF CATEGORY MAKE MODEL QTY UNIT DESCRIPTION
PM MODULE
MISSION
SOLAR MSE375SQ9S 90 EA 375WP, 72 CELL SOLAR MODULE (PROVIDED BY JPMC)
OPT DC OPTIMIZER SOLAREDGE P850 45 EA SOLAREDGE POWER OPTIMIZER
INV1 33.3KW INVERTER SOLAREDGE SE33.3KUS 1 EA
UTILITY INTERACTIVE DC-TO-AC INVERTER: 3-PHASE, 4-WIRE,
480/277VAC, NEMA 3R, NEC 2014 and 2017 RAPID
SHUTDOWN COMPLIANT
CELL1 CELLULAR CDMA KIT SOLAREDGE SE-CELL-B-R05-S-S4 1 EA CDMA MODEM W/SIM, INV≤33.3KVA, 5YRS, HB 15MIN
PNL2
METERING AND SURGE
PROTECTION CABINET VARIES DETAIL 01 1 EA REFER TO DRAWING SE20 FOR CABINET DESIGN AND BOM
TR1 TRANSFORMER HPS 226427 1 EA
TRANSFORMER 45kVA, 480/277 WYE-GND/208VAC DELTA,
NEMA 3R
SW1 UTILITY DISCONNECT EATON DG324NRK 1 EA
240VAC, 200A, 3 POLE GENERAL-DUTY,FUSIBLE,
SINGLE-THROW DISCONNECT SWITCH, NEMA 3R
F1 UTILITY DISCONNECT FUSE BUSSMANN FRN-R-125 3 EA FUSE, 125A, 250VAC, SCCR 200 kA
SW2 INVERTER DISCONNECT EATON DH362NRK 1 EA
600VAC 60A, 3 POLE, HEAVY-DUTY, FUSIBLE, SINGLE-THROW
DISCONNECT SWITCH, NEMA 3R
F2 INVERTER DISCONNECT FUSE BUSSMANN FRS-R-50 3 EA FUSE, 50A, 600VAC, SCCR 200 kA
INVERTER
MAKE SOLAREDGE
MODEL SE33.3KUS
MAXIMUM AC POWER OUTPUT 33,300 W
AC RATED VOLTAGE 480Y/277 V
MAX CONTINUOUS OUTPUT CURRENT 40.0 A
RATED INPUT VOLTAGE 840 V
MAXIMUM INPUT CURRENT 40.0 A
MAXIMUM SHORT CIRCUIT CURRENT 45.0 A
MAXIMUM INPUT VOLTAGE 980 V
TRANSFORMER-LESS, UNGROUNDED YES
SYSTEM SUMMARY
TOTAL DC POWER 33,750 W
TOTAL AC POWER 33,300 W
WEIGHTED ILR 1.01
INVERTER OUTPUT RATED VOLTAGE 480 V
MAX AC CURRENT (480 V) 40.0A
TRANSFORMATION VOLTAGE 208 V
MAX AC CURRENT (208 V) 92.3A
01 ONE LINE DIAGRAM
NOT TO SCALE
JDL
JASON D. LEIMBACK
11100106
INDIANA
JDL 25/JUN/20
NRS APN NRS JDL JDL
CONDITIONS OF USE CONDUCTOR EGC CONDUIT CIRCUIT INFORMATION
CIRCUIT
ID DESCRIPTION
NUMBER OF TYPICAL
CIRCUITS
INSULATION
TEMP. RATING
RACEWAY
LOCATION
MODIFIED
AMBIENT
TEMPERATURE
# CURRENT
CARRYING
CONDUCTORS
CONDUIT FILL
DERATE
FACTOR
TEMPERATURE
DERATE
FACTOR MINIMUM SPECIFICATION MINIMUM SPECIFICATION MIN SIZE
# OF
CONDUCTORS # OF EGC
CONDUIT FILL
%
CONDUCTOR
AMPACITY
CONDUCTOR
DERATED
AMPACITY
CONT.
