HomeMy WebLinkAboutMEP CoordinationEXTERIOR LANDLORD ROOM
ASSUMED 225KVA,120/208V
PAD MOUNTED UTILITY
TRANSFORMER
SCALE: NONE
1
E-1.1
ONE LINE DIAGRAM
SCALE:
1 OR 2 HOUR RATED
UL #WL1001
GYPSUM WALL BOARD ASSEMBLY
INTUMESCENT FIRESTOP SEALANT,
DEPTH AS REQUIRED BY THE
MANUFACTURER
METALLIC CONDUIT
NONE
5
E-1.1
FIRESTOP FOR METALLIC CONDUIT
M
GROUNDED CONDUCTOR (NEUTRAL) FROM
UTILITY COMPANY TRANSFORMER
10' 10'
10'
WITHIN 5' OF WATER
ENTRANCE TO BUILDING
SCALE: NONE
2
E-1.1
SERVICE GROUNDING AND BONDING DETAIL
INCOMING CONDUIT GROUND
(IF STEEL CONDUIT)
EQUIPMENT GROUNDING BUS
EQUIPMENT BONDING JUMPER
ENCLOSURE GROUND
MAIN BONDING JUMPER (#2/0)
PER NEC 250.102.(C)(1).
#6 AWG MINIMUM
10" X 2" X 1/4" COPPER GROUND BAR.
INSTALL ON TELEPHONE BACKBOARD WITH
(2) UL LISTED STANDOFF INSULATORS.
BONDING JUMPER
SOURCE (DIRECT CONTACT WITH EARTH
FOR 10' OR MORE)
COPPER CLAD STEEL, 10' x 3/4" WITH TOP
OF ROD 6" BELOW FINISH GRADE
(TYPICAL)
CLAMPS SUITABLE FOR DIRECT
BURIAL (TYPICAL)
NON-METALLIC PROTECTIVE SLEEVE
CONNECTOR LISTED FOR PURPOSE
CONCRETE ENCASED ELECTRODE
(REINFORCING STEEL)
EXOTHERMIC
CONNECTION
(TYPICAL)
METAL FRAME OF
BUILDING STRUCTURE
BONDING JUMPER (#2/0)
ABBREVIATIONS
UNDERWRITERS LABORATORIES, INC.
UNDERGROUND
UNLESS OTHERWISE NOTED
MAXIMUM OVER CURRENT PROTECTION
MCB MAIN CIRCUIT BREAKER
METAL HALIDE
MINIMUM
MTD MOUNTED
MOCP
MIN
MH
LOCKED ROTOR AMPS
MINIMUM CIRCUIT AMPACITY
MAXIMUM
LIGHTING
MAX
MCA
LTG
LRA
KILOVOLT-AMPS
KILOWATT-HOUR
KILOWATTS
KVA
KWH
KW
HEATER
HVAC HEATING, VENTILATING & A/C
HTR
GENERAL CONTRACTOR
GFI, GFIC GROUND FAULT INTERRUPTER
GC
FOOT, FEET
ELECTRICAL WATER COOLER
EXISTING
FIRE ALARM
FULL LOAD AMPS
FIRE ALARM CONTROL PANEL
EXHAUST
FT
FACP
FLA
FA
EX, EXIST
EWC
EXH
W WATT, WIDTH
VA
UL
UON
UG
T/C
VOLT-AMPERE
TIME CLOCK
SQUARE FEET, SQUARE FOOT
REFLECTED CEILING PLAN
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
OCCUPATIONAL SAFETY &HEALTH ADMIN.
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E0.3
PANEL SCHEDULES
05/10/21
106
VACANT
105
GARBANZO
104
RESTORE HYPER
WELLNESS
103
RISE 'N ROLL
102
DRY CLEANER
101
TROPICAL SMOOTHIE
CAFE
A
B
1 2 3 4 5 6
1 2 3 4 5 6
SCALE: 3/32" = 1'-0"
1
E1.1
ELECTRICAL PLAN
1
2
4
5
6
8
9 11
9
7
T1-4
T2-4
T3-4
T5a-4
PANEL T1
PANEL T2
PANEL T3
PANEL T5a
WP
GFI
WP H-6
H-6
3
PANEL H
7
T4-4
PANEL T4
SHEET KEYNOTES
1 UTILITY TRANSFORMER, PAD AND GROUNDING BY EC TO UTILITY COMPANY SPECIFICATIONS. REFER TO
SHEET E0.1 AND E1.2 FOR MORE INFORMATION.
2 LOCATION OF METER CENTER. FINAL APPROVED LOCATION SHALL BE VERIFIED WITH OWNER PRIOR TO
INSTALLATION OF SERVICE EQUIPMENT. SEE ONE-LINE DIAGRAM (SHEET E-1.1)
3 120/208V, 200AMP LANDLORD PANEL, VERIFY LOCATION WITH OWNER PRIOR TO ROUGH-IN.
4 4" TELEPHONE BACKBOARD, VERIFY LOCATION WITH OWNER PRIOR TO INSTALLATION.
5 UNDERGROUND SERVICE ENTRANCE CONDUITS. REFER TO DETAILS AND ONE LINE DIAGRAM ON SHEET
E0.1 FOR MORE INFORMATION.
6 STUB OUT FOR CONNECTION TO TELEPHONE. COORDINATE WITH TELEPHONE COMPANY AND VERIFY
CONNECTION LOCATION PRIOR TO INSTALLATION. REFER TO CIVIL PLANS FOR CONTINUATION.
7 400AMP, 120/208V PANEL FED FROM METER CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR
/ /
/
/
/ /
/
/
/
/ /
/
/
/
/ /
/
/
/ /
/
/
/
/ /
/
/
/
/
/
/ /
/
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/ /
/
/
/
/ /
/
/
/
/ /
/
1
T
RISE
POINT OF CONNECTION - NEW TO EXISTING
TURNING VANES
INCLINED RISE IN DUCT
IN-LINE 90 DEGREE RISE IN DUCT
RETURN OR EXHAUST AIR DUCT DOWN
DUCTWORK SIZE TRANSITION
RETURN OR EXHAUST AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT UP
SUPPLY OR OUTSIDE AIR DUCT DOWN
HVAC SYMBOLS
20/12
12"Ø
SUPPLY OR OUTSIDE AIR DUCT
90 DEGREE DUCTWORK ELBOW W/ TURNING VANES
ROUND OR RECTANGULAR
RECTANGULAR DUCTWORK BRANCH TAKE-OFF
HIGH EFFIECENY "BUCKLEY" TAP WITH DAMPER
RADIUS DUCTWORK ELBOW -
WITH 45 DEGREE BRANCH INLET
DIFFUSER/GRILLE LABEL:
B - NECK SIZE (INCHES)
A - TYPE/DESIGNATION
C - AIRFLOW (CFM)
RETURN, RELIEF OR EXHAUST AIR DUCT
PATTERN. NO PATTERN SHOWN EQUALS 4-WAY
FIRST NUMBER IS SIDE SHOWN
ROUND DUCTWORK. DIAMETER IN INCHES
RECTANGULAR DUCTWORK. SIZE IN INCHES,
SUPPLY AIR DIFFUSER - SHADING INDICATES
RETURN OR EXHAUST AIR GRILLE
OR AS NOTED
MANUAL VOLUME DAMPER
THERMOSTAT
SD
DRAWING NOTE REFERENCE
OVAL OR FLAT OVAL
ROUND
DUCT SMOKE DETECTOR
H HUMIDISTAT
S SENSOR
F
FIRE DAMPER
C CARBON DIOXIDE SENSOR
UC UNDERCUT DOOR 3/4" FOR AIRFLOW
XX/XXL INTERNALLY LINED DUCT
IN-LINE 90 DEGREE DROP IN DUCT
MOTORIZED DAMPER
MD
ABBREVIATIONS
EWB ENTERING WET BULB
TSTAT THERMOSTAT
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES, INC.
MAXIMUM OVER CURRENT PROTECTION
MAKE-UP AIR
MECHANICAL
MANHOLE, METAL HALIDE
MECHANICAL SPECIFICATIONS
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
M0.2
MECHANICAL
SPECIFICATIONS
05/10/21
106
VACANT
105
GARBANZO
104
RESTORE HYPER
WELLNESS
103
RISE 'N ROLL
102
DRY CLEANER
101
TROPICAL SMOOTHIE
CAFE
A
B
1 2 3 4 5 6
1 2 3 4 5 6
SCALE: 3/32" = 1'-0"
1
M1.1
MECHANICAL PLAN
ROOFTOP HVAC UNIT SCHEDULE
TAG SERVICE MFR MODEL No.
NOMINAL
TONS
EER
MIN OA
(CFM)
SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS
AIR FLOW NOTES/ACCESSORIES
(CFM)
ESP
(IN WC)
MOTOR
(HP)
FAN
(RPM)
EAT °DB/°WB
(°F)
LAT °DB/°WB
(°F)
SENSIBLE
(MBH)
TOTAL
(MBH)
COOLING
STAGES
EAT/LAT
(°F)
OUTPUT
(MBH)
HEATING
STAGES
VOLTAGE
(V-ɸ-Hz)
UNIT MCA UNIT MOCP
OPERATING
WEIGHT
(LBS)
GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD
WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY.
CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR
INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS.
2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS
TO ADJACENT SPACES.
5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE
AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE
REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN
CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS.
6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR
DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND
QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS
WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS.
7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION,
ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA.
8. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE
CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE
DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70.
10. PROVIDE STOP VALVES AT EVERY FIXTURE ON BOTH HOT AND COLD WATER SUPPLY LINES. VALVES,
ESCUTCHEONS, FITTINGS, ETC. MUST BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS
TO BE USED.
11. ALL SANITARY PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 1% SLOPE EXCEPT FOR 2" LINES
WHICH SHALL BE PITCHED AT 2% SLOPE.
12. ALL GREASE WASTE PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 2% SLOPE.
13. ALL OVERHEAD PIPING IS TO BE ROUTED TIGHT TO BUILDING STRUCTURE.
14. PIPING IS NOT PERMITTED IN DEMISING WALLS.
15. ALL EXPOSED, EXTERIOR PIPING SHALL BE PAINTED WITH RUST INHIBITIVE PRIMER, COLOR CODED
FINISH, AND IDENTIFICATION LABELS.
16. VERIFY NATURAL GAS AVAILABILITY AND CAPACITY. COORDINATE PRESSURE, SERVICE CONNECTION,
AND METER INSTALLATION WITH THE LANDLORD AND LOCAL UTILITY COMPANY.
17. PROVIDE GAS PIPE SUPPORTS ON ROOF. PROVIDE 10'-0" ON CENTER AND AT ALL CHANGES OF
DIRECTION. REFER TO DETAIL 6 ON THIS SHEET.
18. CLEAN AND REFURBISH EXISTING PLUMBING FIXTURES TO BE RE-USED. FIELD VERIFY EXISTING
PLUMBING FIXTURES ARE IN PROPER WORKING ORDER. NOTIFY OWNER IMMEDIATELY SHOULD
OPERATIONAL CHECK OF FIXTURES REVEAL ANY MAJOR COMPONENT FAILURES.
19. DO NOT ROUTE ANY WATER CONVEYING PIPING OVER ELECTRICAL EQUIPMENT.
20. ALL ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH BOTTOM CLEANOUT PLUGS.
21. INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING SERVING HANDICAPPED LAVATORIES.
22. TENANT SPACES, THAT ARE UN-OCCUPIED AT TIME OF OPENING, ARE TO HAVE PROVIDED BY FIRE
PROTECTION CONTRACTOR BRANCH PIPING AND SPRINKLER SPACING BASED ON THE ORDINARY
HAZARD GROUP II OCCUPANCY PER NFPA 13.
23. ALL PIPING TO POINTS 5'-0" OUTSIDE THE BUILDING IS BY THE PLUMBING CONTRACTOR.
24. PROVIDE A WALL CLEANOUT AT THE BASE OF ALL VERTICAL STORM AND SANITARY RISERS 1'-0" AFF.
25. FINISHED FLOOR ELEVATION = XXX.00
26. ALL STORM PIPING OUTSIDE THE PERIMETER OF THE BUILDING REQUIRES COORDINATION WITH THE
STRUCTURAL FOOTERS TO AVOID TRENCHING AND PIPE PLACEMENT WITHIN THE FOOTING ANGLE OF
REPOSE.
27. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
PLUMBING SPECIFICATIONS
I. GENERAL PROVISIONS
A. GENERAL CONDITIONS, CODES & STANDARDS
1. GENERAL CONDITIONS OF THE CONTRACT FOUND IN THE ARCHITECTURAL DRAWINGS, GENERAL
AND SPECIAL CONDITIONS OF THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND ANY OF THE
OWNER'S GENERAL REQUIREMENTS SHALL APPLY UNLESS NOTED OTHERWISE.
2. REFER TO THE GENERAL CONDITIONS ON THE ARCHITECTURAL DOCUMENTS AND THE GENERAL
AND SPECIAL CONDITIONS OF THE AIA FOR ADDITIONAL REQUIREMENTS REGARDING; SAFETY,
COORDINATION & COOPERATION, WORKMANSHIP, PROTECTION, CUTTING AND PATCHING, DAMAGE
TO OTHER WORK, PRELIMINARY OPERATIONS, STORAGE, ADJUSTMENTS, CLEANING, ETC.
3. ALL WORK SHALL BE IN CONFORMANCE WITH ALL LOCALLY ENFORCED, FEDERAL, STATE, AND
LOCAL CODES AND ORDINANCES INCLUDING ANY SPECIAL THE OWNER REQUIREMENTS IN ADDITION
TO THOSE SPECIFIED.
4. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS
REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION
WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS.
B. SCOPE OF WORK
1. THIS CONTRACT SHALL INCLUDE THE FURNISHING, INSTALLING, CONNECTING, AND OPERATION OF
ALL EQUIPMENT WHICH IS A PART OF THE FIRE SUPPRESSION SYSTEMS AS SHOWN ON THE
DRAWINGS AND AS REQUIRED BY SIMILAR INSTALLATIONS. ANY MATERIAL OR LABOR WHICH IS
NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS
OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF
A SIMILAR CHARACTER SHALL BE FURNISHED AND INSTALLED UNDER THIS CONTRACT AT NO
ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS
REQUIRED TO PROVIDE THE OWNER A COMPLETE, CODE APPROVED AND OPERATIONAL FIRE
SUPPRESSION SYSTEM.
2. CAREFULLY READ SPECIFICATION FOR ALL PARTS OF THE WORK SO AS TO BECOME FAMILIAR WITH
ALL TRADES' WORK SCOPE. CONSULT WITH OTHER TRADES TO INSURE PROPER LOCATIONS AND
AVOID INTERFERENCES. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER
BEFORE WORK IS COMMENCED.
