HomeMy WebLinkAboutE2-1ALL OCCUPANCY SENSOR TO BE SET TO TURN
OFF LIGHTS LESS THAN 30 MINUTES AFTER
ANYBODY LEAVES THE ROOM.
1
NL, NIGHT LIGHTS TO BE ON NON SWITCHING OPERATION
ALL NIGHT LIGHTS NL, TO HAVE EMERGENCY BATTERY
BACK UP 90 MINUTE.
UL 924 DEVICE REQUIRED AT LED FIXTURES WHEN
USED AS EM & ALSO USED AS DIMMABLE FIXTURES.
2
3
4
L I G H T I N G N O T E S
NIGHT LIGHTS NLA, NLB, TO BE CONTROLLED THRU TIME
CLOCK.
5
6
SEE ELECTRICAL LEGEND FOR OCCUPANCY SENSORS,
POWER PACKS TYPES.
EXACT LOCATION OF DRIVE LANE OPEN CLOSE SIGNS
& CONTROLS BY OWNER.
7 NEW OCCUPANCY SENSOR THIS AREA. TIE INTO EXTG.
LIGHTING CIRCUITS. ADD LIGHTING CIRCUITS AS NEEDED.
8 TIE NEW LIGHTING INTO EXTG. SWITCHING THIS ROOM.
9 REMOVE EXTG. SWITCHING FOR CANOPY. COORDINATE
IF EXTG. CONDUIT CAN BE REUSED.
REUSE EXTG. CIRCUITING AND WIRING IF POSSIBLE.
ADD CIRCUITS IN THE EXTG. ELEC. PANELS AS NEEDED.
EC RESPONSIBLE FOR ELEC. LOADS AND WIRING SIZING
AND ROUTES OF CONDUIT OF WIRING FOR NEW OR EXTG.
ELECTRICAL ITEMS.
10
11 JBL BRAND SPEAKER IN CEILING. PLAYLIST TO BE CONTROLLED
BY IPAD. VOLUME BY CONTROL ON THE WALL. HARDWIRED TO
VOLUME CONTROL.
SOUND SYSTEM REQUIREMENTS
1, SONOS AMP. MFR # AMPG1US1BLK, Attach desired speakers
Your speakers’ power rating should be at least 125W for 8 ohm
speakers, and at least 200W for 4 ohm speakers. Do not connect
speakers rated at less than 4 ohm.
Note:Amp can drive speakers with nominal impedance above 4 ohms.
Two pairs of 8 ohm speakers wired in parallel are also supported. Don’t
wire your speakers in series because it will result in poor sound quality.
Remove the cap from the banana plug to reveal the connection hole.
Insert the stripped end of the speaker wire into the hole, then return the
cap to the banana plug to secure the connection.
2, New-construction Bracket for Director 6.5" and
8" and Thinfit In-ceiling speakers
3, JBL Control® 26CT 6-1/2" commercial in-ceiling speaker
4, 3 Episode® Electronics 100 Watt Rotary Volume
Control (Each | White & Light Almond)
5, 3 14/4 Audio wire up to 100' run
12 OCCUPANCY SENSOR OVERIDE WALL SWITCH.
13 SEE ELECTRICAL RISER DIAGRAM FOR CONTROL OF EXERIOR
FIXTURES. THE EXTG. SITE LIGHTS TO BE CONTROLLED BY THE
EXTG. TIMING DEVICE.
LIGHT FIXTURE SCHEDULE GENERAL NOTES:
A. ALL LIGHT FIXTURES SHALL BE UL LISTED.
B. REFERENCE SPECIFICATION SECTION FOR ADDITIONAL REQUIREMENTS.
C. ALL BIDDERS, INCLUDING THOSE SPECIFIED AND MANUFACTURERS LISTED AS EQUAL, SHALL SUBMIT
PRODUCT CUTSHEETS TO THE ENGINEER TEN (10) DAYS PRIOR TO BID FOR FINAL WRITTEN APPROVAL. EQUAL
FIXTURES SHALL BE OF EQUAL OR BETTER QUALITY AND PERFORMANCE TO THE SPECIFIED FIXTURE. BURDEN OF
PROOF SHALL BE ON THE MANUFACTURER AND SHALL PROVIDE WORKING 120 VOLT SAMPLE WITH CORD AND
PLUG AT THE REQUEST OF THE ENGINEER.
