HomeMy WebLinkAbout45_M6016GTOKPCN1WVNGVU Mark Function Price Model Airflow Range (CFM) Face Size (in.) Neck Size (in.)Color Remarks PD-1 Plaque Diffuser SPD 50-180 24 x 24 6Ø By Architect 1,2,3 PD-2 Plaque Diffuser SPD 181-300 24 x 24 8Ø By Architect 1,2,3 PDF-1 Perforated Plaque Diffuser SPD 50-180 24 x 24 6Ø By Architect 1,2,3 PDF-2 Perforated Plaque Diffuser SPD 181-300 24 x 24 8Ø By Architect 1,2,3 SDG-1 Spiral Duct Grille SDGE 50-175 10 x 4 N/A By Architect 4 SDG-2 Spiral Duct Grille SDGE 175-300 12 x 6 N/A By Architect 4 SR-4 Supply Register 520L 351-670 23 34 x 13 34 18x10 By Architect 1,2,3 ER-2 Exhaust Register 530 101-200 9 34 x 9 34 8 x8 By Architect 1,2,3 ER-3 Exhaust Register 530 201-500 27 34 x 27 34 26 x 26 By Architect 1,2,3 RG-1 Return Grille 535 0-4000 50 x 32 48 x 30 By Architect 1,2,3 RG-2 Return Grille 535 50 x 38 48 x 36 By Architect 1,2,3 ECR-1 Eggcrate Return 80 501-1500 24 x 12 22 x 10 By Architect 1,2,3 ECR-2 Eggcrate Return 80 1501-2000 24 x 24 22 x 22 By Architect 1,2,3 RD-1 Round Diffuser RCDA 400-500 27"Ø 12"Ø By Architect 1,2,3 RD-2 Round Diffuser RCDA 501-700 31.5"Ø 14"Ø By Architect 1,2,3 RD-3 Round Diffuser RCDA 1000-1100 40.5"Ø 18"Ø By Architect 1,2,3 RD-4 Round Diffuser RCDA 1200-1300 45"Ø 20"Ø By Architect 1,2,3 RD-5 Round Diffuser RCDA 1500-1600 54"Ø 24"Ø By Architect 1,2,3 Notes: 1. Provide factory extended panel for any diffuser which is smaller than the grid in which it is installed. 2. Sound baffle by Sheet Metal Contractor. 3. Provide plaster frame for diffusers, registers and grilles installed in gypsum board. 4. Provide optional air scoop. 'NGEVTKE9CNN*GCVGT5EJGFWNG Mark Area Served Model Type Electrical Connection Disconnect Remarks Power (Watts)Voltage (V)Phase (Ø) MCA (A) EWH-1 Varies Raywall 3310 Series Wall Heater 1500 120 1 12.5 MFR See Notes EWH-2 Vestibule B Raywall 3310 Series Wall Heater 3000 208 1 14.4 MFR See Notes Notes: 1. Fan forced heater. 2. Integral T-Stat. 3. Recessed in wall. Acceptable Manufacturers: 1. Raywall 2. Qmark 3. Markell )TCXKV[4QQH8GPVKNCVQTU5EJGFWNG Mark Greenheck Model Discharge Static Pressure (in. w.g.) Weight (lbs)Remarks FGI-1 FGI - 36x48 Intake 0.1 180 See Notes GRSR-1 GRSR-8 Relief 0.08 13 See Notes Notes: 1. Install on curb provided by Fan MFR. Provide tapered curb. 2. Gravity back draft damper by Fan MFR. 3. Provide Bird screen. Acceptable Manufacturers: 1. Greenheck 2. Loren Cook 3. PennBarry 4. Twin City 'ZJCWUV(CP5EJGFWNG Mark Area Served Greenheck Model Airflow (CFM) Static Pressure (in. w.g.) Electrical Connection Weight (lbs)Remarks Voltage (V) Phase (Ø) Input (HP) EF-1 Various G-095 300 0.4 120 1 1 / 8 33 1,2,3,4 EF-2 Various SP-B110 70 0.4 120 1 0.1 10 1,2,3,4 EF-3 Compressor/ Storage GB-220 4400 0.2 208 3 1.5 124 1,2,3,5 EF-4 Mech/Utility - 205 GB-220 3600 0.2 208 3 1.5 124 1,2,3,5 Notes: 1. Install fan on curb provided by Fan MFR. 2. Gravity back draft damper by Fan MFR. 3. Direct drive with solid state speed controller. 4. Fan shall operate from switch. See electrical plans for more information. 