HomeMy WebLinkAboutMEP CoordinationEXTERIOR LANDLORD ROOM ASSUMED 225KVA,120/208V PAD MOUNTED UTILITY TRANSFORMER SCALE: NONE 1 E-1.1 ONE LINE DIAGRAM SCALE: 1 OR 2 HOUR RATED UL #WL1001 GYPSUM WALL BOARD ASSEMBLY INTUMESCENT FIRESTOP SEALANT, DEPTH AS REQUIRED BY THE MANUFACTURER METALLIC CONDUIT NONE 5 E-1.1 FIRESTOP FOR METALLIC CONDUIT M GROUNDED CONDUCTOR (NEUTRAL) FROM UTILITY COMPANY TRANSFORMER 10' 10' 10' WITHIN 5' OF WATER ENTRANCE TO BUILDING SCALE: NONE 2 E-1.1 SERVICE GROUNDING AND BONDING DETAIL INCOMING CONDUIT GROUND (IF STEEL CONDUIT) EQUIPMENT GROUNDING BUS EQUIPMENT BONDING JUMPER ENCLOSURE GROUND MAIN BONDING JUMPER (#2/0) PER NEC 250.102.(C)(1). #6 AWG MINIMUM 10" X 2" X 1/4" COPPER GROUND BAR. INSTALL ON TELEPHONE BACKBOARD WITH (2) UL LISTED STANDOFF INSULATORS. BONDING JUMPER SOURCE (DIRECT CONTACT WITH EARTH FOR 10' OR MORE) COPPER CLAD STEEL, 10' x 3/4" WITH TOP OF ROD 6" BELOW FINISH GRADE (TYPICAL) CLAMPS SUITABLE FOR DIRECT BURIAL (TYPICAL) NON-METALLIC PROTECTIVE SLEEVE CONNECTOR LISTED FOR PURPOSE CONCRETE ENCASED ELECTRODE (REINFORCING STEEL) EXOTHERMIC CONNECTION (TYPICAL) METAL FRAME OF BUILDING STRUCTURE BONDING JUMPER (#2/0) ABBREVIATIONS UNDERWRITERS LABORATORIES, INC. UNDERGROUND UNLESS OTHERWISE NOTED MAXIMUM OVER CURRENT PROTECTION MCB MAIN CIRCUIT BREAKER METAL HALIDE MINIMUM MTD MOUNTED MOCP MIN MH LOCKED ROTOR AMPS MINIMUM CIRCUIT AMPACITY MAXIMUM LIGHTING MAX MCA LTG LRA KILOVOLT-AMPS KILOWATT-HOUR KILOWATTS KVA KWH KW HEATER HVAC HEATING, VENTILATING & A/C HTR GENERAL CONTRACTOR GFI, GFIC GROUND FAULT INTERRUPTER GC FOOT, FEET ELECTRICAL WATER COOLER EXISTING FIRE ALARM FULL LOAD AMPS FIRE ALARM CONTROL PANEL EXHAUST FT FACP FLA FA EX, EXIST EWC EXH W WATT, WIDTH VA UL UON UG T/C VOLT-AMPERE TIME CLOCK SQUARE FEET, SQUARE FOOT REFLECTED CEILING PLAN NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MFR'S ASSOC. NATIONAL FIRE PROTECTION ASSOC. OCCUPATIONAL SAFETY &HEALTH ADMIN. ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E0.3 PANEL SCHEDULES 05/10/21 106 VACANT 105 GARBANZO 104 RESTORE HYPER WELLNESS 103 RISE 'N ROLL 102 DRY CLEANER 101 TROPICAL SMOOTHIE CAFE A B 1 2 3 4 5 6 1 2 3 4 5 6 SCALE: 3/32" = 1'-0" 1 E1.1 ELECTRICAL PLAN 1 2 4 5 6 8 9 11 9 7 T1-4 T2-4 T3-4 T5a-4 PANEL T1 PANEL T2 PANEL T3 PANEL T5a WP GFI WP H-6 H-6 3 PANEL H 7 T4-4 PANEL T4 SHEET KEYNOTES 1 UTILITY TRANSFORMER, PAD AND GROUNDING BY EC TO UTILITY COMPANY SPECIFICATIONS. REFER TO SHEET E0.1 AND E1.2 FOR MORE INFORMATION. 2 LOCATION OF METER CENTER. FINAL APPROVED LOCATION SHALL BE VERIFIED WITH OWNER PRIOR TO INSTALLATION OF SERVICE EQUIPMENT. SEE ONE-LINE DIAGRAM (SHEET E-1.1) 3 120/208V, 200AMP LANDLORD PANEL, VERIFY LOCATION WITH OWNER PRIOR TO ROUGH-IN. 4 4" TELEPHONE BACKBOARD, VERIFY LOCATION WITH OWNER PRIOR TO INSTALLATION. 5 UNDERGROUND SERVICE ENTRANCE CONDUITS. REFER TO DETAILS AND ONE LINE DIAGRAM ON SHEET E0.1 FOR MORE INFORMATION. 6 STUB OUT FOR CONNECTION TO TELEPHONE. COORDINATE WITH TELEPHONE COMPANY AND VERIFY CONNECTION LOCATION PRIOR TO INSTALLATION. REFER TO CIVIL PLANS FOR CONTINUATION. 7 400AMP, 120/208V PANEL FED FROM METER CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / 1 T RISE POINT OF CONNECTION - NEW TO EXISTING TURNING VANES INCLINED RISE IN DUCT IN-LINE 90 DEGREE RISE IN DUCT RETURN OR EXHAUST AIR DUCT DOWN DUCTWORK SIZE TRANSITION RETURN OR EXHAUST AIR DUCT UP SUPPLY OR OUTSIDE AIR DUCT UP SUPPLY OR OUTSIDE AIR DUCT DOWN HVAC SYMBOLS 20/12 12"Ø SUPPLY OR OUTSIDE AIR DUCT 90 DEGREE DUCTWORK ELBOW W/ TURNING VANES ROUND OR RECTANGULAR RECTANGULAR DUCTWORK BRANCH TAKE-OFF HIGH EFFIECENY "BUCKLEY" TAP WITH DAMPER RADIUS DUCTWORK ELBOW - WITH 45 DEGREE BRANCH INLET DIFFUSER/GRILLE LABEL: B - NECK SIZE (INCHES) A - TYPE/DESIGNATION C - AIRFLOW (CFM) RETURN, RELIEF OR EXHAUST AIR DUCT PATTERN. NO PATTERN SHOWN EQUALS 4-WAY FIRST NUMBER IS SIDE SHOWN ROUND DUCTWORK. DIAMETER IN INCHES RECTANGULAR DUCTWORK. SIZE IN INCHES, SUPPLY AIR DIFFUSER - SHADING INDICATES RETURN OR EXHAUST AIR GRILLE OR AS NOTED MANUAL VOLUME DAMPER THERMOSTAT SD DRAWING NOTE REFERENCE OVAL OR FLAT OVAL ROUND DUCT SMOKE DETECTOR H HUMIDISTAT S SENSOR F FIRE DAMPER C CARBON DIOXIDE SENSOR UC UNDERCUT DOOR 3/4" FOR AIRFLOW XX/XXL INTERNALLY LINED DUCT IN-LINE 90 DEGREE DROP IN DUCT MOTORIZED DAMPER MD ABBREVIATIONS EWB ENTERING WET BULB TSTAT THERMOSTAT UNLESS OTHERWISE NOTED UNDERWRITERS LABORATORIES, INC. MAXIMUM OVER CURRENT PROTECTION MAKE-UP AIR MECHANICAL MANHOLE, METAL HALIDE MECHANICAL SPECIFICATIONS ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 M0.2 MECHANICAL SPECIFICATIONS 05/10/21 106 VACANT 105 GARBANZO 104 RESTORE HYPER WELLNESS 103 RISE 'N ROLL 102 DRY CLEANER 101 TROPICAL SMOOTHIE CAFE A B 1 2 3 4 5 6 1 2 3 4 5 6 SCALE: 3/32" = 1'-0" 1 M1.1 MECHANICAL PLAN ROOFTOP HVAC UNIT SCHEDULE TAG SERVICE MFR MODEL No. NOMINAL TONS EER MIN OA (CFM) SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS AIR FLOW NOTES/ACCESSORIES (CFM) ESP (IN WC) MOTOR (HP) FAN (RPM) EAT °DB/°WB (°F) LAT °DB/°WB (°F) SENSIBLE (MBH) TOTAL (MBH) COOLING STAGES EAT/LAT (°F) OUTPUT (MBH) HEATING STAGES VOLTAGE (V-ɸ-Hz) UNIT MCA UNIT MOCP OPERATING WEIGHT (LBS) GENERAL SHEET NOTES 1. EXISTING PLUMBING INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT. 3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS TO ADJACENT SPACES. 5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS. 6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS. 7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION, ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA. 8. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70. 10. PROVIDE STOP VALVES AT EVERY FIXTURE ON BOTH HOT AND COLD WATER SUPPLY LINES. VALVES, ESCUTCHEONS, FITTINGS, ETC. MUST BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS TO BE USED. 11. ALL SANITARY PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 1% SLOPE EXCEPT FOR 2" LINES WHICH SHALL BE PITCHED AT 2% SLOPE. 