HomeMy WebLinkAbout202.01.18 THREE PENN ADA RR CONSTRUCTION DRAWINGSTENANT/CLIENT REPRESENTATIVE SIGNATURE
DATETENANT/CLIENT REPRESENTATIVE NAME PRINTED
THE TENANT/CLIENT AGREES THAT THESE DRAWINGS AND SPECIFICATIONS
REPRESENT THE ENTIRE SCOPE OF WORK FOR THE IMPROVEMENTS TO BE
PROVIDED. THE TENANT/CLIENT'S SIGNATURE BELOW REPRESENTS ACCEPTANCE
OF THE FINAL DESIGN. ANY CHANGES TO THIS SCOPE OF WORK INITIATED BY THE
TENANT/CLIENT WILL CAUSE CHANGES IN THE TOTAL COST TO THE TENANT/CLIENT
AND IN THE COMPLETION DATE FOR THE PROJECT.
APPROVAL FOR CONSTRUCTION
DRAWING INDEX
PROJECT TEAM
INTERIOR DESIGNER
PARALLEL DESIGN GROUP
8940 RIVER CROSSING BLVD.
SUITE 150
INDIANAPOLIS, IN 46240
KAITLYN BARRETT
317.721.4399
kaitlyn@paralleldg.com
PROJECT INFORMATION
1. EACH CONTRACTOR SHALL BECOME COMPLETELY FAMILIAR WITH ALL ASPECTS OF
THE WORK, EVEN THOSE AREAS DESIGNATED TO BE PROVIDED BY OTHERS. THIS
FAMILIARIZATION INCLUDES FULL AND COMPLETE UNDERSTANDING OF THE WORK
DESCRIBED ON ALL SHEETS OF THE DRAWINGS. FAILURE BY THE CONTRACTOR TO
BECOME COMPLETELY FAMILIAR OF ALL ASPECTS OF THE WORK SHALL NOT RELIEVE
THE CONTRACTOR OF THE RESPONSIBILITY TO PROVIDE MATERIALS ASSEMBLIES, OR
SERVICES INDICATED IN THE CONTRACT DOCUMENTS.
2. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF ALL APPLICABLE STATE
AND LOCAL BUILDING CODES. CONTRACTORS ARE RESPONSIBLE FOR VERIFYING THE
CURRENT APPLICABLE BUILDING CODE(S) FOR THEIR RESPECTIVE SCOPE OF WORK.
ALWAYS ABIDE BY THE MOST RESTRICTIVE CODE.
3. FIELD VERIFY ALL EXISTING CONDITIONS AND MEASUREMENTS INDICATED ON THE
DRAWINGS AND REPORT ANY DISCREPANCY THROUGH THE GENERAL CONTRACTOR
TO PARALLEL DESIGN GROUP BEFORE BEGINNING ANY CONSTRUCTION.
4. THE GENERAL CONTRACTOR SHALL COORDINATE WITH THE OWNER REGARDING
ALL ON-SITE ACTIVITIES; SUCH AS, BUT NOT LIMITED TO, WORK SCHEDULE,
MATERIALS STORAGE AND HANDLING, DELIVERIES, ACCESS TO THE WORKSITE,
TRAFFIC CONTROL, AND BUILDING/PUBLIC SAFETY PROCEDURES DURING
CONSTRUCTION. THE CONTRACTOR SHALL ALSO COORDINATE WORK "BY OTHERS"
WITH HIS/HER OWN ACTIVITIES AS NECESSARY TO EXECUTE THE OVERALL PROJECT
SCOPE.
5. GENERAL CONTRACTOR TO REVIEW DOCUMENTS IN DETAIL AND COMMUNICATE
ANY ITEMS THAT MAY REQUIRE LEAD TIMES. CONTRACTOR TO COORDINATE PROJECT
SCHEDULE ACCORDINGLY AND COMMUNICATE TO TEAM ANY DECISIONS THAT NEED
TO BE MADE TO KEEP PROJECT SCHEDULE ON TRACK. CONTRACTOR IS RESPONSIBLE
FOR DELAYS WHEN LEAD TIMES ARE NOT PROPERLY COMMUNICATED TO OWNER
AND PARALLEL DESIGN GROUP.
6. NO SUBSTITUTIONS FOR SPECIFICALLY NAMED PRODUCTS/MATERIALS WILL BE
ALLOWED WITHOUT PRIOR APPROVAL FROM PARALLEL DESIGN GROUP. PRODUCT
CHANGE SUBMITTALS SHOULD BE COMMUNICATED TO PARALLEL DESIGN GROUP
ALLOWING ADEQUATE TIME TO RESPOND.
7. CONTACT THE DESIGNER IMMEDIATELY IF, IN THE FIELD, CONFLICTS ARE
DISCOVERED BETWEEN COMPONENTS OF DIFFERENT SYSTEMS THAT PREVENT THE
INSTALLATION OF THOSE COMPONENTS AS INDICATED ON THE DRAWINGS. (I.E.
WHERE EXISTING MECHANICAL DUCTWORK MAY PREVENT THE INSTALLATION OF
LIGHTING FIXTURES AS INDICATED ON THE CEILING PLAN).
8. SHOP DRAWINGS OR CATALOG CUTS MUST BE SUBMITTED TO PARALLEL DESIGN
GROUP FOR APPROVAL ON ALL MATERIALS/PRODUCTS IF THE DRAWINGS DO NOT
INDICATE A SPECIFIC MANUFACTURER OR MODEL NUMBER.
9. PROVIDE SUBMITTAL SHOP DRAWINGS IN A TIMELY FASHION TO ALLOW
SUFFICIENT TIME FOR CHECKING, APPROVAL, ORDERING, FABRICATION, AND
DELIVERY OF MATERIALS AND EQUIPMENT.
10. ALL MATERIAL AND EQUIPMENT OF INDUSTRY STANDARD QUALITY SPECIFIED OR
NOT, AND WITH THE LIMITATION OF THE CONTRACT DOCUMENTS TO CAUSE THE
INSTALLATION TO FUNCTION IN ACCORDANCE WITH THE INTENTION AND OBJECTIVE
OF THE FINISHED PROJECT.
11. EACH CONTRACTOR SHALL FULLY REVIEW DRAWING SHEETS TO FULLY
UNDERSTAND NEW WORK AND EXISTING CONDITIONS TO DETERMINE FULL EXTENT
OF RESPONSIBILITIES FOR EACH RESPECTIVE TRADE IN ADDITION TO COORDINATING
FULL EXTENT OF RESPONSIBILITIES WITH ALL OTHER TRADES. FIELD WORK ORDERS &
CHANGE ORDERS WILL NOT BE APPROVED FOR ANY CONDITIONS OR CONFLICTS
THAT COULD HAVE BEEN ACCOUNTED FOR BY THE BIDDER DURING PRE-BID FIELD
INSPECTION AND AFTER AWARD OF CONTRACT.
12. THE GENERAL CONTRACTOR IS REQUIRED TO PATCH AND REPAIR ANY DAMAGED
EXISTING SURFACE TO MATCH NEW.
13. WHEN REQUIRED BY STATE BUILDING CODE, THE CONTRACTOR(S) SHALL
PROVIDE DESIGN/BUILD DRAWINGS FOR MECHANICAL, PLUMBING, ELECTRICAL, OR
FIRE SUPPRESSION. DRAWINGS SHALL BE CERTIFIED BY A LICENSED ENGINEER AND
SUBMITTED BY THE CONTRACTOR FOR STATE DESIGN REVIEW.
14. ALL EQUIPMENT, MATERIALS AND/OR FIXTURES SHALL BE INSTALLED IN STRICT
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS OR INSTRUCTIONS.
15. EXECUTE A THOROUGH FINAL CLEAN AND INSPECTION OF THE SPACE UPON
COMPLETION OF THE PROJECT. ALL SURFACES, FIXTURES, AND EQUIPMENT SHALL BE
CLEAN, AND THE SPACE SHALL BE TURNED OVER TO THE OWNER IN A CONDITION
THAT REPRESENTS THE HIGHEST LEVEL OF CARE AND PROFESSIONALISM. ENSURE ALL
GENERAL CONTRACTOR INSTALLED APPLIANCES WORK & DO NOT LEAK.
16. PROVIDE TO THE OWNER ALL OPERATION AND/OR MAINTENANCE MANUALS, OR
INSTRUCTIONS FOR ALL EQUIPMENT AND SYSTEMS AT THE COMPLETION OF THE
PROJECT.