3. CONTRACTORS SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO COMPARE
THEM WITH THE DRAWINGS AND SPECIFICATIONS, NOTE THE EXISTING CONDITIONS AND OTHER
WORK THAT WILL BE REQUIRED, AND THE NATURE OF THE CONDITIONS UNDER WHICH THE WORK IS
TO BE PERFORMED. NO ALLOWANCE SHALL BE MADE TO THE CONTRACTOR BY REASON OF THIS
FAILURE TO HAVE MADE SUCH EXAMINATION OR OF ANY ERROR ON HIS PART.
4. ALL EXISTING UTILITY AND FIRE SUPPRESSION SERVICES SHALL BE FIELD VERIFIED. CORRECTIONS
TO THE DESIGN AND INSTALLATION SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER.
5. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF FIRE PROTECTION WORK.
ALL CORE DRILLING OR CUTTING OF FIRE RATED FLOORS, SHAFTS, AND WALLS SHALL BE
FIRESTOPPED PRIOR TO FINISH PATCHING. ALL PENETRATIONS SHALL BE FIRE SEALED TO MATCH
THE FIRE RATING OF THE FLOORS, SHAFTS, AND WALLS PENETRATED. THIS CONTRACTOR IS
RESPONSIBLE TO COORDINATE THE OPENINGS IN WALLS AND FLOORS WITH THE GENERAL TRADES
CONTRACTOR. THE FINAL LOCATIONS AND SIZES OF ALL PIPE OPENINGS SHALL BE PROVIDED BY
THIS CONTRACTOR.
6. THIS CONTRACT SHALL ALSO INCLUDE ALL LABOR, MATERIALS AND MISCELLANEOUS EXPENSES
REQUIRED FOR ALL REQUIRED FIRE SUPPRESSION DEMOLITION OF THE EXISTING AREAS BEING
RENOVATED.
a. THE DEMOLITION SHALL CONSIST OF THE COMPLETE REMOVAL (PROPERLY DISPOSED OFF SITE
UNLESS OTHERWISE NOTED) OF ALL FIRE SUPPRESSION EQUIPMENT, PIPING, MATERIALS, ETC.
NOT REQUIRED IN THE FINAL DESIGN AND INSTALLATION OF THE FIRE SUPPRESSION SYSTEMS
FOR THE NEW RENOVATED AREAS.
b. ALL ABOVE GROUND SERVICES SHALL BE REMOVED BACK TO THEIR RESPECTIVE MAIN AND
CAPPED OR IF THE MAIN IS NOT REQUIRED, THE MAIN SHALL BE REMOVED IN IT'S ENTIRETY.
c. COORDINATE ALL DEMOLITION WITH THE ARCHITECTURAL DOCUMENTS AND THE ARCHITECT
AND THE OWNER'S GENERAL REQUIREMENTS.
7. ALL WORK INCLUDING, BUT NOT LIMITED TO PARTS, MATERIAL, EQUIPMENT AND LABOR SHALL BE
GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY THE ENGINEER AND OWNER. WHERE AN
EQUIPMENT MANUFACTURER HAS A WARRANTY THAT EXCEEDS ONE YEAR, THAT WARRANTY
PERIOD SHALL APPLY TO THIS PROJECT.
C. DOCUMENTS
106
VACANT
105
GARBANZO
104
RESTORE HYPER
WELLNESS
103
RISE 'N ROLL
102
DRY CLEANER
101
TROPICAL SMOOTHIE
CAFE
A
B
1 2 3 4 5 6
1 2 3 4 5 6
SHEET KEYNOTES
1 SEE SITE UTILITY PLAN FOR CONTINUATION
2 GAS METER
3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION.
4 EX 1000 GT
5
6
7
8
9
10
SCALE: 3/32" = 1'-0"
1
P1.1
PLUMBING PLAN
M
SEE ENLARGED
PLAN
EX CO
SEE ENLARGED
PLAN
SEE ENLARGED
PLAN
FCO
FCO
FCO
FCO
FCO
FCO
FCO
FCO
FCO
FCO
6" GW
6" SAN
EX CO
EX CO
EX CO
4
1
1
2
104
RESTORE HYPER
WELLNESS
4
SHEET KEYNOTES
1 SEE SITE UTILITY PLAN FOR CONTINUATION
2 GAS METER
3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION.
4 EX 1000 GT
5
6
7
8
9
10
SCALE: 1/4" = 1'-0"
1
P1.2
ENLARGED PLUMBING PLAN UNIT 104
GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR
SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER,
ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM
THAT IS DESCRIBED IN THE DOCUMENTS.
2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
STEEL WHICH EXISTS ABOVE THE SPACE.
5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT.
EWC
WH
MS
LAV WC
SK
SINK
SINK
SH
FCO
FCO
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
SHEET KEYNOTES
1 SEE SITE UTILITY PLAN FOR CONTINUATION
2 GAS METER
3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION.
4 EX 1000 GT
5
6
7
8
9
10
SCALE: 1/4" = 1'-0"
1
P1.2
ENLARGED PLUMBING PLAN UNIT 104
GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR
SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER,
ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM
THAT IS DESCRIBED IN THE DOCUMENTS.
2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
STEEL WHICH EXISTS ABOVE THE SPACE.
5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT.
SCALE: 1/4" = 1'-0"
3
P1.2
ENLARGED RESTROOM UNIT 103
SCALE: 1/4" = 1'-0"
5
P1.2
ENLARGED RESTROOM UNIT 101
FCO
LAV
WC
SCALE: 1/4" = 1'-0"
2
P1.2
ENLARGED RESTROOM UNIT 103
SCALE: 1/4" = 1'-0"
4
P1.2
ENLARGED RESTROOM UNIT 101
FD
LAV
WC
FCO
FD
LAV
WC
FCO
WH
FFD
TP
LAV
WC
TP
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P1.3
ENLARGED PLUMBING
PLANS
05/10/21
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P1.2
ENLARGED PLUMBING
PLAN
add rough ins as
required in walls.
05/10/21
3
GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR
SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER,
ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM
THAT IS DESCRIBED IN THE DOCUMENTS.
2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
STEEL WHICH EXISTS ABOVE THE SPACE.
5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT.
FCO FCO FCO FCO FCO FCO
FCO FCO FCO FCO FCO FCO FCO
M
1
1
2
3
M
1
1
2
3
M
1
1
2
3
M
1
1
2
3
M
1
1
2
3
M
1
1
2
3
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P1.1
PLUMBING
PLAN
hose bib
05/10/21
1. THE DRAWINGS ARE DIAGRAMMATIC, ALL WORK SHALL BE PERFORMED AS INDICATED ON THE
DRAWINGS UNLESS EXISTING CONDITIONS OR COORDINATION ISSUES REQUIRE CHANGES. THESE
CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER.
2. ANY INCIDENTAL ITEMS OR LABOR, ETC. NOT INCLUDED IN THE SPECIFICATIONS OR THE DRAWINGS
BUT REASONABLY IMPLIED AS NECESSARY FOR THE COMPLETE INSTALLATION OF ALL APPARATUS
SHALL BE INCLUDING IN BID.
3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY
MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NOT MENTIONED IN
BOTH.
4. IF ERRORS ARE FOUND IN THE DRAWINGS OR SPECIFICATIONS OR DISCREPANCIES OCCUR
BETWEEN THE SAME, OR BETWEEN THE FIGURES ON THE DRAWINGS, AND THE SCALE OF SAME OR
BETWEEN THE LARGER AND SMALLER DRAWINGS, OR IN THE DESCRIPTIVE MATTER ON THE
DRAWINGS SHALL BE REFERRED TO THE OWNER FOR REVIEW AND FINAL DECISION PRIOR TO THE
BID DUE DATE.
5. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY
AS SPECIFIED HEREIN. WHERE MORE THAN ONE MANUFACTURER IS MENTIONED ANY ONE MAY BE
UTILIZED. SUBSTITUTE MANUFACTURERS MAY BE OFFERED ONLY AS AN ALTERNATE TO THE
SPECIFIED EQUIPMENT AND MATERIAL AND MUST BE SUBMITTED AS SPECIFIED IN THE
ARCHITECTURAL DOCUMENTS.
6. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY RECOGNIZED
MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN THESE
SPECIFICATIONS. REFER TO EACH SECTION FOR ANY SPECIFIC REQUIREMENTS.
D. COORDINATION
1. CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES WHICH ARE
REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA CAUTION IN THE
PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF
DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE.
2. EACH CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGE TO OTHER WORK CAUSED BY
HIS WORK OR THROUGH THE NEGLECT OF HIS, OR HIS SUB-TRADE'S PERSONNEL. ALL PATCHING,
REPAIRING, REPLACEMENT AND PAINTING, ETC. SHALL BE DONE AS DIRECTED BY THE OWNER BY
THE CRAFTSMEN OF THE TRADES INVOLVED. THE COSTS OF SUCH WORK SHALL BE PAID BY THE
CONTRACTOR CAUSING THE DAMAGE.
E. METHODS
1. EQUIPMENT, PIPING, DUCTWORK, ETC. SHALL NOT BE SUPPORTED FROM ANY CEILINGS, OTHER
PIPING, CONDUIT OR DUCTWORK, ROOF DECK, OR JOIST BRIDGING. ITEMS SHALL BE SUPPORTED
FROM ACCEPTABLE STRUCTURAL BUILDING COMPONENTS AS DETERMINED BY THE ARCHITECT AND
STRUCTURAL ENGINEER.
F. SUBMITTALS
1. SHOP DRAWINGS
a. PREPARE AND SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE MECHANICAL GENERAL
PROVISIONS.
b. SHOW PLANS, CROSS SECTION, ELEVATIONS, DETAILS AND JOB CONDITIONS, RELATIONSHIP
TO OTHER WORK. PIPE SIZES, ELEVATIONS ABOVE FLOOR, HEAD LOCATIONS, INSPECTORS
TEST CONNECTION, SPRINKLER ENTRANCE, VALVES, ALARMS, BACKFLOW PREVENTER, FLOW
SWITCH AND SUPERVISORY DEVICES.
c. SUBMIT DATA ON THE FOLLOWING ITEMS:
(1)PIPING AND COUPLINGS.
(2)WET ALARM VALVE.
(3)BACKFLOW PREVENTER.
(4) VALVES AND SUPERVISORY DEVICES.
(5)SPRINKLER HEADS AND ESCUTCHEON PLATES.
(6)SUPPORTS, HANGERS AND ACCESSORIES.
(7)SEISMIC CALCULATIONS
(8)SUBMIT AND RECEIVE APPROVAL FROM THE AUTHORITY HAVING JURISDICTION PRIOR TO
SUBMITTAL.
d. ONCE THE AUTHORITY HAVING JURISDICTION HAS APPROVED SHOP DRAWINGS, THE
SUBCONTRACTOR SHALL SEND EIGHT SETS OF APPROVED STAMPED PLANS AND EQUIPMENT
CUTS TO THE ARCHITECT FOR APPROVAL.
e. PLANS SUBMITTED WITHOUT ALL HYDRAULIC CALCULATIONS WILL BE RETURNED "REJECTED".
d. PROVIDE INDEPENDENT HYDRAULIC CALCULATION SHEETS.
f.ALL SPRINKLER PLANS SHALL BEAR THE STAMP OF A REGISTERED PROFESSIONAL FIRE
PROTECTION ENGINEER LICENSED WITH THE STATE WHERE THE STORE IS LOCATED.
2. AT THE COMPLETION OF THE PROJECT, PROVIDE OWNER WITH OPERATION AND MAINTENANCE
MANUALS INCLUDING "AS-BUILT" RECORD DRAWINGS, SPECIFICATIONS AND APPROVED PLANS.
3. PROJECT RECORD DOCUMENTS - MAINTAIN AT THE JOBSITE ONE COPY OF ALL CONTRACT
DOCUMENTS CLEARLY MARKED AS “PROJECT RECORD COPY”. THESE DRAWINGS ARE TO BE
MAINTAINED IN GOOD CONDITION, UPDATED DAILY FOR CHANGES ENCOUNTERED AND AVAILABLE
AT ALL TIMES FOR INSPECTION BY THE OWNER. DO NOT USE FOR FIELD CONSTRUCTION! PROJECT
RECORD DOCUMENTS ARE TO BE KEPT CURRENT WITH EXACT DIMENSIONS OF ALL WORK,
EQUIPMENT, PIPING, VALVES, DUCTWORK, ETC. MARK ALL INFORMATION IN RED LINES AND NOTES
SO AS TO BE EASILY IDENTIFIED FROM THE BASE DRAWING. UPON COMPLETION OF THE WORK,
ONE SET OF THESE DOCUMENTS SHALL BE TURNED OVER TO THE OWNER AS ONE QUALIFICATION
FOR FINAL PAYMENT.
4. AFTER THE ACCEPTANCE TESTS ARE COMPLETED AND ACCEPTED BY THE OWNER, THREE
COMPLETE SETS OF AS-BUILT DOCUMENTATION SHALL BE PROVIDED. IT SHALL INCLUDE, BUT NOT
BE LIMITED TO ACCURATE PLAN DRAWINGS AND OPERATION AND MAINTENANCE MANUALS.
II. SPRINKLER
A. GENERAL
1. THE ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF NFPA 13, THE BUILDING
OWNER'S INSURANCE COMPANY, THE LOCALLY ENFORCED BUILDING CODE, LOCAL BUILDING AND
FIRE OFFICIALS AND ALL OTHER LOCAL AUTHORITIES HAVING JURISDICTION.
2. ALL WORK SHALL BE PERFORMED BY A LANDLORD APPROVED, STATE OF IN WHICH THE PROJECT IS
BEING CONSTRUCTED LICENSED SPRINKLER CONTRACTOR.
3. THIS WORK SHALL INCLUDE ALL PIPING, FITTINGS, HANGERS, EQUIPMENT, ETC., REQUIRED TO
COMPLETE THE WORK.
4. SPRINKLER HEADS ARE TO BE CENTERED IN LAY-IN CEILING TILES. HEADS ARE TO BE SPACED
SYMMETRICALLY WITH LIGHTING AND OTHER CEILING FIXTURES WHEN INSTALLED IN DRYWALL
CEILINGS.
5. DETERMINE VOLUME AND PRESSURE OF INCOMING WATER SUPPLY FROM WATER FLOW TEST DATA.
REVISE DESIGN WHEN TEST DATA BECOMES AVAILABLE PRIOR TO SUBMITTALS.
B. CRITERIA
1. CONTRACTOR SHALL VERIFY WITH THE OWNER'S REPRESENTATIVE FOR ANY ADDITIONAL CRITERIA
(PIPE SIZING; PIPE SCHEDULE OR HYDRAULIC).