12. ALL GREASE WASTE PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 2% SLOPE. 13. ALL OVERHEAD PIPING IS TO BE ROUTED TIGHT TO BUILDING STRUCTURE. 14. PIPING IS NOT PERMITTED IN DEMISING WALLS. 15. ALL EXPOSED, EXTERIOR PIPING SHALL BE PAINTED WITH RUST INHIBITIVE PRIMER, COLOR CODED FINISH, AND IDENTIFICATION LABELS. 16. VERIFY NATURAL GAS AVAILABILITY AND CAPACITY. COORDINATE PRESSURE, SERVICE CONNECTION, AND METER INSTALLATION WITH THE LANDLORD AND LOCAL UTILITY COMPANY. 17. PROVIDE GAS PIPE SUPPORTS ON ROOF. PROVIDE 10'-0" ON CENTER AND AT ALL CHANGES OF DIRECTION. REFER TO DETAIL 6 ON THIS SHEET. 18. CLEAN AND REFURBISH EXISTING PLUMBING FIXTURES TO BE RE-USED. FIELD VERIFY EXISTING PLUMBING FIXTURES ARE IN PROPER WORKING ORDER. NOTIFY OWNER IMMEDIATELY SHOULD OPERATIONAL CHECK OF FIXTURES REVEAL ANY MAJOR COMPONENT FAILURES. 19. DO NOT ROUTE ANY WATER CONVEYING PIPING OVER ELECTRICAL EQUIPMENT. 20. ALL ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH BOTTOM CLEANOUT PLUGS. 21. INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING SERVING HANDICAPPED LAVATORIES. 22. TENANT SPACES, THAT ARE UN-OCCUPIED AT TIME OF OPENING, ARE TO HAVE PROVIDED BY FIRE PROTECTION CONTRACTOR BRANCH PIPING AND SPRINKLER SPACING BASED ON THE ORDINARY HAZARD GROUP II OCCUPANCY PER NFPA 13. 23. ALL PIPING TO POINTS 5'-0" OUTSIDE THE BUILDING IS BY THE PLUMBING CONTRACTOR. 24. PROVIDE A WALL CLEANOUT AT THE BASE OF ALL VERTICAL STORM AND SANITARY RISERS 1'-0" AFF. 25. FINISHED FLOOR ELEVATION = XXX.00 26. ALL STORM PIPING OUTSIDE THE PERIMETER OF THE BUILDING REQUIRES COORDINATION WITH THE STRUCTURAL FOOTERS TO AVOID TRENCHING AND PIPE PLACEMENT WITHIN THE FOOTING ANGLE OF REPOSE. 27. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL PLUMBING SPECIFICATIONS I. GENERAL PROVISIONS A. GENERAL CONDITIONS, CODES & STANDARDS 1. GENERAL CONDITIONS OF THE CONTRACT FOUND IN THE ARCHITECTURAL DRAWINGS, GENERAL AND SPECIAL CONDITIONS OF THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND ANY OF THE OWNER'S GENERAL REQUIREMENTS SHALL APPLY UNLESS NOTED OTHERWISE. 2. REFER TO THE GENERAL CONDITIONS ON THE ARCHITECTURAL DOCUMENTS AND THE GENERAL AND SPECIAL CONDITIONS OF THE AIA FOR ADDITIONAL REQUIREMENTS REGARDING; SAFETY, COORDINATION & COOPERATION, WORKMANSHIP, PROTECTION, CUTTING AND PATCHING, DAMAGE TO OTHER WORK, PRELIMINARY OPERATIONS, STORAGE, ADJUSTMENTS, CLEANING, ETC. 3. ALL WORK SHALL BE IN CONFORMANCE WITH ALL LOCALLY ENFORCED, FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES INCLUDING ANY SPECIAL THE OWNER REQUIREMENTS IN ADDITION TO THOSE SPECIFIED. 4. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS. B. SCOPE OF WORK 1. THIS CONTRACT SHALL INCLUDE THE FURNISHING, INSTALLING, CONNECTING, AND OPERATION OF ALL EQUIPMENT WHICH IS A PART OF THE FIRE SUPPRESSION SYSTEMS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY SIMILAR INSTALLATIONS. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF A SIMILAR CHARACTER SHALL BE FURNISHED AND INSTALLED UNDER THIS CONTRACT AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS REQUIRED TO PROVIDE THE OWNER A COMPLETE, CODE APPROVED AND OPERATIONAL FIRE SUPPRESSION SYSTEM. 2. CAREFULLY READ SPECIFICATION FOR ALL PARTS OF THE WORK SO AS TO BECOME FAMILIAR WITH ALL TRADES' WORK SCOPE. CONSULT WITH OTHER TRADES TO INSURE PROPER LOCATIONS AND AVOID INTERFERENCES. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER BEFORE WORK IS COMMENCED. 3. CONTRACTORS SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO COMPARE THEM WITH THE DRAWINGS AND SPECIFICATIONS, NOTE THE EXISTING CONDITIONS AND OTHER WORK THAT WILL BE REQUIRED, AND THE NATURE OF THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. NO ALLOWANCE SHALL BE MADE TO THE CONTRACTOR BY REASON OF THIS FAILURE TO HAVE MADE SUCH EXAMINATION OR OF ANY ERROR ON HIS PART. 4. ALL EXISTING UTILITY AND FIRE SUPPRESSION SERVICES SHALL BE FIELD VERIFIED. CORRECTIONS TO THE DESIGN AND INSTALLATION SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER. 5. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF FIRE PROTECTION WORK. ALL CORE DRILLING OR CUTTING OF FIRE RATED FLOORS, SHAFTS, AND WALLS SHALL BE FIRESTOPPED PRIOR TO FINISH PATCHING. ALL PENETRATIONS SHALL BE FIRE SEALED TO MATCH THE FIRE RATING OF THE FLOORS, SHAFTS, AND WALLS PENETRATED. THIS CONTRACTOR IS RESPONSIBLE TO COORDINATE THE OPENINGS IN WALLS AND FLOORS WITH THE GENERAL TRADES CONTRACTOR. THE FINAL LOCATIONS AND SIZES OF ALL PIPE OPENINGS SHALL BE PROVIDED BY THIS CONTRACTOR. 6. THIS CONTRACT SHALL ALSO INCLUDE ALL LABOR, MATERIALS AND MISCELLANEOUS EXPENSES REQUIRED FOR ALL REQUIRED FIRE SUPPRESSION DEMOLITION OF THE EXISTING AREAS BEING RENOVATED. a. THE DEMOLITION SHALL CONSIST OF THE COMPLETE REMOVAL (PROPERLY DISPOSED OFF SITE UNLESS OTHERWISE NOTED) OF ALL FIRE SUPPRESSION EQUIPMENT, PIPING, MATERIALS, ETC. NOT REQUIRED IN THE FINAL DESIGN AND INSTALLATION OF THE FIRE SUPPRESSION SYSTEMS FOR THE NEW RENOVATED AREAS. b. ALL ABOVE GROUND SERVICES SHALL BE REMOVED BACK TO THEIR RESPECTIVE MAIN AND CAPPED OR IF THE MAIN IS NOT REQUIRED, THE MAIN SHALL BE REMOVED IN IT'S ENTIRETY. c. COORDINATE ALL DEMOLITION WITH THE ARCHITECTURAL DOCUMENTS AND THE ARCHITECT AND THE OWNER'S GENERAL REQUIREMENTS. 