HomeMy WebLinkAboutE001.0EXTERIOR LANDLORD ROOM
ASSUMED 225KVA,120/208V
PAD MOUNTED UTILITY
TRANSFORMER
SCALE: NONE
1
E-1.1
ONE LINE DIAGRAM
SCALE:
1 OR 2 HOUR RATED
UL #WL1001
GYPSUM WALL BOARD ASSEMBLY
INTUMESCENT FIRESTOP SEALANT,
DEPTH AS REQUIRED BY THE
MANUFACTURER
METALLIC CONDUIT
NONE
5
E-1.1
FIRESTOP FOR METALLIC CONDUIT
M
GROUNDED CONDUCTOR (NEUTRAL) FROM
UTILITY COMPANY TRANSFORMER
10' 10'
10'
WITHIN 5' OF WATER
ENTRANCE TO BUILDING
SCALE: NONE
2
E-1.1
SERVICE GROUNDING AND BONDING DETAIL
INCOMING CONDUIT GROUND
(IF STEEL CONDUIT)
EQUIPMENT GROUNDING BUS
EQUIPMENT BONDING JUMPER
ENCLOSURE GROUND
MAIN BONDING JUMPER (#2/0)
PER NEC 250.102.(C)(1).
#6 AWG MINIMUM
10" X 2" X 1/4" COPPER GROUND BAR.
INSTALL ON TELEPHONE BACKBOARD WITH
(2) UL LISTED STANDOFF INSULATORS.
BONDING JUMPER
SOURCE (DIRECT CONTACT WITH EARTH
FOR 10' OR MORE)
COPPER CLAD STEEL, 10' x 3/4" WITH TOP
OF ROD 6" BELOW FINISH GRADE
(TYPICAL)
CLAMPS SUITABLE FOR DIRECT
BURIAL (TYPICAL)
NON-METALLIC PROTECTIVE SLEEVE
CONNECTOR LISTED FOR PURPOSE
CONCRETE ENCASED ELECTRODE
(REINFORCING STEEL)
EXOTHERMIC
CONNECTION
(TYPICAL)
METAL FRAME OF
BUILDING STRUCTURE
BONDING JUMPER (#2/0)
PER NEC 250.102.(C)(1)
GROUNDING ELECTRODE CONDUCTOR
(#2/0) PER NEC 250.66.
GROUNDED OR
NEUTRAL BUS
SERVICE EQUIPMENT
TC
H-4
H-2
RESTAURANT EXTERIOR BUILDING LIGHTS
ZONE SCHEDULE:
1. BUILDING MOUNTED LIGHTING; PS ON, PS OFF
2. MONUMENT SIGN; PS ON, TC OFF
SCALE: NONE
4
E-1.1
LIGHTING CONTROL DIAGRAM (PACKAGED)
RELAY PANEL WITH INTEGRATED DIGITAL
TIME CLOCK, 8 LIGHTING RELAYS, WITH
RELAY CONTROL CARD FOR MANUAL
CONTROL OF ZONES OR INDIVIDUAL
RELAYS. EATON LITEKEEPER LK8 OR
EQUAL.
OUTDOOR PHOTOSENSOR;
FACE NORTH
3/C #18 LV CABLE
PS
SCALE:
18"
MIN.
12"
MIN.
30"
MIN.
4" 4"
5"
FINISHED GRADE
RED MARKER
TAPE
"ELECTRICAL"
SCHEDULE 40
CONDUITS (TYPICAL)
TRENCHING AND SELECT CLEAN BACKFILL
TO 95% COMPACTION BY E.C.
NONE
7 UNDERGROUND CONDUIT DETAIL
SCALE:
12"
24"
(MIN.)
32"
(MIN.)
18"
(MIN.)
5"
5" 7 1/2" 5"
FINISHED GRADE
RED MARKER
TAPE "ELECTRICAL"
BASE SPACER ON
5'-0" MAX. CENTERS
4" SCHEDULE 40
CONDUITS (TYPICAL)
TRENCHING AND SELECT CLEAN
BACKFILL TO 95% COMPACTION BY E.C.