17. DO NOT SCALE DRAWINGS. DIMENSIONS GOVERN. ALL DIMENSIONS ARE FROM
FINISHED FACE OF WALL TO FINISHED FACE OF WALL.
18. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE
REQUIREMENTS REGARDING LOCAL PLAN REVIEW, PERMITS, INSPECTIONS, AND FEES.
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SUBMITTING ALL REQUIRED
DRAWINGS AND SUPPORTING DOCUMENTS TO THE LOCAL BUILDING OFFICIAL
AND/OR PERMIT DEPARTMENT. ALL REQUIRED LOCAL PERMIT FEES SHALL BE PAID BY
THE GENERAL CONTRACTOR UNLESS STIPULATED OTHERWISE IN THE
OWNER/CONTRACTOR AGREEMENT.
19. NOTE REGARDING PROJECTS WITHIN MARION COUNTY: LOCAL ORDINANCE
REQUIRES ONE SET OF CONSTRUCTION DRAWINGS FOR CLASS 1 STRUCTURES, THAT
ARE DESIGNED WITH A FIRE PROTECTION AND LIFE SAFETY SYSTEMS (I.E. FIRE
ALARMS), BE SUBMITTED TO THE INDIANAPOLIS FIRE DEPARTMENT (IFD) FOR THE
PURPOSE OF CONDUCTING A FIRE DEPARTMENT PLAN REVIEW AND ON-SITE
INSPECTIONS. DRAWING SET SHOULD INCLUDE ARCH, STRUCT, MECH, ELEC,
SPRINKLER, FIRE ALARM, AND SITE/CIVIL (WHERE APPLICABLE). DRAWINGS MAY BE
DELIVERED OR MAILED TO THE IFD PLAN REVIEW DIVISION (1200 MADISON AVENUE,
INDIANAPOLIS, IN 46225, ATTENTION: T.J. BURNS). INCLUDE THE DMD STRUCTURAL
PERMIT NUMBER (STR-XXXXXX) WITH THE DRAWING SET. THE GENERAL
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE SUBMISSION OF
THESE DRAWINGS AND THE REQUIRED FEE TO THE IFD PLAN REVIEW DIVISION.
CONTACT THE IFD WITH QUESTIONS REGARDING THIS REQUIREMENT (317-327-5529).
GENERAL PROJECT NOTES DEMOLITION NOTES
1. ALL EXISTING EQUIPMENT, FIXTURES, ETC. SHALL REMAIN PROPERTY OF THE
OWNER. ALL REUSABLE ITEMS SALVAGED DURING DEMOLITION SHALL BE RETAINED
FOR THE OWNER'S INSPECTION. ONLY ITEMS SO INSPECTED AND REJECTED BY THE
OWNER SHALL BE DISPOSED.
2. CONTRACTOR TO VISIT SITE TO BECOME FAMILIAR WITH EXISTING CONDITIONS.
DEMOLITION DRAWINGS ARE A REFERENCE TO AID CONTRACTOR IN EVALUATION OF
THE EXTENT OF THE DEMOLITION, BUT SHALL NOT BE CONSIDERED ALL INCLUSIVE.
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, ETC.
REFERENCE NEW CONSTRUCTION DRAWINGS TO DETERMINE THE FULL EXTENT OF
NECESSARY DEMOLITION.
3. NO STRUCTURAL OR LOAD-BEARING CONSTRUCTION SHALL BE REMOVED,
DEMOLISHED, OR DAMAGED AS A RESULT OF THIS PROJECT UNLESS SPECIFICALLY
NOTED OTHERWISE ON THE DRAWINGS. THE CONTRACTOR SHALL VERIFY IN THE
FIELD, PRIOR TO DEMOLITION, THAT ALL ITEMS NOTED TO BE DEMOLISHED ARE NOT
STRUCTURAL. CONTACT PARALLEL DESIGN GROUP IMMEDIATELY IF THE
CONTRACTOR(S) IN THE FIELD SUSPECT THAT AN ITEM NOTED FOR DEMOLITION
APPEARS TO BE STRUCTURAL OR OTHERWISE LOAD-BEARING. THE CONTRACTOR IS
SOLELY RESPONSIBLE FOR INADVERTENT DAMAGE TO THE BUILDING STRUCTURAL
SYSTEM.
4. EACH TRADE CONTRACTOR IS RESPONSIBLE FOR ALL DEMOLITION WORK REQUIRED
OR NOTED FOR THE INSTALLATION OF THE NEW WORK.
5. EACH TRADE CONTRACTOR IS RESPONSIBLE TO REFER TO NEW CONSTRUCTION
DRAWINGS FOR ADDITIONAL PATCHING AND PREPARATION WORK RELATED TO THE
DEMOLITION ITEMS.
6. WHERE EQUIPMENT, FIXTURES, OR FINISHES ARE MOVED FROM ANY OTHER PART OF
THE BUILDING TO BE REUSED IN THE PROJECT AREA, THE CONTRACTOR SHALL
INCLUDE IN THEIR SCOPE OF WORK ANY NECESSARY PATCHING OR REPAIRING OF THE
REMAINING AREAS FROM WHERE THE ITEMS WERE RELOCATED, UNLESS OTHERWISE
DIRECTED BY OWNER.
7. CHECK EXISTING FLOOR LEVEL BEFORE INSTALLATION OF NEW FLOORING. PREPARE
FLOOR WITH CEMENTITIOUS LEVELING COMPOUND PRIOR TO INSTALLATION OF NEW
FLOOR FINISH AS REQUIRED TO MAINTAIN LEVEL.
8. REMOVE ALL ITEMS ASSOCIATED WITH DEMOLISHED WALL IF NOT NOTED OR
SHOWN OTHERWISE. SALVAGE ANY ITEMS IS GOOD CONDITION FOR REUSE IN NEW
CONSTRUCTION, e.g., OUTLETS.
9. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING
SURFACES, MATERIALS, COMPONENTS, ETC. TO REMAIN OR BE RELOCATED. ANY
DAMAGE TO THESE RESULTING FROM PERFORMANCE OF WORK SHALL BE REPAIRED BY
THE CONTRACTOR TO THE SATISFACTION OF THE OWNER AND PARALLEL DESIGN
GROUP AT NO ADDITIONAL EXPENSE TO THE OWNER.
10. COMPLY WITH ALL APPLICABLE LOCAL, STATE AND FEDERAL CODES AND
REGULATIONS. ALWAYS ABIDE BY THE MOST RESTRICTIVE CODE.
11. THE CONTRACTOR SHALL PROVIDE TEMPORARY DUST PROTECTION AS REQUIRED
BY THE OWNER TO PREVENT CONSTRUCTION DEBRIS AND DUST FROM MIGRATING
OUT OF THE PROJECT AREA. THE OWNER SHALL CONFIRM ALL DUST PREVENTION
MEASURE/LOCATIONS, AND SHALL DETERMINE ANY CHANGES TO THESE MEASURES.
12. REMOVE DUST AND DEBRIS FROM NEWLY EXPOSED SURFACES.
13. CONTRACTOR TO PROVIDE AN "AS-BUILT" SET INDICATING THE LOCATION OF ALL
PERMANENTLY ABANDONED SYSTEMS.
14. GENERAL CONTRACTOR TO PROVIDE RECYCLING COSTS TO THE BUILDING
OWNER/LANDLORD ON ALL ITEMS BEING DEMOLISHED, SUCH AS, METAL STUDS,
DRYWALL, CARPET, CEILING TILES, DOORS,GLASS, AND CABINETRY.
1. POWER AND COMMUNICATION PLAN IS TO SHOW ELECTRICAL, VOICE/DATA
RECEPTACLES AND TV LOCATIONS. ELECTRICAL CONTRACTOR TO FIELD VERIFY
LOAD CAPACITIES AND AVAILABILITY. PARALLEL DESIGN GROUP AND THEIR
ARCHITECT ARE NOT RESPONSIBLE FOR ANY MECHANICAL OR ELECTRICAL
ENGINEERING.
2. REFLECTED CEILING PLAN IS TO SHOW LIGHT FIXTURE, DIFFUSER, AND SWITCH
LOCATIONS ONLY. PARALLEL DESIGN GROUP AND THEIR ARCHITECT ARE NOT
RESPONSIBLE FOR ANY MECHANICAL OR ELECTRICAL ENGINEERING.
