HomeMy WebLinkAbout57_P801NOTE:
Details shown here are typical only and may not be complete. Contractor shall provide all
material and labor necessary for the configuration, piping and accessories required to
operate this system in the manner intended with complete safety.
Recirculating pump
(RP-A)
Check valve (typ)
Exist. pad
Mixing valve (MV-A) locate
below water line
Floor
Tank drain
(typ)
Thermometer (typ)
Thermal exp. absorber.
Support as necessary.
Ball valve (typ)
Strainer
Exist.
HWR
Exist.
CW
Exist.
N.C. HW
N.C.
Pre-heater (WH-2)
New Existing
Gas cock
(typ)
Dirt leg
(typ)
To floor
drain
Water heater (WH-1)
3"Ø flue
(typ)
Min.
3
4"G (typ)
ASME T&P relief
valve (typ)
Dielectric
union (typ)
3"Ø intake
(typ)
Thermometer
Finished
floor
1" Min.
2"W
2" Deep
seal P-trap.
Trap Seal
NOTE:
This contractor to provide for testing and
certification per state requirements.
Pipe discharge to
floor drain
Air gap drain funnel
From water
supply source
Line size
shut-off (typ)
To system
Vent air
Combustion air
Maintain 12" min.
clearance above highest
anticipated snow level.
Max. of 24" above roof
Maintain 12" min.
clearance above highest
anticipated snow level.
Max. of 24" above roof
Vent air
Combustion air Roof boot/flashing
(field supplied)
Support (field supplied)
Elbow (field supplied)
Combustion air
Vent air
Concentric Vent Roof Installation
Concentric Vent and Combustion-Air
Roof Termination
3
1
2" Concrete housekeeping
pad
Brine tank
w/float valve
Resin tank
(typ)
Shut-off valve (typ)
Union (typ)
2"
Pressure gauge (typ)
2"CW-S
2"CW
N.C.
Floor drain
2"
7
P
R
O
F
E
S
S
I
O
N
A
L
E
N
G
N
I
E
E
R
S
A
M
U
E
L
L.
H
U
R
T
I
N
D
I
A
N
A
0
N
P E 1 6
o .
10 0 87
S T A T E O F
R
E
T
E
G
I
S
D
E
R
Exp. 7.31.2022
PROJECT NUMBER: 2020-007
CERTIFICATION:
SITE ARCHITECTURE
architecture + landscape architecture
ARCHITECT:
SITE ARCHITECTURE
architecture + landscape architecture
BRAD SMITH, RA | LEED AP
13144 EAST 186TH STREET
NOBLESVILLE, IN. 46060
PH: 317.374.8720
E-MAIL: brad@site-architecture.com
PROJECT CONTACT:
These drawings are intended for construction.
DATE ISSUED: 12.23.2020
REVISIONS ISSUED:
CARMEL, IN 46033
NEEDLER'S FRESH MARKET
4755 EAST 126TH STREET
TENANT FINISH IMPROVEMENTS
THE ENGINEERING
COLLABORATIVE
SAM HURT, P.E.
2410 EXECUTIVE DRIVE, SUITE 100
INDIANAPOLIS, IN. 46241
PH: 317.636.3941
E-MAIL: sam@tec-mep.com
PROJECT CONTACT:
MEP ENGINEER:
CONSTRUCTION ISSUE SET
#7 - 3.30.2021
WATER HEATER DETAIL
1 SCALE: NTS P801
PLUMBING DETAILS
CONCENTRIC VENT DETAILS
2 SCALE: NTS
RPZ DETAIL
HUB DRAIN DETAIL 3 SCALE: NTS
4 SCALE: NTS
GREASE INTERCEPTOR SIZING
5 SCALE: NTS
WATER SOFTENER DETAIL
6 SCALE: NTS
05/06/21