HomeMy WebLinkAboutE0-1J
S
FACP
SYMBOL I T E M
FIRE SPRINKLER TAMPER SWITCH
FAN SPEED CONTROL
CIRCUITING BACK TO THE PANEL BOX
LOCATION OF ELECTRICAL PANEL SEE
THIS SHEET FOR TYPE AND VOLTAGE
FAN MOTOR
FIRE ALARM CONTROL PANEL
JUNCTION BOX HARDWIRE ELECTRICAL
CONNECTION
SPECIALTY APPLIANCE RECEPTACLES
GROUND FAULT DUPLEX RECEPTACLE
+ 44" ABOVE FINISHED FLOOR
30AMP
+44"
GFI
4 PLEX RECEPTACLES
DUPLEX RECEPTACLE IN FLOOR BOX
DEVICE BOX FOR TELEPHONE JACK LOCATION
W/ METAL CONDUIT GOING ABOVE THE CEILING
DUPLEX RECEPTACLE
CABLE TV CONNECTION
METER LOCATION
NON FUSED DISCONNECT SWITCH
3R DENOTES NEMA CONSTRUCTION TYPE
40AMP
1 RJ45 DATA JACK & 1 TELEPHONE
JACK IN FLOOR BOX
ME
4-PLUG RECEPTACLE W/ ISOLATED GROUND FOR
COMPUTERS
FUSED DISCONNECT SWITCH 60 AMP IS
RATING / 50 INDICATES FUSE SIZE 3R
DENOTES NEMA CONSTRUCTION TYPE
DEVICE BOX FOR DATA JACK LOCATIONS W/ METAL
CONDUIT GOING ABOVE THE CEILING
OR FLOOR WITH CAT 6 CABLES
# INDICATES # OF DATA JACKS & CABLEING
E L E C T R I C A L L E G E N D
CA
TPR
DUPLEX RECEPTACLE
1 RJ45 DATA JACK &
1 TELEPHONE JACK ONE SINGLE FLOOR BOX
RECESSED CAN LIGHT FIXTURE
EXIT
SURFACE MOUNTED LIGHT FIXTURE
EMERGENCY LIGHTS WITH BATTERY BACK-UP
UNIVERSAL EXIT LIGHTS W/ BATTERY BACK-UP AND
EMERGENCY LIGHTS
2 X 4 GRID CEILING
EXHAUST FAN
RECESSED MOUNTED FLOURESCENT FIXTURE
T
WP WEATHERPROOF DUPLEX RECP.
EP
SURFACE MOUNTED LIGHT FIXTURE
S ON OFF WALL SWITCH
SC
BB
BASEBOARD HEATER
SYMBOL I T E M
EXIT
EXIT SIGN W/ BATTERY BACK-UP
DIRECTIONAL ARROW
HC HANDICAP DOOR OPERATOR REMOTE
ODM OVERHEAD DOOR MOTOR
V VOLUME CONTROL
COND
AC CONDENSER
TELEPHONE DMARK LOCATION
FIBER OPTIC LOCATION
DMARK
FIBER
ANTENNA FOR RIALTOS LIGHTING CONTROL
ANTNN SYSTEM
WP WALL POD NLIGHT, N POD GFX GRAPHIC
LIGHT CONTROLLER
FAN
EH ELECTRIC CEILING OR WALL HEATER
TRANSFORMER
S
OCCUPANCY SENSOR CEILING MOTION & SOUND
D WALL SWITCH WITH DIMMER
OCC
OCCUPANCY SENSOR WALL MOTION & SOUND
ODS
OCCUPANCY DAYLIGHTING SENSOR NLIGHT
PHOTOCELL HUBBLE #LUXSTATLS
PP
POWER PACK
LV
LOW VOLTAGE MANUAL ON SWITCH
OCW
LV D
LOW VOLTAGE MANUAL ON SWITCH WITH DIMMER
LEVITON #LVS-1x
AUTOMATIC OFF OCC SENSOR
LEVITON # 0PP20-D2
LEVITON # 0SC20-MOW
LEVITON # 0SSMT-GDx
LEVITON # IP710-LFZ
PS PHOTO CELL HUBBLE #LUXSTATLSO
2
AD ALARM DEVICE
T TIMER
S
F
ON OFF SWITCH FOR 120 V POWER TO FROSTED WIN.
SCP SECURITY CONTROL PANEL
AREA SITE LIGHTING FIXTURE
AREA SITE LIGHTING FIXTURE
GENERAL ELECTRICAL NOTES
1. SEE THE DIVISION 16 SPECIFICATION BOOK WHICH HAS BEEN INCLUDED WITH THIS PLAN SET,
2. E.C. TO INCLUDE 10 ADDITIONAL 120V/1P 20A CIRCUITS FOR ADDED EQUIPMENT AND PLAN REVISIONS, LENGTH NOT TO EXCEED 100' FROM PANEL AND INCLUDE A
SEPARATE CONDUIT SYSTEM FOR EACH CIRCUIT, A 20A DISCONNECT FOR EACH CIRCUIT.