NONE
6
E-1.1
PRIMARY POWER DUCT BANK DETAIL
E-1.1
(3)4" PVC WITH (4)#600KCMIL, EACH
400AMP
TENANT 101
M
200AMP
TENANT 102
M
200AMP
TENANT 103
M
400AMP
TENANT 104
M
400AMP
TENANT 105
M
200AMP
TENANT 106
M
200AMP
FUTURE
TENANT 107
M
1200A, 120/208V 3ΙΈ,4W
METER CENTER
PANEL
"H"
200A MCB
120/208V
TYPICAL TENANT
SPACE
PANEL FOR
TENANT
SPACE
MCB
120/208V
(4)#3/0,(1)#6GND-2"C
F=16,877 (MAX)
F=16,066(MAX)
F=(MAX) 1
SHEET KEYNOTES
1 PROVIDE CONDUIT AND WIRE AS INDICATED BELOW;
SPACE 101: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 12,827
SPACE 102: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 12,471
SPACE 103: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 14,658
SPACE 104: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 16,445
SPACE 105: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 14,915
SPACE 106: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 11,216
SPACE 107: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 8,844
M
FACP
M C C
TS FS
F
F
L
V
C
H-8
20A/1P
FIRE ALARM CONTROL
PANEL SURFACE
MOUNTED, #108. (DACT
REQUIRES TWO ACTIVE
PHONE LINES).
PROVIDE CONTROL MODULE
FOR REQUIRED FUNCTION
(TYPICAL).
PROVIDE MONITOR MODULE
FOR REQUIRED FUNCTION
(TYPICAL).
INITIATING/
CONTROL
LOOP
SIGNALING
LOOP
SD HD SD C
FIRE ALARM DETAIL NOTES
1.
THIS DIAGRAM REPRESENTS A TYPICAL SYSTEM AND IS NOT INTENDED FOR INSTALLATION. SYSTEM
SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND SCHEMATIC WIRING DIAGRAMS. EXACT
SYSTEM REQUIREMENTS SHALL BE COORDINATED WITH THE SYSTEM SUPPLIER. SYSTEM INSTALLER
SHALL BE NICET CERTIFIED, IF REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION.
2.
SYSTEM SUPPLIER SHALL SUPERVISE INSTALLATION, PROGRAM AND TEST SYSTEM AND INSTRUCT
OWNER ON SYSTEM OPERATION.
3.
ALL FIRE ALARM WIRING SHALL BE PLENUM RATED. EXPOSED FIRE ALARM WIRING, 10'-0" AFF AND
BELOW, SHALL BE INSTALLED IN CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR STRUCTURE.
4.
ALL CONTROL CABINETS SHALL BE GROUNDED PER NEC REQUIREMENTS AND PER SPECIFICATIONS.
5.
COORDINATE CITY TIE-IN REQUIREMENTS WITH LOCAL AUTHORITY.
6.
DUCT SMOKES ARE FURNISHED AND WIRED BY EC, AND INSTALLED PER CODE BY MC.
7.
ALL FIRE ALARM DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 & 'ADA'.
PROVIDE WIRING PER
MANUFACTURER'S
INSTALLATION DRAWING
(TYP)
SYNCHRONIZING
MODULE
PROVIDE TELEPHONE
LINE TO TERMINAL
BOARD FOR CITY
TIE-IN OR OFF-SITE
MONITORING.
PROVIDE TELEPHONE
LINE FOR SECONDARY
OFF-SITE MONITORING.
2#12 AWG, 1#12 AWG
GND, 3/4"C.
SCALE: NONE
3
E-1.1
ADDRESSABLE FIRE ALARM SYSTEM TYPICAL WIRING DIAGRAM
PROVIDE WIRING TO EACH SECURITY DOOR
MAG LOCK POWER SUPPLY LOCATION FOR
UNLOCKING OF SECURITY DOORS DURING
FIRE ALARM CONDITION. (COORDINATE
WITH SECURITY SYSTEM SUPPLIER).
PROVIDE WIRING TO PRE-ACTION (OR DRY
TYPE) SPRINKLER SYSTEM CONTROL PANEL.
PROVIDE WIRING TO STARTERS FOR FAN SHUTDOWN.
PROVIDE WIRING AND RELAY
REQUIRED TO SHUTDOWN TENANT SOUND
SYSTEM UPON FIRE ALARM ACTIVATION.
PANEL FOR
TENANT 105
T5a
200A MCB
120/208V
F=(MAX) 1
INCOMING SECTION
WITH MAIN SWITCH
200AMP
LANLDORD
PANEL FOR
TENANT 105
T5b
200A MCB
120/208V
WIREWAY
1
TENANT 105
1
TENANT 106
PANEL FOR
TENANT
SPACE 106
MCB
120/208V
F=(MAX) 1
2" CONDUIT AND PULLWIRE, STUB
UP FROM METER CENTER TO
TENANT 106 SPACE FOR FUTURE
TENANT 107. COORDINATE STUB UP
LOCATION WITH LANDLORD PRIOR
TO INSTILLATION.
F=(MAX) 1
H-10 SITE POLE LIGHTING
H-12 RETAIL EXTERIOR BUILDING LTGS
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E0.1
ELECTRICAL
LEGEND, NOTES, DETAILS
05/10/21