2. CONTRACTOR SHALL DESIGN AND MODIFY THE EXISTING SPRINKLER SYSTEM PIPING AND HEADS
FOR THE SPACE. THIS WORK SHALL INCLUDE THE RAISING OF ANY EXISTING SPRINKLER PIPING
WHICH INTERFERES WITH DESIGNED CEILING ELEVATIONS. WHERE REQUIRED, THE CONTRACTOR
SHALL ALSO INCLUDE COMBINING THE EXISTING SYSTEM TO A SINGLE SOURCE WHEN TAKING OVER
MULTIPLE TENANTS. PROVIDE ANY AUXILIARY DRAIN PIPING REQUIRED FOR ANY TRAPPED
SPRINKLER PIPING.
3. SEE ARCHITECTURAL DRAWINGS FOR CEILING ELEVATIONS.
C. COMPONENTS
1. FIRE DEPARTMENT CONNECTION: POTTER-ROEMER OR EQUAL SERIES 5020 (CONNECTION SIZES
COORDINATED AND APPROVED BY THE LOCAL AUTHORITITES), WITH ALL STANDARD FEATURES,
"AUTO. SPKR." LETTERING, AND THREAD TO MATCH LOCAL FIRE DEPARTMENT REQUIREMENTS. -
FLUSH MOUNTED FIRE DEPARTMENT INLET CONNECTION WITH WALL PLATE WITH “AUTOMATIC
SPRINKLER” IDENTIFICATION, ALL BRASS CONSTRUCTION AND POLISHED BRASS FINISH. CONTACT
THE FIRE DEPARTMENT TO VERIFY FIRE DEPARTMENT CONNECTION TYPE AND TREAD PATTERN TO
MATCH THAT OF THE FIRE DEPARTMENT EQUIPMENT. PROVIDE 4" UL LISTED CHECK VALVE WITH
BALL DRIP PIPED TO DRAIN.
D. SUPERVISION
1. THE RISER CONTROL VALVE AND ALL ZONE VALVES SHALL HAVE ELECTRIC SUPER VISION TO
SIGNAL THE BUILDING FIRE ALARM SYSTEM. TAMPER SWITCHES PROVIDED BY SPRINKLER
SUBCONTRACTOR AND WIRED BY THE ELECTRICAL SUBCONTRACTOR.
2. MECHANICAL: ALL OTHER VALVES SHALL BE PADLOCKED IN STANDARD OPERATING POSITION, WITH
2 KEYS PER PADLOCK AND ALL PADLOCKS SHALL BE KEYED THE SAME. CHAIN AND PADLOCK ALL
VALVES OVER 2" SIZE.
E. PIPING
1. PIPING SHALL BE BLACK STEEL PIPE PER NFPA 13.
F. SPRINKLER HEADS
1. SPRINKLER HEADS IN AREAS WITH CEILINGS SHALL BE RECESSED, POLISHED CHROME PENDANT
AUTOMATIC SPRINKLER HEAD WITH TWO PIECE FACTORY WHITE METAL ESCUTCHEON.
2. SPRINKLER HEADS IN AREAS WITH DRYWALL CEILINGS SHALL BE FLUSH SERIES WITH A WHITE
CEILING PLATE.
3. SPRINKLER HEADS IN AREAS WITH EXPOSED STRUCTURE SHALL BE BRASS UPRIGHT.
III. LABELING
A. TAGS
1. METAL TAGS:
a. BRASS WITH STAMPED LETTERS; TAG SIZE MINIMUM 1-1/2 INCHES DIAMETER.
2. TAG CHART: TYPEWRITTEN LETTER SIZE LIST OF APPLIED TAGS AND LOCATION IN ANODIZED
ALUMINUM FRAME.
B. PIPE MARKERS
1. COLOR AND LETTERING: CONFORM TO ASME A13.1.
2. PLASTIC PIPE MARKERS:
a. FACTORY FABRICATED, FLEXIBLE, SEMI-RIGID PLASTIC, PREFORMED TO FIT AROUND PIPE OR
PIPE COVERING. LARGER SIZES MAY HAVE MAXIMUM SHEET SIZE WITH SPRING FASTENER.
C. INSTALLATION
1. INSTALL IDENTIFYING DEVICES AFTER COMPLETION OF COVERINGS AND PAINTING.
2. INSTALL PLASTIC NAMEPLATES WITH CORROSIVE-RESISTANT MECHANICAL FASTENERS, OR
ADHESIVE.
3. INSTALL TAGS USING CORROSION RESISTANT CHAIN. NUMBER TAGS CONSECUTIVELY BY
LOCATION.
4. IDENTIFY VALVES IN MAIN AND BRANCH PIPING WITH TAGS.
5. IDENTIFY PIPING, CONCEALED OR EXPOSED, WITH PLASTIC PIPE MARKERS, PLASTIC TAPE PIPE
MARKERS OR STENCILED PAINTING. IDENTIFY SERVICE, FLOW DIRECTION, AND PRESSURE.
INSTALL IN CLEAR VIEW AND ALIGN WITH AXIS OF PIPING. LOCATE IDENTIFICATION NOT TO EXCEED
20 FEET ON STRAIGHT RUNS INCLUDING RISERS AND DROPS, ADJACENT TO EACH VALVE AND TEE,
AT EACH SIDE OF PENETRATION OF STRUCTURE OR ENCLOSURE, AND AT EACH OBSTRUCTION.
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P0.2
PLUMBING
SPECIFICATIONS
05/10/21
STEEL WHICH EXISTS ABOVE THE SPACE.
28. CONTRACTOR SHALL VERIFY IF SPRINKLER HEADS UNDER STOCK SHELVING ARE REQUIRED.
29. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN LEAK PROOF AND FREE FROM DEFECTS PRIOR
TO CONCEALMENT.
30. ALL FLOOR DRAINS AND CLEANOUTS ARE TO BE INSTALLED FLUSH WITH THE FINISHED FLOOR.
31. ALL FLOOR SINKS ARE TO BE INSTALLED EITHER FLUSH WITH FINISHED FLOOR, OR RAISED PER LOCAL
CODE REQUIREMENTS.
ABBREVIATIONS
TMV THERMOSTATIC MIXING VALVE
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES, INC.
MAKE-UP AIR
MECHANICAL
MANHOLE
MANUFACTURER
MINIMUM
MTD MOUNTED
MUA
MECH
MFR
MIN
MH
1000 BTU PER HOUR
MAXIMUM
LOW PRESSURE
POUNDS
MAX
MBH
LBS, #
LP
H HEIGHT
KEC KITCHEN EQUIPMENT CONTRACTOR
HEAD, HUB DRAIN
HORSEPOWER
HEATING, VENTILATING & A/C
HYDRANT
DOMESTIC HOT WATER
HERTZ
HVAC
HYD
HW
HZ
HD
HP
ELECTRICAL CONTRACTOR
GALLON
GALVANIZED
GENERAL CONTRACTOR
GREASE INTERCEPTOR
GALLONS PER MINUTE
GALLONS PER HOUR
GALLONS PER DAY
GAUGE
GREASE WASTE
GI
GPD
GPM
GPH
GW
GAL
GALV
GC
GA
DEGREES FAHRENHEIT
FOOT, FEET
EXISTING
FLOOR DRAIN
FLEXIBLE
FEET PER MINUTE
FLOOR SINK
FLOOR CLEANOUT
EXHAUST
°F
FT
FLEX
FPM
FCO
FD
FS
EX
EXH
EC
W/
W/O
WC
VTR
WITH
WATER COLUMN
WITHOUT
VENT THROUGH ROOF
VAC
UON
U/F
U/G
U/S
UL
TYP
VACUUM
VENT
UNDERGROUND
UNDERSLAB
UNDERFLOOR
TYPICAL
SQUARE FEET, SQUARE FOOT
REVOLUTIONS PER MINUTE
TOTAL STATIC PRESSURE
STORM WATER
POST INDICATOR VALVE
POUNDS PER SQUARE INCH
PRESSURE RELIEF VALVE
REFLECTED CEILING PLAN
REINFORCING, REINFORCED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
OUTSIDE STEM AND YOKE
OCCUPATIONAL SAFETY & HEALTH ADMIN.
AWWA AMERICAN WATER WORKS ASSOC.
EXTERNAL STATIC PRESSURE
ELECTRICAL
ELEVATION
EQUIPMENT
ENCLOSURE
DRAWING
EACH
ESP
ENCL
ELEC
EQUIP
ELEV
EA
DWG
DOMESTIC COLD WATER
DOWNSPOUT
DIAMETER
DEGREES
DIMENSION
DOWN
DS
DIA (OR Ø)
DN
DIM
CW
DEG
SPEC SPECIFICATION
THRU
TP
TSP
TDH
STD
SUSP
SURF
ST
SQ
TOTAL DYNAMIC HEAD
THROUGH
TOTAL PRESSURE
SUSPEND
STANDARD
SURFACE
SQUARE
SECT
SHT
SF
RPM
SECTION
SHEET
CONCRETE
CENTERLINE
COLUMN
CLEANOUT
CEILING
CUBIC FEET PER MINUTE
CUBIC FEET PER HOUR
L
CLG
COL
CO
C
CC
CFM
CFH
ASSY ASSEMBLY
RD
REQ
REV
REINF
RCP
ROOF DRAIN
REQUIRED
REVISION, REVISE
PRV
PSI
PH, Ø
PIV
PLBG
PD
PLUMBING
PRESSURE DROP
PHASE
AMERICAN NAT'L STANDARDS INSTITUTE
AMERICAN SOCIETY OF TESTING & MATLS
AMERICAN SOCIETY OF MECHANICAL ENGRS
ABOVE FINISHED GRADE
AUXILIARY
ARCHITECT, ARCHITECTURAL
AMERICAN WELDING SOCIETY
ADJUSTABLE
ABOVE FINISHED FLOOR
ABOVE FINISHED CEILING
ASME
ASTM
AUX
AWS
AFG
ARCH
ANSI
ADJ
AFF
AFC
ABV ABOVE
OS&Y
OSHA
OD
OC
NFPA
NTS
N.O.
NIC
OVERFLOW DRAINAGE
ON CENTER
NOT TO SCALE
NORMALLY OPEN
NOT IN CONTRACT
NEC
NEMA
N/A NOT APPLICABLE
ETR EXISTING TO REMAIN
REX REMOVE EXISTING
COP CLEANOUT PLUG
ORD OVERFLOW ROOF DRAIN
RWC RAIN WATER CONDUCTOR
BOTTOM OF PIPE
BUILDING
BRITISH THERMAL UNIT
BOTTOM OF STRUCTURE
BUILDING AUTOMATION SYSTEM
BLDG
BOP
BOS
BTU
BAS
BELOW FLOOR
BMS BUILDING MANAGEMENT SYSTEM
DOM DOMESTIC
FP FIRE PROTECTION
FW FILTERED WATER
GRD GROUND
MC MECHANICAL CONTRACTOR
O/H OVERHEAD
OPNG OPENING
REL RELOCATED
SAN SANITARY
D DEPTH
G GAS
CONN CONNECT, CONNECTION
STUB UP FOR FUTURE
DCV
PLUMBING SYMBOLS
GAS MANIFOLD LOCATION
DOMESTIC WATER RISER
PLUMBING FIXTURES
DOUBLE CHECK BACKFLOW PREVENTER
SPRINKLER HEAD (SEMI-RECESSED)
SPRINKLER HEAD (FULLY-RECESSED)
SPRINKLER HEAD (UPRIGHT)
TENANT CONNECTION
N.C. NORMALLY CLOSED
PB PUSH BUTTON
HWR DOMESTIC HOT WATER RETURN
B/F
CTE CONNECT TO EXISTING
FF FINISHED FLOOR
RR REMOVE AND RELOCATE
ID INSIDE DIAMETER
INVERT ELEVATION
INCH, INCHES
IN w.c INCHES OF WATER COLUMN (GAS)
IN
IE
V
OS&Y VALVE
BALL VALVE
ELBOW DOWN
ELBOW UP
UNION
TEE OUTLET UP
TEE OUTLET DOWN
DIRECTION OF FLOW
VALVE IN DROP
EXPANSION JOINT
GATE VALVE
CALIBRATED BALANCING VALVE
PIPE GUIDE
3-WAY SELF OPERATING VALVE
BUTTERFLY VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
MOTOR OPERATED VALVE
2-WAY SELF OPERATING VALVE
M
HOSE BIB
GW GREASE WASTE
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE REMOVED
NEW PIPING / EQUIPMENT
FS
T&P RELIEF VALVE
PRESSURE SWITCH
CAP ON END LINE
FLOW SWITCH
PRESSURE GAUGE WITH GAUGE COCK
THERMOMETER
FLEXIBLE CONNECTION
PIPE FLANGE
THERMOMETER WELL
GAS VALVE
WALL CLEANOUT OR CLEAOUT PLUG
FLOOR CLEANOUT
M WATER METER
R GAS REGULATOR
FLOOR SINK (FS)
FLOOR DRAIN WITH P-TRAP
DRAWING NOTE REFERENCE
NEW TO EXISTING
POINT OF CONNECTION -
1
PS
(ALL ABBREVIATIONS SHOWN ARE NOT
NECESSARILY USED ON DRAWINGS)
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS)
PIPING ABOVE FLOOR
PIPING BELOW FLOOR
SAN SANITARY PIPING
OD
RWC
G
OVERFLOW DRAIN PIPING
HOT WATER (HW) PIPING
COLD WATER (CW) PIPING
NATURAL GAS PIPING
HOT WATER RECIRCULATION (HWR)
STORM PIPING (ABOVE GROUND)
V SANITARY VENT PIPING
ST STORM PIPING (UNDERGROUND)
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P0.1
PLUMBING
LEGEND, NOTES, DETAILS
05/10/21
RTU-1 TROPICAL SMOOTHIE TRANE YSC120 10 11.2 200 4000 0.75 2.75 1465 80.0/67.0 58.8/58.0 96.8 116.3 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18
RTU-2 DRY CLEANER TRANE YSC036 3 12.0 60 1200 0.75 0.75 1061 80.0/67.0 59.3/57.9 29.2 37.0 MOD 50.0/112.7 81.0 2 208-3-60 20.0 30.0 850 1-18
RTU-3 RISE AND ROLL TRANE YSC048 4 12.0 80 1600 0.75 1.00 1181 80.0/67.0 58.8/57.6 37.9 48.9 MOD 50.0/97.1 81.0 2 208-3-60 26.0 35.0 850 1-18
RTU-4 RESTORE HYPER WELLNESS TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18
RTU-5 RESTORE HYPER WELLNESS TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18
RTU-6 GARBANZO TRANE YSC060 5 12.0 110 2100 0.75 1.50 1147 80.0/67.0 60.2/58.7 49.6 60.3 MOD 50.0/86.0 81.0 2 208-3-60 30.0 45.0 880 1-18
RTU-7 GARBANZO TRANE YSC060 5 12.0 110 2100 0.75 1.50 1147 80.0/67.0 60.2/58.7 49.6 60.3 MOD 50.0/86.0 81.0 2 208-3-60 30.0 45.0 880 1-18