D. MANUFACTURERS/VENDORS WISHING TO BID SUBSTITUTE FIXTURES OTHER THAN THOSE LISTED ON THE
LIGHT FIXTURE SCHEDULE, SHALL SUBMIT CUTSHEETS AS REQUIRED PER SPECIFICATION SECTION 16500 AND AT
THE REQUEST OF THE ENGINEER PROVIDE FACTORY POINT-BY-POINT CALCULATIONS USING AGI32 AND PROVIDE
ELECTRONIC .AGI FILE TEN (10) DAYS PRIOR TO BID FOR WRITTEN APPROVAL. BURDEN OF PROOF SHALL BE ON
THE MANUFACTURER AND SHALL PROVIDE WORKING 120 VOLT SAMPLE OF EACH SUBSTITUTE FIXTURE WITH CORD
AND PLUG AT THE REQUEST OF THE ENGINEER.
E. CONTRACTOR SHALL PROVIDE UNSWITCHED CONDUCTORS TO ALL FIXTURES WITH EMERGENCY LED BATTERY
PACKS AS REQUIRED.
F. CONTRACTOR SHALL FOCUS, AIM AND ADJUST LIGHT FIXTURES UNDER THE SUPERVISION AND DIRECTION OF
THE ENGINEER AND ARCHITECT. ALLOW LABOR FOR FINAL FOCUS AND ADJUSTMENTS AFTER DARK. LIFTS AND
SCAFFOLDING SHALL BE AVAILABLE.
G. CONFIRM ALL FINISHES AND MOUNTING HEIGHTS WITH ARCHITECT DURING SHOP DRAWING REVIEW. PROVIDE
CUSTOM, FACTORY CUT STEM LENGTHS AS REQUIRED.
H. REFER TO DRAWINGS FOR MOUNTING REQUIREMENTS, NUMBER OF FACES AND ARROWS (CHEVRONS) FOR ALL
EXIT SIGNS. COORDINATE WITH ARCHITECTS REFLECTED CEILING PLANS.
I. CONTRACTOR SHALL VERIFY CEILING TYPES PRIOR TO ORDERING FIXTURE AND PROVIDE FIXTURES
APPROPRIATE TO THE ACTUAL CONDITION. THIS IS TO INCLUDE SPECIFIC TYPE OF LAY-IN CEILING GRID.
J. ALL FIXTURES SHALL HAVE INTERNAL FAST-BLOW FUSING.
K. ALL LAY-IN FIXTURES SHALL BE PROVIDED WITH SCREW ON HOLD DOWN CLIPS, AND MAX. 6-0 LONG ½
FLEXIBLE CONDUIT WHIPS WITH TWO #12 AND #12 GROUND.
L. COORDINATE EXIT / EM MOUNTING HEIGHT AT LOCATION SHOWN
M. FOR LIGHTING IN EXPOSED STRUCTURE AREAS, EC SHALL PROVIDE UNI-STRUT OR SIMILAR HARDWARE FOR FIXTURE
INSTALLATION BETWEEN JOISTS.
N. ALL CEILING OR HIGH WALL MOUNTED OCCUPANCY VACANCY, OR DAY LIGHT HARVESTING SENSORS SHALL HAVE A WALL
MOUNTED OVERIDE SWITCH IN THE LOCATION SHOWN.
LAY-IN CEILING
LAY-IN CEILING
FLEXIBLE CONDUIT
W/#12 WIRE (6' MAX.)
