HomeMy WebLinkAboutE501 - ELECTRICAL ONELINE RISER DIAGRAMSECOND FLOOR
FIRST FLOOR
THIRD FLOOR
480V
UTILITY
TRANSFORMER
F1600
F400
400A
MLO
1H1
3P-4W
277/480V
277/480V
3P-4W
MDP
MCB
1600A
GND
F225
225A
MCB
1L1
3P-4W
T-208V1L1 120/
75 KVA
(1) #2, AL GND, 3/4"C TO
BUILDING GROUNDING SYSTEM.
F125
F400
400A
MLO
2H1
3P-4W
277/480V
F225
225A
MCB
2L1
3P-4W
T-208V2L1 120/
75 KVA
(1) #2, AL GND, 3/4"C TO
BUILDING GROUNDING SYSTEM.
F125
F400
400A
MLO
3H1
3P-4W
277/480V
F300
300A
MCB
3L1
3P-4W
T-208V3L1 120/
112.5 KVA
(1) #2, AL GND, 3/4"C TO
BUILDING GROUNDING SYSTEM.
F150
F225 225A
MLO
1L2
3P-4W
120/208V
4
4 4
5
100A
MLO
3L2
3P-4W
120/208V
100A
3LE1
1P-3W
120/240V
6
6
6 6
6 6
6
6
6
GEN
F50
F100
F100
ATS
100A
22KW
240/120V, 1 PH, 3 W
NATURAL GAS
FEEDER AND BRANCH CIRCUIT SCHEDULE
NOTE: SEE DRAWINGS FOR NUMBER OF WIRES IN HOMERUN
FEEDER/BRANCH CIRCUIT
DESIGNATION
CONDUCTOR SIZE TYPE CABLE CONDUIT
PHASE & NEUTRAL
EQUIPMENT
GROUND
ALUMINUM COPPER
F20 12 12 X MC
F30 10 10 X MC
F40-50 8 10 X MC
F60 6 10 X MC
F70-80 4 8 X MC
F90 3 8 X MC
F100 3 8 X MC
F125 1/0 4 X MC
F150 3/0 4 X 2-1/2"
F175 4/0 4 X 2-1/2"
F200 250 4 X 3"
F225 300 2 X 3"
F250 350 2 X 3"
F300 500 2 X 3-1/2"
F350 2 RUNS OF 4/0 1 X 2-1/2"
F400 2 RUNS OF 250 1 X 3" EACH
F600 2 RUNS OF 500 2/0 X 3-1/2" EACH
F800 3 RUNS OF 400 3/0 X 3-1/2" EACH
F1000 3 RUNS OF 600 4/0 X 4" EACH
F1200 4 RUNS OF 500 250 X 3-1/2" EACH
F1600 5 RUNS OF 600 350 X 4" EACH
F2000 6 RUNS OF 600 400 X 4" EACH
F2500 7 RUNS OF 750 600 X 5" EACH
F3000 8 RUNS OF 750 600 X 5" EACH
NOTES:
1. 20 A BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO
COMPENSATE FOR VOLTAGE DROP. FOR THESE CIRCUITS, CONTRACTOR SHALL UTILIZE WIRE SIZE SHOWNABOVE FOR
DISTANCES LISTED ABOVE.
2. VOLTAGE DROP WIRE SIZES WILL BE STRICTLY INFORCED. CONTRACTOR SHALL SUBMIT A LIST OF CIRCUITS THAT WILL
EXCEED THE DISTANCES ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING INSTALLED.
3. DO NOT SHARE NEUTRAL CONDUCTORS FOR ANY BRANCH CIRCUITS. ALL BRANCH CIRCUIT SHALL HAVE SEPARATE,
INDEPENDENT NEUTRAL CONDUCTORS.
4. ALL BRANCH CIRCUIT WIRING SHALL BE MC CABLE WITH THE FOLLOWING EXCEPTIONS:
a. ALL WIRING IN PATIENT CARE EXAM OR TREATMENT ROOMS SHALL BE HEALTHCARE RATED MC CABLE
COMPLETE ALL THE WAY BACK TO THE PANEL.
5. ALL CONDUIT PENETRATIONS THRU THE FLOOR SLAB SHALL BE MADE WITH CAUTION. CONTRACTOR SHALL
COORDINATE ALL HOLE LOCATIONS WITH STRUCTURAL ENGINEER PRIOR TO CUTTING ANY NEW HOLES. NEW HOLES
SHALL BE ADJUSTED AS REQUIRED TO MISS REBAR AS DETERMINED BY THE STRUCTURAL ENGINEER.
FED FROM MDP
120/208V 3P 4W.