CURRENT
MAXIMUM
CURRENT OCPD
ESTIMATED
CIRCUIT LENGTH
% VOLTAGE
DROP
% AVERAGE
LOSSES
01 STRING TO INVERTER (NOTE 1) 3 90 °C > 3.5" & < 12" 49 °C 2 0.8 0.82 8 AWG, COPPER, PV WIRE 10 AWG, COPPER, RHW-2 1.25", EMT 6 1 33% 55 A 36 A 18.0A 22.5A 25 278 FT 0.69% 0.69%
02 33.3KW INVERTER TO INVERTER DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 8 AWG, COPPER, THWN-2 10 AWG, COPPER, THWN-2 0.75", EMT 4 1 31% 55 A 53 A 40.0A 50.0A 50 10 FT 0.11% 0.11%
03 INVERTER DS TO TRANSFORMER 1 90 °C UNDER ROOF 32 °C 3 1 0.96 8 AWG, COPPER, THWN-2 8 AWG, COPPER, THWN-2 0.75", EMT 4 1 34% 55 A 53 A 40.0A 50.0A 50 10 FT 0.11% 0.11%
04 TRANSFORMER TO UTILITY DS 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1 AWG, COPPER, THWN-2 6 AWG, COPPER, THWN-2 1.5", EMT 3 1 26% 145 A 139 A 92.3A 115.4A 125 20 FT 0.25% 0.25%
05 UTILITY DS TO POI 1 90 °C UNDER ROOF 32 °C 3 1 0.96 1 AWG, COPPER, THWN-2 NA 1.5", RMC 4 0 30% 145 A 139 A 92.3A 115.4A 125 10 FT 0.12% 0.12%
TOTAL 1.36% 1.36%
11-FEB-2021
04/20/21
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x220 25/JUN/20 ISSUED FOR PERMITTING
1 11/FEB/21 ISSUED FOR PERMITTING 02/14/2017 04:16 PM
25/JUN/20
DESIGNER
1R
J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
PLACARDS
SERVICE DISCONNECTING
MEANS
PV ARRAY
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
IN-156701-E30
GENERATOR DISCONNECT
SWITCH
OPERATING DC CURRENT: 54 A
OPERATING DC VOLTAGE: 840 V
MAX SHORT CURRENT: 45 A
MAX VOLTAGE: 980 V
AT EACH 33.3 KW INVERTER DC DISCONNECTING MEANS
[NEC 690.53]
20
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE
GENERATOR DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10
SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS [NEC 690.4(D)]
PHOTOVOLTAIC
AC DISCONNECT
AT POINT OF INTERCONNECTION, MARKED AT
DISCONNECTING MEANS
[NEC 690.54]
OPERATING AC CURRENT: 92.3A
OPERATING AC VOLTAGE: 208V, 3Ф
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
AT EACH JUNCTION, COMBINER, DISCONNECT AND
DEVICE WHERE ENERGIZED UNGROUNDED
CONDUCTORS MAY BE EXPOSED DURING SERVICE
[NEC 690.35(F)]
! WARNING !
ELECTRIC SHOCK HAZARD.
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE UNGROUNDED
AND MAY BE ENERGIZED.
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
PHOTOVOLTAIC
DC DISCONNECT
GENERATOR
DISCONNECT SWITCH
WARNING: PHOTOVOLTAIC
POWER SOURCE
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
INVERTER OUTPUT CONNECTION.
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM METER INTERACTIVE
PHOTOVOLTAIC SYSTEM CONNECTED
AT UTILITY METER
[NEC 690.56(B)]
PLAQUE
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO SUNLIGHT
! WARNING !
TURN OFF PHOTOVOLTAIC AC DISCONNECT
PRIOR TO WORKING INSIDE PANEL
AT EACH BREAKER PANEL AND MAIN SERVICE
DISCONNECT.
[NEC 110.27(C)]
! WARNING !
PHOTOVOLTAIC SYSTEM DATA
ACQUISITION SYSTEM
AUTHORIZED PERSONNEL ONLY
THE PV DAS SHALL BE LABELED WITH THE FOLLOWING
INFORMATION
AT EACH AC DEDICATED PHOTOVOLTAIC SYSTEM
COMBINER PANEL AND DISCONNECT.
[NEC 110.16]
! WARNING !
ARC FLASH HAZARD.
APPROPRIATE PPE REQUIRED.
FAILURE TO COMPLY MAY RESULT IN
INJURY OR DEATH.
REFER TO NFPA 70 E.
AT EACH PHOTOVOLTAIC SYSTEM
SERVICE DISCONNECT SWITCH.
! DANGER !
