HomeMy WebLinkAboutM600 - MECHANICAL DETAILSSQUARE DIFFUSER OBSTRUCTED INSTALLATION SQUARE DIFFUSER INSTALLATION INSULATED FLEXIBLE DUCTWORK ROUND BRANCH DUCT TO MAIN (SEE SCHEDULE FOR SIZE) SLOT DIFFUSER INSTALLATION SLOT DIFFUSER (THREE SLOT SHOWN) ADJUST AIR FLOW SLOTS PER SCHEDULE AND PLANS. PLENUM BOX HEIGHT = ROUND DUCT DIAMETER + 4" DUCTWORK/DIFFUSER SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING) INSIDE OF PLENUM TO BE PAINTED FLAT BLACK. PLENUM BOX HEIGHT = ROUND DUCT DIA. + 4" SHEETMETAL PLENUM SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING) INSIDE OF PLENUM SHALL BE PAINTED FLAT BLACK PLENUM TO BE EXTERNALLY INSULATED SQUARE DIFFUSER ROUND BRANCH DUCT TO MAIN (SEE SCHEDULE FOR SIZE) INSULATED FLEXIBLE DUCTWORK DUCTWORK/DIFFUSER SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING). . . 1 2 1 2 PLAN NOTES A MINIMUM OF FIVE (5) FEET LENGTH OF FLEXIBLE DUCT SHALL BE PROVIDED TO EACH DIFFUSER. DUCTWORK SHALL CONTAIN 180° OF BENDING. FLEXIBLE DUCTWORK LENGTH SHALL NOT EXCEED EIGHT(8) FEET EXCEPT WHERE SPECIFICALLY NOTED. FLEX DUCT SHALL NOT CONTACT CEILING AND SHALL BE PROPERLY SUPPORTED SO AS TO HAVE NO KINKS. TIE-WRAP CONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DIFFUSER NECK AND TO ROUND METAL DUCTWORK AT OTHER END OF FLEX DUCT. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE-WRAP AND INSTALL SECOND TIE-WRAP OVER THE VAPOR BARRIER. INSULATE METAL DUCT OR DIFFUSER OVER TOP OF SECOND TIE-WRAP AND INSTALL INSULATOR'S TAPE ON EDGES. PROVIDE A MINIMUM OF 18" OF STRAIGHT, VERTICALLY ORIENTED, FLEXIBLE DUCT AT THE DIFFUSER NECK. IF UNABLE TO PROVIDE STRAIGHT DUCT RUN THEN PROVIDE OBSTRUCTED INSTALLATION PLENUM IN ACCORDANCE WITH THIS DETAIL. 1 2 3 INSULATED FLEXIBLE DUCTWORK DUCTWORK/DIFFUSER SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING) 1 30° MIN. SQUARE DIFFUSER 2 DUCT RADIUS TO DIFFUSER MIN. 2 DUCT DIAMETERS ROUND BRANCH DUCT TO MAIN (SEE SCHEDULE FOR SIZE) 3 DISCHARGE DUCT FULL SIZE OF TERMINAL BOX COIL UNLESS NOTED OTHERWISE DO NOT CONNECT DIFFUSERS TO END OF DISCHARGE DUCT DISCHARGE DUCT TO EXTEND 9" BEYOND LAST DIFFUSER TAKEOFF REFER TO DRAWINGS FOR RUNOUT SIZE (TYP.) PROVIDE TRANSITION DUCT AS REQUIRED ELECTRIC REHEAT COIL TERMINAL BOX SPIN-IN TAKEOFF WITH VOLUME DAMPER WITH INSULATION STANDOFF (TYP.) AIRFLOW MAIN BRANCH TAP SQUARESQUAREBOOTTAP 45° SQUARE ROUND BELLMOUTH ROUNDROUNDLATERAL 45° 5 7 1 8 9 10 4 6 3 7 2 11 PLAN NOTES A MINIMUM OF THREE (3) DUCT DIAMETERS (MAXIMUM OF 3'-0") OF STRAIGHT HARD METAL DUCT SHALL BE PROVIDED DIRECTLY UPSTREAM OF TERMINAL BOX INLET AFTER