HomeMy WebLinkAboutE001.0EXTERIOR LANDLORD ROOM ASSUMED 225KVA,120/208V PAD MOUNTED UTILITY TRANSFORMER SCALE: NONE 1 E-1.1 ONE LINE DIAGRAM SCALE: 1 OR 2 HOUR RATED UL #WL1001 GYPSUM WALL BOARD ASSEMBLY INTUMESCENT FIRESTOP SEALANT, DEPTH AS REQUIRED BY THE MANUFACTURER METALLIC CONDUIT NONE 5 E-1.1 FIRESTOP FOR METALLIC CONDUIT M GROUNDED CONDUCTOR (NEUTRAL) FROM UTILITY COMPANY TRANSFORMER 10' 10' 10' WITHIN 5' OF WATER ENTRANCE TO BUILDING SCALE: NONE 2 E-1.1 SERVICE GROUNDING AND BONDING DETAIL INCOMING CONDUIT GROUND (IF STEEL CONDUIT) EQUIPMENT GROUNDING BUS EQUIPMENT BONDING JUMPER ENCLOSURE GROUND MAIN BONDING JUMPER (#2/0) PER NEC 250.102.(C)(1). #6 AWG MINIMUM 10" X 2" X 1/4" COPPER GROUND BAR. INSTALL ON TELEPHONE BACKBOARD WITH (2) UL LISTED STANDOFF INSULATORS. BONDING JUMPER SOURCE (DIRECT CONTACT WITH EARTH FOR 10' OR MORE) COPPER CLAD STEEL, 10' x 3/4" WITH TOP OF ROD 6" BELOW FINISH GRADE (TYPICAL) CLAMPS SUITABLE FOR DIRECT BURIAL (TYPICAL) NON-METALLIC PROTECTIVE SLEEVE CONNECTOR LISTED FOR PURPOSE CONCRETE ENCASED ELECTRODE (REINFORCING STEEL) EXOTHERMIC CONNECTION (TYPICAL) METAL FRAME OF BUILDING STRUCTURE BONDING JUMPER (#2/0) PER NEC 250.102.(C)(1) GROUNDING ELECTRODE CONDUCTOR (#2/0) PER NEC 250.66. GROUNDED OR NEUTRAL BUS SERVICE EQUIPMENT TC H-4 H-2 RESTAURANT EXTERIOR BUILDING LIGHTS ZONE SCHEDULE: 1. BUILDING MOUNTED LIGHTING; PS ON, PS OFF 2. MONUMENT SIGN; PS ON, TC OFF SCALE: NONE 4 E-1.1 LIGHTING CONTROL DIAGRAM (PACKAGED) RELAY PANEL WITH INTEGRATED DIGITAL TIME CLOCK, 8 LIGHTING RELAYS, WITH RELAY CONTROL CARD FOR MANUAL CONTROL OF ZONES OR INDIVIDUAL RELAYS. EATON LITEKEEPER LK8 OR EQUAL. OUTDOOR PHOTOSENSOR; FACE NORTH 3/C #18 LV CABLE PS SCALE: 18" MIN. 12" MIN. 30" MIN. 4" 4" 5" FINISHED GRADE RED MARKER TAPE "ELECTRICAL" SCHEDULE 40 CONDUITS (TYPICAL) TRENCHING AND SELECT CLEAN BACKFILL TO 95% COMPACTION BY E.C. NONE 7 UNDERGROUND CONDUIT DETAIL SCALE: 12" 24" (MIN.) 32" (MIN.) 18" (MIN.) 5" 5" 7 1/2" 5" FINISHED GRADE RED MARKER TAPE "ELECTRICAL" BASE SPACER ON 5'-0" MAX. CENTERS 4" SCHEDULE 40 CONDUITS (TYPICAL) TRENCHING AND SELECT CLEAN BACKFILL TO 95% COMPACTION BY E.C. NONE 6 E-1.1 PRIMARY POWER DUCT BANK DETAIL E-1.1 (3)4" PVC WITH (4)#600KCMIL, EACH 400AMP TENANT 101 M 200AMP TENANT 102 M 200AMP TENANT 103 M 400AMP TENANT 104 M 400AMP TENANT 105 M 200AMP TENANT 106 M 200AMP FUTURE TENANT 107 M 1200A, 120/208V 3ΙΈ,4W METER CENTER PANEL "H" 200A MCB 120/208V TYPICAL TENANT SPACE PANEL FOR TENANT SPACE MCB 120/208V (4)#3/0,(1)#6GND-2"C F=16,877 (MAX) F=16,066(MAX) F=(MAX) 1 SHEET KEYNOTES 1 PROVIDE CONDUIT AND WIRE AS INDICATED BELOW; SPACE 101: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 12,827 SPACE 102: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 12,471 SPACE 103: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 