RTU-8 TENANT TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18
RTU-9 TENANT TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18
NOTES/ACCESSORIES
1. 95° CONDENSING TEMPERATURE
2. REFRIGERANT - R410A
3. REFERENCE ENTHALPY ECONOMIZER WITH FAULT DIAGNOSTIC DETECTION
4. BAROMETRIC RELIEF
5. 14"INSULATED ROOF CURB
6. UNIT MOUNTED NON FUSED DISCONNECT
7. UNPOWERED GFCI RECEPTACLE
8. SUPPLY FAN VFD WITH SINGLE ZONE VAV CONTROLLER
9. THROUGH THE BASE ELECTRICAL
10. HAIL GUARD - WITH TOOL LESS REMOVAL
11. RTU MFANUACTURER'S PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT WITH OCCUPANCY OUTSIDE AIR CONTROL.
12. HINGED ACCESS DOORS
13. ONCE THE RTU’S ARE OPERATIONAL - PROVIDE 2” MERV 8 FILTERS. INSPECT FILTERS DAILY. REPLACE AS NEEDED BUT NOT LONGER THAN 7 DAYS UNTIL UNIT IS ADJUSTED BY BALANCE CONTRACTOR. AT THE
DISCRETION OF THE TENANT CONSTRUCTION REPRESENTATIVE THIS FILTER REPLACEMENT CAN BE EXTENDED PAST THE 7 DAY LIMIT. ALL UN-USED FILTERS TO REMAIN ON SITE
FOR FUTURE USE BY TENANT. NEVER OPERATE THE RTU(S) IN COOLING DURING ANY SANDING OR DEMOLITION OR IF ANY TYPE OF FINE PARTICULATE COULD BE AIR BORNE. ALL RETURN AIR GRILLES OPENING IN
RETURN AIR DUCTWORK SHALL BE COVERED WITH CHEESE CLOTH OR A THROW AWAY FILTER (CHEAP CUT TO FIT FILTER ROLL) UNTIL UNITS ARE ADJUSTED BY THE
BALANCING CONTRACTOR. REMOVE THIS CHEESE CLOTH FILTER UPON TESTING BY BALANCE CONTRACTOR.
14. MICRO-PROCESSOR CONTROLS
15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY
16. STAINLESS STEEL HEAT EXCHANGER WITH STAGED HEAT
17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER
18. APPROVED ALTERNATES: CARRIER, AAON, YORK/JOHNSON CONTROLS, AND LENNOX
OUTLINE
OF RTU-1
ON ROOF
GENERAL SHEET NOTES
1. EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND
FIELD WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR
ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY
SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN
THE DOCUMENTS.
2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS
PROJECT.
3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL
PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN
THE INFORMATION PRESENTED AND FIELD CONDITIONS.
4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF
SYSTEMS TO ADJACENT SPACES.
5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST
DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT,
ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE
DEMOLITION AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS.
6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR
DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL
CAPACITY AND QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE
USED, USE MATERIALS WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF
THE EXISTING MATERIALS.
7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW
CONSTRUCTION, ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION
AREA.
8. MECHANICAL SYSTEMS INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND
FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL
PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE
W/ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS
ABOVE CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50
SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA
70.
10. LIMITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF
MECHANICAL WORK WITH ALL DUCTWORK, SPRINKLERS, LIGHT FIXTURES, AND OTHER CEILING
BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT
ARISE.
11. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD
APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ROOF
PENETRATIONS AND ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL
CONTRACTOR.
12. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF
DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR
THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE.
13. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH LANDLORDS STRUCTURAL ENGINEER.
ROOFTOP UNITS AND MAKE-UP AIR UNIT TO BE LOCATED WITHIN STRUCTURAL BAY. PROVIDE 10'
CLEARANCE FROM UNIT OUTSIDE AIR INTAKE TO ANY EXHAUST/VENTS ON ROOF.
14. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE
NUMBER AND EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND
STANDARDS.
15. REFER TO MALL CRITERIA MANUAL FOR ADDITIONAL STANDARDS AND REQUIREMENTS.
16. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND
ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC
CONTRACTOR, MOUNT PER ADA REQUIREMENTS.
17. ALL EXPOSED DUCTWORK TO BE PAINTED. REFER TO ARCHITECTURAL PLANS.
18. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM
INCLUDE ANGLE OF DIVERGENCE OF 15 DEGREE.
19. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE
ALLOWANCE FOR INTERNAL INSULATION.
20. ALL SUPPLY AND MAKE-UP AIR DUCTWORK NOT EXPOSED SHALL BE EXTERNALLY INSULATED.
21. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE
INDICATED UNLESS NOTED OTHERWISE.
22. PROVIDE A STRAIGHT INLET LENGTH TO THE VAV BOX OF A MINIMUM (4) DUCT DIAMETERS.
REFER TO DETAIL FOR ADDITIONAL INFORMATION.
23. PROVIDE ACCESS HATCHES (24"x24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD
CEILING. COORDINATE W/ ARCHITECTURAL CEILING PLANS.
24. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR
CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR
THROUGH PRE-MANUFACTURED PIPING CURB.
25. COORDINATE EXACT MOUNTING REQUIREMENTS AND LOCATION OF HOOD WITH HOOD SHOP
DRAWINGS AND OWNER REQUIREMENTS.
26. GREASE EXHAUST DUCT ACCESS PANEL CLEANOUT OPENINGS SHALL BE EQUIPPED WITH
TIGHT FITTING DOORS (EQUAL TO THE THICKNESS OF THE DUCT) AND SHALL HOLD TIGHTLY
CLOSED.
27. ALL DUCTWORK, DIFFUSERS AND GRILLES IN POOL AREA SHALL BE ALUMINUM CONSTRUCTION.
28. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN ROOFTOP UNITS WITH NEW CLEAN FILTERS
BEFORE AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT.
SHEET KEYNOTES
1 TRANSITION LINED SUPPLY DUCT IN RISE TO FULL SIZE OF RTU SUPPLY OPENING. CONNECT TO
FULL SIZE OF RTU SUPPLY OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND SA
DUCTWORK TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION.
REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
2 TRANSITION LINED RETURN DUCT IN RISE TO FULL SIZE OF RTU RETURN OPENING. CONNECT
TO FULL SIZE OF RTU RETURN OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND
RA DUCTWORK TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION.
REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
3 SMOKE DETECTOR MOUNTED IN RETURN DUCT. DETECTOR SHALL BE PROVIDED AND WIRED BY
ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. COORDINATE WITH
GENERAL CONTRACTOR TO PROVIDE 24/24 ACCESS PANEL FOR DUCT MOUNTED SMOKE
DETECTOR. ACCESS PANEL MAY BE OMITTED IT DETECTOR IS ACCESSIBLE THROUGH LAY-IN
DIFFUSER, OR IF DETECTOR IS LOCATED IN AREA WITH NO CEILING.
1
2 SD 3
1
2 SD 3
1
2 SD
3
SD 3
1
2
1
2
1
2
3 SD
SD 3
1
2
1
2
1
2 SD
SD 3 SD 3 3
OUTLINE
OF RTU-2
ON ROOF
OUTLINE
OF RTU-3
ON ROOF
OUTLINE
OF RTU-4
ON ROOF
OUTLINE
OF RTU-6
ON ROOF
OUTLINE
OF RTU-8
ON ROOF
OUTLINE
OF RTU-9
ON ROOF
OUTLINE
OF RTU-5
ON ROOF
OUTLINE
OF RTU-7
ON ROOF
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
M1.1
MECHANICAL
PLAN
note to refer to
tenant's plan and
install trunks and
diffusers
note to refer to
tenant's plan and
install trunks and
diffusers
note to refer to
tenant's plan and
install trunks and
diffusers
add a note to install
complete HVAC as
required by tenant's
plans.
05/10/21
MANUFACTURER
MINIMUM
MOUNTED
MOTORIZED DAMPER
MOTOR CONTROL CENTER
MTD
MUA
MECH
MFR
MOCP
MIN
MH
MCC
MD
LEAVING WATER TEMPERATURE
LOCKED ROTOR AMPS
1000 BTU PER HOUR
MINIMUM CIRCUIT AMPACITY
MAXIMUM
LIGHTING
LEAVING WET BULB
LEAVING DRY BULB
LOW PRESSURE
LEAVING AIR TEMPERATURE
INTERNALLY LINED
POUNDS
LWB
LWT
MAX
MCA
MBH
LTG
LBS, #
L
LAT
LRA
LDB
LP
H HEIGHT
KILOVOLT-AMPS
KILOWATT-HOUR
KILOWATTS
KVA
KWH
KW
HEAD, HUB DRAIN
HAND-OFF-AUTOMATIC
HORSEPOWER, HEAT PUMP
HUMIDISTAT
HEATER
HEATING
HEATING, VENTILATING & A/C
HYDRANT
DOMESTIC HOT WATER
HERTZ
HVAC
HYD
HW
HZ
HSTAT
HTR
HTG
HOA
HD
HP
ELECTRICAL CONTRACTOR
GALLON
GALVANIZED
GENERAL CONTRACTOR
GROUND FAULT INTERRUPTER
GALLONS PER MINUTE
GALLONS PER HOUR
GALLONS PER DAY
GAUGE
GREASE WASTE
GFI, GFIC
GPD
GPM
GPH
GW
GAL
GALV
GC
GA
DEGREES FAHRENHEIT
FOOT, FEET
ENTERING WATER TEMPERATURE
EXISTING
FIRE ALARM
FIRE DAMPER
FLEXIBLE
FEET PER MINUTE
FULL LOAD AMPS
FLOOR CLEANOUT
FIRE ALARM CONTROL PANEL
EXHAUST
°F
FT
FACP
FLEX
FPM
FCO
FD
FLA
FA
EX
EWT
EXH
EC
VAV VARIABLE AIR VOLUME
W/
W/O
WB
WC
W
VD
VTR
WITH
WET BULB
WATER COLUMN
WITHOUT
VENT THROUGH ROOF
VOLUME DAMPER
WATT, WIDTH
VAC
VA
UON
U/F
U/G
U/S
UL
TYP
VOLT-AMPERE, VALVE
VACUUM
VOLT, VENT
UNDERGROUND
UNDERSLAB
UNDERFLOOR
TYPICAL
SQUARE FEET, SQUARE FOOT
SMOKE DETECTOR, STORM DRAIN
REVOLUTIONS PER MINUTE
SHEET METAL & A/C CONT NAT'L ASSOC.
TOTAL STATIC PRESSURE
STORM WATER
POST INDICATOR VALVE
POUNDS PER SQUARE INCH
PRESSURE RELIEF VALVE
REFLECTED CEILING PLAN
REINFORCING, REINFORCED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
NOISE CRITERIA
OUTSIDE STEM AND YOKE
OCCUPATIONAL SAFETY &HEALTH ADMIN.
OPPOSED BLADE DAMPER
OUTSIDE AIR (VENTILATION AIR)
TENANT EXHAUST (TOILET)
AWWA AMERICAN WATER WORKS ASSOC.
RL REFRIGERANT LIQUID
EXTERNAL STATIC PRESSURE
ELECTRICAL
ELEVATION
EQUIPMENT
ENCLOSURE
ENTERING DRY BULB
ENTERING AIR TEMPERATURE
DIRECT EXPANSION
DRAWING
EACH
DIRECT DIGITAL CONTROL
ESP
ENCL
ELEC
EQUIP
EDB
ELEV
EA
EAT
DX
DWG
DDC
DOMESTIC COLD WATER
DOWNSPOUT
DECIBEL
DIAMETER
DEGREES
DRY BULB
DEGREES CELSIUS
DISCONNECT
DIMENSION
DOWN
DS
DIA (OR Ø)
DN
DISC
DIM
CW
°C
dB
DEG
DB
SPEC SPECIFICATION
TE
THRU
TP
TSP
TDH
STD
SUSP
SURF
ST
SQ
TOTAL DYNAMIC HEAD
THROUGH
TOTAL PRESSURE
SUSPEND
STANDARD
SURFACE
SQUARE
SMACNA
SM
SP
SECT
SHT
SF
SD
RS
SA
RPM
RLA
SHEET METAL
STATIC PRESSURE
SECTION
SHEET
REFRIGERANT SUCTION
SUPPLY AIR
RUNNING LOAD AMPS
CONCRETE
CIRCUIT
CENTERLINE
CIRCULATING
COLUMN
CLEANOUT
CEILING
CUBIC FEET PER MINUTE
CUBIC FEET PER HOUR
CKT
L
CLG
COL
CO
C
CC
CIRC
CFM
CFH
ASSY ASSEMBLY
RECIRC
RD
REQ
REV
RHG
RH
REINF
RCP
RA
ROOF DRAIN
REFRIGERANT HOT GAS
REQUIRED
REVISION, REVISE
RELATIVE HUMIDITY
RECIRCULATE
RETURN AIR
PRV
PSI
PH, Ø
PIV
PLBG
PD
PLUMBING
PRESSURE DROP
PHASE
AMERICAN NAT'L STANDARDS INSTITUTE
AIR CONDITIONER, AIR CONDITIONING,
AMERICAN SOCIETY OF TESTING & MATLS
AMERICAN SOCIETY OF MECHANICAL ENGRS
REFRIGERATION & AC ENGINEERS
AIR CONDITIONING & REFRIG INSTITUTE
ABOVE FINISHED GRADE
AMP, AMPERE
AUXILIARY
AMERICAN SOCIETY OF HEATING,
ARCHITECT, ARCHITECTURAL
AMERICAN WELDING SOCIETY
AMERICAN WIRE GAUGE
AIR PRESSURE DROP
ADJUSTABLE
ABOVE FINISHED FLOOR
ABOVE FINISHED CEILING
ARI
ASME
ASTM
AUX
AWG
AWS
ASHRAE
AFG
ARCH
A
ANSI
APD
ADJ
AFF
AFC
AIR COOLED CONDENSING UNIT
AIR COOLED CHILLER
ABOVE
ACCU
ACC
ABV
A/C
OBD
OS&Y
OSHA
OD
OC
OA
NFPA
NTS
N.O.
