HomeMy WebLinkAboutE4-1FEEDER SIZES
A
C
B
(1) SETS, 3 #3 MCM THWN CU. W/ GRD #8 1 1/2"C 100A
(1) SETS, 4 #4/0 MCM THWN CU. W/ GRD #4 2 1/2"C 225A
(1) SETS, 3 #600 MCM THWN CU. W/ GRD #3 3 1/2"C 400A
D (1) SETS, 4 #1/0 MCM THWN CU. W/ GRD #6 2"C 150A
E (2) SETS, 4 #400 MCM THWN CU EACH. W/ GRD #1 3"C 600A
F (1) SETS, 4 #300 MCM THWN CU. W/ GRD #4 3"C 250A
PAD MOUNT
TRANSFORMER
ADDENDUM #4
ELECTRICAL RISER DIAGRAM
120 / 208 VOLT
3 PHASE
D
C
B
MDP
A
100 AMP
100 AMP 100 AMP
60 AMP 60 AMP
1st FLOOR
EM
PANEL E
150 AMP
42 POLE
3 PHSE.
120 / 208 VOLT
ADD NEW 150 AMP
SWITCH TO EXTG. MDP
FOR NEW E PANEL
D
TIME
CLOCK
2 POLE TIMER
INTERMATIC
ET8415CR
ASTRO 7 DAY
EXTG
NEW
NLA, NLB , NLC
FINISH FLOOR
FINISH CEILING
POWER/ COMMUNICATIONS
DEVICES AND SYSTEMS
FURNITURE OUTLETS
ABOVE COUNTER DEVICES.
COORDINATE WITH ARCH.
ELEVATIONS AND CABINETRY
SHOP DRAWINGS
CATV OUTLET AND DEVICES
AND MOUNTING BRACKETS
WALL -MOUNTED
OPERABLE DEVICES
PULL STATION
WALL -MOUNTED DEVICE W/
SIDE ACCESSIBILITY
WALL -MOUNTED
DETECTOR
1'-0"
DO NOT PLACE DETECTOR
IN THIS AREA
HORN/ STROBE
HORN
STROBE
CEILING -MOUNTED
DETECTOR
CEILING -MOUNTED HORN
OR HORN/ STROBE
88"
80"
54"
48"
40"
16"
4"
4"
GENERAL NOTES:
1. MOUNTING HEIGHTS SHOWN IN THIS DETAIL ARE
TYPICAL UNLESS OTHERWISE NOTED ON THE PLANS
2. SEE ARCHITECTURAL ELEVATIONS FOR SPECIAL
CONDITIONS. NOTIFY ARCHITECT IMMEDIATELY OF ANY
CONFLICTS.
3. ALL INSTALLATIONS SHALL COMPLY WITH ADA.
VISUAL FIRE ALARM NOTIFICATION DEVICES (STROBE)
LOCATE DEVICE SO THE BOTTOM OF THE DEVICE IS
BETWEEN 80" AND 96" A.F.F. (NFPA) OR 6" BELOW
CEILING, WHICHEVER IS LOWER (ADA 2010)
96"
AUDIBLE FIRE ALARM NOTIFICATION DEVICES (HORN)
LOCATE DEVICE SO THE TOP OF THE UNIT IS NOT MORE
THAN 90" A.F.F. AND NOT LESS THAN 6" BELOW CEILING
(NFPA)
FIRE ALARM ACTIVATION DEVICES (PULL STATION)
LOCATE FRONT -APPROACH DEVICES SO THAT THE
HIGHEST OPERABLE PORTION OF THE DEVICE IS NOT
MORE THAN 48" A.F.F. (ADA 2010) AND NOT LESS THAN 42"
A.F.F. (NFPA)
POWER/ COMMUNICATION DEVICES:
OUTLETS SHALL BE LOCATED AT 16" A.F.F. TO THE
BOTTOM OF THE BOX. ABOVE COUNTER DEVICES SHALL
BE LOCATED AT 2" ABOVE THE BACKSPLASH OF THE
COUNTER TO THE BOTTOM OF THE DEVICES. VERIFY
WITH ARCHITECTURAL DETAILS.
WALL -MOUNTED OPERABLE DEVICES:
OPERABLE DEVICES SHALL BE LOCATED AT 48" A.F.F. TO
THE TOP OF THE OPERABLE PORTION OF THE DEVICE.
WALL -MOUNTED OPERABLE DEVICES INCLUDE, BUT ARE
NOT LIMITED TO THE FOLLOWING: PUSH BUTTONS
LIGHT SWITCHES, DIMMERS, CONTROLS, ETC.
NURSE/ PATIENT CALL DEVICES (INCLUDING THOSE FOR
STAFF USE)
OTHER CONTROL OR "CALL" DEVICES
8'-8"
10'-6"
8'-0"
COUPLING FLUSH WITH
FINISH FLOOR
COUNTER OUTLET
CONDUIT UP TO
LIQUIDTIGHT FLEXIBLE
CONDUIT FITTING
LIQUIDTIGHT FLEXIBLE
TYPICALLY MOUNT
OUTLETS AT +18" AFF
CONDUIT STUB-UP FOR:
DATA/COMMUNICATION TO BE 1"C.
POWER RECEPTACLES TO BE 3/4"C.
FINISHED
FLOOR
PANEL C
PANEL D
tel: 765.649.8477
www.krMarchitecture.com
ANDERSON
INDIANAPOLIS
DETROIT
DRAWN BY
krM JOB NO.
DRAWING NO.
REVISIONS
DRAWING NAME
E4-1
ELECTRICAL RISER
& DETAILS
DKM
20128
02/12/2021
BID SET
4775 E 126th St Carmel IN 46033
STATE BANK
20128 - CARMEL BRANCH
BID SET
02/12/2021
SCALE: 3/8" = 1'-0"
3
Standard Mounting Heights
SCALE: 3/16" = 1'-0"
4
Undercounter Device Box1
SCALE: 3/8" = 1'-0"
5
Telephone Conduit Stub Detail1
SCALE: 1/4" = 1'-0"
7
Occupancy Sensor Wiring -Multiple Ceiling Mount1
SCALE: 1/4" = 1'-0"
8
Occupancy Sensor Wiring -Single Ceiling Mount1
SCALE: 1" = 1'-0"
6
ELECTRICAL PANELS
05/07/21