PANEL 1LN1 EQUIPMENT SERVED
INFORMATION PLATE
SOURCE OF POWER
VOLTAGE
LAMACOID PLATE
NOTE: PROVIDE I.D. PLATE LABEL
FOR ELECTRICAL EQUIPMENT SUCH
AS MAIN SWITCHGEAR,
SWITCHBOARD PANELBOARDS,
ANDTRANSFORMERS
! WARNING
Arc Flash Hazard
Appropriate PPE Required
Equipment Type
Grounding
Work Distance
Availiable 3-Ph Bolted Current
Flash Protection Boundary
Incident Energy at 11 inches
Risk Category
Equipment Name:
480V Switchgear
Grounded
11 inches (300 mm)
25 kA
27 inches
4.39 cal/cm2
2
Switchboard
NOTE: PROVIDE WARNING LABEL FOR ALL
ELECTRICAL EQUIPMENT SUCH AS MAIN
SWITCHGEAR, SWITCHBOARDS, PANELBOARDS, AND
TRANSFORMERS.
WALL MOUNTED
1/4"x6"Hx24"W
GROUND BUSBAR
(1) #3/0 Cu GND, 1"C TO INCOMING WATER
SERVICE PIPE
(1) #3/0 Cu GND, 1"C TO BUILDING STEEL GROUND
(1) #3/0 Cu GND, 1"C TO UFER GROUND
FIRST FLOOR
ELEC ROOM 'MDP'
1 2 3
(1) #3/0 Cu GND, 1"C TO ELECTRICAL
SERVICE GROUND ROD FIELD
(1) #3/0 Cu GND, 1"C TO INCOMING NATRUAL GAS SERVICE
PIPE WHERE REQUIRED AND PERMITTED BY CODE
(1) #1 AL GND, 3/4"C TO PANEL '1H1'
(1) #1 AL GND, 3/4"C TO PANEL '2H1'
(1) #1 AL GND, 3/4"C TO PANEL '3H1'
277V
200 FEET
360 FEET
120V
FEEDER SIZE TO USE
F20
F30
VOLTAGE DROP FOR 20A
BRANCH CIRCUITS
100 FEET
150 FEET
MAXIMUM DISTANCE ALLOWED
550 FEET
885 FEET
F40-50
F60
240 FEET
385 FEET
1. CONDUCTORS FOR 20 AMP BRANCH CIRCUITS SHALL BE SIZED FOR VOLTAGE
DROP. WIRE SIZES ARE NOT INDICATED ON THE DRAWINGS TO COMPENSATE
FOR VOLTAGE DROP FOR THESE CIRCUITS. CONTRACTOR SHALL UTILIZE
WIRE SIZE SHOWN ABOVE FOR THE DISTANCES LISTED ABOVE.
2. VOLTAGE DROP WIRE SIZES WILL BE STRICTLY ENFORCED. CONTRACTOR
SHALL SUBMIT A LIST OF CIRCUITS THA WILL EXCEED THE DISTANCES
ALLOWED AND INDICATE WIRE SIZE TO BE USED PRIOR TO ANY WIRE BEING
INSTALLED.
3. PROVIDE SEPARATE, INDEPENDENT NEUTRAL CONDUCTORS FOR ALL BRANCH
CIRCUITS. DO NO SHARE NEUTRALS BETWEEN CIRCUITS.
NOTES
Project Number
CERTIFIED BY
ISSUANCE INDEX
DATE:
PROJECT PHASE:
2/11/2021 10:05:42 AM
E501
ELECTRICAL ONELINE
RISER DIAGRAM
2019.00780
11.5.2020
CONSTRUCTION DOCUMENTS
CARMEL MEDICAL
ARTS PAVILION
12174 N. Meridian Street
Carmel, Indiana 46032
NO SCALE
1
ELECTRICAL ONE-LINE RISER DIAGRAM
PLAN NOTES
1 BOND ALL METAL PIPING DESCRIBED IN NFPA 70-250.104, INCLUDING GAS PIPING.
2 GROUNDING CONDUCTORS SHALL BE INSTALLED IN CONDUIT WHERE INSTALLED ABOVE GRADE.
3 CONNECT WATER SERVICE GROUNDING CONDUCTOR TO STREET SIDE OF WATER METER. PROVIDE BONDING
JUMPER ACROSS WATER METER AND INSTALL WITH TAG.
4 PANEL AND FEEDER INSTALLED IN TI PACKAGE.
5 PROVIDE NEW NATURAL GAS GENERATOR SIMILAR TO GENERAC GUARDIAN SERIES IN TI PACKAGE. COORDINATE
ROOF INSTALLTION AND GAS CONNECTION.
6 EQUIPMENT INSTALLED IN SHELL PACKAGE.
NO SCALE
3
ELECTRICAL EQUIPMENT I.D. LABELING DETAIL
NO SCALE
4
ELECTRICAL EQUIPMENT WARNING LABEL DETAIL
NO SCALE
5
MAIN DISTRIBUTION PANEL 'MDP' GROUND BUSBAR DETAIL
NO SCALE
7
VOLTAGE DROP SCHEDULE
REVISION SCHEDULE
NO. DESCRIPTION DATE