7. ALL WORK INCLUDING, BUT NOT LIMITED TO PARTS, MATERIAL, EQUIPMENT AND LABOR SHALL BE GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY THE ENGINEER AND OWNER. WHERE AN EQUIPMENT MANUFACTURER HAS A WARRANTY THAT EXCEEDS ONE YEAR, THAT WARRANTY PERIOD SHALL APPLY TO THIS PROJECT. C. DOCUMENTS 106 VACANT 105 GARBANZO 104 RESTORE HYPER WELLNESS 103 RISE 'N ROLL 102 DRY CLEANER 101 TROPICAL SMOOTHIE CAFE A B 1 2 3 4 5 6 1 2 3 4 5 6 SHEET KEYNOTES 1 SEE SITE UTILITY PLAN FOR CONTINUATION 2 GAS METER 3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION. 4 EX 1000 GT 5 6 7 8 9 10 SCALE: 3/32" = 1'-0" 1 P1.1 PLUMBING PLAN M SEE ENLARGED PLAN EX CO SEE ENLARGED PLAN SEE ENLARGED PLAN FCO FCO FCO FCO FCO FCO FCO FCO FCO FCO 6" GW 6" SAN EX CO EX CO EX CO 4 1 1 2 104 RESTORE HYPER WELLNESS 4 SHEET KEYNOTES 1 SEE SITE UTILITY PLAN FOR CONTINUATION 2 GAS METER 3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION. 4 EX 1000 GT 5 6 7 8 9 10 SCALE: 1/4" = 1'-0" 1 P1.2 ENLARGED PLUMBING PLAN UNIT 104 GENERAL SHEET NOTES 1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT. EWC WH MS LAV WC SK SINK SINK SH FCO FCO KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY SHEET KEYNOTES 1 SEE SITE UTILITY PLAN FOR CONTINUATION 2 GAS METER 3 X" GAS UP EXTERIOR WALL. SEE ROOF PLAN FOR CONTINUATION. 4 EX 1000 GT 5 6 7 8 9 10 SCALE: 1/4" = 1'-0" 1 P1.2 ENLARGED PLUMBING PLAN UNIT 104 GENERAL SHEET NOTES 1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT. SCALE: 1/4" = 1'-0" 3 P1.2 ENLARGED RESTROOM UNIT 103 SCALE: 1/4" = 1'-0" 5 P1.2 ENLARGED RESTROOM UNIT 101 FCO LAV WC SCALE: 1/4" = 1'-0" 2 P1.2 ENLARGED RESTROOM UNIT 103 SCALE: 1/4" = 1'-0" 4 P1.2 ENLARGED RESTROOM UNIT 101 FD LAV WC FCO FD LAV WC FCO WH FFD TP LAV WC TP KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 P1.3 ENLARGED PLUMBING PLANS 05/10/21 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 P1.2 ENLARGED PLUMBING PLAN add rough ins as required in walls. 05/10/21 3 GENERAL SHEET NOTES 1. EXISTING PLUMBING INFORMATION IS BASED ON EXISTING BUILDING DRAWINGS. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 3. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 4. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 5. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN WEATHERPROOF PRIOR TO CONCEALMENT. FCO FCO FCO FCO FCO FCO FCO FCO FCO FCO FCO FCO FCO M 1 1 2 3 M 1 1 2 3 M 1 1 2 3 M 1 1 2 3 M 1 1 2 3 M 1 1 2 3 KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 P1.1 PLUMBING PLAN hose bib 05/10/21 1. THE DRAWINGS ARE DIAGRAMMATIC, ALL WORK SHALL BE PERFORMED AS INDICATED ON THE DRAWINGS UNLESS EXISTING CONDITIONS OR COORDINATION ISSUES REQUIRE CHANGES. THESE CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER. 2. ANY INCIDENTAL ITEMS OR LABOR, ETC. NOT INCLUDED IN THE SPECIFICATIONS OR THE DRAWINGS BUT REASONABLY IMPLIED AS NECESSARY FOR THE COMPLETE INSTALLATION OF ALL APPARATUS SHALL BE INCLUDING IN BID. 3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NOT MENTIONED IN BOTH. 4. IF ERRORS ARE FOUND IN THE DRAWINGS OR SPECIFICATIONS OR DISCREPANCIES OCCUR BETWEEN THE SAME, OR BETWEEN THE FIGURES ON THE DRAWINGS, AND THE SCALE OF SAME OR BETWEEN THE LARGER AND SMALLER DRAWINGS, OR IN THE DESCRIPTIVE MATTER ON THE DRAWINGS SHALL BE REFERRED TO THE OWNER FOR REVIEW AND FINAL DECISION PRIOR TO THE BID DUE DATE. 5. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY AS SPECIFIED HEREIN. WHERE MORE THAN ONE MANUFACTURER IS MENTIONED ANY ONE MAY BE UTILIZED. SUBSTITUTE MANUFACTURERS MAY BE OFFERED ONLY AS AN ALTERNATE TO THE SPECIFIED EQUIPMENT AND MATERIAL AND MUST BE SUBMITTED AS SPECIFIED IN THE ARCHITECTURAL DOCUMENTS. 6. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN THESE SPECIFICATIONS. REFER TO EACH SECTION FOR ANY SPECIFIC REQUIREMENTS. D. COORDINATION 1. CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. 2. EACH CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGE TO OTHER WORK CAUSED BY HIS WORK OR THROUGH THE NEGLECT OF HIS, OR HIS SUB-TRADE'S PERSONNEL. ALL PATCHING, REPAIRING, REPLACEMENT AND PAINTING, ETC. SHALL BE DONE AS DIRECTED BY THE OWNER BY THE CRAFTSMEN OF THE TRADES INVOLVED. THE COSTS OF SUCH WORK SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. E. METHODS 1. EQUIPMENT, PIPING, DUCTWORK, ETC. SHALL NOT BE SUPPORTED FROM ANY CEILINGS, OTHER PIPING, CONDUIT OR DUCTWORK, ROOF DECK, OR JOIST BRIDGING. ITEMS SHALL BE SUPPORTED FROM ACCEPTABLE STRUCTURAL BUILDING COMPONENTS AS DETERMINED BY THE ARCHITECT AND STRUCTURAL ENGINEER. F. SUBMITTALS 1. SHOP DRAWINGS a. PREPARE AND SUBMIT SHOP DRAWINGS IN ACCORDANCE WITH THE MECHANICAL GENERAL PROVISIONS. b. SHOW PLANS, CROSS SECTION, ELEVATIONS, DETAILS AND JOB CONDITIONS, RELATIONSHIP TO OTHER WORK. PIPE SIZES, ELEVATIONS ABOVE FLOOR, HEAD LOCATIONS, INSPECTORS TEST CONNECTION, SPRINKLER ENTRANCE, VALVES, ALARMS, BACKFLOW PREVENTER, FLOW SWITCH AND SUPERVISORY DEVICES. c. SUBMIT DATA ON THE FOLLOWING ITEMS: (1)PIPING AND COUPLINGS. (2)WET ALARM VALVE. (3)BACKFLOW PREVENTER. (4) VALVES AND SUPERVISORY DEVICES. (5)SPRINKLER HEADS AND ESCUTCHEON PLATES. (6)SUPPORTS, HANGERS AND ACCESSORIES. (7)SEISMIC CALCULATIONS (8)SUBMIT AND RECEIVE APPROVAL FROM THE AUTHORITY HAVING JURISDICTION PRIOR TO SUBMITTAL. d. ONCE THE AUTHORITY HAVING JURISDICTION HAS APPROVED SHOP DRAWINGS, THE SUBCONTRACTOR SHALL SEND EIGHT SETS OF APPROVED STAMPED PLANS AND EQUIPMENT CUTS TO THE ARCHITECT FOR APPROVAL. e. PLANS SUBMITTED WITHOUT ALL HYDRAULIC CALCULATIONS WILL BE RETURNED "REJECTED". d. PROVIDE INDEPENDENT HYDRAULIC CALCULATION SHEETS. f.ALL SPRINKLER PLANS SHALL BEAR THE STAMP OF A REGISTERED PROFESSIONAL FIRE PROTECTION ENGINEER LICENSED WITH THE STATE WHERE THE STORE IS LOCATED. 2. AT THE COMPLETION OF THE PROJECT, PROVIDE OWNER WITH OPERATION AND MAINTENANCE MANUALS INCLUDING "AS-BUILT" RECORD DRAWINGS, SPECIFICATIONS AND APPROVED PLANS. 3. PROJECT RECORD DOCUMENTS - MAINTAIN AT THE JOBSITE ONE COPY OF ALL CONTRACT DOCUMENTS CLEARLY MARKED AS “PROJECT RECORD COPY”. THESE DRAWINGS ARE TO BE MAINTAINED IN GOOD CONDITION, UPDATED DAILY FOR CHANGES ENCOUNTERED AND AVAILABLE AT ALL TIMES FOR INSPECTION BY THE OWNER. DO NOT USE FOR FIELD CONSTRUCTION! PROJECT RECORD DOCUMENTS ARE TO BE KEPT CURRENT WITH EXACT DIMENSIONS OF ALL WORK, EQUIPMENT, PIPING, VALVES, DUCTWORK, ETC. MARK ALL INFORMATION IN RED LINES AND NOTES SO AS TO BE EASILY IDENTIFIED FROM THE BASE DRAWING. UPON COMPLETION OF THE WORK, ONE SET OF THESE DOCUMENTS SHALL BE TURNED OVER TO THE OWNER AS ONE QUALIFICATION FOR FINAL PAYMENT. 