Mark Function Price
Model
Airflow
Range
(CFM)
Face Size
(in.)
Neck Size
(in.)Color Remarks
PD-1 Plaque Diffuser SPD 50-180 24 x 24 6Ø By Architect 1,2,3
PD-2 Plaque Diffuser SPD 181-300 24 x 24 8Ø By Architect 1,2,3
PDF-1 Perforated Plaque
Diffuser SPD 50-180 24 x 24 6Ø By Architect 1,2,3
PDF-2 Perforated Plaque
Diffuser SPD 181-300 24 x 24 8Ø By Architect 1,2,3
SDG-1 Spiral Duct Grille SDGE 50-175 10 x 4 N/A By Architect 4
SDG-2 Spiral Duct Grille SDGE 175-300 12 x 6 N/A By Architect 4
SR-4 Supply Register 520L 351-670 23 34 x 13 34 18x10 By Architect 1,2,3
ER-2 Exhaust Register 530 101-200 9 34 x 9 34 8 x8 By Architect 1,2,3
ER-3 Exhaust Register 530 201-500 27 34 x 27 34 26 x 26 By Architect 1,2,3
RG-1 Return Grille 535 0-4000 50 x 32 48 x 30 By Architect 1,2,3
RG-2 Return Grille 535 50 x 38 48 x 36 By Architect 1,2,3
ECR-1 Eggcrate Return 80 501-1500 24 x 12 22 x 10 By Architect 1,2,3
ECR-2 Eggcrate Return 80 1501-2000 24 x 24 22 x 22 By Architect 1,2,3
RD-1 Round Diffuser RCDA 400-500 27"Ø 12"Ø By Architect 1,2,3
RD-2 Round Diffuser RCDA 501-700 31.5"Ø 14"Ø By Architect 1,2,3
RD-3 Round Diffuser RCDA 1000-1100 40.5"Ø 18"Ø By Architect 1,2,3
RD-4 Round Diffuser RCDA 1200-1300 45"Ø 20"Ø By Architect 1,2,3
RD-5 Round Diffuser RCDA 1500-1600 54"Ø 24"Ø By Architect 1,2,3
Notes:
1. Provide factory extended panel for any diffuser which is smaller than the grid in which it is installed.
2. Sound baffle by Sheet Metal Contractor.
3. Provide plaster frame for diffusers, registers and grilles installed in gypsum board.
4. Provide optional air scoop.
'NGEVTKE9CNN*GCVGT5EJGFWNG
Mark Area
Served Model Type
Electrical Connection
Disconnect Remarks
Power (Watts)Voltage
(V)Phase (Ø) MCA (A)
EWH-1 Varies Raywall
3310 Series Wall Heater 1500 120 1 12.5 MFR See Notes
EWH-2 Vestibule B Raywall 3310
Series Wall Heater 3000 208 1 14.4 MFR See Notes
Notes:
1. Fan forced heater.
2. Integral T-Stat.
3. Recessed in wall.
Acceptable Manufacturers:
1. Raywall
2. Qmark
3. Markell
)TCXKV[4QQH8GPVKNCVQTU5EJGFWNG
Mark Greenheck
Model Discharge
Static
Pressure (in.
w.g.)
Weight
(lbs)Remarks
FGI-1 FGI - 36x48 Intake 0.1 180 See Notes
GRSR-1 GRSR-8 Relief 0.08 13 See Notes
Notes:
1. Install on curb provided by Fan MFR. Provide tapered curb.
2. Gravity back draft damper by Fan MFR.
3. Provide Bird screen.
Acceptable
Manufacturers:
1. Greenheck
2. Loren Cook
3. PennBarry
4. Twin City
'ZJCWUV(CP5EJGFWNG
Mark Area
Served
Greenheck
Model
Airflow
(CFM)
Static Pressure
(in. w.g.)
Electrical
Connection Weight
(lbs)Remarks
Voltage
(V)
Phase
(Ø)
Input
(HP)
EF-1 Various G-095 300 0.4 120 1 1 / 8 33 1,2,3,4
EF-2 Various SP-B110 70 0.4 120 1 0.1 10 1,2,3,4
EF-3 Compressor/
Storage GB-220 4400 0.2 208 3 1.5 124 1,2,3,5
EF-4 Mech/Utility -
205 GB-220 3600 0.2 208 3 1.5 124 1,2,3,5
Notes:
1. Install fan on curb provided by Fan MFR.
2. Gravity back draft damper by Fan MFR.
3. Direct drive with solid state speed controller.
4. Fan shall operate from switch. See electrical plans for more information.
5. Fan shall operate from T-sensor in space. See sequence of operations and
plans for more information.