14,658 SPACE 104: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 16,445 SPACE 105: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 14,915 SPACE 106: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 11,216 SPACE 107: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 8,844 M FACP M C C TS FS F F L V C H-8 20A/1P FIRE ALARM CONTROL PANEL SURFACE MOUNTED, #108. (DACT REQUIRES TWO ACTIVE PHONE LINES). PROVIDE CONTROL MODULE FOR REQUIRED FUNCTION (TYPICAL). PROVIDE MONITOR MODULE FOR REQUIRED FUNCTION (TYPICAL). INITIATING/ CONTROL LOOP SIGNALING LOOP SD HD SD C FIRE ALARM DETAIL NOTES 1. THIS DIAGRAM REPRESENTS A TYPICAL SYSTEM AND IS NOT INTENDED FOR INSTALLATION. SYSTEM SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND SCHEMATIC WIRING DIAGRAMS. EXACT SYSTEM REQUIREMENTS SHALL BE COORDINATED WITH THE SYSTEM SUPPLIER. SYSTEM INSTALLER SHALL BE NICET CERTIFIED, IF REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION. 2. SYSTEM SUPPLIER SHALL SUPERVISE INSTALLATION, PROGRAM AND TEST SYSTEM AND INSTRUCT OWNER ON SYSTEM OPERATION. 3. ALL FIRE ALARM WIRING SHALL BE PLENUM RATED. EXPOSED FIRE ALARM WIRING, 10'-0" AFF AND BELOW, SHALL BE INSTALLED IN CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR STRUCTURE. 4. ALL CONTROL CABINETS SHALL BE GROUNDED PER NEC REQUIREMENTS AND PER SPECIFICATIONS. 5. COORDINATE CITY TIE-IN REQUIREMENTS WITH LOCAL AUTHORITY. 6. DUCT SMOKES ARE FURNISHED AND WIRED BY EC, AND INSTALLED PER CODE BY MC. 7. ALL FIRE ALARM DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 & 'ADA'. PROVIDE WIRING PER MANUFACTURER'S INSTALLATION DRAWING (TYP) SYNCHRONIZING MODULE PROVIDE TELEPHONE LINE TO TERMINAL BOARD FOR CITY TIE-IN OR OFF-SITE MONITORING. PROVIDE TELEPHONE LINE FOR SECONDARY OFF-SITE MONITORING. 2#12 AWG, 1#12 AWG GND, 3/4"C. SCALE: NONE 3 E-1.1 ADDRESSABLE FIRE ALARM SYSTEM TYPICAL WIRING DIAGRAM PROVIDE WIRING TO EACH SECURITY DOOR MAG LOCK POWER SUPPLY LOCATION FOR UNLOCKING OF SECURITY DOORS DURING FIRE ALARM CONDITION. (COORDINATE WITH SECURITY SYSTEM SUPPLIER). PROVIDE WIRING TO PRE-ACTION (OR DRY TYPE) SPRINKLER SYSTEM CONTROL PANEL. PROVIDE WIRING TO STARTERS FOR FAN SHUTDOWN. PROVIDE WIRING AND RELAY REQUIRED TO SHUTDOWN TENANT SOUND SYSTEM UPON FIRE ALARM ACTIVATION. PANEL FOR TENANT 105 T5a 200A MCB 120/208V F=(MAX) 1 INCOMING SECTION WITH MAIN SWITCH 200AMP LANLDORD PANEL FOR TENANT 105 T5b 200A MCB 120/208V WIREWAY 1 TENANT 105 1 TENANT 106 PANEL FOR TENANT SPACE 106 MCB 120/208V F=(MAX) 1 2" CONDUIT AND PULLWIRE, STUB UP FROM METER CENTER TO TENANT 106 SPACE FOR FUTURE TENANT 107. COORDINATE STUB UP LOCATION WITH LANDLORD PRIOR TO INSTILLATION. F=(MAX) 1 H-10 SITE POLE LIGHTING H-12 RETAIL EXTERIOR BUILDING LTGS ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E0.1 ELECTRICAL LEGEND, NOTES, DETAILS 05/10/21