ARC FLASH AND SHOCK HAZARD PRESENT
DO NOT OPEN DOOR WHILE ENERGIZED
INCIDENT ENERGY EXCEEDS MAX PPE PROTECTION
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
PHOTOVOLTAIC
SYSTEM SERVICE
DISCONNECT SWITCH
DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL DO NOT
ADD LOADS TO THIS PANEL
AT DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL (IF
APPLICABLE)
AT THE SERVICE ENTRANCE (ELECTRICAL SERVICE PANEL) AND
GENERATOR DISCONNECT SWITCH
NET GENERATION
OUTPUT METER
AT NET GENERATION OUTPUT
METER
AT THE ELECTRICAL SERVICE PANEL
! WARNING !
A GENERATION SOURCE IS CONNECTED TO THE SUPPLY (UTILITY) SIDE OF THE
SERVICE DISCONNECTING MEANS. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES
TO ENSURE THE PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH IS OPENED
PRIOR TO PERFORMING WORK ON THE DEVICE.
1 2 3
5
1716 15 14
13 12 9 10 11
6 7 8
419 18
AT EACH AC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT EACH DC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT PHOTOVOLTAIC SYSTEM SERVICE
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT GENERATOR
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT EACH DC DISCONNECTING MEANS
[NEC 690.14(C)(2)]
AT EACH DISTRIBUTION EQUIPMENT ADJACENT TO
THE BACK-FED BREAKER FROM THE INVERTER.
[NEC 705.12(D)(7)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT PHOTOVOLTAIC SYSTEM SERVICE DISCONNECT
SWITCH
[NEC 2014 - 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE [IFC 605.11.1.1].
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS;
SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY
ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(E)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2008 NATIONAL ELECTRICAL CODE.
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT FOR WHICH THEY ARE INSTALLED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
NRS NRS APN
APN
NRS NRS JDL
JASON D. LEIMBACK
11100106
INDIANA
PHOTOVOLTAIC
SYSTEM INVERTER
DISCONNECT SWITCH
21
AT INVERTER DISCONNECT
JDL
25/JUN/20
NRS APN NRS JDL JDL
23
22
11-FEB-2021
04/20/21
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22R
J.P. MORGAN CHASE
TRANCHE 6 - INDIANA
COVER PAGE
J.P. MORGAN CHASE
ROOFTOP SOLAR
PROGRAM
TRANCHE 6 - INDIANA
IN-STNDRD-SG10
STANDARD DRAWING PACKAGE
0 04/JUN/20 ISSUED FOR PERMITTING AWC AWC 02/14/2017 04:16 PM
DESIGNER
AWCAWC
1
JDL JDL
04/JUN/20 JDL
JJA
1 04/FEB/21 APPROVED FOR CONSTRUCTION AWC AWC JDL JDLJJA
4-FEB-2021
04/20/21
4-FEB-2021
04/20/21
4-FEB-2021
04/20/21
04-Feb-2021
04/20/21
4-FEB-2021
04/20/21
4-FEB-2021
04/20/21
4-FEB-2021
04/20/21
J.P. MORGAN CHASE
TRANCHE 6 - INDIANA
THREE PHASE SYSTEM CUTSHEETS
IN-STNDRD-SR10
0 04/JUN/20 ISSUED FOR PERMITTING AWC AWC JDL JDL
02/14/2017 04:16 PM
DESIGNER
AWCJJA
1
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22R
JJA
04/JUN/20 JJA
1 04/FEB/21 APPROVED FOR CONSTRUCTION AWC AWC JDL JDLJJA
4-FEB-2021
04/20/21
J.P. MORGAN CHASE
TRANCHE 6 - INDIANA
ELECTRICAL DATA CUTSHEETS
IN-STNDRD-SR25
004/JUN/20 ISSUED FOR PERMITTING AWC AWC JDL JDL
02/14/2017 04:16 PM
DESIGNER
AWCJJA
1
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22R
JJA
04/JUN/20 JJA
1 04/FEB/21 APPROVED FOR CONSTRUCTION AWC AWC JDL JDLJJA
4-FEB-2021
04/20/21
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22R
J.P. MORGAN CHASE
TRANCHE 6 - INDIANA
ELECTRICAL DATA CUTSHEETS
IN-STNDRD-SR26
004/JUN/20 ISSUED FOR PERMITTING AWC AWC JDL JDL
02/14/2017 04:16 PM
DESIGNER
AWCJJA
1
JJA
04/JUN/20 JJA
1 04/FEB/21 APPROVED FOR CONSTRUCTION AWC AWC JDL JDLJJA
4-FEB-2021
04/20/21
J.P. MORGAN CHASE
TRANCHE 6 - INDIANA
STRUCTURAL COMPONENT CUTSHEETS
IN-STNDRD-SR30
CHECKED DATE
DRAWN CODE
APPPDE CHK DES NO DATE REVISIONS AND RECORD OF ISSUE
DRAWING NUMBERPROJECT REV
AREADRN ANSI D 34x22R
0 04/JUN/20 ISSUED FOR PERMITTING AWC CLB CLB CLB
02/14/2017 04:16 PM
DESIGNER
AWCCLB
2
SAS
04/JUN/20 SAS
1 12/JAN/21 ISSUED FOR PERMITTING AWC CLB CLB CLBSAS
2 04/FEB/21 APPROVED FOR CONSTRUCTION AWC CLB CLB CLBSAS
04-Feb-2021
04/20/21
COVER
SHEET
RMDT.100
GENERAL NOTES:
1. ALL CONSTRUCTION FOR UNIRAC'S 'ROOF MOUNT' (RM) RACKING SYSTEM SHALL CONFORM TO THE
CODES SHOWN IN THE RM DESIGN CRITERIA TABLE BELOW. LOCAL JURISDICTION AMENDMENTS TO
THE CODE MUST BE TAKEN INTO CONSIDERATION.