TRANSITION TO TERMINAL BOX INLET SIZE. MAINTAIN A MINIMUM OF 18" CLEARANCE FOR SERVICE, CONTROLLER, AND ELECTRICAL DISCONNECT. PROVIDE 36" MINIMUM CLEARANCE WHERE VOLTAGE EXCEEDS 24V. OPTIONAL FLEXIBLE DUCT CONNECTION TO THE TERMINAL BOX. HARD DUCT IS PERFECTLY ACCEPTABLE. FLEXIBLE DUCT SHALL NOT EXCEED ONE (1) FOOT IN LENGTH. FLEXIBLE DUCT SHALL BE INSTALLED STRAIGHT WITH NO OFFSETS. REFER TO DRAWINGS FOR RUNOUT SIZES. RUNOUT SIZE IS SAME AS TERMINAL BOX INLET SIZE UNLESS NOTED OTHERWISE. DUCT SIZE AFTER TRANSITION IS SAME SIZE AS SCHEDULED TERMINAL BOX INLET SIZE. TRANSITION AS REQUIRED IF RUNOUT SIZE DIFFERS FROM TERMINAL BOX INLET SIZE. SEE PLANS TIE-WRAP CONNECT FLEX DUCT HELICAL COIL TO ROUND METAL DUCTWORK. PULL FLEX DUCT VAPOR BARRIER OVER LOWER TIE-WRAP AND INSTALL SECOND TIE-WRAP OVER THE VAPOR BARRIER. INSULATE METAL DUCT OVER TOP OF SECOND TIE-WRAP AND INSTALL INSULATOR'S TAPE ON EDGES. INSULATE ALL EXPOSED METAL AT TERMINAL BOX INLET. INSULATE AROUND FLOW SENSORS. DUCTWORK INSULATION SHALL OVERLAP THE INTERNALLY INSULATED TERMINAL UNIT BY TWO INCHES. SUPPORT TERMINAL BOX SUCH THAT IT CAN HANG INDEPENDENTLY OF ANY DUCTWORK CONNECTIONS. ATTACH FOUR STRAP HANGERS TO UNIT. SEAL SCREW PENETRATIONS OF TERMINAL BOX. PROVIDE MINIMUM 8"X8" ACCESS DOOR DOWNSTREAM OF REHEAT COIL. 1 2 3 4 5 6 7 8 9 10 11 . SHEETMETAL STRAP SUPPORTS SECURE TO STRUCTURE ABOVE 1'-6" TO CEILING PLENUM ALL DUCTWORK SHALL BE 1" FIBERGLASS DUCTBOARD DUCT SIZE SAME AS RETURN GRILLE 12" INSIDE CLEAR DIMENSION (TYP.) PAINT INSIDE OF TRAP BLACK CEILING EGGCRATE RETURN GRILLE MIN. OF 12" RECTANGULAR BRANCH DUCT TO MAIN BOOT TAP OUT BOTTOM DUCTWORK/GRILLE SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING) RETURN/EXHAUST GRILLE RECTANGULAR INSTALLATION PLENUM BOX HEIGHT = ROUND DUCT DIAMETER + 4" ROUND BRANCH DUCT TO MAIN (SEE SCHEDULE FOR SIZE) PLASTIC WRAP TIE AROUND FLEXIBLE DUCT AT COLLAR AND TAPE VAPOR BARRIER. OPTIONAL TOP CONNECTION (SQUARE TO ROUND FITTING MAY BE SUBSTITUTED) PLENUM SHALL BE SUPPORTED INDEPENDENTLY FROM STRUCTURE (NOT SUPPORTED BY CEILING) INSIDE OF PLENUM SHALL BE PAINTED FLAT BLACK INSULATED FLEXIBLE DUCTWORK (5'-0" MAX.) RETURN/EXHAUST GRILLE Certified By: Scale: Date: Checked By: Drawn By: Job Number: Drawing Number: Drawing Name: CARMEL, IN 46032 PRIORITY PHYSICIANS 12.03.2020 Revisions: 12174 N. MERIDIAN SUITE 300 AS NOTED - - PERMIT SET 12.03.2020 M600 MECHANICAL DETAILS SCALE: NO SCALE A DIFFUSER DETAIL SCALE: NO SCALE B TERMINAL BOX DETAIL SCALE: NO SCALE C RETURN GRILLE SOUND TRAP DETAIL SCALE: NO SCALE 1 RETURN/EXHAUST GRILLE DETAIL