3. ELECTRICAL CONTRACTOR RESPONSIBLE FOR RELOCATION AND/OR
ADDITION OF HORN STROBES, FIRE ALARM STATIONS AND EXIST SIGNS AS
REQUIRED BY CODE.
4. VERIFY IF ANY SPECIAL EQUIPMENT WILL REQUIRE ADDITIONAL AIR FLOW.
PROVIDE ADDITIONAL HVAC REQUIREMENTS AFTER APPROVAL FROM TENANT.
REVISE ZONING AS NEEDED.
5. PLUMBING, FIRE SUPPRESSION, AND FIRE ALARM SYSTEMS SHALL BE DESIGNED
AND INSTALLED BY THE RESPECTIVE DESIGN/BUILD CONTRACTORS PER
AGREEMENT WITH THE OWNER. ALL TRADES SHALL DESIGN AND INSTALL THEIR
RESPECTIVE SYSTEMS IN ACCORDANCE WITH ALL APPLICABLE STATE AND LOCAL
BUILDING CODES. COORDINATE WITH THE ARCHITECT IF ADDITIONAL
INFORMATION IS REQUIRED IN ORDER TO DO THE WORK IN THE FIELD. PARALLEL
DESIGN GROUP AND THEIR ARCHITECT ARE NOT RESPONSIBLE FOR ANY
ENGINEERING FOR THESE SYSTEMS.
6. COORDINATE CIRCUITRY REQUIREMENTS FOR FURNITURE SYSTEMS WITH
TENANT, BEFORE RUNNING WIRING TO JUNCTION BOXES.
7. CENTER IN CEILING TILES RECESSED DOWNLIGHTS, SMOKE DETECTORS,
SPRINKLER HEADS, AND EXIT SIGNS, UNLESS OTHERWISE NOTED.
8. REVIEW FIRE DETECTION DEVICE LOCATIONS WITH TENANT PRIOR TO
INSTALLATION.
9. THE DESIGN/BUILD CONTRACTOR SHALL COMPLY WITH THE INDIANA
BUILDING CODE, THE INDIANA FIRE CODE, AND ALL OTHER APPLICABLE LAWS,
CODES, RULES AND REGULATIONS THAT APPLY TO DESIGN AND INSTALLATION
OF FIRE SPRINKLER/FIRE SUPPRESSION SYSTEMS.
MECHANICAL &
ELECTRICAL NOTES
FIRE PROTECTION NOTES
1. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD SERVICES UNDER
THE GENERAL CONTRACT. PROVIDE A COMPLETE, WORKING SYSTEM. PARALLEL
DESIGN GROUP IS NOT RESPONSIBLE FOR THE DESIGN, INSTALLATION, OR
RENOVATION OF THE FIRE SPRINKLER SYSTEM.
2. THE DESIGN/BUILD CONTRACTOR SHALL COMPLY WITH THE INDIANA BUILDING
CODE, THE INDIANA FIRE CODE, AND ALL OTHER APPLICABLE LAWS, CODES, RULES AND
REGULATIONS THAT APPLY TO DESIGN AND INSTALLATION OF FIRE SPRINKLER/FIRE
SUPPRESSION SYSTEMS.
3. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED DRAWINGS,
AND SHALL FILE THOSE DRAWINGS, AND RELATED DOCUMENTS, WITH THE STATE AND
LOCAL AUTHORITIES HAVING JURISDICTION OVER THE PROJECT.
4. PROVIDE NEW OR RELOCATE EXISTING SPRINKLER HEADS AS REQUIRED. PROVIDE
MISSING COVER/ESCUTCHEON PLATES FOR SPRINKLER HEADS WHERE APPLICABLE.
FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF WORK.
5. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND EXISTING FIRE
EXTINGUISHERS ARE INSTALLED ACCORDING TO NFPA 10. COORDINATE WITH
OWNER/LANDLORD ON EXTINGUISHER TYPE AND HOUSING. MAXIMUM TRAVEL
DISTANCE OF 75 FEET FROM ANY POINT TO A VISIBLE EXTINGUISHER.
1. ALL MATERIALS TO BE DELIVERED IN THEIR ORIGINAL PACKAGING WITH
MANUFACTURER'S LABELS. CONTRACTOR WILL BE RESPONSIBLE FOR RECEIVING,
STORING AND PROTECTING MATERIALS FROM ANY DAMAGE BY MOISTURE, WIND,
SUN ABUSE, OR ANY HARMFUL EFFECTS. DAMAGED MATERIALS WILL BE
REJECTED AND MUST BE REPLACED BY THE CONTRACTOR.
2. REMOVE ALL PLATES AND SWITCHES BEFORE PAINTING AND REATTACH
AFTERWARDS.
3. ALL REMAINING PAINT (1 GALLON MINIMUM) TO BE LEFT WITH THE OWNER.
4. WALLCOVERING SHALL BE FROM THE SAME PRODUCTION RUN.
5. DO NOT LOCATE WALLCOVERING SEAMS ON CORNERS. WRAP 6" BEYOND
INSIDE OR OUTSIDE CORNERS AS INDICATED ON THE FINISH PLAN WHERE
CHANGE OF WALLCOVERING LOCATION OCCURS.
6. CONTRACTOR TO REMOVE EXCESS ADHESIVE IMMEDIATELY FROM SURFACE
OR WALLCOVERING AS EACH JOINT OR SEAM IS MADE AND BEFORE PROCEEDING
TO THE NEXT JOINT OR SEAM.
7. ALL WALLCOVERING SEAMS ARE TO BE CUT STRAIGHT. ASSURE INSTALLATION
IS SECURE, SMOOTH, CLEAN, AND WITHOUT WRINKLES, BUBBLES, GAPS, AND/OR
OVERLAPS.
8. FOR ALL NEW DRYWALL INSTALLATIONS, INSTALL AS RECOMMENDED BY THE
GYPSUM ASSOCIATION. (SUCH AS, CONTROL JOINTS, FINISH LEVELS, FASTENERS,
TAPING DETAILS, CORNER BEADS, ETC.)
9. TRANSITION OF DIFFERENT FLOORING MATERIALS SHALL OCCUR AT THE
CENTERLINE OF THE DOOR.
10. CONTRACTOR TO PROVIDE AND INSTALL TRANSITION STRIP BETWEEN
DISSIMILAR FLOORING MATERIALS. TRANSITION STRIP IS TO BE SCHLUTER OR
EQUAL WITH BRUSHED ALUMINUM FINISH OR IS TO BE VINYL AND MATCH VINYL
BASE COLOR (e.g. WHERE VCT MEETS CARPET). CONTRACTOR TO DETERMINE
TYPE OF SCHLUTER STRIP BASED ON DISSIMILAR FLOORING MATERIALS.
CONTRACTOR TO VERIFY TYPE OF TRANSITION WITH PARALLEL DESIGN, IF NOT
NOTED, PRIOR TO PLACING ORDER.
11. SUBFLOOR MUST BE LEVEL, SOUND, RIGID, CLEAN/FREE OF ANY DEBRIS, AND
PERMANENTLY DRY PRIOR TO INSTALLATION. THE INSTALLATION OF FINISH
FLOORING MATERIALS SHALL SERVE AS ACCEPTANCE OF SLAB CONDITION.
12. FLOORING MATERIALS SHALL BE FROM THE SAME PRODUCTION RUN.
13. CONTRACTOR SHALL REPAIR, REFINISH OR TOUCH-UP SURFACES DAMAGED
BY SUBSEQUENT WORK. (EXAMPLE: WHERE NEW OUTLETS/FIXTURES HAVE BEEN
INSTALLED)
14. LOW VOC CONTENT PAINT AND ADHESIVES TO BE USED THROUGHOUT
PROJECT.
15. REVIEW AND ABIDE BY ALL MANUFACTURER INSTALLATION INSTRUCTIONS
PRIOR TO INSTALLATION OF FINISH MATERIALS. MANUFACTURER
RECOMMENDED ADHESIVES/SEALANTS TO BE USED.
16. UPON COMPLETION OF ALL FINISH APPLICATIONS, ALL MATERIALS AND
EQUIPMENT SHALL BE REMOVED. CONTRACTOR SHALL INSURE THAT ALL AREAS
ARE LEFT CLEAN AND DAMAGE FREE.