4. AFTER THE ACCEPTANCE TESTS ARE COMPLETED AND ACCEPTED BY THE OWNER, THREE COMPLETE SETS OF AS-BUILT DOCUMENTATION SHALL BE PROVIDED. IT SHALL INCLUDE, BUT NOT BE LIMITED TO ACCURATE PLAN DRAWINGS AND OPERATION AND MAINTENANCE MANUALS. II. SPRINKLER A. GENERAL 1. THE ENTIRE INSTALLATION SHALL CONFORM TO THE REQUIREMENTS OF NFPA 13, THE BUILDING OWNER'S INSURANCE COMPANY, THE LOCALLY ENFORCED BUILDING CODE, LOCAL BUILDING AND FIRE OFFICIALS AND ALL OTHER LOCAL AUTHORITIES HAVING JURISDICTION. 2. ALL WORK SHALL BE PERFORMED BY A LANDLORD APPROVED, STATE OF IN WHICH THE PROJECT IS BEING CONSTRUCTED LICENSED SPRINKLER CONTRACTOR. 3. THIS WORK SHALL INCLUDE ALL PIPING, FITTINGS, HANGERS, EQUIPMENT, ETC., REQUIRED TO COMPLETE THE WORK. 4. SPRINKLER HEADS ARE TO BE CENTERED IN LAY-IN CEILING TILES. HEADS ARE TO BE SPACED SYMMETRICALLY WITH LIGHTING AND OTHER CEILING FIXTURES WHEN INSTALLED IN DRYWALL CEILINGS. 5. DETERMINE VOLUME AND PRESSURE OF INCOMING WATER SUPPLY FROM WATER FLOW TEST DATA. REVISE DESIGN WHEN TEST DATA BECOMES AVAILABLE PRIOR TO SUBMITTALS. B. CRITERIA 1. CONTRACTOR SHALL VERIFY WITH THE OWNER'S REPRESENTATIVE FOR ANY ADDITIONAL CRITERIA (PIPE SIZING; PIPE SCHEDULE OR HYDRAULIC). 2. CONTRACTOR SHALL DESIGN AND MODIFY THE EXISTING SPRINKLER SYSTEM PIPING AND HEADS FOR THE SPACE. THIS WORK SHALL INCLUDE THE RAISING OF ANY EXISTING SPRINKLER PIPING WHICH INTERFERES WITH DESIGNED CEILING ELEVATIONS. WHERE REQUIRED, THE CONTRACTOR SHALL ALSO INCLUDE COMBINING THE EXISTING SYSTEM TO A SINGLE SOURCE WHEN TAKING OVER MULTIPLE TENANTS. PROVIDE ANY AUXILIARY DRAIN PIPING REQUIRED FOR ANY TRAPPED SPRINKLER PIPING. 3. SEE ARCHITECTURAL DRAWINGS FOR CEILING ELEVATIONS. C. COMPONENTS 1. FIRE DEPARTMENT CONNECTION: POTTER-ROEMER OR EQUAL SERIES 5020 (CONNECTION SIZES COORDINATED AND APPROVED BY THE LOCAL AUTHORITITES), WITH ALL STANDARD FEATURES, "AUTO. SPKR." LETTERING, AND THREAD TO MATCH LOCAL FIRE DEPARTMENT REQUIREMENTS. - FLUSH MOUNTED FIRE DEPARTMENT INLET CONNECTION WITH WALL PLATE WITH “AUTOMATIC SPRINKLER” IDENTIFICATION, ALL BRASS CONSTRUCTION AND POLISHED BRASS FINISH. CONTACT THE FIRE DEPARTMENT TO VERIFY FIRE DEPARTMENT CONNECTION TYPE AND TREAD PATTERN TO MATCH THAT OF THE FIRE DEPARTMENT EQUIPMENT. PROVIDE 4" UL LISTED CHECK VALVE WITH BALL DRIP PIPED TO DRAIN. D. SUPERVISION 1. THE RISER CONTROL VALVE AND ALL ZONE VALVES SHALL HAVE ELECTRIC SUPER VISION TO SIGNAL THE BUILDING FIRE ALARM SYSTEM. TAMPER SWITCHES PROVIDED BY SPRINKLER SUBCONTRACTOR AND WIRED BY THE ELECTRICAL SUBCONTRACTOR. 2. MECHANICAL: ALL OTHER VALVES SHALL BE PADLOCKED IN STANDARD OPERATING POSITION, WITH 2 KEYS PER PADLOCK AND ALL PADLOCKS SHALL BE KEYED THE SAME. CHAIN AND PADLOCK ALL VALVES OVER 2" SIZE. E. PIPING 1. PIPING SHALL BE BLACK STEEL PIPE PER NFPA 13. F. SPRINKLER HEADS 1. SPRINKLER HEADS IN AREAS WITH CEILINGS SHALL BE RECESSED, POLISHED CHROME PENDANT AUTOMATIC SPRINKLER HEAD WITH TWO PIECE FACTORY WHITE METAL ESCUTCHEON. 2. SPRINKLER HEADS IN AREAS WITH DRYWALL CEILINGS SHALL BE FLUSH SERIES WITH A WHITE CEILING PLATE. 3. SPRINKLER HEADS IN AREAS WITH EXPOSED STRUCTURE SHALL BE BRASS UPRIGHT. III. LABELING A. TAGS 1. METAL TAGS: a. BRASS WITH STAMPED LETTERS; TAG SIZE MINIMUM 1-1/2 INCHES DIAMETER. 2. TAG CHART: TYPEWRITTEN LETTER SIZE LIST OF APPLIED TAGS AND LOCATION IN ANODIZED ALUMINUM FRAME. B. PIPE MARKERS 1. COLOR AND LETTERING: CONFORM TO ASME A13.1. 2. PLASTIC PIPE MARKERS: a. FACTORY FABRICATED, FLEXIBLE, SEMI-RIGID PLASTIC, PREFORMED TO FIT AROUND PIPE OR PIPE COVERING. LARGER SIZES MAY HAVE MAXIMUM SHEET SIZE WITH SPRING FASTENER. C. INSTALLATION 1. INSTALL IDENTIFYING DEVICES AFTER COMPLETION OF COVERINGS AND PAINTING. 2. INSTALL PLASTIC NAMEPLATES WITH CORROSIVE-RESISTANT MECHANICAL FASTENERS, OR ADHESIVE. 3. INSTALL TAGS USING CORROSION RESISTANT CHAIN. NUMBER TAGS CONSECUTIVELY BY LOCATION. 4. IDENTIFY VALVES IN MAIN AND BRANCH PIPING WITH TAGS. 5. IDENTIFY PIPING, CONCEALED OR EXPOSED, WITH PLASTIC PIPE MARKERS, PLASTIC TAPE PIPE MARKERS OR STENCILED PAINTING. IDENTIFY SERVICE, FLOW DIRECTION, AND PRESSURE. INSTALL IN CLEAR VIEW AND ALIGN WITH AXIS OF PIPING. LOCATE IDENTIFICATION NOT TO EXCEED 20 FEET ON STRAIGHT RUNS INCLUDING RISERS AND DROPS, ADJACENT TO EACH VALVE AND TEE, AT EACH SIDE OF PENETRATION OF STRUCTURE OR ENCLOSURE, AND AT EACH OBSTRUCTION. ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 P0.2 PLUMBING SPECIFICATIONS 05/10/21 STEEL WHICH EXISTS ABOVE THE SPACE. 28. CONTRACTOR SHALL VERIFY IF SPRINKLER HEADS UNDER STOCK SHELVING ARE REQUIRED. 29. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN LEAK PROOF AND FREE FROM DEFECTS PRIOR TO CONCEALMENT. 30. ALL FLOOR DRAINS AND CLEANOUTS ARE TO BE INSTALLED FLUSH WITH THE FINISHED FLOOR. 