5. Fan shall operate from T-sensor in space. See sequence of operations and plans for more information. Acceptable Manufacturers: 1. Greenheck 2. Loren Cook 3. PennBarry 4. Twin City &WEVNGUU5RNKV*GCV2WOR Mark Area Served Manufacturer Indoor Model Outdoor Model Cooling Capacity (BTU/hr) Heating Capacity (BTU/hr) Nominal Tons Airflow (CFM)SEER Electrical Connection Disconnect RemarksVoltage (V) Phase (Ø)MCA (Amps) MOCP (Amps) Indoor Unit Outdoor Unit FCU-203 & 204 DSHP-203 & 204 Various Bryant 40MBCQ09 38MAQ 9000 10000 3 / 4 320 20 208 1 9 15 MFR See Notes FCU-202 DHHP-202 Pricing Coordinator - 202 Bryant 40MBCQ12 38MAQ 12000 12000 1 400 19.5 208 1 18 25 MFR See Notes Notes: 1. Provide flooded drain pan interlock. 2. Line voltage to outdoor unit. 3. Provide locking disconnect. 4. Follow manufacturers instructions on installation. Use Caddy Pyramid ST series strut base thermoplastic supports or similar for HP supports. Acceptable Manufacturers: 1. Bryant 2. Daikin 3. Trane 4. Johnson Controls Acceptable Manufacturers: 1. Price 2. Titus 3. Metal Aire 0QVG 6JGOGEJCPKECNEQPVTCEVQTKUVQRTGRCTGCPFTGSWKTGFVQRTQXKFG /GEJCPKECN5WDOKVVCNURTKQTVQQTFGTKPICP[OGEJCPKECN GSWKROGPV6JGOGEJCPKECNUWDOKVVCNUCTGUWDLGEVVQOGEJCPKECN FGUKIPGTžUTGXKGY+VKUVQKPENWFGJKIJNKIJVGFOQFGNPWODGTU 5GSWGPEGQH1RGTCVKQPU EF-3 and 4 One of the Exhaust fans shall be energized when the Temp in space goes above 85 Deg F (ADJ.) and shall run till the space temp is 72 Deg F (ADJ.) The second Exhaust fan shall energize when the Temperature in space reaches 90 Deg F (ADJ.) and shall run until space Temp is 72 Deg F(ADJ.). See plans for location of T-stat. Provide necessary controls to open intake damper when one (or both) fan(s) are energized. DSFCU-# This unit will operate from integral thermostat. .QWXGTÄ+PVCMG Mark Space Served Greenheck Model Air Volume (CFM) Static Pressure (in w.c.) Size Type Remarks LVR-1 Mech/Utility (206)EDJ-401 7200 .055 72x48 Wall See Notes Notes: 1. Color selected by architect. 2. Provide bird screen. 3. Provide motorized damper to open when EF in room is energized. 4. Maintain at least 10'-0" between intakes and exhausts and all other flues or vents. Acceptable Manufacturers: 1. Greenheck 2. Ruskin 6 PROF E SS IONAL E N G NI EERSA M U E L L.HU R T INDIA N A 0 N EP1 6 .o 01087 ATS FOETRETEGISDER Exp. 7.31.2022 PROJECT NUMBER: 2020-007 CERTIFICATION:SITE ARCHITECTUREarchitecture + landscape architectureARCHITECT: SITE ARCHITECTURE architecture + landscape architecture BRAD SMITH, RA | LEED AP 13144 EAST 186TH STREET NOBLESVILLE, IN. 46060 PH: 317.374.8720 E-MAIL: brad@site-architecture.com PROJECT CONTACT: These drawings are intended for construction. 12.23.2020DATE ISSUED: REVISIONS ISSUED:CARMEL, IN 46033NEEDLER'S FRESH MARKET4755 EAST 126TH STREETTENANT FINISH IMPROVEMENTSTHE ENGINEERING COLLABORATIVE SAM HURT, P.E. 2410 EXECUTIVE DRIVE, SUITE 100 INDIANAPOLIS, IN. 46241 PH: 317.636.3941 E-MAIL: sam@tec-mep.com PROJECT CONTACT: MEP ENGINEER: CONSTRUCTION ISSUE SET #6 - 3.5.2021 M601 HVAC SCHEDULES 05/06/21