17. ANY VARIATION IN PATTERN, TEXTURE, COLOR OR ANY OTHER DEFECT
SHOULD BE BROUGHT TO THE ATTENTION OF PARALLEL DESIGN GROUP FOR
DIRECTION AND APPROVAL.
FINISH NOTES
10. PROVIDE NEW OR RELOCATE EXISTING SPRINKLER HEADS AS REQUIRED.
PROVIDE MISSING COVER/ESCUTCHEON PLATES FOR SPRINKLER HEADS WHERE
APPLICABLE. FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE START OF
WORK.
11. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL REQUIRED
DRAWINGS. AND SHALL FILE THOSE DRAWINGS, AND RELATED DOCUMENTS,
WITH THE STATE AND LOCAL AUTHORITIES HAVING JURISDICTION OVER THE
PROJECT.
MECHANICAL &
ELECTRICAL NOTES CONTINUED
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA000
COVER SHEET
A000 COVER SHEET
A001 LIFE SAFETY PLAN
A003 ACCESSIBILITY
D101 DEMOLITION PLAN
A100 WALL TYPES
A101 FLOOR PLAN
A101D DIMENSION PLAN
A110 DOOR SCHEDULES
A120 ENLARGED RESTROOM PLANS
A201 REFLECTED CEILING PLAN
A301 POWER & DATA PLAN
A401 FINISH PLAN
VICINITY MAP KEY PLAN
TOTAL BUILDING AREA:
32,804 SF
PROJECT TYPE:
REMODEL
CONSTRUCTION TYPE:
II-A
TOTAL AREA ON FLOOR:
16,402 SF
11455 NORTH MERIDIAN STREET,
SECOND FLOOR
OCCUPANCY:
(B)USINESS
USABLE AREA:
91 SF
CARMEL, INDIANA 46032
REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
APPLICABLE CODES:
ALL CONSTRUCTION SHALL COMPLY WITH THE FOLLOWING
BUILDING CODE
2014 INDIANA BUILDING CODE (2012 IBC WITH STATE AMENDMENTS)
STRUCTURAL CODE
2012 INDIANA BUILDING (2012 IBC, ASCE-7-2010)
PLUMBING CODE
2012 INDIANA PLUMBING CODE
MECHANICAL CODE
2014 INDIANA MECHANICAL CODE (2012 IMC WITH STATE AMENDMENTS)
ELECTRICAL CODE
2009 INDIANA ELECTRICAL CODE (2008 NEC WITH AMENDMENTS)
FIRE/LIFE SAFETY CODE
2014 INDIANA FIRE CODE (2012 IFC WITH STATE AMENDMENTS)
ACCESSIBILITY CODE
2014 INDIANA BUILDING CODE, CH11-ACCESSIBILITY, ANSI A-117.1 STANDARD, ADA ACCESSIBILITY GUIDELINES -
2009 EDITION
ENERGY CODE
2010 INDIANA ENERGY CONSERVATION CODE (ASHRAE 90.1-2007) WITH INDIANA AMMENDMENTS
GENERAL ADMINISTRATIVE RULES 2ND EDITION.
CODE SUMMARY
GENERAL NOTES
1. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED
PER NEMA AND IBC. EMERGENCY BATTERY PACKS OR LIGHTS
CONNECTED TO AN EMERGENCY POWER SOURCE ARE
REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE.
FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY.
2. PROVIDE ALARM NOTIFICATION APPLIANCES (HORNS/STROBES),
EMERGENCY SPEAKERS, SMOKE DETECTORS, FIRE PULLS, AND
ANY OTHER REQUIRED ALARM & DETECTION SYSTEMS AS
NECESSARY TO MEET ALL APPLICABLE CODES (INTERNATIONAL
BUILDING CODE, INTERNATIONAL FIRE CODE, NFPA).
3. FIRE PROTECTION WORK IS TO BE PROVIDED BY DESIGN/BUILD
SERVICES UNDER THE GENERAL CONTRACT. PROVIDE A
COMPLETE, WORKING SYSTEM. PARALLEL DESIGN GROUP, IS NOT
RESPONSIBLE FOR THE DESIGN, INSTALLATION, OR RENOVATION
OF THE FIRE SPRINKLER SYSTEM.
4. THE FIRE PROTECTION CONTRACTOR SHALL GENERATE ALL
REQUIRED DRAWINGS, AND SHALL FILE THOSE DRAWINGS, AND
RELATED DOCUMENTS, WITH THE STATE AND LOCAL
AUTHORITIES HAVING JURISDICTION OVER THE PROJECT.
5. FIRE EXTINGUISHERS: CONTRACTOR TO ENSURE ALL NEW AND
EXISTING FIRE EXTINGUISHERS ARE INSTALLED ACCORDING TO
NFPA 10. COORDINATE WITH OWNER/LANDLORD ON
EXTINGUISHER TYPE AND HOUSING. MAXIMUM TRAVEL DISTANCE
OF 75 FEET FROM ANY POINT TO A VISIBLE EXTINGUISHER.
6. REFER TO SHEET A100 FOR WALL TYPE AND CONSTRUCTION
DETAILS
7. EXISTING EXIT SIGNS, FIRE PULLS, FIRE EXTINGUISHERS, ALARM
NOTIFICATION APPLIANCES TO REMAIN.
APPLICABLE BUILDING CODES
OCCUPANCY LOADS
EXISTING ELECTRICAL PANEL LOCATION
EXISTING EXIT -BUILDING EXIT LOCATION
EMERGENCY LIGHTING
NIGHT LIGHT/EMERGENCY LIGHTING,
REFERENCE A200 FOR LOCATION.
LEGEND
EX
EL
NL
EP
ASSEMBLY OCCUPANCY REGION(S)
STORAGE AREA REGION(S)
FE
EXIT DOOR
RECESSED FIRE EXTINGUISHER OR
SURFACE OR RECESSED FIRE EXTINGUISHER
AREA NOT IN CONTRACT
AREA OF WORK
COMMON PATH OF EGRESS
EXIT ACCESS TRAVEL DISTANCE
EXIT ACCESS TRAVEL
DISTANCE: 30'
EX
EL
EX
EP [PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA001
LIFE SAFETY PLAN
CHANGE OF OCCUPANCY CLASS:
No
SPRINKLER SYSTEM (YES/NO):
Yes
TOTAL BUILDING SQ FT:
32,804 SF
SCOPE OF WORK:
ADDITION OF COMMON SPACE ADA RESTROOM.
FIRE WALLS, AND/OR OCCUPANCY SEPARATIONS:
No
3/32" = 1'-0"
LIFE SAFETY PLAN1
OCCUPANCY:
(B)USINESS
EXIT TRAVEL DISTANCE (FEET):
300
NUMBER OF REQUIRED EXITS:
1
COMMON TRAVEL PATH OF EGRESS (FEET):
100
USABLE AREA:
91 SF
TOTAL AREA ON FLOOR:
16,402 SF
OCC KEY SPACE TYPE OCC CLASSIFICATION AREA SF PER
OCCUPANT
OCCUPANT
LOAD
(B)USINESS IBC Business areas 91 SF 100 0.9
Total Project Area / Total Project Occupant Load 91 SF 0.9
REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
18"1 1/2" DIAMETER GRAB
BAR, 1 1/2" MIN. GAP
FROM WALL (TYPICAL)
FOLD DOWN
SHOWER SEAT
1 1/2" DIAMETER GRAB
BAR, 1 1/2" MIN. GAP
FROM WALL (TYPICAL)
SOAP SHELF, WHERE
INDICATED
CONTROL AREA
HAND HELD ADJUSTABLE
SHOWER HEAD (ADA)
TRANSFER ADA SHOWER
1' - 6" 1' - 6"3' - 4" 33" - 36"3' - 10"4' - 0 1/4"3' - 1 3/4" MAX32" MIN - 34" MAX19" MIN
MAINTAIN MIN.
ACCESSIBLE
CLEARANCES AS
DIMENSIONED 9" MIN 27" MIN
ACCESSIBILITY ROLL-UNDER CLEARANCES
T-SHAPED TURNING SPACEARMARMBASE
MIN.
1' - 0"
MIN.
3' - 0"
MIN.
1' - 0"MIN.3' - 0"MIN.2' - 0"MIN.
5' - 0"MIN.5' - 0"X > 24"36" MIN.
MANEUVERING CLEARANCE IN AN ALCOVE:
FORWARD APPROACH X > 15"60" MIN.