2. WHENEVER THE TERM "CONTRACTOR" IS USED IN THE CONSTRUCTION DOCUMENT, IT SHALL BE
DEFINED TO MEAN THE GENERAL CONTRACTOR AND ANY SUB-CONTRACTOR COLLECTIVELY AS
APPLICABLE AND AS REQUIRED.
3. THE CONTRACT "STRUCTURAL RACKING" DRAWINGS REPRESENT THE FINISHED STRUCTURE.
UNIRAC AND THE ENGINEER OF RECORD WILL NOT BE RESPONSIBLE FOR THE CONTRACTOR'S
MEANS, METHODS, TECHNIQUES, SEQUENCES OR PROCEDURES OF CONSTRUCTION.
4. UNIRAC AND THE ENGINEER OF RECORD WILL NOT BE RESPONSIBLE FOR CONSTRUCTION SITE
SAFETY OR SAFETY PRECAUTIONS AND PROGRAMS INCIDENT HERETO.
5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ENSURE THAT ALL WORK IS IN
CONFORMANCE WITH THE CONTRACT DOCUMENTS. ANY STRUCTURAL INSPECTION/OBSERVATION
PROVIDED BY OTHERS (INCLUDING UNIRAC AND THE ENGINEER OF RECORD) DOES NOT RELIEVE
THE CONTRACTOR OF THE RESPONSIBILITY. ANY DEVIATION FROM THE CONTRACT DOCUMENTS
THAT IS ENCOUNTERED AT A LATER DATE AND IS DECLARED TO BE SIGNIFICANT BY UNIRAC AND
THE ENGINEER OF RECORD SHALL BE CORRECTED BY THE CONTRACTOR (AT THE CONTRACTOR'S
EXPENSE). ANY INDIVIDUALS FROM UNIRAC OR THE ENGINEER OF RECORD'S OFFICE PERFORMING
SITE VISITS OR STRUCTURAL OBSERVATIONS ARE NOT AUTHORIZED TO DIRECT OR APPROVE ANY
CHANGES FROM THE CONTRACT DOCUMENTS OR STOP AND/OR DELAY THE WORK.
6. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND COORDINATE SITE CONDITIONS WITH THE
DRAWING PRIOR TO BIDDING AND THE START OF CONSTRUCTION. ANY CONFLICTS,
DISCREPANCIES, OR OMISSIONS SHALL BE RESOLVED WITH UNIRAC AND THE ENGINEER OF RECORD
PRIOR TO PROCEEDING. DO NOT SCALE DIMENSIONS FROM DRAWINGS. WRITTEN DIMENSIONS
SHALL BE USED OR WHERE NO DIMENSION IS PROVIDED. CONSULT WITH UNIRAC FOR
CLARIFICATION BEFORE PROCEEDING.
7. WHERE ANY DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, STRUCTURAL NOTES AND
SPECIFICATIONS, THE GREATER (MOST CONSERVATIVE) REQUIREMENTS SHALL GOVERN. WHERE
NO SPECIFIC DETAIL IS SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE
PROJECT. IF THERE IS NO SIMILAR WORK CONSTRUCTION SHALL CONFORM TO INDUSTRY
STANDARDS. CONTRACTOR MUST INFORM UNIRAC OF ANY DISCREPANCIES.