3. E.C. TO INCLUDE 6 DATA JACKS & CABLEING BACK TO IT ROOM.
4. E.C. TO ACCEPT, UNLOAD, AND ASSEMBLE LIGHT FIXTURES AS REQUIRED. FIXTURES MAY NOT HAVE THE REQUIRED VOLTAGE PRE-WIRED, WHIPS MAY NOT BE
INCLUDED. E.C. SHALL SIGN FREIGHT SLIPS WITH "CONCEALED DAMAGE" TO EASE THE PROCESS FOR FREIGHT CLAIMS.
5. E.C. SHALL PROVIDE A ONE YEAR LABOR WARRANTY FOR ALL EQUIPMENT INSTALLED, INCLUDING BUT NOT LIMITED TO OWNER AND CONTRACTOR PROVIDED
EQUIPMENT.
6. ALL CONDUITS INSTALLED UNDER GROUND SHALL BE PVC SCHEDULE 80. PROVIDE GRMC ELBOWS AT FLOOR PENETRATIONS.
7. BRANCH CIRCUITS RUN CONCEALED IN WALLS OR ABOVE CEILINGS SHALL BE RUN IN EMT.
8. ALL BRANCH CIRCUITS SHALL INCLUDE A GROUNDING CONDUCTOR.
9. CONDUCTORS SHALL BE COPPER WITH THE TYPE "THHN-THWN" INSULATION RATED AT 600 VOLTS, CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID.
10. COLOR CODING FOR 120/208, 3ø , 4W SYSTEMS SHALL BE: PHASE A-BLACK, PHASE B-RED, PHASE C-BLUE, NEUTRAL-WHITE.
11. COLOR CODING FOR 277/480, 3ø , 4W SYSTEMS SHALL BE: PHASE A-BROWN, PHASE B-ORANGE, PHASE C-YELLOW, NEUTRAL-GREY. (IF APPLICABLE)
12. E.C SHALL PROVIDE APPROPRIATE FIRE STOPPING AT ALL PENETRATIONS OF RATED FLOORS, WALLS, AND CEILINGS TO MEET U.L. LISTING OF INSTALLED
ASSEMBLIES. DETAILS HAVE BEEN PROVIDED FOR TYPICAL RATED ASSEMBLIES BUT ELECTRICAL CONTRACTOR SHALL COORDINATE W/ARCHITECTURAL PLANS FOR
FINAL RATINGS AND PROVIDE APPROPRAITE FIRE RATING MATERIALS. SEE ARCH DWG FOR RATED WALL AND CEILING LOCATIONS.
13. MINIMUM SIZE LINE VOLTAGE CONDUCTORS SHALL BE #12. MINIMUM SIZE LOW VOLTAGE WIRING SHALL BE #14 AWG.
14. ALL ELECTRICAL INSTALLATIONS SHALL BE IN COMPLIANCE WIT NFPA 70 NEC 2011, AND APPLICABLE LOCAL ELECTRICAL CODES.
15. PROVIDE WATERPROOF SEALS IN ALL CONDUITS THAT ENTER OR LEAVE UNDERGROUND CONDUIT SYSTEMS.
16. E.C. IS RESPONSIBLE FOR PROVIDING ALL PENETRATIONS THRU CONSTRUCTION ELEMENTS.
17. PROVIDE EXPANSION FITTING AT ALL EXPANSION JOINTS.
18. MINIMUM SIZE HOMERUN CONDUIT SIZE FOR BRANCH CIRCUITS SHALL BE 3/4" U.O.N.
19. MINIMUM SIZE CONDUIT FOR TELEPHONE CONDUITS SHALL BE 1".
20. MINIMUM SIZE CONDUIT FOR F.A. SYSTEM SHALL BE 1/2".
21. LABEL ALL JUNCTION BOXES WITH DESCRIPTION OF CIRCUITS CONTAINED.
22. ALL F.A. JUNCTION BOXES ARE TO BE PAINTED RED.
23. EMT CONDUIT CONNECTORS SHALL UTILIZE STEEL COMPRESSION FITTINGS.
24. ALL CONDUITS SHALL BE ROUTED PERPENDICULAR AND PARALLEL TO BUILDING STRUCTURE.
25. ALL TELEPHONE OUTLETS SHOWN ARE TO INCLUDE A TELEPHONE AND DATA PORT.
26. ON ALL ELECTRICAL DEVICES, REUSE EXTG. CIRCUITING AND WIRING IF POSSIBLE. ADD CIRCUITS IN THE EXTG. ELEC. PANELS AS NEEDED. EC
RESPONSIBLE FOR ELEC. LOADS AND WIRING SIZING AND ROUTES OF CONDUIT OF WIRING FOR NEW OR EXTG.ELECTRICAL ITEMS. CONNECT
NEW DEVICES INTO THE CLOSEST ELECTRICAL PANEL. USE THE NEW ELECTRICAL PANEL AS NEEDED FOR ANY NEW CIRCUITS.