MANEUVERING CLEARANCE IN AN
ALCOVE: PARALLEL APPROACH
ELEVATION PLAN9"MAX.
6" 30" MIN.17"-25"
TOE CLEARANCE
8" MIN.2' - 4" MIN.9" MIN.MIN.
11"
MAX.
1' - 5"2' - 6" MIN.ELEVATION PLAN
KNEE CLEARANCE
4" MAX.X > 27"X 80"³LIMITS OF PROTRUDING OBJECTS 27" MAX.X > 80"VERTICAL CLEARANCE
15" MIN.48" MAX.UNOBSTRUCTED FORWARD REACH
20" MAX.48" MAX.44" MAX.UNOBSTRUCTED HIGH FORWARD REACH
A. B.32" MIN.36" MIN.32" MIN.36" MIN.24" MAX. 48" MIN. 24" MAX.
CLEAR WIDTH OF AN ACCESSIBLE ROUTE
(A)
180 DEGREE TURN
(B)
180 DEGREE TURN (EXCEPTION)48" MIN.42" MIN. 42" MIN.
X < 48"
36" MIN. 36" MIN.
X < 48"60" MIN.CLEAR WIDTH AT TURN
(C)
FOLDING DOOR
(A)
HINGED DOOR
(B)
SLIDING DOOR
32" MIN. 32" MIN. 32" MIN.90°CLEAR WIDTH OF DOORWAYS
(A)
FRONT APPROACH, PULL SIDE (B)
FRONT APPROACH, PUSH SIDE
(C)
FRONT APPROACH, PUSH SIDE
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
(D)
HINGE APPROACH, PULL SIDE
(E)
HINGE APPROACH, PULL SIDE
(F)
HINGE APPROACH, PUSH SIDE
(G)
HINGE APPROACH, PUSH SIDE,
DOOR PROVIDED WITH BOTH
CLOSER AND LATCH
(H)
LATCH APPROACH, PULL SIDE
(I)
LATCH APPROACH, PULL SIDE,
DOOR PROVIDED WITH CLOSER
(J)
LATCH APPROACH, PUSH SIDE
(K)
LATCH APPROACH, PUSH SIDE,
DOOR PROVIDED WITH CLOSER
18" MIN.48" MIN.12" MIN. 48" MIN.36" MIN. 60" MIN.42" MIN.54" MIN.42" MIN.22" MIN. 48" MIN.22" MIN.48" MIN.24" MIN. 54" MIN.24" MIN 24" MIN. 42" MIN.24" MIN.48" MIN.60" MIN.(A)
PULL SIDE
(B)
PUSH SIDE
(C)
PUSH SIDE, DOOR PROVIDED
WITH BOTH CLOSER AND LATCH60" MIN.18" MIN.X > 8"48" MIN.X > 8"X > 8"12" MIN.48" MIN.MANEUVERING CLEARANCE AT RECESSED DOORS AND GATES
(A) (B)
(C)
48" MIN. 48" MIN.48" MIN.
DOOR IN SERIES AND GATES IN SERIES
(A)
STAIRS
(B)
RAMPS
(C)
WALKING SURFACES34" - 38"34" - 38" 34" - 38"HANDRAIL HEIGHT
1 1/2" MIN.1 1/2" MIN.HANDRAIL CLEARANCE HANDRAIL PROJECTIONS
BELOW GRIPPING SURFACE
NOTE: X = TREAD DEPTH
12" MIN.
12" MIN.
12" MIN.
X
X
TOP AND BOTTOM HANDRAIL
EXTENSION AT RAMPS
TOP HANDRAIL EXTENSION
AT STAIRS
BOTTOM HANDRAIL
EXTENSION AT STAIRS
5" MAX. 15" MIN.
DRINKING FOUNTAIN SPOUT LOCATION
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA003
ACCESSIBILITYREVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
1. REMOVE WALL CONSTRUCTION IN ITS ENTIRETY.
2. PATCH CORE DRILLS/HOLES IN FLOOR AS REQUIRED.
3. REMOVE HVAC DIFFUSERS AND RETURNS AS REQUIRED.
4. EXISTING CEILING GRID AND TILE TO REMAIN.
GENERAL NOTES
LEGEND
NEW CONSTRUCTION
SOLID LINES INDICATE EXISTING ITEMS TO REMAIN.
NOTE: REFERENCE THE COVER SHEET FOR GENERAL
DEMOLITION NOTES.
KEYED NOTES
DASHED LINES AND SYMBOLS INDICATE EXISTING
ITEMS TO BE REMOVED OR SALVAGED. REFERENCE
PLAN NOTES.
PATCH AND PREP WALLS WHERE DEMOLITION
OCCURS ADJACENT AN EXISTING WALL. TERMINATE
PLUMBING AT THE NEAREST LOCATION.
REUSE EXISTING FIXTURES IF IN GOOD CONDITION.
1
2
10' - 3 3/4"
3
2' - 6 5/8"3' - 2"
AREA NOT IN CONTRACT
AREA OF WORK
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORD101
DEMOLITION PLAN
1 EXISTING FINISHES TO REMAIN. PATCH AND REPAIR WHERE NEEDED.
2 SALVAGE EXISTING DOOR FOR REUSE. PATCH AND REPAIR WALLS AS
NEEDED.
3 DEMO FINISHES IN NEW RESTROOM BOUNDARIES.
3/16" = 1'-0"
DEMOLITION PLAN1 REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
A2
A3
WALL PARTITION TYPEPLAN VIEW SECTION VIEW SECTION VIEW
REMARKS
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
A
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
ELIMINATOR TRACK
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
CEILING GRID
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
3 -3/4"
4 -7/8"3 -5/8"
2 -1/2"
STC:
NO SOUND
WITH SOUND
A2S
A3SB2
B3
B6
B1 B1S
WALL PARTITION TYPE 42" FINISHEDPLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
B
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
B2S
B3S
B6S
B8 NON-
RATED NA9 -1/4"8"
B8S
UNDERSIDE OF
STRUCTURE
C2
C3
C6
C1 C1S
WALL PARTITION TYPE 4"PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
C
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, ONE SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL.
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE
OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -1/4"
3 -1/8"
4 -1/4"
6 -5/8"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
C2S
C3S
C6S
C8 NON-
RATED NA8 -5/8" 8"
C8S
LATERAL BRACING AT 4'-0" O.C. MAX.
E2
E3
E6
E1 E1S
WALL PARTITION TYPE PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
E
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, ONE SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL.
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE
OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -1/4"
3 -1/8"
4 -1/4"
6 -5/8"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
E2S
E3S
E6S
E8 NON-
RATED NA 8 -5/8"8"
E8S
D2
D3
D6
D1 D1S
WALL PARTITION TYPE4"PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
NON-
RATED
NON-
RATED
NON-
RATED
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
D
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA
NA
NA
NA
2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
D2S
D3S
D6S
D8 NON-
RATED NA9 -1/4"8"
D8S
LATERAL BRACING AT 4'-0" O.C. MAX.
F2
F3
F6
F1 F1S
WALL PARTITION TYPE PLAN VIEW SECTION VIEWSECTION VIEW
REMARKS
REFER TO SCHEDULE BELOW FOR PARTITION WIDTH
NON-
RATED
F
METAL STUD FRAMING @ 16" O.C. MAX.
ONE LAYER 5/8" (TYPE-X) GYPSUM WALL BOARD, EACH SIDE
PROVIDE SOUND ATTENUATION INSULATION AS REQUIRED -SEE SCHEDULE BELOW
METAL RUNNER
ADDITIONAL WALL FINISH (SHOWN DASHED) ON ONE OR BOTH SIDES WHERE OCCURS;
REFER TO FLOOR PLANS AND ROOM FINISH SCHEDULE FOR OCCURRENCE, LOCATION,
AND EXTENT OF WALL COVERAGE. 5/8" MOISTURE RESISTANT GYPSUM WALL BOARD
REPLACES TYPE-X AS SUBSTRATE IN ALL RESTROOMS AND JANITOR'S CLOSETS,TYPICAL
METAL RUNNER
LINE OF
STRUCTURE
UNDERSIDE OF
STRUCTURE
LINE OF
CEILING
STUD
WIDTH
PART.
