J.P. MORGAN CHASE
13085 PETTIGRU DRIVE, CARMEL, IN 46032-4436
PLACARDS
SERVICE DISCONNECTING
MEANS
PV ARRAY
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
IN-156701-E30
GENERATOR DISCONNECT
SWITCH
OPERATING DC CURRENT: 54 A
OPERATING DC VOLTAGE: 840 V
MAX SHORT CURRENT: 45 A
MAX VOLTAGE: 980 V
AT EACH 33.3 KW INVERTER DC DISCONNECTING MEANS
[NEC 690.53]
20
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE
GENERATOR DISCONNECTING MEANS IF NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10
SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS [NEC 690.4(D)]
PHOTOVOLTAIC
AC DISCONNECT
AT POINT OF INTERCONNECTION, MARKED AT
DISCONNECTING MEANS
[NEC 690.54]
OPERATING AC CURRENT: 92.3A
OPERATING AC VOLTAGE: 208V, 3Ф
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
AT EACH JUNCTION, COMBINER, DISCONNECT AND
DEVICE WHERE ENERGIZED UNGROUNDED
CONDUCTORS MAY BE EXPOSED DURING SERVICE
[NEC 690.35(F)]
! WARNING !
ELECTRIC SHOCK HAZARD.
THE DC CONDUCTORS OF THIS
PHOTOVOLTAIC SYSTEM ARE UNGROUNDED
AND MAY BE ENERGIZED.
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
PHOTOVOLTAIC
DC DISCONNECT
GENERATOR
DISCONNECT SWITCH
WARNING: PHOTOVOLTAIC
POWER SOURCE
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
INVERTER OUTPUT CONNECTION.
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM METER INTERACTIVE
PHOTOVOLTAIC SYSTEM CONNECTED
AT UTILITY METER
[NEC 690.56(B)]
PLAQUE
INTERACTIVE PHOTOVOLTAIC SYSTEM
CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE BUILDING
! WARNING !
ELECTRIC SHOCK HAZARD
DO NOT TOUCH TERMINALS
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO SUNLIGHT
! WARNING !
TURN OFF PHOTOVOLTAIC AC DISCONNECT
PRIOR TO WORKING INSIDE PANEL
AT EACH BREAKER PANEL AND MAIN SERVICE
DISCONNECT.
[NEC 110.27(C)]
! WARNING !
PHOTOVOLTAIC SYSTEM DATA
ACQUISITION SYSTEM
AUTHORIZED PERSONNEL ONLY
THE PV DAS SHALL BE LABELED WITH THE FOLLOWING
INFORMATION
AT EACH AC DEDICATED PHOTOVOLTAIC SYSTEM
COMBINER PANEL AND DISCONNECT.
[NEC 110.16]
! WARNING !
ARC FLASH HAZARD.
APPROPRIATE PPE REQUIRED.
FAILURE TO COMPLY MAY RESULT IN
INJURY OR DEATH.
REFER TO NFPA 70 E.
AT EACH PHOTOVOLTAIC SYSTEM
SERVICE DISCONNECT SWITCH.
! DANGER !
ARC FLASH AND SHOCK HAZARD PRESENT
DO NOT OPEN DOOR WHILE ENERGIZED
INCIDENT ENERGY EXCEEDS MAX PPE PROTECTION
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
PHOTOVOLTAIC
SYSTEM SERVICE
DISCONNECT SWITCH
DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL DO NOT
ADD LOADS TO THIS PANEL
AT DEDICATED PHOTOVOLTAIC
SYSTEM COMBINER PANEL (IF
APPLICABLE)
AT THE SERVICE ENTRANCE (ELECTRICAL SERVICE PANEL) AND
GENERATOR DISCONNECT SWITCH
NET GENERATION
OUTPUT METER
AT NET GENERATION OUTPUT
METER
AT THE ELECTRICAL SERVICE PANEL
! WARNING !
A GENERATION SOURCE IS CONNECTED TO THE SUPPLY (UTILITY) SIDE OF THE
SERVICE DISCONNECTING MEANS. FOLLOW PROPER LOCKOUT/TAGOUT PROCEDURES
TO ENSURE THE PHOTOVOLTAIC SYSTEM UTILITY DISCONNECT SWITCH IS OPENED
PRIOR TO PERFORMING WORK ON THE DEVICE.
1 2 3
5
1716 15 14
13 12 9 10 11
6 7 8
419 18
AT EACH AC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT EACH DC DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.17]
AT PHOTOVOLTAIC SYSTEM SERVICE
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT GENERATOR
DISCONNECT SWITCH [NEC 690.14(C)(2)]
AT EACH DC DISCONNECTING MEANS
[NEC 690.14(C)(2)]
AT EACH DISTRIBUTION EQUIPMENT ADJACENT TO
THE BACK-FED BREAKER FROM THE INVERTER.
[NEC 705.12(D)(7)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT POINT OF INTERCONNECTION; LABEL
MUST IDENTIFY PHOTOVOLTAIC SYSTEM
[NEC 705.12(D)(4)]
AT PHOTOVOLTAIC SYSTEM SERVICE DISCONNECT
SWITCH
[NEC 2014 - 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE [IFC 605.11.1.1].
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS;
SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY
ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS.
[NEC 690.31(E)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2008 NATIONAL ELECTRICAL CODE.
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT FOR WHICH THEY ARE INSTALLED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
NRS NRS APN
APN
NRS NRS JDL
JASON D. LEIMBACK
11100106
INDIANA
PHOTOVOLTAIC
SYSTEM INVERTER
DISCONNECT SWITCH
21
AT INVERTER DISCONNECT
JDL
25/JUN/20
NRS APN NRS JDL JDL
23
22
04/20/21