27. NOT USED
28. NOT USED
29. ALL ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE INTENDED TO SHOW THE APPROXIMATE LOCATION OF EQUIPMENT AND PIPING AND MUST NOT BE USED
FOR OBTAINING LINEAL RUNS OF WIRING OR CONDUIT.
30. ALL DIMENSIONS GIVEN ON THE PLANS SHALL BE VERIFIED IN THE FIELD. DRAWINGS MAY NOT BE SCALED TO OBTAIN EXACT DIMENSIONS OR LOCATIONS. PROVIDE
SHOPS DRAWINGS WITH DIMENSIONS TO THE PROJECT ENGINEER AND GENERAL CONTRACTOR FOR REVIEW.
31. E.C. TO REVIEW MECHANICAL AND PLUMBING DRAWINGS AND VERIFY ELECTRICAL CONNECTIONS REQUIRED FOR THE EQUIPMENT.
32. E.C. SHALL SUPPLY CIRCUIT AND DEVICE POWER TO THE EQUIPMENT LOCATED ON MECHANICAL AND PLUMBING DRAWINGS, INCLUDING A SERVICE DISCONNECT
SWITCH FUSED AT THE REUQIRED MOTOR OR NAMEPLATE RATING. E.C. SHALL CONNECT ALL STARTERS, FURNISHED AND INSTALLED BY M.C..
33. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE TO INCLUDE IN THEIR BASE BID THE INSTALLATION OF ALL CONTROL CONDUITS, WIRING, AND DEVICES, BOTH
LINE AND LOW VOLTAGE, WHICH WILL REQUIRE THE SERVICES OF A LICENSED ELECTRICIAN QUALIFIED TO WORK IN THE JURISDICTION OF THISPROJECT AND
APPROVED BY THE PROJECT MANAGER.
34. PER NEC 376.22 METAL WIREWAYS SHALL NOT CONTAIN MORE THAN 30 CURRENT CARRYING CONDUCTORS AT ANY CROSS SECTION.
35. PER NEC 408.4 E.C. SHALL LEGIBLY IDENTIFY EACH CIRCUIT ON THE PANEL SCHEDULES AND CIRCUIT DIRECTORY. INCLUDE ROOM NAME AND DEVICE, LIGHT, OR
EQUIPMENT LIGHT FIXTURE IS CONNECTED TO.
36. PER NEC 230.95 SERVICE ENTRANCE MAIN SWITCH GROUND FAULT TESTNG IS REQUIRED AND SHALL BE THE RESPONSIBILITY OF THE E.C.
37. VERIFY ALL SWITCH, DEVICE, AND OUTLET COLORS WITH THE OWNER.
CAM CAMERA LOCATION
ACCESS CONTROL SYSTEM SYMBOL LEGEND
CAM
EX EXTERIOR CAMERA LOCATION
CR ACCESS CONTROL CARD READER
DC MAGNETIC DOOR CONTACT
EL ELECTRIC LOCK / POWER SUPPLY BY OTHERS
SEC SECURITY SYSTEM PANEL
ACP ACCESS CONTROL PANEL
NVR NETWORK VIDEO RECORDER
POE POE NETWORK SWITCH
K ACCESS CONTROL KEYPAD
POWERED WITH CAT 6 CABLEING
POWERED WITH CAT 6 CABLEING
NVR - IP04-16T-R4A EXACQ VID SERV, 16TB, WIN10 EXACQ
EVIP01 CAMERA LICENSE EXACQ
RACK - 119-5028 4U WALL RACK RACKSOLUTIONS
UPS - PS15-1100RT120 LIEBERT UPS 1100VA LIEBERT BATTERY BACK UP
POE - 1920S HP POE SWITCH, 24 PORT, 2SFP HP
CAMERA - XNV-6011 INTERIOR DOME CAM 2MP HANWAH
CAMERA - XNO-8080R EXTERIOR BULLET CAM 5MP HANWAH
VIDEO SYSTEM EQUIPMENT
MS MOTION SENOR
GB MOTION SENOR
HUB HOLD UP BUTTON
AKP ACCESS KEYPAD
tel: 765.649.8477
www.krMarchitecture.com
ANDERSON
INDIANAPOLIS
DETROIT
DRAWN BY
krM JOB NO.
DRAWING NO.
REVISIONS
DRAWING NAME
E0-1
ELECTRICAL NOTES
& LEGENDS
DKM
20128
02/12/2021
BID SET
4775 E 126th St Carmel IN 46033
STATE BANK
20128 - CARMEL BRANCH
BID SET
02/12/2021
D R A W I N G L I S T
E0-1 - Electrical Notes & Legends
E1-1 - Electrical Power Plan
E1-2 - Electrical Basement Floor Plan
E2-1 - Electrical Lighting Plan
E4-1 - Electrical Riser & Details
M1-1 - HVAC Plan
M2-1 - Mechanical Details & Schedules
M2-2 - Mechanical Details & Schedules
P1-1 - Plumbing Plan
P2-1 - Plumbing Details & Schedules
05/07/21