31. ALL FLOOR SINKS ARE TO BE INSTALLED EITHER FLUSH WITH FINISHED FLOOR, OR RAISED PER LOCAL CODE REQUIREMENTS. ABBREVIATIONS TMV THERMOSTATIC MIXING VALVE UNLESS OTHERWISE NOTED UNDERWRITERS LABORATORIES, INC. MAKE-UP AIR MECHANICAL MANHOLE MANUFACTURER MINIMUM MTD MOUNTED MUA MECH MFR MIN MH 1000 BTU PER HOUR MAXIMUM LOW PRESSURE POUNDS MAX MBH LBS, # LP H HEIGHT KEC KITCHEN EQUIPMENT CONTRACTOR HEAD, HUB DRAIN HORSEPOWER HEATING, VENTILATING & A/C HYDRANT DOMESTIC HOT WATER HERTZ HVAC HYD HW HZ HD HP ELECTRICAL CONTRACTOR GALLON GALVANIZED GENERAL CONTRACTOR GREASE INTERCEPTOR GALLONS PER MINUTE GALLONS PER HOUR GALLONS PER DAY GAUGE GREASE WASTE GI GPD GPM GPH GW GAL GALV GC GA DEGREES FAHRENHEIT FOOT, FEET EXISTING FLOOR DRAIN FLEXIBLE FEET PER MINUTE FLOOR SINK FLOOR CLEANOUT EXHAUST °F FT FLEX FPM FCO FD FS EX EXH EC W/ W/O WC VTR WITH WATER COLUMN WITHOUT VENT THROUGH ROOF VAC UON U/F U/G U/S UL TYP VACUUM VENT UNDERGROUND UNDERSLAB UNDERFLOOR TYPICAL SQUARE FEET, SQUARE FOOT REVOLUTIONS PER MINUTE TOTAL STATIC PRESSURE STORM WATER POST INDICATOR VALVE POUNDS PER SQUARE INCH PRESSURE RELIEF VALVE REFLECTED CEILING PLAN REINFORCING, REINFORCED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MFR'S ASSOC. NATIONAL FIRE PROTECTION ASSOC. OUTSIDE STEM AND YOKE OCCUPATIONAL SAFETY & HEALTH ADMIN. AWWA AMERICAN WATER WORKS ASSOC. EXTERNAL STATIC PRESSURE ELECTRICAL ELEVATION EQUIPMENT ENCLOSURE DRAWING EACH ESP ENCL ELEC EQUIP ELEV EA DWG DOMESTIC COLD WATER DOWNSPOUT DIAMETER DEGREES DIMENSION DOWN DS DIA (OR Ø) DN DIM CW DEG SPEC SPECIFICATION THRU TP TSP TDH STD SUSP SURF ST SQ TOTAL DYNAMIC HEAD THROUGH TOTAL PRESSURE SUSPEND STANDARD SURFACE SQUARE SECT SHT SF RPM SECTION SHEET CONCRETE CENTERLINE COLUMN CLEANOUT CEILING CUBIC FEET PER MINUTE CUBIC FEET PER HOUR L CLG COL CO C CC CFM CFH ASSY ASSEMBLY RD REQ REV REINF RCP ROOF DRAIN REQUIRED REVISION, REVISE PRV PSI PH, Ø PIV PLBG PD PLUMBING PRESSURE DROP PHASE AMERICAN NAT'L STANDARDS INSTITUTE AMERICAN SOCIETY OF TESTING & MATLS AMERICAN SOCIETY OF MECHANICAL ENGRS ABOVE FINISHED GRADE AUXILIARY ARCHITECT, ARCHITECTURAL AMERICAN WELDING SOCIETY ADJUSTABLE ABOVE FINISHED FLOOR ABOVE FINISHED CEILING ASME ASTM AUX AWS AFG ARCH ANSI ADJ AFF AFC ABV ABOVE OS&Y OSHA OD OC NFPA NTS N.O. NIC OVERFLOW DRAINAGE ON CENTER NOT TO SCALE NORMALLY OPEN NOT IN CONTRACT NEC NEMA N/A NOT APPLICABLE ETR EXISTING TO REMAIN REX REMOVE EXISTING COP CLEANOUT PLUG ORD OVERFLOW ROOF DRAIN RWC RAIN WATER CONDUCTOR BOTTOM OF PIPE BUILDING BRITISH THERMAL UNIT BOTTOM OF STRUCTURE BUILDING AUTOMATION SYSTEM BLDG BOP BOS BTU BAS BELOW FLOOR BMS BUILDING MANAGEMENT SYSTEM DOM DOMESTIC FP FIRE PROTECTION FW FILTERED WATER GRD GROUND MC MECHANICAL CONTRACTOR O/H OVERHEAD OPNG OPENING REL RELOCATED SAN SANITARY D DEPTH G GAS CONN CONNECT, CONNECTION STUB UP FOR FUTURE DCV PLUMBING SYMBOLS GAS MANIFOLD LOCATION DOMESTIC WATER RISER PLUMBING FIXTURES DOUBLE CHECK BACKFLOW PREVENTER SPRINKLER HEAD (SEMI-RECESSED) SPRINKLER HEAD (FULLY-RECESSED) SPRINKLER HEAD (UPRIGHT) TENANT CONNECTION N.C. NORMALLY CLOSED PB PUSH BUTTON HWR DOMESTIC HOT WATER RETURN B/F CTE CONNECT TO EXISTING FF FINISHED FLOOR RR REMOVE AND RELOCATE ID INSIDE DIAMETER INVERT ELEVATION INCH, INCHES IN w.c INCHES OF WATER COLUMN (GAS) IN IE V OS&Y VALVE BALL VALVE ELBOW DOWN ELBOW UP UNION TEE OUTLET UP TEE OUTLET DOWN DIRECTION OF FLOW VALVE IN DROP EXPANSION JOINT GATE VALVE CALIBRATED BALANCING VALVE PIPE GUIDE 3-WAY SELF OPERATING VALVE BUTTERFLY VALVE PRESSURE REDUCING VALVE CHECK VALVE MOTOR OPERATED VALVE 2-WAY SELF OPERATING VALVE M HOSE BIB GW GREASE WASTE EXISTING PIPING TO REMAIN EXISTING PIPING TO BE REMOVED NEW PIPING / EQUIPMENT FS T&P RELIEF VALVE PRESSURE SWITCH CAP ON END LINE FLOW SWITCH PRESSURE GAUGE WITH GAUGE COCK THERMOMETER FLEXIBLE CONNECTION PIPE FLANGE THERMOMETER WELL GAS VALVE WALL CLEANOUT OR CLEAOUT PLUG FLOOR CLEANOUT M WATER METER R GAS REGULATOR FLOOR SINK (FS) FLOOR DRAIN WITH P-TRAP DRAWING NOTE REFERENCE NEW TO EXISTING POINT OF CONNECTION - 1 PS (ALL ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS) (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS) PIPING ABOVE FLOOR PIPING BELOW FLOOR SAN SANITARY PIPING OD RWC G OVERFLOW DRAIN PIPING HOT WATER (HW) PIPING COLD WATER (CW) PIPING NATURAL GAS PIPING HOT WATER RECIRCULATION (HWR) STORM PIPING (ABOVE GROUND) V SANITARY VENT PIPING ST STORM PIPING (UNDERGROUND) ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 P0.1 PLUMBING LEGEND, NOTES, DETAILS 05/10/21 RTU-1 TROPICAL SMOOTHIE TRANE YSC120 10 11.2 200 4000 0.75 2.75 1465 80.0/67.0 58.8/58.0 96.8 116.3 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18 RTU-2 DRY CLEANER TRANE YSC036 3 12.0 60 1200 0.75 0.75 1061 80.0/67.0 59.3/57.9 29.2 37.0 MOD 50.0/112.7 81.0 2 208-3-60 20.0 30.0 850 1-18 RTU-3 RISE AND ROLL TRANE YSC048 4 12.0 80 1600 0.75 1.00 1181 80.0/67.0 58.8/57.6 37.9 48.9 MOD 50.0/97.1 81.0 2 208-3-60 26.0 35.0 850 1-18 RTU-4 RESTORE HYPER WELLNESS TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18 RTU-5 RESTORE HYPER WELLNESS TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18 RTU-6 GARBANZO TRANE YSC060 5 12.0 110 2100 0.75 1.50 1147 80.0/67.0 60.2/58.7 49.6 60.3 MOD 50.0/86.0 81.0 2 208-3-60 30.0 45.0 880 1-18 RTU-7 GARBANZO TRANE YSC060 5 12.0 110 2100 0.75 1.50 1147 80.0/67.0 60.2/58.7 49.6 60.3 MOD 50.0/86.0 81.0 2 208-3-60 30.0 45.0 880 1-18 RTU-8 TENANT TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18 RTU-9 TENANT TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 880 1-18 NOTES/ACCESSORIES 1. 95° CONDENSING TEMPERATURE 2. REFRIGERANT - R410A 3. REFERENCE ENTHALPY ECONOMIZER WITH FAULT DIAGNOSTIC DETECTION 4. BAROMETRIC RELIEF 5. 14"INSULATED ROOF CURB 6. UNIT MOUNTED NON FUSED DISCONNECT 7. UNPOWERED GFCI RECEPTACLE 8. SUPPLY FAN VFD WITH SINGLE ZONE VAV CONTROLLER 9. THROUGH THE BASE ELECTRICAL 10. HAIL GUARD - WITH TOOL LESS REMOVAL 11. RTU MFANUACTURER'S PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT WITH OCCUPANCY OUTSIDE AIR CONTROL. 12. HINGED ACCESS DOORS 13. ONCE THE RTU’S ARE OPERATIONAL - PROVIDE 2” MERV 8 FILTERS. INSPECT FILTERS DAILY. REPLACE AS NEEDED BUT NOT LONGER THAN 7 DAYS UNTIL UNIT IS ADJUSTED BY BALANCE CONTRACTOR. AT THE DISCRETION OF THE TENANT CONSTRUCTION REPRESENTATIVE THIS FILTER REPLACEMENT CAN BE EXTENDED PAST THE 7 DAY LIMIT. ALL UN-USED FILTERS TO REMAIN ON SITE FOR FUTURE USE BY TENANT. NEVER OPERATE THE RTU(S) IN COOLING DURING ANY SANDING OR DEMOLITION OR IF ANY TYPE OF FINE PARTICULATE COULD BE AIR BORNE. ALL RETURN AIR GRILLES OPENING IN RETURN AIR DUCTWORK SHALL BE COVERED WITH CHEESE CLOTH OR A THROW AWAY FILTER (CHEAP CUT TO FIT FILTER ROLL) UNTIL UNITS ARE ADJUSTED BY THE BALANCING CONTRACTOR. REMOVE THIS CHEESE CLOTH FILTER UPON TESTING BY BALANCE CONTRACTOR. 