NIC
OVERFLOW DRAINAGE, OUTSIDE DIAMETER
ON CENTER
NOT TO SCALE
NORMALLY OPEN
NOT IN CONTRACT
NEC
NEMA
N/A
NC
NOT APPLICABLE
ETR EXISTING TO REMAIN
REX REMOVE EXISTING
COP CLEANOUT PLUG
ORD OVERFLOW ROOF DRAIN
RWC RAIN WATER CONDUCTOR
ABOVE CEILING
AL ACOUSTIC LINING
BOTTOM OF PIPE
BUILDING
BRITISH THERMAL UNIT
BOTTOM OF STRUCTURE
BOTTOM OF DUCT
BOILER FEED WATER
BACKDRAFT DAMPER
BUILDING AUTOMATION SYSTEM
BLDG
BOP
BOS
BTU
BOD
BAS
BFW
BDD
BELOW FLOOR
BMS BUILDING MANAGEMENT SYSTEM
DOM DOMESTIC
FP FIRE PROTECTION
FW FILTERED WATER
GRD GROUND
MC MECHANICAL CONTRACTOR
O/H OVERHEAD
OPNG OPENING
REL RELOCATED
SAN SANITARY
D DEPTH
G GAS
CWR/CWS CONDENSING WATER RETURN/SUPPLY
CONN CONNECT, CONNECTION
CA COMBUSTION AIR
TWR/TWS TOWER WATER RETURN/SUPPLY
CHWR/CHWS CHILLED WATER RETURN/SUPPLY
N.C. NORMALLY CLOSED
PB PUSH BUTTON
HHWR/HHWS HEATING HOT WATER RETURN/SUPPLY
HWR DOMESTIC RECIRCULATED HOT WATER
B/F
CTE CONNECT TO EXISTING
FF FINISHED FLOOR
RR REMOVE AND RELOCATE
ID INSIDE DIAMETER
INVERT ELEVATION
INCH, INCHES
IN WC INCHES OF WATER COLUMN
IN
IE
V
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS)
(ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS)
A B
C
END VIEW
18"MIN
18" MIN
SIDE VIEW
DETAIL NOTES
1. PROVIDE SEISMIC/HURRICANE RESTRAINTS WHEN REQUIRED BY CODE. SEISMIC/HURRICANE
RESTRAINTS SHALL BE FURNISHED BY ROOFTOP UNIT MANUFACTURER AND INSTALLED BY
CONTRACTOR. RESTRAINTS SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO EACH CORNER OF ROOF
CURB.
SA
ROOF TOP UNIT
SEAL BETWEEN ALL DUCTS AND ROOF
DECK WITH ACOUSTICAL SEALANT
FLEX CONNECTION
VERTICAL SUPPLY AIR DUCT
SHALL BE FULL SIZE OF UNIT
OPENING, TRANSITION TO DUCT
SIZE INDICATED ON PLAN
DUCT TRANSITIONS SHALL BE
MADE WITH A MAXIMUM ANGLE
OF 15° AND A MINIMUM OF 18" IN
LENGTH
DUCT TRANSITIONS SHALL BE
MADE WITH A MAXIMUM ANGLE
OF 15° AND MINIMUM OF 18" IN
LENGTH
PROVIDE FLEX CONNECTION
BELOW ROOF DECK FOR
SUPPLY AND RETURN AIR DUCT
DROPS
ROOFTOP UNIT
SEAL BETWEEN ALL DUCTS
AND ROOF DECK WITH
ACOUSTICAL SEALANT
DUCT MOUNTED SMOKE DETECTOR
SEISMIC/HURRICANE RESTRAINT
(TYPICAL AT 4 LOCATIONS, REFER
TO DETAIL NOTE 1)
1" INTERNALLY LINED
RETURN AIR DUCTWORK
SCALE: NONE
1
M0.1
RTU SECTION DETAIL
UNION
HAND TIGHT PLUG
COPPER CONDENSATE DRAIN LINES PAST
CURB TO PREVENT CURB FROM RUST DAMAGE,
DO NOT USE PVC FOR CONDENSATE DRAIN
LINES, KEEP VERTICAL CONDENSATE LINE A
MINIMUM OF 3" FROM CURB
MINIMUM 1/2"
"H" = 1 1/4"
EXTEND TO ROOF WHERE
EXISTING IS PIPED TO ROOF
DRAIN OR REQ'D BY LOCAL
AUTHORITIES, SECTION TO
DRAIN ONLY MAY BE PVC
SCALE: NONE
2
M0.1
RTU CONDENSATE DETAIL
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
M0.1
MECHANICAL
LEGEND AND DETAILS
05/10/21
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/
/
/ /
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/ /
/
/
/
/ /
/
/
/
/ /
/
/
/
/ /
/
/ /
/
/
/
/
/ /
/
/
/
/ /
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
/
PROPOSED
MULTI-TENANT
BUILDING
1-STORY, 11,000 GSF
PROPOSED
BUILDING
1-STORY, 2,000 GSF
MICHIGAN ROAD (US 421)
BENNETT PARKWAY
(VAR. R/W)
REDD ROAD
(60' R/W)
REDD ROAD
(50' R/W)
GAS
METER
GAS
METER
GAS
METER
GAS
METER
GAS
METER
GAS
METER
GAS
METER
CT
CT
E
A
A
A
A
A
A
A
A
A
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W1
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
W2
SCALE: 1" = 30'-0"
1
E1.2
SITE LIGHTING PLAN
H-10
H-10
H-10
H-10
H-10
H-10
H-10
H-10
H-10
H-4
H-4
H-4
H-4
H-4
H-4
H-4
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12 H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
H-12
RETAIL BUILDING
TRANSFORMER LOCATION.
REFER TO E0.1 FOR
ADDITIONAL INFORMATION
UNDERGROUND CONDUIT AND
WIRE, REFER TO E0.1 FOR
ADDITIONAL INFORMATION.
DETECTION LOOP FOR DRIVE THRU
COORDINATE EXACT REQUIREMENTS WITH
OWNER PRIOR TO PAVEMENT CONSTRUCTION.
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E1.2
SITE LIGHTING PLAN
SITE LUMINAIRE SCHEDULE
TYPE
WATTAGE
DESCRIPTION CATALOG NUMBER VOLTAGE
LAMP FIXTURE
A LED 150 OUTDOOR LED AREA LIGHT, 24000 LUMENS, FORWARD THROW, 5000K, 70 CRI CBMC; DL149573-LED-24L-SIL-FT-UNV-50-70CRI-IL 120
W1 LED 29
LED WALL SCONCE, 50K, 8000 LUMENS, WITH INTEGRAL EMERGENCY
BATTERY PACK FOR 90 MINUTES OF BACK-UP POWER.
CBMC; DL146539-FT-LED-8L-50-BB 120
W2 LED 32 LED WALL SCONCE, 4000K, 85 CRI, 2470 LUMENS WAC LIGHTING; DS-WE0517-F-40S 120
GENERAL SHEET NOTES
1. ELECTRICAL CONTRACTOR TO REFER TO ARCHITECTURAL DRAWINGS FOR ALL LIGHT FIXTURE
LOCATIONS.
2. ALL BRANCH CIRCUIT WIRING SHALL BE #12 AWG UNLESS OTHERWISE NOTED. EACH BRANCH CIRCUIT
SHALL HAVE A SEPARATE NEUTRAL CONDUCTOR.
3. WIRE ALL NIGHT LIGHTING, EXIT SIGNS, EMERGENCY FIXTURES AHEAD OF LOCAL SWITCHING, UNLESS
OTHERWISE NOTED.
SHEET KEYNOTES
1 PHOTOCELL ON WALL FACING NORTH. SHIELD PHOTOTCELL FROM ARTIFICIAL LIGHT SOURCES.
05/10/21
ONE LINE DIAGRAM INFORMATION.
8 TWO 4" CONDUITS WITH PULLSTRING TO UTILITY POINT OF CONNECTION. COORDINATE EXACT
REQUIREMENTS WITH ENERGY COMPANY. REFER TO ONE LINE DIAGRAM ON SHEET E0.1 FOR MORE
INFORMATION.
9 200AMP, 120/208V PANEL FED FROM METER CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR
ONE LINE DIAGRAM INFORMATION.
10 400AMP, 120/208V DISCONNECT FROM METER CENTER AT BACK OF BUILDING, PLUS TWO 200AMP
PANELS. REFER TO SHEET E-1.1 FOR ONE LINE DIAGRAM INFORMATION.
11 STUB UP LOCATION FOR FUTURE TENANT SPACE, PROVIDE CONDUIT AND PULLSTRING FROM METER
CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR ONE LINE DIAGRAM INFORMATION.
12 4" TELEPHONE SERVICE CONDUIT ROUTED OVERHEAD AND STUBBED IN TENANT SPACE. TELEPHONE
CONDUCTORS SHALL BE FURNISHED AND INSTALLED FROM LANDLORD TELEPHONE BOARD TO TENANT
SPACE AS INDICATED ON PLAN.
13 4" TELEPHONE SERVICE CONDUIT AND PULL WIRE. CONDUIT ROUTED OVERHEAD AND STUBBED IN
TENANT SPACE. TELEPHONE CONDUCTORS SHALL BE FURNISHED AND INSTALLED FROM LANDLORD
TELEPHONE BOARD TO TENANT SPACE BY THE TENANT AT A LATER DATE.
9
T6-4
PANEL T6
PANEL T5b
10
WP
T1-6
T1-8
12 13
13
13
WP
T3-6
13
13
KEY PLAN
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
N
PROJECT
LOCATION
WESTON POINTE DRIVE
U.S. HIGHWAY 421
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E1.1
ELECTRICAL
PLAN
(1) layin light fixture
per 90 sf.
add em and exit
lights per work
letters.
please note to
install outlets per
tenant's plans
05/10/21
DWG DRAWING
DECIBEL
DIAMETER
DISCONNECT
DOWN
DIA
DN
DISC
dB
THRU THROUGH
SF
RTU
RR REMOVE AND RELOCATE
ROOF TOP UNIT
CLOSED CIRCUIT TELEVISION
CIRCUIT
CEILING
CABLE TELEVISION SYSTEM
CKT
CLG
CCTV
CATV
REV
RCP
REVISION
PVC
PF
PH
POLYVINYL CHLORIDE
POWER FACTOR
PHASE
AMERICAN NAT'L STANDARDS INSTITUTE
ABOVE FINISHED GRADE
ARCHITECT, ARCHITECTURAL
AUDIO/VISUAL
ABOVE FINISHED FLOOR
ABOVE FINISHED CEILING
A/V
AFG
ARCH
ANSI
AFF
AFC
OSHA
OC
NFPA
NTS
N.O.
NIC
ON CENTER
NOT TO SCALE
NORMALLY OPEN
NOT IN CONTRACT
NEC
NEMA
N/A NOT APPLICABLE
ETR EXISTING TO REMAIN
REX REMOVE EXISTING
BREAKER
BLDG BUILDING
BKR
BMS BUILDING MANAGEMENT SYSTEM
GROUND
ELECTRICAL SYMBOLS
"IG" INDICATES ISOLATED GROUND TYPE
"WP" INDICATES WEATHERPROOF COVER
"54" INDICATES 54" AFF
"C" INDICATES MOUNTED 8" ABOVE COUNTER
DRY TYPE TRANSFORMER
"2" INDICATES CIRCUIT NUMBER
DISCONNECT SWITCH UNFUSED
JUNCTION BOX
CIRCUITRY TURNING UP
INFLOOR/UNDERFLOOR CONDUIT/WIRE
PANELBOARD - 208Y/120 VOLT, 3Ø, 4 WIRE
PANELBOARD - 480Y/277 VOLT, 3Ø, 4 WIRE
1,3,5
A
"a" INDICATES SWITCHED FIXTURE CONTROL
EMERGENCY LIGHTING BATTERY UNIT WITH HEADS AS INDICATED.
TIME CLOCK
NL
A
a
13
"OS" INDICATES DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH
"C" INDICATES SWITCH MOUNTED 8" ABOVE COUNTER
"3" INDICATES THREE WAY SWITCH
S
PUSHBUTTON
DOOR BUZZER
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
FIRE ALARM VISUAL ONLY ALARM SIGNAL WALL MOUNTED AT 80" AFF.
FIRE ALARM MANUAL PULL STATION MOUNTED AT 48" AFF.
FIRE ALARM AUDIO/VISUAL ALARM SIGNAL WALL MOUNTED AT 80" AFF.
HOMERUN TO PANEL "A", CIRCUIT #1,3,5 (VIA 20A-1P CIRCUIT BREAKERS), TWO #12
CONDUCTORS (MINIMUM SIZE), UON. A GROUNDING CONDUCTOR SHALL BE
PROVIDED IN ALL CONDUITS. REFER TO SPECIFICATIONS FOR ADDITIONAL
GROUNDING REQUIREMENTS.
DISCONNECT SWITCH FUSED: "AS" - INDICATES AMPERE SWITCH SIZE
"AF" - INDICATES AMPERE FUSE SIZE
"GFI" INDICATES GROUND FAULT CIRCUIT INTERRUPTER TYPE
DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, GROUNDING TYPE, 20
AMPERE, MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED.
FIRE RATED POKE-THROUGH DEVICE
"T" INDICATES TELEPHONE/DATA
"D" INDICATES DIMMER SWITCH - WATTAGE AS INDICATED ON PANEL
SCHEDULE. EACH BRANCH CIRCUIT SHALL INCLUDE A SEPARATE
NEUTRAL CONDUCTOR
"DF" INDICATES FLUORESCENT DIMMER SWITCH - WATTAGE AS
INDICATED ON PANEL SCHEDULE. EACH BRANCH CIRCUIT
SHALL INCLUDE A SEPARATE NEUTRAL CONDUCTOR
LIGHT FIXTURE: "A" INDICATES FIXTURE TYPE, "13" INDICATES CIRCUIT NUMBER, "a"
INDICATES SWITCH CONTROL. REFER TO LUMINAIRE SCHEDULE FOR DESCRIPTION.
ILLUMINATED "EXIT" SIGN LIGHTING FIXTURE. CEILING MOUNTED OR WALL
MOUNTED. PROVIDE DIRECTIONAL ARROWS AS INDICATED ON FLOOR PLANS.
COMBINATION VOICE/DATA OUTLET - MOUNTED AT 18" AFF UNLESS OTHERWISE
NOTED. PROVIDE SINGLE GANG BOX WITH PLASTER RING AND 3/4" CONDUIT TO
ABOVE THE ACCESSIBLE CEILING. "W" INDICATES WALL MOUNTED AT 54" AFF, "C"
INDICATES MOUNTED 8" ABOVE COUNTER.
DOOR BELL
FIRE ALARM DUCT MOUNTED SMOKE DETECTOR WITH SAMPLING TUBE,
FURNISHED AND WIRED BY EC, MOUNTED BY MC.
LIGHTING FIXTURE WITH 1 BALLAST WIRED TO EMERGENCY AND/OR NIGHT LIGHTING
CKT.