8. ANY EQUIPMENT OR CONDUIT BEING SUPPORTED BY OR SUSPENDED FROM THE RACKING
STRUCTURE SHALL BE COORDINATED WITH UNIRAC AND THE ENGINEER OF RECORD FOR REVIEW
AND APPROVAL PRIOR TO PURCHASE AND INSTALLATION OF EQUIPMENT OR CONDUIT.
9. ASTM SPECIFICATIONS ON THE DRAWINGS SHALL BE OF THE LATEST ASTM STANDARD
SPECIFICATION OR ASTM STANDARD ADOPTED BY THE SITE JURISDICTION.
10. ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE
SEAL OF A PROFESSIONAL CIVIL OR STRUCTURAL ENGINEER REGISTERED IN THE STATE OF THE
LOCAL JURISDICTION.
11. THE FOLLOWING DESIGN CRITERIA IS EXCLUDED FROM DESIGN: FLOOD LOADING, DEBRIS LOADING ,
DYNAMIC ANALYSIS, ACTS OF GOD (TORNADO, HURRICANE, WATER INUNDATION LOADING, ETC.),
AND DYNAMIC LOADING FROM SEISMIC EVENTS AND CONDITIONS.
12. THE MINIMUM DISTANCE BETWEEN ROOF EDGE AND MODULES OR RM RACKING SYSTEM MUST BE 4
FT UNLESS NOTED OTHERWISE IN THE UNIRAC ENGINEERING REPORT.
13. UNIRAC IS NOT RESPONSIBLE FOR THE ORIGINAL BUILDING STRUCTURE. CONSULT WITH A
LICENSED PROFESSIONAL ENGINEER IN THE JURISDICTION OF THE PROJECT TO ENSURE THE
EXISTING BUILDING IS CAPABLE OF HANDLING ADDITIONAL LOAD FROM THE RM STRUCTURE.
14. IN THE EVENT THAT THE ARRAY IS DISPLACED FOR ANY REASON, THE ARRAY SHALL BE
REPOSITIONED INTO ITS ORIGINAL DESIGN LOCATION SO AS TO ENSURE THAT PROPER SEISMIC AND
FIREFIGHTING ACCESS CLEARANCES AND SEPARATIONS ARE MAINTAINED, IN ADDITION TO
ELECTRICAL WIRING SEISMIC SLACK REQUIREMENTS.
15. THESE GENERAL NOTES APPLY TO ALL SHEETS IN THIS PACKAGE.
SOLAR DESIGN:
UNIRAC IS NOT THE SOLAR DESIGN ENGINEER OF RECORD AND IS NOT RESPONSIBLE FOR ANY
SOLAR DESIGN, OUTPUT EFFICIENCIES, SHADING, ETC. IT IS THE RESPONSIBILITY OF THE
INSTALLING CONTRACTOR TO CONFIRM THAT THE LOCATION OF THE RACKING/MODULES DOES NOT
INTERFERE WITH OR BECOME SHADED BY OBSTRUCTIONS.
ELECTRICAL DESIGN:
UNIRAC IS NOT THE ELECTRICAL ENGINEER OF RECORD AND IS NOT RESPONSIBLE FOR THE
ELECTRICAL DESIGN FOR THIS PROJECT. THE UNIRAC SYSTEM IS CERTIFIED TO UL-2703 WHEN
PROPERLY INSTALLED. SEE THE RM INSTALLATION GUIDE FOR MORE DETAIL.
MATERIAL MANAGEMENT:
1. PRIOR TO INSTALLATION , ALL MATERIALS MUST BE STORED PROPERLY. THIS MEANS MATERIALS
REMAINING IN ONE PLACE FOR MORE THAN ONE WEEK MUST BE IN OPEN AIR CONDITIONS (I.E. UP
AND ABOVE THE GROUND AND WATER TABLE). IF TARPS OR OTHER PROTECTIVE COVERS ARE
USED, THEN ENDS SHALL BE LEFT OPEN FOR VENTILATION. TIGHT FITTING COVERINGS ARE NOT
RECOMMENDED SINCE THEY CAN TRAP MOISTURE.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR AND PROVIDE ALL MEASURES NECESSARY TO
PROTECT THE RACKING SYSTEM FROM THE POINT OF UNIRAC DELIVERY THROUGHOUT THE
COMPLETION OF CONSTRUCTION.