WIDTH
FIRE
RATING
UL LISTING
WITH SOUND
ATTENUATION
DESIGNATION
NO SOUND
ATTENUATION
DESIGNATION
NA 2 -7/8"
3 -3/4"
4 -7/8"
7 -1/4"6"
3 -5/8"
2 -1/2"
1 -5/8"
STC:
NO SOUND
WITH SOUND
F2S
F3S
F6S
F8
9 -1/4" 8"
F8S
NON-
RATED NA
NON-
RATED NA
NON-
RATED NA
NON-
RATED NA
WALL TYPES
NOTE:
ALL PLAN DIMENSIONS ARE FROM FACE TO FACE OF FINISHED WALL. NOT
ALL WALL TYPES LISTED ARE NECESSARILY USED ON THIS PROJECT. REFER
TO REFLECTED CEILING PLAN FOR CEILING HEIGHTS.[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA100
WALL TYPESREVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
1. PROVIDE BRACING AND FIRE-TREATED BLOCKING AS REQUIRED IN WALLS
SUPPORTING CASEWORK, RESTROOM ACCESSORIES, EQUIPMENT, OR ANY OTHER
MISC. ITEM REQUIRING ADDITIONAL SUPPORT.
GENERAL NOTES
ALL PLAN DIMENSIONS ARE FROM FACE TO FACE OF FINISHED WALL.
REFRENCE A100 FOR WALL TYPE DESCRIPTION. NOT ALL WALL TYPES
LISTED ARE NECESSARILY USED ON THIS PROJECT. REFER TO REFLECTED
CEILING PLAN FOR CEILING HEIGHTS.
WALL TYPES
KEYNOTES
201200RESTROOM
201
ADA
CORRIDOR
200
A120
1
1
1 1
F3S
F3S
F3S
LEGEND
NEW CONSTRUCTION EXISTING TO REMAIN
X1
DOOR AND
FRAME
(SEE DOOR
SCHEDULE)
NOTE: IF IN GOOD CONDITION, EXISTING DOORS
SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED FOR
NEW DOORS.
DOOR AND
FRAME
WALLWALL
AREA NOT IN CONTRACT
AREA OF WORK
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA101
FLOOR PLAN
1 EXISTING WALL TO GO TO DECK AND MATCH PROPERTIES OF WALL
TYPE F3S.
3/16" = 1'-0"
FLOOR PLAN1 REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
GENERAL NOTES
1. DO NOT SCALE THE DRAWINGS. REFER DISCREPANCIES TO
PARALLEL DESIGN GROUP, INC FOR FINAL DECISIONS.
2. ALL DIMENSIONS SHOWN ARE TO FINISHED FACE OF WALL UNLESS
NOTED OTHERWISE. DIMENSIONS TO EXISTING WALL ARE SHOWN
TO FACE OF EXISTING FINISH. DIMENSIONS DESIGNATED AS "CLR"
OR "CLEAR" INDICATE A CLEAR DIMENSION FROM FACE OF FINISH
TO FACE OF FINISH.
KEYED NOTES
AREA NOT IN CONTRACT
AREA OF WORK
LEGEND
NEW CONSTRUCTION EXISTING TO REMAIN
X1
DOOR AND
FRAME
(SEE DOOR
SCHEDULE)
NOTE: IF IN GOOD CONDITION, EXISTING DOORS
SALVAGED FROM DEMOLITION CAN BE SUBSTITUTED FOR
NEW DOORS.
DOOR AND
FRAME
WALLWALL
7' - 10 7/8" 5' - 7" MIN.4' - 6"1
2' - 6 5/8"
3' - 11 1/2" 12' - 3 1/2"±5' - 10 7/8"4' - 10 7/8" 4' - 8 1/8" MIN.
1' - 0"[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA101D
DIMENSION PLAN
3/16" = 1'-0"
DIMENSION PLAN1
1 ALIGN FINISHED WALL SURFACES. PROVIDE SAME THICKNESS
STUDS AS EXISTING WALL AT DOOR INFILLS OR WHERE NEW
WALLS ARE IN LINE WITH EXISTING WALLS.REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
DOOR HARDWARE
AFB AUTOMATIC FLUSH BOLT
CH COAT HOOK
CR CARD READER BY TENANT (N.I.C.)
CL CLOSER
DB DEADBOLT
DL DUMMY LEVER
ES ELECTRIC STRIKE BY TENANT (N.I.C.)
H HOLD OPEN
KS KICK STOP
KF KEY FOB
KP KICK PLATE
KS KICK STOP
ML MAGNETIC LOCK
OL OFFICE LOCKSET
PH PANIC HARDWARE
PL PRIVACY LOCKSET
PP PUSH/PULL
PS PASSAGE LATCHSET
PV PIVOT HINGE
RL ROLLER LATCHES
SL STOREROOM LOCKSET
TS TOP STRIKES
DOOR FRAME
1. CONTRACTOR TO VERIFY THAT NO HOLES/OPENINGS ARE IN
EXISTING DOOR DUE TO HARDWARE CHANGES. IF HOLES
ARE PRESENT THAT WILL NOT BE FILLED BY NEW HARDWARE,
CONTRACTORS TO CONTACT PARALLEL DESIGN GROUP TO
CONFIRM ON HOW TO MOVE FORWARD.
2. REUSE DOORS FROM DEMOLITION WHERE POSSIBLE.
PROVIDE NEW BUILDING STANDARD DOORS MATCHING
EXISTING VENEER AS REQUIRED. STAIN NEW DOORS TO
MATCH EXISTING. PRE-MACHINE NEW DOORS FOR
CYLINDRICAL LOCKSETS.
3. PROVIDE NEW HARDWARE ON NEW DOORS. REUSE
EXISTING HARDWARE ON EXISTING DOORS WHERE
POSSIBLE. FOR NEW DOOR HARDWARE, PROVIDE BUILDING
STANDARD. PROVIDE A.D.A. ACCESSIBLE LEVER HANDLES ON
NEW LOCK AND LATCHSETS.
4. PROVIDE NEW BUILDING STANDARD FRAMES AS REQUIRED.
REUSE EXISTING FROM DEMOLITION WHERE POSSIBLE.
5. FRAME ALL DOOR ROUGH OPENINGS 4" FROM ADJACENT
WALL CORNERS UNLESS OTHERWISE NOTED ON PLAN.
6. REFER TO TENANT AND LANDLORD FOR KEYING
REQUIREMENTS AND LOCKSETS.
7. TENANT'S SECURITY VENDOR IS RESPONSIBLE FOR THE
SPECIFICATION, PURCHASE, AND INSTALLATION OF ALL
ACCESS CONTROLLED ELECTRONIC AND/OR MAGNETIC
HARDWARE AND ASSOCIATED DEVICES. ALL SPECIFICATIONS
AND INSTALLATIONS MUST COMPLY WITH THE INDIANA
BUILDING CODE, CHAPTER 10, MEANS OF EGRESS.
8. PROVIDE BUTT HINGES ON ALL DOORS AS FOLLOWS:
· 7'-0" HT. TO HAVE 3 HINGES
· GREATER THAN 7'-0" IN HT. TO HAVE 4 HINGES
· FINISH TO MATCH HARDWARE SET
9. PROVIDE 1 SET OF SILENCERS ON ALL DOOR FRAMES UNLESS
OTHERWISE NOTED.
10. PROVIDE WALL STOP (FLOOR STOP WHERE APPLICABLE) AT
EACH DOOR UNLESS OTHERWISE NOTED. PROVIDE WOOD
BLOCKING BEHIND WALL STOP.
11. PROVIDE COAT HOOK ON THE BACK OF ALL RESTROOM AND
OFFICE DOORS UNLESS NOTED OTHERWISE.
DOOR TYPES
FRAME TYPES
F1 F2
D1
2" SEE SCHEDULE 2"
SEE SCHED.
2"SEE SCHEDULESEE SCHED.
1/4" TEMPERED GLASS,
MATCH EXISTING
GLASS TEXTURE
2"
SEE SCHED.
2"
1' - 6"
2" SEE SCHEDULE 2"[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA110
DOOR SCHEDULES
DOOR SCHEDULE
DOOR NUMBER ROOM DOOR FRAME COMMENTSWIDTH x HEIGHT x THICKNESS TYPE MATERIAL FINISH TYPE MATERIAL FINISH HARDWARE SET
200 CORRIDOR 3' - 6" x 7' - 0" x1 3/4" EXISTING EXISTING EXISTING F2 MATCH EXISTING MATCH EXISTING CL, CR, ES, SL HARDWARE TO MATCH EXISTING
201 RESTROOM 3' - 0" x 7' - 0" x1 3/4" D1 WOOD MATCH EXISTING F1 MATCH EXISTING MATCH EXISTING CH, KP, PL
REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
PLUMBING RISER DIAGRAM
TYPICAL WATER CLOSET AND SINK TYPICAL ALL SINGLE LOCATIONS
NOT TO SCALE
MA
I
N
B
LDG
.