SWITCH - SINGLE POLE TOGGLE TYPE - 120/277 VOLT, 1-HP RATED, 20 AMPERE,
MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED:
"P" INDICATES DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20
AMPERE
COMBINATION DUPLEX RECEPTACLE AND VOICE/DATA OUTLET MOUNTED IN
FLOOR BOX.
DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN
FLOOR BOX.
SINGLE (SIMPLEX) RECEPTACLE, TYPE AND MOUNTING AS INDICATED ON THE
DRAWINGS.
DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, GROUNDING TYPE, 20
AMPERE, MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED:
TELEPHONE FIRE RATED PLYWOOD BACKBOARD - SIZE INDICATED ON PLAN
DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN
FLOOR BOX.
C CONDUIT
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
AUX AUXILIARY
BAS BUILDING AUTOMATION SYSTEM
DDC DIRECT DIGITAL CONTROL
C/B CIRCUIT BREAKER
D DEEP, DEPTH
EC ELECTRICAL CONTRACTOR
FPC FIRE PROTECTION CONTRACTOR
HID HIGH INTENSITY DISCHARGE
L LENGTH
IBC INTERNATIONAL BUILDING CODE
LED LIGHT EMITTING DIODE
MECH MECHANICAL
MC MECHANICAL CONTRACTOR
N.C. NORMALLY CLOSED
P POLE
MCC MOTOR CONTROL CENTER
PB PUSH BUTTON
PC PLUMBING CONTRACTOR
A AMP, AMPERES
IN INCH, INCHES
DELTA
CT CURRENT TRANSFORMER
G,GRD
SE SERVICE ENTRANCE
XFMR TRANSFORMER
Y WYE
Δ
REMOTE ANNUNCIATOR LIGHT/AUDIBLE ALARM FOR DUCT SMOKE DETECTOR
AWG AMERICAN WIRE GAUGE
ADA AMERICANS WITH DISABILITIES ACT
CUBIC FEET PER MINUTE
CW COLD WATER
CFM
EF EXHAUST FAN
EMT ELECTRICAL METALLIC TUBING
FARA FIRE ALARM REMOTE ANNUNCIATOR
MUA MAKE UP AIR
O/H OVERHEAD
RM
RLA RUNNING LOAD AMPS
ROOM
RGS RIGID GALVANIZED STEEL
TRANS TRANSFORMER
TYP TYPICAL
UPS UNINTERRUPTED POWER SUPPLY
W/ WITH
POWER POLE
"4" INDICATES FOUR WAY SWITCH
"3" INDICATES THREE WAY SWITCH
SWITCH - DUAL TECHNOLOGY, CEILING MOUNTED - SINGLE POLE, TOGGLE TYPE -
120/277 VOLT, 20 AMPERE
"4" INDICATES FOUR WAY SWITCH
WP WEATHERPROOF
REMOTE EMERGENCY WEATHERPROOF LIGHTING HEAD SUPPLIED FROM REMOTE
BATTERY UNIT.
DATA OUTLET MOUNTED IN FLOOR BOX
FIRE ALARM REMOTE ANNUNCIATOR
FIRE ALARM CONTROL PANEL
DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN
CEILING.
FIRE ALARM HEAT DETECTOR
DACT DIGITAL ALARM COMMUNICATING TRANSMITTER
FIRE ALARM CARBON MONOXIDE DETECTOR
TAMPER SWITCH
FLOW SWITCH
KITCHEN HOOD SUPPRESSION SYSTEM
FIRE PUMP CONTROL PANEL
ELECTRICAL SPECIFICATIONS
DIVISION 26 - ELECTRICAL
I. GENERAL PROVISIONS
A. GENERAL CONDITIONS, CODES & STANDARDS
1. GENERAL CONDITIONS OF THE CONTRACT FOUND IN THE ARCHITECTURAL DRAWINGS, GENERAL AND
SPECIAL CONDITIONS OF THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND ANY OF THE OWNER'S
GENERAL REQUIREMENTS SHALL APPLY UNLESS NOTED OTHERWISE.
2. REFER TO THE GENERAL CONDITIONS ON THE ARCHITECTURAL DOCUMENTS AND THE GENERAL AND
SPECIAL CONDITIONS OF THE AIA FOR ADDITIONAL REQUIREMENTS REGARDING; SAFETY, COORDINATION
& COOPERATION, WORKMANSHIP, PROTECTION, CUTTING AND PATCHING, DAMAGE TO OTHER WORK,
PRELIMINARY OPERATIONS, STORAGE, ADJUSTMENTS, CLEANING, ETC.
3. ALL WORK SHALL BE IN CONFORMANCE WITH ALL LOCALLY ENFORCED, FEDERAL, STATE, AND LOCAL
CODES AND ORDINANCES INCLUDING ANY SPECIAL THE OWNER REQUIREMENTS IN ADDITION TO THOSE
SPECIFIED.
4. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS
REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION WITH THE
LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS.
5. ALL EQUIPMENT AND MATERIALS USED SHALL BE NEW AND UL LISTED FOR THE APPLICATION, AND SHALL
BEAR AN APPROPRIATE UL LABEL.
B. SCOPE OF WORK
1. THIS CONTRACT SHALL INCLUDE THE FURNISHING, INSTALLING, CONNECTING, AND OPERATION OF ALL
EQUIPMENT WHICH IS A PART OF THE ELECTRICAL SYSTEMS AS SHOWN ON THE DRAWINGS AND AS
REQUIRED BY SIMILAR INSTALLATIONS. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE
DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO
COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF A SIMILAR CHARACTER SHALL BE
FURNISHED AND INSTALLED UNDER THIS CONTRACT AT NO ADDITIONAL COST TO THE OWNER.
CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS REQUIRED TO PROVIDE THE OWNER A
COMPLETE, CODE APPROVED AND OPERATIONAL ELECTRICAL SYSTEM.
2. CAREFULLY READ SPECIFICATION FOR ALL PARTS OF THE WORK SO AS TO BECOME FAMILIAR WITH ALL
TRADES' WORK SCOPE. CONSULT WITH OTHER TRADES TO INSURE PROPER LOCATIONS AND AVOID
INTERFERENCES. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER BEFORE WORK
IS COMMENCED.
3. CONTRACTORS SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO COMPARE THEM
WITH THE DRAWINGS AND SPECIFICATIONS, NOTE THE EXISTING CONDITIONS AND OTHER WORK THAT
WILL BE REQUIRED, AND THE NATURE OF THE CONDITIONS UNDER WHICH THE WORK IS TO BE
PERFORMED. NO ALLOWANCE SHALL BE MADE TO THE CONTRACTOR BY REASON OF THIS FAILURE TO
HAVE MADE SUCH EXAMINATION OR OF ANY ERROR ON HIS PART.
4. ALL EXISTING UTILITY AND ELECTRICAL SERVICES SHALL BE FIELD VERIFIED. CORRECTIONS TO THE
DESIGN AND INSTALLATION SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER.
5. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. ALL CORE
DRILLING OR CUTTING OF FIRE RATED FLOORS, SHAFTS, AND WALLS SHALL BE FIRESTOPPED PRIOR TO
FINISH PATCHING. ALL PENETRATIONS SHALL BE FIRE SEALED TO MATCH THE FIRE RATING OF THE
FLOORS, SHAFTS, AND WALLS PENETRATED.
6. TEMPORARY ELECTRICAL SERVICE, LIGHTING, AND RELATED WIRING SHALL BE PROVIDED TO OSHA
REQUIREMENTS FOR THE USE OF ALL TRADES DURING CONSTRUCTION.
7. TEMPERATURE AND INTERLOCK CONTROL COMPONENTS AND ALL RELATED WIRING AND CONDUIT SHALL
BE PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE INDICATED ON THE DRAWINGS.
9. ALL WORK INCLUDING, BUT NOT LIMITED TO PARTS, MATERIAL, EQUIPMENT AND LABOR SHALL BE
GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY THE ENGINEER AND OWNER. WHERE AN
EQUIPMENT MANUFACTURER HAS A WARRANTY THAT EXCEEDS ONE YEAR, THAT WARRANTY PERIOD
SHALL APPLY TO THIS PROJECT.
C. DOCUMENTS
1. THE DRAWINGS ARE DIAGRAMMATIC; ALL WORK SHALL BE PERFORMED AS INDICATED ON THE DRAWINGS
UNLESS EXISTING CONDITIONS OR COORDINATION ISSUES REQUIRE CHANGES. THESE CHANGES SHALL
BE MADE WITH NO ADDITIONAL COST TO THE OWNER.
2. ANY INCIDENTAL ITEMS OR LABOR, ETC. NOT INCLUDED IN THE SPECIFICATIONS OR THE DRAWINGS BUT
REASONABLY IMPLIED AS NECESSARY FOR THE COMPLETE INSTALLATION OF ALL APPARATUS SHALL BE
INCLUDING IN BID.
3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL
OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NOT MENTIONED IN BOTH.
4. IF ERRORS ARE FOUND IN THE DRAWINGS OR SPECIFICATIONS OR DISCREPANCIES OCCUR BETWEEN THE
SAME, OR BETWEEN THE FIGURES ON THE DRAWINGS, AND THE SCALE OF SAME OR BETWEEN THE
LARGER AND SMALLER DRAWINGS, OR IN THE DESCRIPTIVE MATTER ON THE DRAWINGS SHALL BE
REFERRED TO THE OWNER FOR REVIEW AND FINAL DECISION PRIOR TO THE BID DUE DATE.
5. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY AS
SPECIFIED HEREIN. WHERE MORE THAN ONE MANUFACTURER IS MENTIONED ANY ONE MAY BE UTILIZED.
SUBSTITUTE MANUFACTURERS MAY BE OFFERED ONLY AS AN ALTERNATE TO THE SPECIFIED EQUIPMENT
AND MATERIAL AND MUST BE SUBMITTED AS SPECIFIED IN THE ARCHITECTURAL DOCUMENTS.
6. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY RECOGNIZED
MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN THESE SPECIFICATIONS.
REFER TO EACH SECTION FOR ANY SPECIFIC REQUIREMENTS.
D. COORDINATION
1. CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES WHICH ARE REQUIRED TO
BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK
TO AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL
BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE.
2. EACH CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGE TO OTHER WORK CAUSED BY HIS
WORK OR THROUGH THE NEGLECT OF HIS, OR HIS SUB-TRADE'S PERSONNEL. ALL PATCHING, REPAIRING,
REPLACEMENT AND PAINTING, ETC. SHALL BE DONE AS DIRECTED BY THE OWNER BY THE CRAFTSMEN OF
THE TRADES INVOLVED. THE COSTS OF SUCH WORK SHALL BE PAID BY THE CONTRACTOR CAUSING THE
DAMAGE.
3. IT IS ESSENTIAL THAT ALL WORK AT THE PROJECT BE DONE AT SUCH TIME AND IN SUCH MANNER AS NOT
TO INTERFERE WITH THE OPERATIONS OF THE SPACE, ADJACENT SPACES, OR FACILITY. A WORK
SCHEDULE SHALL BE ARRANGED WITH THE OWNER, INCLUDING PREMIUM TIME WORK TO FACILITATE
WORK WITH A MINIMUM OF INTERFERENCE TO THE OWNER'S OPERATIONS.
E. METHODS
1. EXCAVATIONS SHALL BE MADE IN OPEN TRENCHES. FLOORS SHALL BE SAW CUT. CONDUIT SHALL BE LAID
ON AN APPROPRIATELY GRADED 6" BED OF CLEAN AND DRY SAND. ENGINEERED FILL SHALL BE USED TO
BACKFILL TO 6" ABOVE THE CONDUIT. BACKFILL THE REMAINDER OF THE TRENCH UTILIZING THE
EXCAVATED MATERIAL IF APPROVED BY THE ARCHITECT OR THE OWNER. IF THE EXCAVATED MATERIALS
ARE NOT ACCEPTABLE, ENGINEERED FILL ACCEPTABLE TO THE ARCHITECT SHALL BE UTILIZED TO
BACKFILL THE REMAINDER OF THE TRENCH. BACKFILL SHALL BE ACCOMPLISHED IN 9" LIFTS WITH ALL
LIFTS COMPACTED TO 95% PROCTOR. PATCH FLOOR TO MATCH EXISTING.
2. EQUIPMENT, CONDUIT, ETC. SHALL NOT BE SUPPORTED FROM ANY CEILINGS, OTHER PIPING, OTHER
CONDUIT OR DUCTWORK, ROOF DECK, OR JOIST BRIDGING. ITEMS SHALL BE SUPPORTED FROM
ACCEPTABLE STRUCTURAL BUILDING COMPONENTS AS DETERMINED BY THE ARCHITECT AND
STRUCTURAL ENGINEER.
3. ALL ROOF PENETRATIONS, FLASHINGS AND COUNTER FLASHINGS SHALL BE PERFORMED BY THE OWNER'S
ROOFING CONTRACTOR AT THE REQUESTING CONTRACTORS COST.
F. SUBMITTALS
1. SHOP DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT OF ALL EQUIPMENT AND ACCESSORIES
PROVIDED FOR THE PROJECT WHETHER SPECIFIED HERE-IN OR ON THE DRAWINGS. REVIEW OF THE SHOP
DRAWINGS SHALL BE FOR GENERAL DESIGN CONCEPT AND ADHERENCE WITH THE SPECIFICATIONS.
QUANTITY OF SHOP DRAWINGS SUBMITTED SHALL BE AS SPECIFIED BY THE ARCHITECT. SHOP DRAWINGS
SHALL BE PREPARED BY THE CONTRACTOR SHOWING LOCATIONS AND MEASUREMENTS FROM COLUMNS
OF ALL CONCEALED AND EXPOSED PIPING, DUCTWORK, CONDUIT, EQUIPMENT, ACCESSORIES, ETC., AND
SUBMITTED PRIOR TO INSTALLATION. THE OWNER MAY MAKE REPRODUCIBLE COPIES OF THEIR
DRAWINGS AVAILABLE FOR USE IN PREPARATION OF SHOP DRAWINGS, HOWEVER THE OWNER SHALL NOT
BE HELD RESPONSIBLE FOR NOT CONFIRMING ALL INFORMATION ON THE DRAWINGS PRIOR TO
FABRICATION AND/OR INSTALLATION.