RM STEEL COMPONENTS:
1. ALL STEEL RMDT BAYS ARE MANUFACTURED USING 16 GAGE ASTM A653 GRADE 50 STEEL
GALVANIZED TO G235.
2. ALL MID CLAMPS AND END CLAMPS ARE MANUFACTURED USING 12 GAGE 300 SERIES 1/4 HARD
STAINLESS STEEL WITH A MINIMUM TENSILE STRENGTH OF 125 KSI PER ASTM 666 WITH A MILL (2B)
FINISH.
3. ALL WIRE MANAGEMENT CLIPS PROVIDED BY UNIRAC ARE MANUFACTURED USING 302 0.090Ø
STAINLESS STEEL.
BALLAST BLOCK (CONCRETE MASONRY UNIT (CMU)):
1. INSTALLER IS RESPONSIBLE FOR PROCURING THE BALLAST BLOCKS (CMU) AND VERIFYING THE
REQUIRED MINIMUM WEIGHT NEEDED FOR THIS DESIGN. CMU TO COMPLY WITH ASTM STANDARD
SPECIFICATION FOR CONCRETE ROOF PAVERS DESIGNATION C1491 OR C90 WITH AN INTEGRAL
WATER REPELLANT SUITABLE FOR THE CLIMATE IT IS PLACED. IT IS RECOMMENDED THAT THE
BLOCKS ARE INSPECTED PERIODICALLY FOR ANY SIGNS OF DEGRADATION. IF DEGRADATION OF
THE BLOCK IS OBSERVED, THE BLOCK SHOULD IMMEDIATELY BE REPLACED.
2. ACTUAL BLOCK DIMENSIONS ARE 3/8" LESS THAN NOMINAL DIMENSIONS.
3. THE CMU BALLAST BLOCK SHOULD HAVE NOMINAL DIMENSIONS OF 4"X8"X16".
HARDWARE:
1. ALL STEEL U-NUTS ARE MANUFACTURED USING 304 STAINLESS STEEL.
2. ALL 1/4 - 20 BOLTS ARE MANUFACTURED USING 18-8 STAINLESS STEEL.
3. ALL 1/4 INCH FENDER WASHERS ARE MANUFACTURED USING 18-8 STAINLESS STEEL.REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -NAERIAL PHOTO
NOT TO SCALE
NOTE: *SANTOPRENE PAD ONLY REQUIRED ON ROOFS WITH PVC MEMBRANE. FIELD VERIFY
PVC ROOF MEMBRANE PRIOR TO PURCHASING PART NUMBER M60700.
TORQUE REQUIREMENTS
1/4"Ø STAINLESS STEEL HARDWARE FOR CLAMPS 7-9 FT-LBS
1/4"Ø STAINLESS STEEL HARDWARE FOR DEFLECTORS 10-15 FT-LBS
SINGLE USE ONLY-DO NOT RE-TORQUE ONCE FULLY SEATED
PROJECT OVERVIEW
PROJECT SIZE 33.75 KW
MODULE QUANTITY 90
DESIGN CRITERIA
BUILDING CODE ASCE 7-16
OCCUPANCY/RISK CATEGORY II
WIND SPEED 110.00 MPH
WIND EXPOSUIRE B
GROUND SNOWLOAD 20 PSF
SEISMIC SS 0.168
SEISMIC S1 0.082
ROOF HEIGHT 20 FT
BUILDING LENGTH 63 FT
PARAPET HEIGHT <= 1 Array Height
ROOF MEMBRANE TYPE OTHER
SITE ELEVATION ABOVE MSL 904 FT
MODULE SPECIFICATIONS
MANUFACTURER MISSION
MODEL MSE375SQ9S
LENGTH 78.23 IN
WIDTH 39.33 IN
WEIGHT 47.60 LB
OUTPUT 375 WATT
ENGINEERING OUTPUT
PRODUCT LINE RMDT
TILT ANGLE 8 DEG
AVERAGE WEIGHT TO ROOF 5.5 PSF
TOTAL AREA 2183 SQ FT
TOTAL WEIGHT ON ROOF 12006 LB
TOTAL WEIGHT OF RACKING 858 LB
TOTAL WEIGHT OF MODULES 4284 LB
TOTAL WEIGHT OF BALLAST 6864 LB
ARRAY PARTS LIST
PART NUMBER DESCRIPTION QUANTITY