W
A
S
T
E
2" W
A
S
T
E
T
O
C.O. 2" V.SINK
MAIN BLDG. VENT
2" VENT TO
W.C.
MA
I
N BLD
G
.
W
A
S
T
E
2" W
A
S
T
E
T
O
C.O.2" V.SINK
MAIN BLDG. VENT
2" VENT TO
24" STD.15" STD.LAVATORY OR VANITY SINK URINALWATER CLOSET BACK WALLWATER CLOSET SIDE WALL
MIN. ACCESSIBLE
KNEE CLEARANCE
ACCESSIBLE SINK
BOWL -6 1/2" DEEP
TOE CLEARANCE
SPACE
TOE CLEARANCE
SPACE
URINAL SCREEN
WHERE OCCURS
TOILET PAPER
MOUNTING AREA
1 1/2" DIA. GRAB
BAR W/ 1 1/2" MIN.
GAP FROM WALL
TOILET PARTITION
WHERE OCCURS
24"1 1/2" MIN.56" MIN. @ WALL-HUNG TOILET
5' - 10"9"6"3' - 4" 1' - 6 1/4"3' - 6" 1' - 0"
3' - 4"
7" - 9"
4' - 11" MIN. @ FLOOR-MOUNTED TOILET
1' - 5" H.C.2' - 10"1' - 0" 2' - 0"
5' - 0" MIN
6"9"1' - 5" MAX H.C.8"
11"2' - 3" 2' - 10" MAX1' - 3" MIN
1' - 6"COORDINATE WITHB.O. MIRRORTOP OF CONTROLCL OF SLOTSANITARY NAPKIN/
TAMPON VENDOR
PAPER TOWEL
DISPENSER/
WASTE
RECEPTACLE TOP OF CNTR SURFACETOP OF UNITSOAP DISPENSER BOTTOM EDGEOF REFLECTIVESURFACEMIRROR RECESSED
PAPER TOWEL
DISPENSER CL OF UNITCLOTHES
HOOK
CHANGING
STATION TOP OF CHANGINGSURFACETOP OF HOOK2' - 10"3' - 4"'42" @4' - 6"2' - 9 1/2"MAXTOILET TISSUE/
SANITARY NAPKIN
DISPOSAL/ SEAT
COVER
DISPENSER 3' - 2"MAX. 4' - 0"MAX. 4' - 0"PAPER TOWEL
DISPENSER TOP OF HANDLE2' - 0"15" MIN. BOTTOM OF UNIT2' - 1"15" MIN. BOTTOM OF UNITTOILET PAPER
DISPENSER
TOILET PAPER
HOLDERMAX. 4' - 0"2' - 6"SANITARY
NAPKIN
DISPOSAL TOP OF UNITMAX. 40"WARM AIR
HAND DRYER COUNTERTOPS1C
1B
1A
2
5
4
3
6
7
8 [PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBA120
ENLARGED
RESTROOM PLANSADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOOR(KEY)_TOILET ACCESSORY SCHEDULE
MARK DESCRIPTION BOD PRODUCT
1A 42" GRAB BAR BOBRICK #B-5806
1B 36" GRAB BAR BOBRICK #B-5806
1C 18" VERTICAL GRAB BAR BOBRICK #B-5806
2 SURFACE MOUNTED TOILET PAPER DISPENSER BOBRICK #B-2888
3 SURFACE MOUNTED WASTE RECEPTACLE/TOWEL DISPENSER BOBRICK #B-3949
4 SURFACE MOUNTED SOAP DISPENSER BOBRICK #B-2111
5 18"x36" MIRROR BOBRICK #B-165
6 PULL FOR ASSISTANCE CORD. INSTALL ON CEILING ADJACENT TO ADA TOILET. TBD
7 ALARM RESET BUTTON. INSTALL ON WALL ADJACENT TO ADA TOILET. TBD
8 INPUT POWER, LIGHT AND BUZZER. INSTALL OUTSIDE AND ABOVE DOOR. TBD
NOTE: FOR CLEARANCE REFRENCE ONLY,
NOT DESIGN INTENT
ALL A.D.A. COMPLIANT CONSTRUCTION, FIXTURE MOUNTINGS
, AND ACCESSORY MOUNTINGS MUST COMPLY WITH INDIANA
ACCESSIBILITY REGULATIONS (INDIANA BUILDING CODE (IBC),
CHAPTER 11: ACCESSIBILITY; 675 IAC 13-2-4).
TOILET ROOM-TYPICAL ELEVATIONS
1/2" = 1'-0"
ENLARGED PLAN -ADA RESTROOM1 REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
OSEX
LEGEND
INDICATES NIGHT LIGHT LOCATION
EXIT LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE
LIGHT SWITCH
LIGHT SWITCH, 3-WAY
OCCUPANCY SENSOR
3
O/C
EL
1. REUSE EXISTING CEILING GRID UNLESS OTHERWISE NOTED. EXISTING GRID IS 2' x
4' AT 8'-10" A.F.F. REPAIR ANY DAMAGED GRID AND PAINT GRID WHITE AS
REQUIRED.
2. REUSE EXISTING CEILING TILE UNLESS OTHERWISE NOTED. REPLACE ALL
DAMAGED OR DIRTY CEILING TILES WITH NEW TO MATCH EXISTING. PROVIDE
LIKE TILES IN INDIVIDUAL ROOMS TO CREATE UNIFORM LOOK.
3. WHERE MULTIPLE SWITCHES ARE SHOWN, PROVIDE (1) GANG BOX WITH A SINGLE
COVERPLATE.
4. PROVIDE EMERGENCY LIGHTING IN TENANT SPACE AS REQUIRED PER NEMA AND
IBC. EMERGENCY BATTERY PACKS OR LIGHTS CONNECTED TO AN EMERGENCY
POWER SOURCE ARE REQUIRED IF THE SPACE CONTAINS 50 PERSONS OR MORE.
FIXTURES SHOWN ON PLAN ARE FOR REFERENCE ONLY.
5. LIGHTING PLACEMENT AND QUANTITIES ARE FOR REFERENCE ONLY AND ARE TO
BE PROVIDED BY LIGHTING CONSULTANT AND ELECTRICIAN. ELECTRICAL
CONTRACTOR IS RESPONSIBLE FOR VERIFYING THAT LAY-OUT AND TOTAL
WATTAGE MEETS ASHRAE 90.1 STANDARDS AND LIGHT LEVELS ARE APPROPRIATE
FOR THE USE OF EACH SPACE. OVER 50% OF THE LIGHTING WILL BE REPLACED
WITH NEW, SO ASHRAE WATTAGE REQUIREMENTS WILL NEED TO BE MET.
6. UNLESS NOTED OTHERWISE ALL NEW SWITCHES MUST BE AN OCCUPANCY
SENSOR COMBO UNIT WITH BOTH ULTRASONIC AND INFRARED TECHNOLOGY
WITH A ONE BUTTON OVERRIDE. OCCUPANCY SENSORS ARE TO BE LOCATED
SUCH THAT OCCUPANCY WITHIN ANY PORTION OF INCLUDED AREA IS DETECTED.
PROVIDE CEILING MOUNTED OCCUPANCY SENSORS IN OPEN AREAS AS
REQUIRED.
7. CAN LIGHT FIXTURES TO BE ON SEPERATE SWITCH.
8. ALL DEVICES AND COVERS TO MATCH EXISTING.
9. IF IN GOOD CONDITION, EXISTING H.V.A.C. DEVICES SALVAGED FROM
DEMOLITION CAN BE SUBSTITUTED FOR NEW. NO NEW HVAC DUCTWORK IS TO
BE INSTALLED PER THIS SHEET.