14. MICRO-PROCESSOR CONTROLS 15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY 16. STAINLESS STEEL HEAT EXCHANGER WITH STAGED HEAT 17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER 18. APPROVED ALTERNATES: CARRIER, AAON, YORK/JOHNSON CONTROLS, AND LENNOX OUTLINE OF RTU-1 ON ROOF GENERAL SHEET NOTES 1. EXISTING MECHANICAL INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY. CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS. 2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT. 3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION PRESENTED AND FIELD CONDITIONS. 4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS TO ADJACENT SPACES. 5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS. 6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS. 7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION, ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA. 8. MECHANICAL SYSTEMS INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR SMOKE TIGHT ASSEMBLIES. COORDINATE W/ARCHITECTURAL PLANS AND GENERAL CONTRACTOR. 9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70. 10. LIMITED ABOVE CEILING CLEARANCES EXIST. COORDINATE LOCATION AND ELEVATION OF MECHANICAL WORK WITH ALL DUCTWORK, SPRINKLERS, LIGHT FIXTURES, AND OTHER CEILING BUILT-IN FIXTURES. CONTACT ENGINEER OR ARCHITECT IMMEDIATELY SHOULD ANY CONFLICT ARISE. 11. ALL ROOF PENETRATIONS, PATCHING AND FLASHING SHALL BE PERFORMED BY A LANDLORD APPROVED ROOFING CONTRACTOR AT THIS CONTRACTOR'S EXPENSE. COORDINATE ROOF PENETRATIONS AND ROOFTOP EQUIPMENT LOCATIONS WITH LANDLORD AND GENERAL CONTRACTOR. 12. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK. CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL STEEL WHICH EXISTS ABOVE THE SPACE. 13. COORDINATE FINAL ROOFTOP UNIT LOCATIONS WITH LANDLORDS STRUCTURAL ENGINEER. ROOFTOP UNITS AND MAKE-UP AIR UNIT TO BE LOCATED WITHIN STRUCTURAL BAY. PROVIDE 10' CLEARANCE FROM UNIT OUTSIDE AIR INTAKE TO ANY EXHAUST/VENTS ON ROOF. 14. GENERAL CONTRACTOR TO LABEL ALL ROOFTOP EQUIPMENT WITH TENANT NAME, SPACE NUMBER AND EQUIPMENT IDENTIFICATION (RTU-1, ETC.), PER MALL SPECIFICATIONS AND STANDARDS. 15. REFER TO MALL CRITERIA MANUAL FOR ADDITIONAL STANDARDS AND REQUIREMENTS. 16. COORDINATE ALL THERMOSTAT AND SENSOR LOCATIONS WITH FURNITURE LAYOUT AND ARCHITECTURAL PLANS. DEVICES ARE TO BE INSTALLED AND WIRED BY THE HVAC CONTRACTOR, MOUNT PER ADA REQUIREMENTS. 17. ALL EXPOSED DUCTWORK TO BE PAINTED. REFER TO ARCHITECTURAL PLANS. 18. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION WITH A MAXIMUM INCLUDE ANGLE OF DIVERGENCE OF 15 DEGREE. 19. DUCT SIZES INDICATED REPRESENT EXTERNAL SHEET METAL DIMENSIONS AND INCLUDE ALLOWANCE FOR INTERNAL INSULATION. 20. ALL SUPPLY AND MAKE-UP AIR DUCTWORK NOT EXPOSED SHALL BE EXTERNALLY INSULATED. 21. BRANCH DUCTS SERVING DIFFUSERS SHALL BE SIZED TO MATCH DIFFUSER NECK SIZE INDICATED UNLESS NOTED OTHERWISE. 22. PROVIDE A STRAIGHT INLET LENGTH TO THE VAV BOX OF A MINIMUM (4) DUCT DIAMETERS. REFER TO DETAIL FOR ADDITIONAL INFORMATION. 23. PROVIDE ACCESS HATCHES (24"x24") FOR ALL MECHANICAL EQUIPMENT LOCATED ABOVE A HARD CEILING. COORDINATE W/ ARCHITECTURAL CEILING PLANS. 24. PITCH POCKETS ARE NOT PERMITTED ON THE ROOF FOR CONDENSATE DRAINS, POWER OR CONTROL WIRING. ALL CONNECTIONS ARE TO BE MADE INSIDE THE EQUIPMENT CURB OR THROUGH PRE-MANUFACTURED PIPING CURB. 25. COORDINATE EXACT MOUNTING REQUIREMENTS AND LOCATION OF HOOD WITH HOOD SHOP DRAWINGS AND OWNER REQUIREMENTS. 26. GREASE EXHAUST DUCT ACCESS PANEL CLEANOUT OPENINGS SHALL BE EQUIPPED WITH TIGHT FITTING DOORS (EQUAL TO THE THICKNESS OF THE DUCT) AND SHALL HOLD TIGHTLY CLOSED. 27. ALL DUCTWORK, DIFFUSERS AND GRILLES IN POOL AREA SHALL BE ALUMINUM CONSTRUCTION. 28. CONTRACTOR MUST REPLACE ALL AIR FILTERS IN ROOFTOP UNITS WITH NEW CLEAN FILTERS BEFORE AIR BALANCING AND PRIOR TO FINAL TURNOVER TO TENANT. SHEET KEYNOTES 1 TRANSITION LINED SUPPLY DUCT IN RISE TO FULL SIZE OF RTU SUPPLY OPENING. CONNECT TO FULL SIZE OF RTU SUPPLY OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND SA DUCTWORK TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION. REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION. 2 TRANSITION LINED RETURN DUCT IN RISE TO FULL SIZE OF RTU RETURN OPENING. CONNECT TO FULL SIZE OF RTU RETURN OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND RA DUCTWORK TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION. REFER TO RTU SECTION DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION. 3 SMOKE DETECTOR MOUNTED IN RETURN DUCT. DETECTOR SHALL BE PROVIDED AND WIRED BY ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. COORDINATE WITH GENERAL CONTRACTOR TO PROVIDE 24/24 ACCESS PANEL FOR DUCT MOUNTED SMOKE DETECTOR. ACCESS PANEL MAY BE OMITTED IT DETECTOR IS ACCESSIBLE THROUGH LAY-IN DIFFUSER, OR IF DETECTOR IS LOCATED IN AREA WITH NO CEILING. 1 2 SD 3 1 2 SD 3 1 2 SD 3 SD 3 1 2 1 2 1 2 3 SD SD 3 1 2 1 2 1 2 SD SD 3 SD 3 3 OUTLINE OF RTU-2 ON ROOF OUTLINE OF RTU-3 ON ROOF OUTLINE OF RTU-4 ON ROOF OUTLINE OF RTU-6 ON ROOF OUTLINE OF RTU-8 ON ROOF OUTLINE OF RTU-9 ON ROOF OUTLINE OF RTU-5 ON ROOF OUTLINE OF RTU-7 ON ROOF KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 M1.1 MECHANICAL PLAN note to refer to tenant's plan and install trunks and diffusers note to refer to tenant's plan and install trunks and diffusers note to refer to tenant's plan and install trunks and diffusers add a note to install complete HVAC as required by tenant's plans. 