310820 RM END CLAMP 32-40 MM 220
310802 RMDT VALLEY BAY 67
310825 RMDT MID CLAMP 36-40 MM 110
310801 RMDT RIDGE BAY 55
USER SUPPLIED 33 LB CMU BALLAST BLOCK 208
310860 KIT 1/4-20 CLIP ON NUT SS 18-8 330
008002S GROUND WEEBLUG #1 3
*M60700 SANTOPRENE TPV, 64D, ACRYLIC PSA 244*
SHEET INDEX
RMDT.100 COVER SHEET
RMDT.200 KEY PLAN
RMDT.301 & 302 ARRAYS A1 & A2
RMDT.400 RMDT DETAILS
RMDT.401 RMDT DETAILS
RMDT.402 RMDT SANTOPRENE DETAILS
RMDT.500 RMDT CERTIFICATIONS
04/20/21
KEY PLANRMDT.200REVISIONS
DESCRIPTION REV DATE DRWCHK
1411 BROADWAY BOULEVARD NE
ALBUQUERQUE, NEW MEXICO, USA, 87102
WWW.UNIRAC.COMFORENGINEER'S STAMPPROJECTTITLESHEETBLACK&VEATCHIN-156701J.P.MORGAN CHASE13085 Pettigru Dr,Carmel, IN 460320 06/29/2020 Approved for construction IS NT
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -
- - - -NOT TO SCALENKEY PLANDCBA1 2 3 4ARRAY A1ARRAY A204/20/21
2 2 2 2 2 2
2 2 2 2 2 2
LEGEND
RIDGE BAY WITH
BLOCK COUNT
VALLEY BAY WITH
BLOCK COUNT
VALLEY BAY WITH
ATTACHMENT
1 1 1 1 1
1 1 1 2 X
1 1 1 2 X
ARRAY LAYOUT
ARRAY A1
RMDT.301REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -NOT TO SCALE NARRAY A1 LAYOUT
6'-61
4"
7'-103
4"
04/20/21
2 2 2 3 1 3 2 2 2 3 2 2 2
2 3
1 1 1 1 1 1 1 1 1 1 1 3 1
2 4 1 1 1 3 1 1 2 3 1 3 1 2 2
2 2
2 1 1 1 1 0 0 0 2 0 2 0 2 3 2
2 2
1 1 1 1 1 1 1 1 1 3 1 1 1 3 2
2 4 1 4 2 4 1 1 2 4 1 1 1 4 2
2 3 1 1 2 1 1 1 2 1
1 1 1
3 2
2 2 2
LEGEND
RIDGE BAY WITH
BLOCK COUNT
VALLEY BAY WITH
BLOCK COUNT
VALLEY BAY WITH
ATTACHMENT
1 1 1 1 1
1 1 1 2 X
1 1 1 2 X
ARRAY LAYOUT
ARRAY A2
RMDT.302REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -NOT TO SCALE NARRAY A2 LAYOUT
58'-1115
16"
45'-91
8"
04/20/21
RMDT
DETAILS
RMDT.400REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -SCALE:
RMDT BAY - RIDGE DETAIL 1
-NTS SCALE:
RMDT BAY - VALLEY DETAIL2
-NTS
PLAN VIEW FRONT VIEW SIDE VIEW ISOMETRIC VIEW
16 1/8" 26 3/16"
93
4"
NOTE: PER OWNER REQUIREMENT, INSTALLER MUST
PROVIDE SLIP-SHEET BELOW EACH BALLAST BAY.
SHIP SHEET DIMENSIONS MUST EXTEND 4" MINIMUM
BEYOND BAY EDGES.
NOTE: PER OWNER REQUIREMENT, INSTALLER MUST
PROVIDE SLIP-SHEET BELOW EACH BALLAST BAY.
SHIP SHEET DIMENSIONS MUST EXTEND 4" MINIMUM
BEYOND BAY EDGES.
PLAN VIEWFRONT VIEWSIDE VIEW ISOMETRIC VIEW
16 1/8" 19 11/16"
41
4"
SCALE:
RIDGE BALLAST BLOCK - CONFIGURATIONS 3
-NTS NOTE: PER OWNER REQUIREMENT, INSTALLER MUST
PROVIDE SLIP-SHEET BELOW EACH BALLAST BAY.
SHIP SHEET DIMENSIONS MUST EXTEND 4" MINIMUM
BEYOND BAY EDGES.