Acceptable Manufacturers:
1. Greenheck
2. Loren Cook
3. PennBarry
4. Twin City
&WEVNGUU5RNKV*GCV2WOR
Mark
Area Served Manufacturer Indoor
Model
Outdoor
Model
Cooling
Capacity
(BTU/hr)
Heating
Capacity
(BTU/hr)
Nominal
Tons
Airflow
(CFM)SEER
Electrical Connection
Disconnect RemarksVoltage (V) Phase (Ø)MCA
(Amps)
MOCP
(Amps)
Indoor Unit Outdoor
Unit
FCU-203 &
204
DSHP-203
& 204 Various Bryant 40MBCQ09 38MAQ 9000 10000 3 / 4 320 20 208 1 9 15 MFR See Notes
FCU-202 DHHP-202 Pricing
Coordinator - 202 Bryant 40MBCQ12 38MAQ 12000 12000 1 400 19.5 208 1 18 25 MFR See Notes
Notes:
1. Provide flooded drain pan interlock.
2. Line voltage to outdoor unit.
3. Provide locking disconnect.
4. Follow manufacturers instructions on installation. Use Caddy Pyramid ST series strut base thermoplastic supports or similar for HP supports.
Acceptable Manufacturers:
1. Bryant
2. Daikin
3. Trane
4. Johnson Controls
Acceptable Manufacturers:
1. Price
2. Titus
3. Metal Aire
0QVG
6JGOGEJCPKECNEQPVTCEVQTKUVQRTGRCTGCPFTGSWKTGFVQRTQXKFG
/GEJCPKECN5WDOKVVCNURTKQTVQQTFGTKPICP[OGEJCPKECN
GSWKROGPV6JGOGEJCPKECNUWDOKVVCNUCTGUWDLGEVVQOGEJCPKECN
FGUKIPGTUTGXKGY+VKUVQKPENWFGJKIJNKIJVGFOQFGNPWODGTU
5GSWGPEGQH1RGTCVKQPU
EF-3 and 4
One of the Exhaust fans shall be energized when the Temp in space goes above 85 Deg F (ADJ.) and shall run till
the space temp is 72 Deg F (ADJ.) The second Exhaust fan shall energize when the Temperature in space
reaches 90 Deg F (ADJ.) and shall run until space Temp is 72 Deg F(ADJ.). See plans for location of T-stat.
Provide necessary controls to open intake damper when one (or both) fan(s) are energized.
DSFCU-#
This unit will operate from integral thermostat.
.QWXGTÄ+PVCMG
Mark Space
Served
Greenheck
Model
Air
Volume
(CFM)
Static
Pressure
(in w.c.)
Size Type Remarks
LVR-1 Mech/Utility
(206)EDJ-401 7200 .055 72x48 Wall See Notes
Notes:
1. Color selected by architect.
2. Provide bird screen.
3. Provide motorized damper to open when EF in room is
energized.
4. Maintain at least 10'-0" between intakes and exhausts and all
other flues or vents.
Acceptable Manufacturers:
1. Greenheck
2. Ruskin
6
PROF
E
SS
IONAL E N G NI EERSA M U E L L.HU
R
T
INDIA N A
0
N
EP1 6
.o
01087
ATS FOETRETEGISDER
Exp. 7.31.2022
PROJECT NUMBER: 2020-007
CERTIFICATION:SITE ARCHITECTUREarchitecture + landscape architectureARCHITECT:
SITE ARCHITECTURE
architecture + landscape architecture
BRAD SMITH, RA | LEED AP
13144 EAST 186TH STREET
NOBLESVILLE, IN. 46060
PH: 317.374.8720
E-MAIL: brad@site-architecture.com
PROJECT CONTACT:
These drawings are intended for construction.
12.23.2020DATE ISSUED:
REVISIONS ISSUED:CARMEL, IN 46033NEEDLER'S FRESH MARKET4755 EAST 126TH STREETTENANT FINISH IMPROVEMENTSTHE ENGINEERING
COLLABORATIVE
SAM HURT, P.E.
2410 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, IN. 46241
PH: 317.636.3941
E-MAIL: sam@tec-mep.com
PROJECT CONTACT:
MEP ENGINEER:
CONSTRUCTION ISSUE SET
#6 - 3.5.2021
M601
HVAC SCHEDULES