HomeMy WebLinkAbout52_P10727 28 30 31 32 33 35 36 37 39 40 41 42 43
WH-1
WH-2 2
2
1
FCU-202
1
1
2"Cond down along
wall. Route to
discharge floor drain.
FCU-203
6
STAIR A
STA-2
PRICING
COORDINATOR
202
CORRIDOR
201
203
OFFICE
204
MECH/
UTILITY
205
NETWORK/
TELCO
WATER
HEATER
204A
WH-1 2
3 FD-1
FCU-204
A. All fittings, piping, fixtures, materials, etc. to meet the
current Safe Drinking Water Act with all of its
amendments and the Reduction of Lead in Drinking
water Act.
B. All work shall comply with all national, state, local codes
and ordinances pertaining to the work in this project.
C. All plumbing fixtures shall be supplied with individual
water supply stops and code approved traps. Exposed
piping shall be chrome plated.
D. All plumbing fixtures shall be installed with approved
backflow prevention devices.
E. No piping shall pass directly over electrical power
distribution cabinets, panelboards, etc. Contractor to
coordinate panel locations prior to piping installation.
F. All plumbing vents to be a minimum of 10'-0" from any air
intake. Coordinate locations with HVAC plans.
G. Single runouts to plumbing fixtures shall be the same
size as on the plumbing fixture schedule unless
otherwise noted.
H. Concealed gas piping shall be constructed in accordance
with code without unions, tubing fittings or running
threads.
I. Gas lines run on roof to be supported by Roof Top Blox
or similar and equal. DO NOT USE LUMBER FOR GAS
PIPING SUPPORT.
J. Dry-pipe fire protection system shall be used in all areas
subject to freezing.
K. All waste, water, vent, gas and condensate lines shown
to be connected to their associated fixture/equipment,
unless noted otherwise. All equipment and systems
shown must be complete and usable upon completion of
project.
)GPGTCN0QVGU
Hot water recovery tank to be connected to refrigeration
compressor system by others. Provide aquastat
controlled 3-way valve to prevent overheating water.
Coordinate refrigeration connection with Refrigeration
Contractor prior to start of work.
Connect new water heater and heat recovery tanks and
all associated accessories to existing piping serving
removed water heaters. Field verify exact size, location,
material and condition of existing water lines; prior to
installation.
Connect new 2"W to nearest active waste line of equal or
larger size. Field verify exact size, location, elevation,
material and condition of existing waste line; prior to start
of work.
2NCP0QVGU
1
2
3
6
P
R
O
F
E
S
S
I
O
N
A
L
E
N
G
N
I
E
E
R
S
A
M
U
E
L
L.
H
U
R
T
I
N
D
I
A
N
A
0
N
P E 1 6
o .
10 0 87
S T A T E O F
R
E
T
E
G
I
S
D
E
R
Exp. 7.31.2022
PROJECT NUMBER: 2020-007
CERTIFICATION:
SITE ARCHITECTURE
architecture + landscape architecture
ARCHITECT:
SITE ARCHITECTURE
architecture + landscape architecture
BRAD SMITH, RA | LEED AP
13144 EAST 186TH STREET
NOBLESVILLE, IN. 46060
PH: 317.374.8720
E-MAIL: brad@site-architecture.com
PROJECT CONTACT:
These drawings are intended for construction.
DATE ISSUED: 12.23.2020
REVISIONS ISSUED:
CARMEL, IN 46033
NEEDLER'S FRESH MARKET
4755 EAST 126TH STREET
TENANT FINISH IMPROVEMENTS
THE ENGINEERING
COLLABORATIVE
SAM HURT, P.E.
2410 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, IN. 46241
PH: 317.636.3941
E-MAIL: sam@tec-mep.com
PROJECT CONTACT:
MEP ENGINEER:
CONSTRUCTION ISSUE SET
#6 - 3.5.2021
SECOND FLOOR PLUMBING - ENLARGED PLAN
1 SCALE: 3/16" = 1'-0"
N
P107
SECOND FLOOR
PLUMBING -
ENLARGED PLAN
05/06/21