SCALE:
VALLEY BALLAST BLOCK - CONFIGURATIONS4
-NTS NOTE: PER OWNER REQUIREMENT, INSTALLER MUST
PROVIDE SLIP-SHEET BELOW EACH BALLAST BAY.
SHIP SHEET DIMENSIONS MUST EXTEND 4" MINIMUM
BEYOND BAY EDGES.
TWO BLOCKSONE BLOCK TWO BLOCKS ONE BLOCK THREE BLOCK FOUR BLOCK FIVE BLOCK
SCALE: NTS
RIDGE MIDCLAMP5
RMDT
RIDGE
BAY
MODULE
RMDT MIDCLAMP
(ENDCLAMP, U-NUT,
AND BOLT)
SCALE: NTS
VALLEY ENDCLAMP6
-
RMDT
VALLEY
BAY
MODULE
RM5/DT ENDCLAMP
(ENDCLAMP, U-NUT,
AND BOLT)
RM5/DT ENDCLAMP
(ENDCLAMP, U-NUT,
AND BOLT)
-
04/20/21
RMDT
DETAILS
RMDT.401REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -SCALE:
2x4 SAMPLE ARRAY1
-NTS
MODULE
RMDT
VALLEY
BAY
MODULE RMDT
RIDGE
BAY
RMDT
VALLEY
BAY
~ 8.6" BOTTOM OF MODULE TO
BOTTOM OF ADJACENT MODULE (TYP)
1.08" BOTTOM OF MODULE TO BOTTOM
OF ADJACENT MODULE (TYP)
~ 7.9" EDGE OF BAY TO BOTTOM
OF MODULE (TYP)
ISOMETRIC VIEW
ARRAY - PLAN VIEW
FRONT VIEW
N
N
SIDE VIEW
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
04/20/21
RMDT
SANTOPRENE
DETAILS
RMDT.402REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -SIDE VIEW
OBLIQUE VIEW
AA
SECTION A-A
B
DETAIL B
2X AS SHOWN
DO NOT OVERLAP
FLANGE OR RIB EDGES
RMDT RIDGE BAY SANTOPRENE DETAILS1
-
SCALE: NTS
SCALE: NTS
SCALE: NTS
SCALE: NTS
RMDT VALLEY BAY SANTOPRENE DETAILS2
-
DO NOT OVERLAP
FLANGE OR RIB EDGES
APPLY HERE
APPLY HERE
B
SIDE VIEW
OBLIQUE VIEW
SECTION A-A
DETAIL B
2X AS SHOWN
SCALE: NTS
SCALE: NTS
SCALE: NTS
SCALE: NTS
AA
NOTE:
FOR PVC MEMBRANE ROOF APPLY TWO (2)
SANTOPRENE PADS PER RIDGE BAY AS SHOWN.
SANTOPRENE PAD ONLY REQUIRED ON ROOFS WITH
PVC MEMBRANE. FIELD VERIFY PVC ROOF MEMBRANE
PRIOR TO PURCHASING PART NUMBER M60700.
NOTE:
FOR PVC MEMBRANE ROOF APPLY TWO (2) SANTOPRENE
PADS PER VALLEY BAY AS SHOWN. SANTOPRENE PAD
ONLY REQUIRED ON ROOFS WITH PVC MEMBRANE. FIELD
VERIFY PVC ROOF MEMBRANE PRIOR TO PURCHASING
PART NUMBER M60700.
APPLY HERE
APPLY HERE
04/20/21
RMDT
CERTIFICATIONS
RMDT.500REVISIONSDESCRIPTION REVDATE DRWCHK1411 BROADWAY BOULEVARD NEALBUQUERQUE, NEW MEXICO, USA, 87102WWW.UNIRAC.COMFOR
ENGINEER'S STAMP
PROJECT
TITLE
SHEET
BLACK&VEATCH
IN-156701
J.P.MORGAN CHASE
13085 Pettigru Dr,
Carmel, IN 460320 06/29/2020 Approved for construction IS NT- - - -- - - -- - - -- - - -- - - -- - - -- - - -- - - -SCALE: NTS
FIRE RATING1
-
SCALE: NTS
CERTIFICATE OF COMPLIANCE3
-SCALE: NTS
DESTRUCTIVE TEST REPORT4
-
SCALE: NTS
CERTIFICATE LETTER2
-
04/20/21