GENERAL NOTES
2'x2', LED,
BUILDING STANDARD
N
DIFFUSER, LAY-IN, 2'x2'
DIFFUSER, LAY-IN, 1'x4'
DIFFUSER, LAY-IN, 4"X4'
CEILING TYPE
CEILING HEIGHT
ACT1 -2' x 4' ACOUSTICAL CEILING TILE
MFG: EXISTING
TYPE: EXISTING
EDGE TYPE: EXISTING
GRID: 15/16"
NRC RATING: 0.55
FIRE RATING: CLASS A
EXISTING CEILING GRID,
SUSPENDED, 2'x4'
X
X' -X"
KEYNOTES
RECESSED CAN,
MATCH EXISTING
C1
EXHAUST FAN
1
EX C1
22
3
AREA NOT IN CONTRACT
AREA OF WORK
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA201
REFLECTED
CEILING PLAN
1 RECIRCUIT EXISTING LIGHTING. TO BE CONTROLLED WITH NEW
SWITCH AT THIS LOCATION.
2 TIE LIGHTS INTO EXISTING COMMON AREA SWITCH.
3 EXHAUST FAN TIED INTO OCCUPANCY SENSOR SWITCH.
3/16" = 1'-0"
REFLECTED CEILING PLAN1 REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
J
GFI
+44
1. ALL OUTLETS, COVERS, SWITCHES, AND SWITCHPLATE COVERS TO
BE BUILDING STANDARD.
2. ALL ELECTRICAL OUTLETS WITHIN 6'-0" OF WATER ARE TO BE GFI.
3. ALL OUTLETS ARE TO BE INSTALLED 18" MIN. AFF TO THE CENTER OF
THE DEVICE PER ADA GUIDELINES UNLESS NOTED OTHERWISE.
4. REFER TO DOOR SCHEDULE AND COORDINATE WITH
TENANT/OWNER REGARDING JUNCTION BOX LOCATIONS TO
ACCOMMODATE ELECTRIC STRIKES AND CARD READERS. ELECTRIC
STRIKES AND CARD READERS ARE TYPICALLY INSTALLED BY THE
TENANT'S SECURITY CONTRACTOR AND ARE TYPICALLY NOT
SPECIFIED BY PARALLEL DESIGN GROUP.
GENERAL NOTES
LEGEND
POWER OUTLET, DUPLEX
POWER OUTLET, QUADRUPLEX
JUNCTION BOX
CEILING MOUNTED JUNCTION BOX
DATA/COMMUNICATION OUTLET (PROVIDE
BOX AND PULL STRING ONLY)
BOX, BLANK COVER PLATE
BOX, OPEN
P POWER AND DATA POLE
FLOOR BOX WITH JUNCTION BOX AND
DATA, FLUSH MOUNTED
FLOOR BOX WITH POWER AND DATA,
FLUSH MOUNTED
EXISTING TO REMAIN
DEDICATED CIRCUIT
GROUND FAULT CIRCUIT INTERRUPT OUTLET
HEIGHT OF ELECTRICAL OR DATA DEVICE
E
DED
GFI
+44"
B
O
J
DATA
JB
HD
CEILING MOUNTED POWER & HDMIHD
HD FLOOR BOX WITH POWER, DATA, & HDMI
FLUSH MOUNTED
SPECIAL PLUG
HDMI
RANGE PLUGR
KEYNOTES
RESTROOM
201
ADA
CORRIDOR
200
1
AREA NOT IN CONTRACT
AREA OF WORK
[PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA301
POWER & DATA
PLAN
3/16" = 1'-0"
POWER & DATA PLAN1
1 CONFIRM POWER REQUIREMENTS FOR ADA EMERGENCY PULL
CORD WITH TENANT AND ELECTRICIAN.REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21
T1
X
ETR
RESTROOM
201
T1
PT1
TB1
CORRIDOR
200
ETR
MATCH EX.
MATCH
EX.
1
1
1
FINISH SPECIFICATIONS
T1 MFG: TBD
SIZE: TBD
PATTERN: TBD
COLOR: TBD
FLOOR TILE
MFG: TARKETT
TYPE: 4" ROLL STOCK VINYL WALL BASE
COLOR: MATCH EXISTING
WALL BASE
VB1
MFG: SHERWIN WILLIAMS
COLOR: TBD
FINISH: EPOXY
PAINT
PT1
FINISHES SHALL MEET ALL CLASS A FIRE RATINGS & COMPLY WITH
CHAPTER 8 OF INTERNATIONAL BUILDING CODE
MFG: TBD
TYPE: 6" TILE BASE
COLOR: TBD
TILE BASE
TB1
FINISH PLAN TAG
1. ALL AREAS RECEIVING PAINT ARE TO RECEIVE A THREE-COAT
SYSTEM, PRIMER COAT AND TWO (2) FINISH COATS.
2. THE FINISHES AT TIME OF THE ISSUE DATE HAVE BEEN CHECKED
AND ARE AVAILABLE UNLESS OTHERWISE NOTED.
WALLCOVERING, CARPET, CERAMIC TILE AND SPECIALTY ITEMS
CAN BE UP TO 6-8WEEK LEAD TIME.
PARALLEL DESIGN GROUP STRONGLY RECOMMENDS ORDERING
FINISHES IMMEDIATELY TO ENSURE TIMELY DELIVERY FOR AN ON-
TIME INSTALLATION.
3. ALL FINISHES AND SPECIFICATIONS ARE TO BE SUBMITTED TO
PARALLEL DESIGN GROUP FOR FINAL APPROVAL PRIOR TO
ORDERING FINISH MATERIALS.
4. ALL FINISHES SHALL MEET ALL CLASS A FIRE RATINGS AND COMPLY
WITH CHAPTER 8 OF INTERNATIONAL BUILDING CODE.
5. FINISH SPECIFICATIONS CORRESPOND WITH THE FINISH PLAN ON
THIS SHEET ONLY. DO NOT CROSS REFERENCE OTHER PLANS.
6. ALL FINISHES TO COMPLY WITH APPLICABLE CODES.
7. PT1 AND VB1 TO BE USED THROUGHOUT UNLESS OTHERWISE
NOTED.
8. REPRESENTS DIRECTION OF FLOORING
9. FINISH SPECIFICATIONS CORRESPOND WITH THE FINISH PLAN ON
THIS SHEET ONLY. DO NOT CROSS REFERENCE OTHER FLOORS
FOR.
10. IF UNDERCABINET LAMINATE BASE CONTAINS A GAP(S) GREATER
THAN OR EQUAL TO 1/8" BETWEEN FINISH FLOOR, CONTRACTOR
TO ALSO INSTALL SHOE MOLDING.
11. PAINTED SHEEN LEVEL TO BE AS LISTED BELOW, U.N.O.:
EGG-SHELL TO BE APPLIED TO ALL WALLS.
PAINTED DOORS AND FRAMES TO BE SEMI-GLOSS.
WET AREA WALLS TO BE EPOXY. (ALL RESTROOM WALLS).
ALL CEILINGS TO BE FLAT, U.N.O.
ALL EXPOSED DECK LOCATIONS TO BE DRYFALL.
GENERAL NOTES
KEYNOTES
ROOM NAME
ROOM NUMBER
FLOOR BASE
WALL
3/16" = 1'-0"
FINISH PLAN1 [PROJECT NUMBER][DATE][DRAWN BY][CHECKED BY]ALL DESIGNS, CONCEPTS, ARRANGEMENTS AND PLANS
INDICATED OR REPRESENTED BY THESE DRAWINGS ARE
OWNED BY PARALLEL DESIGN GROUP, INC. AND SHALL NOT BE
USED BY OR DISCLOSED TO ANY PERSON, FIRM OR CORP. FOR
ANY REASON WHATSOEVER WITHOUT THE WRITTEN CONSENT
OF PARALLEL DESIGN GROUP INC.
CONTRACTORS SHALL VERIFY AND BE RESPONSIBLE FOR ALL
DIMENSIONS ON THE JOB SITE. PARALLEL DESIGN GROUP INC.
MUST BE NOTIFIED OF ANY DISCREPANCIES OR VARIATIONS
FROM THE DIMENSIONS SHOWN ON THE PLAN.
N [ P ][ W ]Indianapolis, IN 46240ParallelDG.com317.721.4399 8940 River Crossing Blvd. Ste 1502020.27701.18.21BWKBADA RESTROOMCARMEL, INDIANA 4603211455 NORTH MERIDIAN STREET, SECOND FLOORA401
FINISH PLAN
1 PAINT WALLS AND ADD BASE TO MATCH EXISTING (NEW WALLS
ONLY).REVISION SCHEDULEMARK DATE DESCRIPTION05/04/21