HomeMy WebLinkAboutM202 - SECOND FLOOR MECHANICAL PLAN30/25 30/25
20/20 25/25
10ø
18/18
20/18 20/20
30/25 25/25
20/20
18/16 10ø
14ø 18ø
10ø
10ø
10
6ø
10/8
4ø
8ø
16/16
14/14
6ø
8ø
10ø
10/10 8ø
8ø
8ø
4ø
60/40
6ø
14ø 14ø
14
14ø
14ø 14ø
14ø
VAV-207
SD-2 - 120
SD-1 - 30
SD-2 - 165
SD-2 - 165
SD-2 - 165
SD-1 - 30
EG-1 - 75
EG-1 - 75
SD-2 - 200
DS-1
VAV-203
ø
ø
14"x14"
16"x16"
28"x10"
6"ø
2
6"ø
1
16"x16"
1
2
3
Certified By:
Scale:
Date:
Checked By:
Drawn By:
Job Number:
Drawing Number:
Drawing Name:
CARMEL, IN 46032
PRIORITY PHYSICIANS 12.03.2020
Revisions:
12174 N. MERIDIAN
SUITE 300
AS NOTED
-
-
PERMIT SET 12.03.2020
M202
SECOND FLOOR MECHANICAL
PLAN
N
- PLAN NOTES:
1. CONNECT TO EXISTING EXHAUST DUCT ROUTED DOWN TO FIRST
FLOOR.
2. CONNECT TO EXISTING EXHAUST DUCT.
3. 28"X10" EXHAUST DUCT UP.
SCALE: 1/8" = 1'-0"
2 SECOND LEVEL MECHANICAL PLAN
GENERAL NOTES:
A. ALL DUCT DIMENSIONS GIVEN ARE OUTSIDE DIMENSIONED.
B. COORDINATE ALL OPENINGS IN FLOORS, ROOF AND WALLS WITH
THE GENERAL AND STRUCTURAL CONTRACTORS.
C. RUN ALL DUCTS AS HIGH AS POSSIBLE WITH RETURN AND
EXHAUST ABOVE SUPPLY AS OFTEN AS POSSIBLE.
D. INSULATE ALL SUPPLY AIR AND OUTSIDE AIR DUCTWORK WITH 1.5"
FIBERGLASS DUCT WRAP WITH FSK JACKET (R-5 MINIMUM).
E. PROVIDE VOLUME BALANCING DAMPERS UPSTREAM OF ALL AIR
INLET/OUTLETS UNLESS NOTED OTHERWISE.
F. PROVIDE TURNING VANES IN ALL SUPPLY AIR SQUARE THROATED
ELBOWS.
G. ALL RECTANGULAR SUPPLY AIR BRANCH CONNECTIONS SHALL BE
45° TAKE-OFF FITTINGS AND ROUND SUPPLY AIR BRANCH
CONNECTIONS SHALL BE BELLMOUTH FITTINGS.
H. FLEXIBLE DUCTS TO DIFFUSERS MAXIMUM LENGTH 5'-0".
FLEXIBLE DUCTS ARE NOT TO BE USED AS ELBOWS.
I. RETURN DUCTWORK SHALL NOT BE INSULATED UNLESS NOTED
OTHERWISE.
J. ALL EXHAUST DUCTWORK FROM THE BOTTOM OF THE ROOF CURB
TO THE BACK-DRAFT DAMPER SHALL BE EXTERNALLY INSULATED
WITH 1.5" FIBERGLASS DUCT WRAP WITH FSK JACKET (R-5
MINIMUM). ALL OTHER EXHAUST DUCTWORK SHALL NOT BE
INSULATED.