LAY-IN CEILING
JUNCTION BOX
LAY-IN CEILING
12 GAUGE HANGER WIRE OR CHAIN FOR FIXTURE
SUPPORT CONNECTED TO STRUCTURE ABOVE
SEISMIC
CLIP
1 1
D 1
D 2
2
2
OCC
PP
3
3
NL
D 4
4 4
5
5
D 5
6 D
6
NL NL
NL
7
OCW
7
OCC
PP
NL
8
8 8
3
8
D 9
9 9
NL
4 OCC
OCC
PP
3
OCC
3 PP
3
3
3
4
4 4 4
3 3 3
4
D 4
D 3
5
OCW
5
6
6
NL
NL
8
8
6
OC 13
OC 13
OC 13
7 OCW
7
NLA NLA NL NLA
NLB NLB
NLB NLB
NLB NLB
EXIT
EXIT
7
7
7
7
7
7
7
7
8
9
SP
V
SP SP
SP
V
V
11
11 11
11
11 SP
V
R3 R3
P3
S1
S1
D1 D1
R1
R1
P1
P1
R3 R3
R1
R2
D1
D1 D1
D1
D1
D1 D1
M1 3
R1 R1 R1
R1 R1
R3
R3
R1 R1
R3
R3
R3 R3
D1
D1
D1
D1 D1 D1
3 D1
R2 R2
R2 R2
R2 R2
H-24 NLC H-24 NLC H-24 NLC H-24 NLC H-24 NLC H-24 NLC
S1 S1 S1
NLA NLA NLA
W1
NLA
S1 S1 S1 S1
6
D
D
D
Type MFG Part
D1 Intense Lighting SS4G4DS-L4-358 ICS430-HZ-SF I200
M1 Columbia Lighting MPS4-35ML-CW-EDU / CSHC
P1 The Original Cast Lighting GB1-XX-04-FS-XX-LED1-35K-UNV-XXDM1
P1- CLUSTER The Original Cast Lighting GB1-P3CA-06-FS-XX-LED1-35K-UNVXX- DM1
P3 The Original Cast Lighting GL1-C1NB-24-MW-XX-LED2-35K-UNVDM1
R1 Axis Lighting B6RLED-800-80-35-RG-4'-W-UNV-DP-1-TXX
R2 Axis Lighting B6RLED-800-80-35-RG-2'-W-UNV-DP- 1-TXX
R3 Axis Lighting B6RLED-800-80-35-RG-6'-W-UNV-DP- 1-TXX
S1 Scott Architectural Lighting S3A15-L05A-935K-XX-XX
U1 Axis Lighting BCUC-RUN-XX-80-W-UNV-XX-XX
W1 Intense Lighting GD2WS
LIGHT FIXTURE SHCEDULE
F2 Hubbell Lighting Outdoor RFL3-90L-40-XK7-W-UNV-K-XX
H-24 Finelite HP-4 WL R-24'-H-8XX-F-XXV-SC-VF
R2 Intense Lighting SS4G4DS-L3-XX8 / ICS432-HZ-SF / I100
S1 Stone Lighting WO877-XX-LED
V4 Beacon Products VP-S/36L-80/XK7/4F/UNV/A/BLT
Item Note: INSTALLED ON EXISTING POLE. MATCH ADJACENT FIXTURES IN DEVELOPMENT.
W1 Performance iN Lighting SHIELD+ 2, TYPE III, 37W
EXTERIOR LIGHT FIXTURE SHCEDULE
tel: 765.649.8477
www.krMarchitecture.com
ANDERSON
INDIANAPOLIS
DETROIT
DRAWN BY
krM JOB NO.
DRAWING NO.
REVISIONS
DRAWING NAME
E2-1
ELECTRICAL
LIGHTING PLAN
KRM
20128
02/12/2021
BID SET
4775 E 126th St Carmel IN 46033
STATE BANK
20128 - CARMEL BRANCH
BID SET
02/12/2021
SCALE: 1/4" = 1'-0"
3
LIGHT SUPPORT DETAIL
SCALE: 1/4" = 1'-0"
1
FIRST FLOOR REFLECTED CEILING PLAN
05/07/21