2. PROJECT RECORD DOCUMENTS - MAINTAIN AT THE JOBSITE ONE COPY OF ALL CONTRACT DOCUMENTS
CLEARLY MARKED AS “PROJECT RECORD COPY”. THESE DRAWINGS ARE TO BE MAINTAINED IN GOOD
CONDITION, UPDATED DAILY FOR CHANGES ENCOUNTERED AND AVAILABLE AT ALL TIMES FOR INSPECTION
BY THE OWNER. DO NOT USE FOR FIELD CONSTRUCTION! PROJECT RECORD DOCUMENTS ARE TO BE
KEPT CURRENT WITH EXACT DIMENSIONS OF ALL WORK, EQUIPMENT, DISTRIBUTION CONDUIT, CIRCUITS,
ETC. MARK ALL INFORMATION IN RED LINES AND NOTES SO AS TO BE EASILY IDENTIFIED FROM THE BASE
DRAWING. UPON COMPLETION OF THE WORK, ONE SET OF THESE DOCUMENTS SHALL BE TURNED OVER
TO THE OWNER AS ONE QUALIFICATION FOR FINAL PAYMENT.
3. THREE COMPLETE SETS OF AS-BUILT DOCUMENTATION SHALL BE PROVIDED. IT SHALL INCLUDE, BUT NOT
BE LIMITED TO ACCURATE PLAN DRAWINGS, WIRING DIAGRAMS AND OPERATION AND MAINTENANCE
MANUALS.
4. SUBMIT OVERCURRENT DEVICE COORDINATION STUDY INCLUDING EQUIPMENT EVALUATION REPORTS,
ONE LINE DIAGRAM, PROTECTIVE DEVICE COORDINATION STUDY AND TIME-CURRENT COORDINATION
CURVES. STUDY ELECTRICAL DISTRIBUTION SYSTEM FROM NORMAL AND ALTERNATE POWER SOURCES.
THE STUDY SHALL COMPLY WITH IEEE 399 FOR GENERAL STUDY REQUIREMENTS.
II. PRODUCTS
A. CONDUIT
1. CONDUIT SHALL BE HEAVY WALL RIGID GALVANIZED STEEL WHERE EXPOSED AND SUBJECT TO DAMAGE,
8'-0" AFF AND BELOW, AND IN WET LOCATIONS WHERE INDICATED ON THE DRAWINGS. UNDERGROUND
CONDUIT SHALL BE SCHEDULE 40 PVC AND SHALL BE CONCRETE ENCASED (3' MINIMUM) WHERE
INDICATED ON THE DRAWINGS. A TRANSITION SHALL BE MADE TO HEAVY WALL RIGID GALVANIZED STEEL
BEFORE PVC CONDUITS PENETRATE THE FLOOR SLAB. INTERIOR CONDUITS SHALL BE ELECTRICAL
METALLIC TUBING (EMT). METAL CLAD (MC) CABLE MAY BE USED IF APPROVED BY THE OWNER, AND
INSTALLED IN LOCATIONS PERMITTED BY CODE.
2. FLEXIBLE METAL CONDUIT SHALL BE USED FROM OUTLET BOX TO INDIVIDUAL RECESSED LIGHT FIXTURES,
AND FOR FINAL CONNECTIONS TO MOTORS AND OTHER DEVICES SUBJECT TO VIBRATION.
B. CONDUIT FITTINGS AND BOXES
1. INTERIOR OUTLET BOXES SHALL BE STANDARD GALVANIZED SHEET STEEL TYPE, NOT LESS THAN 14
GAUGE IN THICKNESS, WITH KNOCKOUT OPENINGS, EXTENSIONS, PLASTER RINGS AND COVER PLATES TO
ACCOMMODATE THE DEVICES INSTALLED. COVER PLATES SHALL BE SMOOTH PLASTIC TO MATCH DEVICE
COLOR. USE STEEL PLATES WITH ROUNDED CORNERS FOR SURFACE BOXES. OUTDOOR (WET LOCATION)
OUTLET BOXES SHALL BE CAST ALUMINUM TYPE WITH DEVICE COVERS TO SUIT.
2. OUTLET BOXES SHALL NOT BE LESS THAN 4 INCHES SQUARE, 1-1/2 INCHES DEEP.
3. COUPLINGS AND CONNECTORS FOR EMT SHALL BE DIE CAST ZINC OR STEEL. BUSHING SHALL BE
GROUNDING TYPE WITH INSULATING PLASTIC INSERT.
C. WIRE AND CABLE
1. CONDUCTORS FOR POWER AND LIGHTING SHALL BE NEW 600-VOLT, 90°C, TYPE XHHW, THHW, OR THWN
INSULATION, MINIMUM SIZE #12-AWG, EXCEPT FOR CONTROL WIRING WHICH MAY BE #14-AWG. OTHER
SIZES SHALL BE AS NOTED ON THE DRAWINGS. CONDUCTORS SHALL BE COPPER, UNLESS OTHERWISE
APPROVED BY THE OWNER.
2. BRANCH CIRCUIT RUNS EXCEEDING 100 FEET IN TOTAL LENGTH FROM THE PANELBOARD TO THE LAST
DEVICE, SHALL BE #10-AWG CONDUCTORS UNLESS OTHERWISE NOTED.
3. COMPRESSION TYPE LUGS AND CONNECTORS SHALL BE USED FOR ALL TERMINATIONS AND SPLICES.
4. ALL LOW VOLTAGE COMMUNICATIONS, FIRE ALARM, DATA, SECURITY, TELEPHONE AND ALL OTHER
MISCELLANEOUS LOW VOLTAGE WIRING INSTALLED IN CEILING SHALL BE PLENUM RATED.
D. WIRING DEVICES
1. DUPLEX RECEPTACLES SHALL BE GROUNDING TYPE, NEMA 5-20R, RATED FOR 20 AMPS, 125 VOLTS, WITH
PROVISIONS FOR BACK AND SIDE WIRING.
2. SWITCHES SHALL BE TOGGLE OPERATED, QUIET TYPE, RATED FOR 20 AMPS, 120/277 VOLTS, WITH
PROVISIONS FOR BACK AND SIDE WIRING. THREE WAY AND FOUR WAY SWITCHES SHALL BE PROVIDED
WHERE INDICATED.
3. COLORS OF DEVICES SHALL BE SELECTED BY ARCHITECT.
4. WIRING DEVICES SHALL BE SPECIFICATION GRADE, AS MANUFACTURED BY HUBBELL, PASS & SEYMOUR,
ARROW HART, LEVITON AND GENERAL ELECTRIC.
E. LIGHTING AND RECEPTACLE PANELBOARDS
1. BRANCH CIRCUIT PANELBOARDS SHALL BE DEAD FRONT TYPE, WITH MAIN LUGS OR MAIN OVERCURRENT
DEVICE AS INDICATED, BRANCH OVERCURRENT DEVICES AS NOTED AND AN EQUIPMENT GROUND BAR, ALL
IN A SURFACE OR FLUSH MOUNTED SHEET STEEL ENCLOSURE. MINIMUM SHORT CIRCUIT CAPACITY SHALL
BE 10,000 AMPS SYMMETRICAL FOR 120/208V, APPLICATION UNLESS NOTED OTHERWISE.
2. CIRCUIT BREAKERS SHALL BE BOLT ON TYPE; WITH MOLDED PLASTIC CASE; 1, 2, OR 3 POLE AS INDICATED;
QUICK-MAKE, QUICK-BREAK; AND THERMAL-MAGNETIC TRIP DEVICE.
3. ALL BREAKERS FEEDING HVAC EQUIPMENT SHALL BE HACR RATED, UNLESS OTHERWISE NOTED.
4. ALL EQUIPMENT RATED LESS THAN 100A SHALL HAVE 60 DEGREE C MINIMUM TERMINATIONS. ALL
EQUIPMENT RATED 100A OR OVER SHALL HAVE 75 DEGREE MINIMUM TERMINATIONS.
5. INDIVIDUAL SINGLE POLE CIRCUIT BREAKERS, WITH IDENTIFIED TIES, OR 2/3 POLE BREAKERS SHALL BE
PROVIDED FOR EACH UNGROUNDED CONDUCTOR IN ALL MULTI-WIRE BRANCH CIRCUITS.
6. PANELBOARDS SHALL BE AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS, AND CUTLER
HAMMER.
F. SAFETY SWITCHES AND MOTOR STARTERS
1. SAFETY SWITCHES SHALL BE FUSIBLE OR NON-FUSIBLE AS INDICATED ON THE DRAWINGS. SWITCHES
SHALL BE QUICK-MAKE, QUICK-BREAK, HEAVY DUTY VISIBLE BLADE TYPE. ENCLOSURES SHALL BE NEMA 1
TYPE UNLESS OTHERWISE INDICATED ON THE DRAWINGS. FUSES SHALL BE DUAL ELEMENT - TIME DELAY
TYPE.
2. ALL MOTORS OVER 1/8 HP SHALL BE PROVIDED WITH THERMAL OVERLOAD PROTECTION. OVERLOAD
PROTECTION SHALL BE PROVIDED INTEGRAL WITH THE MOTOR WINDINGS AND/OR MOTOR CONTROLLER
(PROVIDED BY OTHERS) UNLESS OTHERWISE INDICATED ON DRAWINGS.
3. ALL EQUIPMENT RATED LESS THAN 100A SHALL HAVE 60 DEGREE C MINIMUM TERMINATIONS. ALL
EQUIPMENT RATED 100A OR OVER SHALL HAVE 75 DEGREE MINIMUM TERMINATIONS.
G. LUMINAIRES AND LAMPS
1. ALL LUMINAIRES SHALL BE SPECIFIED ON THE LUMINAIRE SCHEDULE.
2. ALL FIXTURE / BALLAST / LAMP COMBINATIONS SHALL BE ENERGY SAVING TYPE.
H. FIRE ALARM SYSTEM
1. A COMPLETE FIRE ALARM SYSTEM SHALL BE PROVIDED AS DESCRIBED ON THE DRAWINGS. ALL DEVICES,
WIRING, BACKBOXES, PROGRAMMING, START-UP, INSTRUCTION AND TESTING REQUIRED FOR A COMPLETE
OPERATING SYSTEM SHALL BE PROVIDED.
2. THE ELECTRICAL CONTRACTOR SHALL FURNISH SHOP DRAWINGS, COMPLETE WITH EQUIPMENT CUTS AND
FLOOR PLANS (WITH WIRING INDICATED), AS WELL AS BATTERY CALCULATIONS, AND VOLTAGE DROP
CALCULATIONS FOR REVIEW AND APPROVAL BY THE ARCHITECT, ENGINEER, AND ALL AUTHORITIES
HAVING JURISDICTION. FLOOR PLAN DRAWINGS SHALL BE STAMPED BY A PROFESSIONAL ENGINEER
RETAINED BY THE CONTRACTOR AND/OR SUPPLIER. NICET 4 CERTIFICATION AND STAMP IS ACCEPTABLE,
IF APPROVED BY THE AUTHORITY HAVING JURISDICTION.
3. THE ELECTRICAL CONTRACTOR SHALL FURNISH FIRE ALARM DRAWINGS, CALCULATIONS, AND EQUIPMENT
INFORMATION FOR ALL REQUIRED LOCAL MUNICIPALITY, OR STATE PERMITS. THE ELECTRICAL
CONTRACTOR SHALL ARRANGE AND COORDINATE ALL REQUIRED TESTING AND INSPECTIONS REQUIRED
BY THE LOCAL MUNICIPALITY FIRE DEPARTMENT. THE ELECTRICAL CONTRACTOR SHALL INCLUDE FIRE
DEPARTMENT COSTS IN BID.
4. ALL HVAC UNITS OR GROUP OF HVAC UNITS WITH A COMMON PLENUM AND A DESIGN CAPACITY GREATER
THAN 2000 CFM SHALL AUTOMATICALLY SHUT DOWN ASSOCIATED HVAC UNIT OR UNITS. WHERE A DUCT
SMOKE DETECTOR IS NOT VISIBLE OR ACCESSIBLE FROM THE FLOOR, REMOTE AUDIBLE/VISUAL ALARM
INDICATOR/TEST SWITCHES SHALL BE PROVIDED IN AN APPROVED LOCATION, AT A HEIGHT ACCESSIBLE
AND VISIBLE FROM THE FLOOR. HVAC DUCT DETECTORS SHALL BE CONNECTED TO A CENTRAL STATION
MONITORING SYSTEM UNDER SEPARATE CONTRACT WITH THE OWNER.
5. FIRE ALARM SIGNAL SHALL INITIATE THE FOLLOWING ACTIONS:
a. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES.
b. IDENTIFY ALARM AND SPECIFIC INITIATION DEVICE AT FIRE CONTROL PANEL.
c. TRANSMIT ALARM TO LANDLORD SYSTEM.
d. TRANSMIT ALARM SIGNAL TO REMOTE RECEIVING STATION.
e. INTERRUPT TENANT SOUND SYSTEM.
f. UNLOCK ELECTRIC DOORS IN EGRESS PATHS.
g. RELEASE FIRE AND SMOKE DOORS HELD OPEN BY MAGNETIC DOOR HOLDERS.
h. SHUT DOWN AIR HANDLING SYSTEMS.
i. ACTIVATE EMERGENCY GAS AND HOOD EQUIPMENT SHUTOFFS.
j. SWITCH HVAC EQUIPMENT CONTROLS TO FIRE ALARM MODE.
6. ALL FIRE ALARM VISIBLE DEVICES SHALL BE ADA COMPLIANT WITH A MINIMUM CANDELA RATING OF 75.
CEILING MOUNTED DEVICES SHALL HAVE A RATING WITH THE LISTED REQUIREMENTS FOR A SPECIFIC
CEILING HEIGHT.
7. ALL WALL MOUNTED STROBES, SPEAKER-STROBES, OR HORN STROBES SHALL BE MOUNTED SUCH THAT
THE LENS IS NOT LESS THAN 80 INCHES AND NOT MORE THAN 96 INCHES ABOVE THE FINISHED FLOOR.
8. ALL AUDIBLE NOTIFICATION APPLIANCES SHALL BE SET TO ACHIEVE A SOUND PRESSURE AT LEAST 15dB
ABOVE THE AVERAGE AMBIENT SOUND LEVEL.
9. ALL CABLES FOR THE FIRE ALARM SYSTEM SHALL BE RATED FOR THE INTENDED USE.
10. FIRE ALARM SYSTEM MONITORING SHALL BE BY OTHERS UNDER SEPARATE CONTRACT WITH THE OWNER.
11. PROVIDE A SEPARATE LINE ITEM COST FOR A (1), (3), (5) YEAR MAINTENANCE, TESTING AND MONITORING
AGREEMENT. AGREEMENT TO INCLUDE MONITORING TO A UL LISTED CENTRAL STATION PER NFPA 72
REQUIREMENTS, ALL CODE REQUIRED TESTING OF THE FIRE ALARM SYSTEM PER NFPA 72 AND OBC
(MONTHLY VISUAL INSPECTION SHALL BE BY THE OWNER), CLEANING OF DEVICES SHALL BE DONE UPON
SYSTEM REQUEST, AND ALL COST ASSOCIATED WITH MAINTENANCE OF THE SYSTEM SHALL BE PROVIDED
(DUE TO DEFECTIVE EQUIPMENT ONLY). PROVIDE A YEARLY REPORT TO THE OWNER.
12. FIRE ALARM SYSTEM SHALL BE BY SIMPLEX, NOTIFIER, FCI, SIEMENS OR GAMEWELL.
I. METER CENTER
1. METER CENTER SHALL BE RATED FOR 208/120V, THREE PHASE, FOUR WIRE OPERATION WITH TIN PLATED
ALUMINUM BUSBARS, 100% RATED NEUTRAL BUS AND GROUND BUS. SWITCHBOARD SHALL BE SERVICE
ENTRANCE RATED. REFER TO DRAWINGS FOR ADDITIONAL REQUIREMENTS.
2. METER CENTER SHALL BE FRONT ACCESSIBLE WITH SIDE ACCESS TO THE MAIN DEVICE. MAIN DEVICE
SHALL BE INDIVIDUALLY MOUNTED. BRANCH DEVICES WITH HOT SEQUENCE UTILITY METERING SHALL BE
INDIVIDUALLY MOUNTED. SECTIONS SHALL BE FRONT AND REAR ALIGNED, PROVIDE (3) METERS PER
VERTICAL SECTION.
3. ENCLOSURE SHALL BE NEMA 3R WITH HINGED FRONT DOORS.
4. FUTURE DEVICES: EQUIP COMPARTMENTS WITH MOUNTING BRACKETS, SUPPORTS, BUS CONNECTIONS,
AND APPURTENANCES AT FULL RATING OF BRANCH FEEDER COMPARTMENT.
5. MAIN HEAVY DUTY SWITCH:
a. OPERATING MECHANISM: MANUAL HANDLE OPERATION TO CLOSE SWITCH.
b. SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICE EQUIPMENT.
6. FUSED SWITCH: NEMA KS 1, TYPE HD; CLIPS TO ACCOMMODATE SPECIFIED FUSES; LOCKABLE HANDLE.
8. EQUIPMENT MOUNTING: INSTALL METERING CENTER ON CONCRETE BASE, 4-INCH NOMINAL THICKNESS
WITH CHAMFERED EDGES.
9. DEVICE NAMEPLATES: LABEL EACH DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICE AND EACH
METER AND CONTROL DEVICE MOUNTED IN COMPARTMENT DOORS WITH A NAMEPLATE.
III. EXECUTION
A. GENERAL MISCELLANEOUS
1. ALL CONDUIT RUN IN FINISHED AREAS SHALL BE CONCEALED. CONDUIT SMALLER THAN 3/4" SHALL NOT BE
USED FOR ANY CIRCUIT HOMERUNS.
2. RACEWAYS EXPOSED TO DIFFERENT TEMPERATURES SHALL BE FILLED WITH AN APPROVED MATERIAL IN
ACCORDANCE WITH ARTICLE 300.7 OF THE NATIONAL ELECTRICAL CODE.
3. HANGERS, SUPPORTS, OR FASTENINGS SHALL BE PROVIDED AT EACH ELBOW, AT THE ENDS OF STRAIGHT
RUNS TERMINATING AT BOXES OR CABINETS, AND AT INTERMEDIATE POINTS AS REQUIRED BY CODE.
CONDUITS OR BOXES SHALL NOT BE SUPPORTED BY CEILING SUPPORT WIRES OR OTHER CEILING
SUPPORTING HARDWARE.
4. ACCESS PANELS SHALL BE PROVIDED FOR ALL JUNCTION BOXES AND PULL BOXES INSTALLED ABOVE
DRYWALL CEILINGS, COORDINATE SIZE AND LOCATION WITH ARCHITECT.
5. FIXTURE SUPPORTS SHALL BE IN ACCORDANCE WITH ARTICLE 410-30 OF THE NATIONAL ELECTRICAL
CODE, OR ANY LOCAL CODES WHICH MY APPLY.
6. PROVIDE PERMANENT NAMEPLATES WITH DESIGNATIONS FOR PANELBOARDS, FEEDER DEVICES,
DISTRIBUTION EQUIPMENT AND STARTERS.
7. PROVIDE TYPEWRITTEN DIRECTORY CARDS WITH BRANCH CIRCUIT IDENTIFICATION FOR BRANCH CIRCUIT
PANELBOARDS. PANELBOARDS, FEEDER DEVICES, DISTRIBUTION EQUIPMENT AND STARTERS SHALL BE
FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS IN
ACCORDANCE WITH NEC 110.16.
8. INSTALL HANDLE GUARDS ON ALL BREAKERS FOR NIGHT LIGHTING, EMERGENCY AND SIMILAR CIRCUITS.
9. THE ELECTRICAL CONTRACTOR SHALL BALANCE PANELBOARD LOADING TO WITHIN 10% ON EACH PHASE
BASED ON INSTALLED CONDITIONS. LOAD BALANCING CIRCUIT CHANGES SHALL BE PERFORMED OUTSIDE
THE NORMAL OCCUPANCY WORKING SCHEDULE AND AT A TIME DIRECTED BY LANDLORD.
10. THE FINAL LOCATIONS OF ALL EQUIPMENT, OUTLETS, ETC. SHALL BE SUBJECT TO REASONABLE CHANGES
IN LOCATION UP TO THE TIME OF ROUGHING-IN, AT NO ADDITIONAL COST TO THE OWNER.
11. CONTACT ELECTRIC POWER COMPANY AND MAKE NECESSARY ARRANGEMENTS FOR ELECTRIC SERVICE.
12. CONTACT TELEPHONE COMPANY AND MAKE NECESSARY ARRANGEMENTS FOR TELEPHONE SERVICE.
13. AT ALL TIMES KEEP PREMISES AND BUILDING IN A NEAT AND ORDERLY CONDITION, FOLLOWING OWNER'S
INSTRUCTION IN REGARD TO STORING OF MATERIALS, PROTECTIVE MEASURES AND DISPOSING OF
DEBRIS.
14. ALL SERVICE EQUIPMENT SHALL BE IDENTIFIED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT.
SERVICE EQUIPMENT SHALL BE FIELD MARKED WITH THE MAXIMUM AVAILABLE FAULT CURRENT AND THE
DATE THE CALCULATION WAS PERFORMED. FIELD MARKING SHALL BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE INSTALLATION ENVIRONMENT.
15. RACEWAYS BELOW DRIVEWAYS, PARKING LOTS, AND ANY RACEWAYS INSTALLED BELOW GRADE SHALL BE
INSTALLED A MINIMUM OF 24" BELOW FINISHED GRADE PER NEC 300-5.
B. GROUNDING
1. GROUND ALL CONDUITS, CABINETS, MOTORS, PANELS, AND OTHER EXPOSED NON-CURRENT CARRYING
PARTS OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC ARTICLE 250.
2. BOND METAL WATER PIPING AND OTHER METAL PIPING (INCLUDING GAS PIPING) AND EXPOSED
STRUCTURAL METAL IN ACCORDANCE WITH NEC ARTICLE 250.
3. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF AN INSULATED GROUNDING
CONDUCTOR INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUIT CONDUCTORS IN ALL CONDUITS.
FIRE ALARM NOTES
1. PRINCIPAL OCCUPANCY CLASSIFICATION IS GROUP M.
2. SPACE IS PROVIDED WITH FULL SPRINKLER COVERAGE.
3. OCCUPANT LOAD IS LESS THAN 500.
4. THE LANDLORD DOES REQUIRE ALL TENANTS TO INSTALL A FIRE ALARM SYSTEM
MONITORED BY THE LANDLORD SYSTEM.
5. A FIRE ALARM SYSTEM IS REQUIRED.
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E0.2
ELECTRICAL
SPECIFICATIONS
05/10/21
PER NEC 250.102.(C)(1)
GROUNDING ELECTRODE CONDUCTOR
(#2/0) PER NEC 250.66.
GROUNDED OR
NEUTRAL BUS
SERVICE EQUIPMENT
TC
H-4
H-2
RESTAURANT EXTERIOR BUILDING LIGHTS
ZONE SCHEDULE:
1. BUILDING MOUNTED LIGHTING; PS ON, PS OFF
2. MONUMENT SIGN; PS ON, TC OFF
SCALE: NONE
4
E-1.1
LIGHTING CONTROL DIAGRAM (PACKAGED)
RELAY PANEL WITH INTEGRATED DIGITAL
TIME CLOCK, 8 LIGHTING RELAYS, WITH
RELAY CONTROL CARD FOR MANUAL
CONTROL OF ZONES OR INDIVIDUAL
RELAYS. EATON LITEKEEPER LK8 OR
EQUAL.
OUTDOOR PHOTOSENSOR;
FACE NORTH
3/C #18 LV CABLE
PS
SCALE:
18"
MIN.
12"
MIN.
30"
MIN.
4" 4"
5"
FINISHED GRADE
RED MARKER
TAPE
"ELECTRICAL"
SCHEDULE 40
CONDUITS (TYPICAL)
TRENCHING AND SELECT CLEAN BACKFILL
TO 95% COMPACTION BY E.C.
NONE
7 UNDERGROUND CONDUIT DETAIL
SCALE:
12"
24"
(MIN.)
32"
(MIN.)
18"
(MIN.)
5"
5" 7 1/2" 5"
FINISHED GRADE
RED MARKER
TAPE "ELECTRICAL"
BASE SPACER ON
5'-0" MAX. CENTERS
4" SCHEDULE 40
CONDUITS (TYPICAL)
TRENCHING AND SELECT CLEAN
BACKFILL TO 95% COMPACTION BY E.C.
NONE
6
E-1.1
PRIMARY POWER DUCT BANK DETAIL
E-1.1
(3)4" PVC WITH (4)#600KCMIL, EACH
400AMP
TENANT 101
M
200AMP
TENANT 102
M
200AMP
TENANT 103
M
400AMP
TENANT 104
M
400AMP
TENANT 105
M
200AMP
TENANT 106
M
200AMP
FUTURE
TENANT 107
M
1200A, 120/208V 3ɸ,4W
METER CENTER
PANEL
"H"
200A MCB
120/208V
TYPICAL TENANT
SPACE
PANEL FOR
TENANT
SPACE
MCB
120/208V
(4)#3/0,(1)#6GND-2"C
F=16,877 (MAX)
F=16,066(MAX)
F=(MAX) 1
SHEET KEYNOTES
1 PROVIDE CONDUIT AND WIRE AS INDICATED BELOW;
SPACE 101: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 12,827
SPACE 102: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 12,471
SPACE 103: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 14,658
SPACE 104: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 16,445
SPACE 105: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 14,915
SPACE 106: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 11,216
SPACE 107: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 8,844
M
FACP
M C C
TS FS
F
F
L
V
C
H-8
20A/1P
FIRE ALARM CONTROL
PANEL SURFACE
MOUNTED, #108. (DACT
REQUIRES TWO ACTIVE
PHONE LINES).
PROVIDE CONTROL MODULE
FOR REQUIRED FUNCTION
(TYPICAL).
PROVIDE MONITOR MODULE
FOR REQUIRED FUNCTION
(TYPICAL).
INITIATING/
CONTROL
LOOP
SIGNALING
LOOP
SD HD SD C
FIRE ALARM DETAIL NOTES
1.
THIS DIAGRAM REPRESENTS A TYPICAL SYSTEM AND IS NOT INTENDED FOR INSTALLATION. SYSTEM
SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND SCHEMATIC WIRING DIAGRAMS. EXACT
SYSTEM REQUIREMENTS SHALL BE COORDINATED WITH THE SYSTEM SUPPLIER. SYSTEM INSTALLER
SHALL BE NICET CERTIFIED, IF REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION.
2.
SYSTEM SUPPLIER SHALL SUPERVISE INSTALLATION, PROGRAM AND TEST SYSTEM AND INSTRUCT
OWNER ON SYSTEM OPERATION.
3.
ALL FIRE ALARM WIRING SHALL BE PLENUM RATED. EXPOSED FIRE ALARM WIRING, 10'-0" AFF AND
BELOW, SHALL BE INSTALLED IN CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR STRUCTURE.
4.
ALL CONTROL CABINETS SHALL BE GROUNDED PER NEC REQUIREMENTS AND PER SPECIFICATIONS.
5.
COORDINATE CITY TIE-IN REQUIREMENTS WITH LOCAL AUTHORITY.
6.
DUCT SMOKES ARE FURNISHED AND WIRED BY EC, AND INSTALLED PER CODE BY MC.
7.
ALL FIRE ALARM DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 & 'ADA'.
PROVIDE WIRING PER
MANUFACTURER'S
INSTALLATION DRAWING
(TYP)
SYNCHRONIZING
MODULE
PROVIDE TELEPHONE
LINE TO TERMINAL
BOARD FOR CITY
TIE-IN OR OFF-SITE
MONITORING.
PROVIDE TELEPHONE
LINE FOR SECONDARY
OFF-SITE MONITORING.
2#12 AWG, 1#12 AWG
GND, 3/4"C.
SCALE: NONE
3
E-1.1
ADDRESSABLE FIRE ALARM SYSTEM TYPICAL WIRING DIAGRAM
PROVIDE WIRING TO EACH SECURITY DOOR
MAG LOCK POWER SUPPLY LOCATION FOR
UNLOCKING OF SECURITY DOORS DURING
FIRE ALARM CONDITION. (COORDINATE
WITH SECURITY SYSTEM SUPPLIER).
PROVIDE WIRING TO PRE-ACTION (OR DRY
TYPE) SPRINKLER SYSTEM CONTROL PANEL.
PROVIDE WIRING TO STARTERS FOR FAN SHUTDOWN.
PROVIDE WIRING AND RELAY
REQUIRED TO SHUTDOWN TENANT SOUND
SYSTEM UPON FIRE ALARM ACTIVATION.
PANEL FOR
TENANT 105
T5a
200A MCB
120/208V
F=(MAX) 1
INCOMING SECTION
WITH MAIN SWITCH
200AMP
LANLDORD
PANEL FOR
TENANT 105
T5b
200A MCB
120/208V
WIREWAY
1
TENANT 105
1
TENANT 106
PANEL FOR
TENANT
SPACE 106
MCB
120/208V
F=(MAX) 1
2" CONDUIT AND PULLWIRE, STUB
UP FROM METER CENTER TO
TENANT 106 SPACE FOR FUTURE
TENANT 107. COORDINATE STUB UP
LOCATION WITH LANDLORD PRIOR
TO INSTILLATION.
F=(MAX) 1
H-10 SITE POLE LIGHTING
H-12 RETAIL EXTERIOR BUILDING LTGS
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C COPYGRIHT 2020, CURRANARCHI TECTURE
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
E0.1
ELECTRICAL
LEGEND, NOTES, DETAILS
05/10/21