05/10/21 MANUFACTURER MINIMUM MOUNTED MOTORIZED DAMPER MOTOR CONTROL CENTER MTD MUA MECH MFR MOCP MIN MH MCC MD LEAVING WATER TEMPERATURE LOCKED ROTOR AMPS 1000 BTU PER HOUR MINIMUM CIRCUIT AMPACITY MAXIMUM LIGHTING LEAVING WET BULB LEAVING DRY BULB LOW PRESSURE LEAVING AIR TEMPERATURE INTERNALLY LINED POUNDS LWB LWT MAX MCA MBH LTG LBS, # L LAT LRA LDB LP H HEIGHT KILOVOLT-AMPS KILOWATT-HOUR KILOWATTS KVA KWH KW HEAD, HUB DRAIN HAND-OFF-AUTOMATIC HORSEPOWER, HEAT PUMP HUMIDISTAT HEATER HEATING HEATING, VENTILATING & A/C HYDRANT DOMESTIC HOT WATER HERTZ HVAC HYD HW HZ HSTAT HTR HTG HOA HD HP ELECTRICAL CONTRACTOR GALLON GALVANIZED GENERAL CONTRACTOR GROUND FAULT INTERRUPTER GALLONS PER MINUTE GALLONS PER HOUR GALLONS PER DAY GAUGE GREASE WASTE GFI, GFIC GPD GPM GPH GW GAL GALV GC GA DEGREES FAHRENHEIT FOOT, FEET ENTERING WATER TEMPERATURE EXISTING FIRE ALARM FIRE DAMPER FLEXIBLE FEET PER MINUTE FULL LOAD AMPS FLOOR CLEANOUT FIRE ALARM CONTROL PANEL EXHAUST °F FT FACP FLEX FPM FCO FD FLA FA EX EWT EXH EC VAV VARIABLE AIR VOLUME W/ W/O WB WC W VD VTR WITH WET BULB WATER COLUMN WITHOUT VENT THROUGH ROOF VOLUME DAMPER WATT, WIDTH VAC VA UON U/F U/G U/S UL TYP VOLT-AMPERE, VALVE VACUUM VOLT, VENT UNDERGROUND UNDERSLAB UNDERFLOOR TYPICAL SQUARE FEET, SQUARE FOOT SMOKE DETECTOR, STORM DRAIN REVOLUTIONS PER MINUTE SHEET METAL & A/C CONT NAT'L ASSOC. TOTAL STATIC PRESSURE STORM WATER POST INDICATOR VALVE POUNDS PER SQUARE INCH PRESSURE RELIEF VALVE REFLECTED CEILING PLAN REINFORCING, REINFORCED NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL MFR'S ASSOC. NATIONAL FIRE PROTECTION ASSOC. NOISE CRITERIA OUTSIDE STEM AND YOKE OCCUPATIONAL SAFETY &HEALTH ADMIN. OPPOSED BLADE DAMPER OUTSIDE AIR (VENTILATION AIR) TENANT EXHAUST (TOILET) AWWA AMERICAN WATER WORKS ASSOC. RL REFRIGERANT LIQUID EXTERNAL STATIC PRESSURE ELECTRICAL ELEVATION EQUIPMENT ENCLOSURE ENTERING DRY BULB ENTERING AIR TEMPERATURE DIRECT EXPANSION DRAWING EACH DIRECT DIGITAL CONTROL ESP ENCL ELEC EQUIP EDB ELEV EA EAT DX DWG DDC DOMESTIC COLD WATER DOWNSPOUT DECIBEL DIAMETER DEGREES DRY BULB DEGREES CELSIUS DISCONNECT DIMENSION DOWN DS DIA (OR Ø) DN DISC DIM CW °C dB DEG DB SPEC SPECIFICATION TE THRU TP TSP TDH STD SUSP SURF ST SQ TOTAL DYNAMIC HEAD THROUGH TOTAL PRESSURE SUSPEND STANDARD SURFACE SQUARE SMACNA SM SP SECT SHT SF SD RS SA RPM RLA SHEET METAL STATIC PRESSURE SECTION SHEET REFRIGERANT SUCTION SUPPLY AIR RUNNING LOAD AMPS CONCRETE CIRCUIT CENTERLINE CIRCULATING COLUMN CLEANOUT CEILING CUBIC FEET PER MINUTE CUBIC FEET PER HOUR CKT L CLG COL CO C CC CIRC CFM CFH ASSY ASSEMBLY RECIRC RD REQ REV RHG RH REINF RCP RA ROOF DRAIN REFRIGERANT HOT GAS REQUIRED REVISION, REVISE RELATIVE HUMIDITY RECIRCULATE RETURN AIR PRV PSI PH, Ø PIV PLBG PD PLUMBING PRESSURE DROP PHASE AMERICAN NAT'L STANDARDS INSTITUTE AIR CONDITIONER, AIR CONDITIONING, AMERICAN SOCIETY OF TESTING & MATLS AMERICAN SOCIETY OF MECHANICAL ENGRS REFRIGERATION & AC ENGINEERS AIR CONDITIONING & REFRIG INSTITUTE ABOVE FINISHED GRADE AMP, AMPERE AUXILIARY AMERICAN SOCIETY OF HEATING, ARCHITECT, ARCHITECTURAL AMERICAN WELDING SOCIETY AMERICAN WIRE GAUGE AIR PRESSURE DROP ADJUSTABLE ABOVE FINISHED FLOOR ABOVE FINISHED CEILING ARI ASME ASTM AUX AWG AWS ASHRAE AFG ARCH A ANSI APD ADJ AFF AFC AIR COOLED CONDENSING UNIT AIR COOLED CHILLER ABOVE ACCU ACC ABV A/C OBD OS&Y OSHA OD OC OA NFPA NTS N.O. NIC OVERFLOW DRAINAGE, OUTSIDE DIAMETER ON CENTER NOT TO SCALE NORMALLY OPEN NOT IN CONTRACT NEC NEMA N/A NC NOT APPLICABLE ETR EXISTING TO REMAIN REX REMOVE EXISTING COP CLEANOUT PLUG ORD OVERFLOW ROOF DRAIN RWC RAIN WATER CONDUCTOR ABOVE CEILING AL ACOUSTIC LINING BOTTOM OF PIPE BUILDING BRITISH THERMAL UNIT BOTTOM OF STRUCTURE BOTTOM OF DUCT BOILER FEED WATER BACKDRAFT DAMPER BUILDING AUTOMATION SYSTEM BLDG BOP BOS BTU BOD BAS BFW BDD BELOW FLOOR BMS BUILDING MANAGEMENT SYSTEM DOM DOMESTIC FP FIRE PROTECTION FW FILTERED WATER GRD GROUND MC MECHANICAL CONTRACTOR O/H OVERHEAD OPNG OPENING REL RELOCATED SAN SANITARY D DEPTH G GAS CWR/CWS CONDENSING WATER RETURN/SUPPLY CONN CONNECT, CONNECTION CA COMBUSTION AIR TWR/TWS TOWER WATER RETURN/SUPPLY CHWR/CHWS CHILLED WATER RETURN/SUPPLY N.C. NORMALLY CLOSED PB PUSH BUTTON HHWR/HHWS HEATING HOT WATER RETURN/SUPPLY HWR DOMESTIC RECIRCULATED HOT WATER B/F CTE CONNECT TO EXISTING FF FINISHED FLOOR RR REMOVE AND RELOCATE ID INSIDE DIAMETER INVERT ELEVATION INCH, INCHES IN WC INCHES OF WATER COLUMN IN IE V (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS) (ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS) A B C END VIEW 18"MIN 18" MIN SIDE VIEW DETAIL NOTES 1. PROVIDE SEISMIC/HURRICANE RESTRAINTS WHEN REQUIRED BY CODE. SEISMIC/HURRICANE RESTRAINTS SHALL BE FURNISHED BY ROOFTOP UNIT MANUFACTURER AND INSTALLED BY CONTRACTOR. RESTRAINTS SHALL BE INSTALLED AS CLOSE AS POSSIBLE TO EACH CORNER OF ROOF CURB. SA ROOF TOP UNIT SEAL BETWEEN ALL DUCTS AND ROOF DECK WITH ACOUSTICAL SEALANT FLEX CONNECTION VERTICAL SUPPLY AIR DUCT SHALL BE FULL SIZE OF UNIT OPENING, TRANSITION TO DUCT SIZE INDICATED ON PLAN DUCT TRANSITIONS SHALL BE MADE WITH A MAXIMUM ANGLE OF 15° AND A MINIMUM OF 18" IN LENGTH DUCT TRANSITIONS SHALL BE MADE WITH A MAXIMUM ANGLE OF 15° AND MINIMUM OF 18" IN LENGTH PROVIDE FLEX CONNECTION BELOW ROOF DECK FOR SUPPLY AND RETURN AIR DUCT DROPS ROOFTOP UNIT SEAL BETWEEN ALL DUCTS AND ROOF DECK WITH ACOUSTICAL SEALANT DUCT MOUNTED SMOKE DETECTOR SEISMIC/HURRICANE RESTRAINT (TYPICAL AT 4 LOCATIONS, REFER TO DETAIL NOTE 1) 1" INTERNALLY LINED RETURN AIR DUCTWORK SCALE: NONE 1 M0.1 RTU SECTION DETAIL UNION HAND TIGHT PLUG COPPER CONDENSATE DRAIN LINES PAST CURB TO PREVENT CURB FROM RUST DAMAGE, DO NOT USE PVC FOR CONDENSATE DRAIN LINES, KEEP VERTICAL CONDENSATE LINE A MINIMUM OF 3" FROM CURB MINIMUM 1/2" "H" = 1 1/4" EXTEND TO ROOF WHERE EXISTING IS PIPED TO ROOF DRAIN OR REQ'D BY LOCAL AUTHORITIES, SECTION TO DRAIN ONLY MAY BE PVC SCALE: NONE 2 M0.1 RTU CONDENSATE DETAIL ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 M0.1 MECHANICAL LEGEND AND DETAILS 05/10/21 / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / PROPOSED MULTI-TENANT BUILDING 1-STORY, 11,000 GSF PROPOSED BUILDING 1-STORY, 2,000 GSF MICHIGAN ROAD (US 421) BENNETT PARKWAY (VAR. R/W) REDD ROAD (60' R/W) REDD ROAD (50' R/W) GAS METER GAS METER GAS METER GAS METER GAS METER GAS METER GAS METER CT CT E A A A A A A A A A W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W1 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 SCALE: 1" = 30'-0" 1 E1.2 SITE LIGHTING PLAN H-10 H-10 H-10 H-10 H-10 H-10 H-10 H-10 H-10 H-4 H-4 H-4 H-4 H-4 H-4 H-4 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 H-12 RETAIL BUILDING TRANSFORMER LOCATION. REFER TO E0.1 FOR ADDITIONAL INFORMATION UNDERGROUND CONDUIT AND WIRE, REFER TO E0.1 FOR ADDITIONAL INFORMATION. DETECTION LOOP FOR DRIVE THRU COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO PAVEMENT CONSTRUCTION. KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E1.2 SITE LIGHTING PLAN SITE LUMINAIRE SCHEDULE TYPE WATTAGE DESCRIPTION CATALOG NUMBER VOLTAGE LAMP FIXTURE A LED 150 OUTDOOR LED AREA LIGHT, 24000 LUMENS, FORWARD THROW, 5000K, 70 CRI CBMC; DL149573-LED-24L-SIL-FT-UNV-50-70CRI-IL 120 W1 LED 29 LED WALL SCONCE, 50K, 8000 LUMENS, WITH INTEGRAL EMERGENCY BATTERY PACK FOR 90 MINUTES OF BACK-UP POWER. CBMC; DL146539-FT-LED-8L-50-BB 120 W2 LED 32 LED WALL SCONCE, 4000K, 85 CRI, 2470 LUMENS WAC LIGHTING; DS-WE0517-F-40S 120 GENERAL SHEET NOTES 1. ELECTRICAL CONTRACTOR TO REFER TO ARCHITECTURAL DRAWINGS FOR ALL LIGHT FIXTURE LOCATIONS. 2. ALL BRANCH CIRCUIT WIRING SHALL BE #12 AWG UNLESS OTHERWISE NOTED. EACH BRANCH CIRCUIT SHALL HAVE A SEPARATE NEUTRAL CONDUCTOR. 3. WIRE ALL NIGHT LIGHTING, EXIT SIGNS, EMERGENCY FIXTURES AHEAD OF LOCAL SWITCHING, UNLESS OTHERWISE NOTED. SHEET KEYNOTES 1 PHOTOCELL ON WALL FACING NORTH. SHIELD PHOTOTCELL FROM ARTIFICIAL LIGHT SOURCES. 05/10/21 ONE LINE DIAGRAM INFORMATION. 8 TWO 4" CONDUITS WITH PULLSTRING TO UTILITY POINT OF CONNECTION. COORDINATE EXACT REQUIREMENTS WITH ENERGY COMPANY. REFER TO ONE LINE DIAGRAM ON SHEET E0.1 FOR MORE INFORMATION. 9 200AMP, 120/208V PANEL FED FROM METER CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR ONE LINE DIAGRAM INFORMATION. 10 400AMP, 120/208V DISCONNECT FROM METER CENTER AT BACK OF BUILDING, PLUS TWO 200AMP PANELS. REFER TO SHEET E-1.1 FOR ONE LINE DIAGRAM INFORMATION. 11 STUB UP LOCATION FOR FUTURE TENANT SPACE, PROVIDE CONDUIT AND PULLSTRING FROM METER CENTER AT BACK OF BUILDING. REFER TO SHEET E-1.1 FOR ONE LINE DIAGRAM INFORMATION. 12 4" TELEPHONE SERVICE CONDUIT ROUTED OVERHEAD AND STUBBED IN TENANT SPACE. TELEPHONE CONDUCTORS SHALL BE FURNISHED AND INSTALLED FROM LANDLORD TELEPHONE BOARD TO TENANT SPACE AS INDICATED ON PLAN. 13 4" TELEPHONE SERVICE CONDUIT AND PULL WIRE. CONDUIT ROUTED OVERHEAD AND STUBBED IN TENANT SPACE. TELEPHONE CONDUCTORS SHALL BE FURNISHED AND INSTALLED FROM LANDLORD TELEPHONE BOARD TO TENANT SPACE BY THE TENANT AT A LATER DATE. 9 T6-4 PANEL T6 PANEL T5b 10 WP T1-6 T1-8 12 13 13 13 WP T3-6 13 13 KEY PLAN ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA N PROJECT LOCATION WESTON POINTE DRIVE U.S. HIGHWAY 421 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E1.1 ELECTRICAL PLAN (1) layin light fixture per 90 sf. add em and exit lights per work letters. please note to install outlets per tenant's plans 05/10/21 DWG DRAWING DECIBEL DIAMETER DISCONNECT DOWN DIA DN DISC dB THRU THROUGH SF RTU RR REMOVE AND RELOCATE ROOF TOP UNIT CLOSED CIRCUIT TELEVISION CIRCUIT CEILING CABLE TELEVISION SYSTEM CKT CLG CCTV CATV REV RCP REVISION PVC PF PH POLYVINYL CHLORIDE POWER FACTOR PHASE AMERICAN NAT'L STANDARDS INSTITUTE ABOVE FINISHED GRADE ARCHITECT, ARCHITECTURAL AUDIO/VISUAL ABOVE FINISHED FLOOR ABOVE FINISHED CEILING A/V AFG ARCH ANSI AFF AFC OSHA OC NFPA NTS N.O. NIC ON CENTER NOT TO SCALE NORMALLY OPEN NOT IN CONTRACT NEC NEMA N/A NOT APPLICABLE ETR EXISTING TO REMAIN REX REMOVE EXISTING BREAKER BLDG BUILDING BKR BMS BUILDING MANAGEMENT SYSTEM GROUND ELECTRICAL SYMBOLS "IG" INDICATES ISOLATED GROUND TYPE "WP" INDICATES WEATHERPROOF COVER "54" INDICATES 54" AFF "C" INDICATES MOUNTED 8" ABOVE COUNTER DRY TYPE TRANSFORMER "2" INDICATES CIRCUIT NUMBER DISCONNECT SWITCH UNFUSED JUNCTION BOX CIRCUITRY TURNING UP INFLOOR/UNDERFLOOR CONDUIT/WIRE PANELBOARD - 208Y/120 VOLT, 3Ø, 4 WIRE PANELBOARD - 480Y/277 VOLT, 3Ø, 4 WIRE 1,3,5 A "a" INDICATES SWITCHED FIXTURE CONTROL EMERGENCY LIGHTING BATTERY UNIT WITH HEADS AS INDICATED. TIME CLOCK NL A a 13 "OS" INDICATES DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH "C" INDICATES SWITCH MOUNTED 8" ABOVE COUNTER "3" INDICATES THREE WAY SWITCH S PUSHBUTTON DOOR BUZZER FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR FIRE ALARM VISUAL ONLY ALARM SIGNAL WALL MOUNTED AT 80" AFF. FIRE ALARM MANUAL PULL STATION MOUNTED AT 48" AFF. FIRE ALARM AUDIO/VISUAL ALARM SIGNAL WALL MOUNTED AT 80" AFF. HOMERUN TO PANEL "A", CIRCUIT #1,3,5 (VIA 20A-1P CIRCUIT BREAKERS), TWO #12 CONDUCTORS (MINIMUM SIZE), UON. A GROUNDING CONDUCTOR SHALL BE PROVIDED IN ALL CONDUITS. REFER TO SPECIFICATIONS FOR ADDITIONAL GROUNDING REQUIREMENTS. DISCONNECT SWITCH FUSED: "AS" - INDICATES AMPERE SWITCH SIZE "AF" - INDICATES AMPERE FUSE SIZE "GFI" INDICATES GROUND FAULT CIRCUIT INTERRUPTER TYPE DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, GROUNDING TYPE, 20 AMPERE, MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED. FIRE RATED POKE-THROUGH DEVICE "T" INDICATES TELEPHONE/DATA "D" INDICATES DIMMER SWITCH - WATTAGE AS INDICATED ON PANEL SCHEDULE. EACH BRANCH CIRCUIT SHALL INCLUDE A SEPARATE NEUTRAL CONDUCTOR "DF" INDICATES FLUORESCENT DIMMER SWITCH - WATTAGE AS INDICATED ON PANEL SCHEDULE. EACH BRANCH CIRCUIT SHALL INCLUDE A SEPARATE NEUTRAL CONDUCTOR LIGHT FIXTURE: "A" INDICATES FIXTURE TYPE, "13" INDICATES CIRCUIT NUMBER, "a" INDICATES SWITCH CONTROL. REFER TO LUMINAIRE SCHEDULE FOR DESCRIPTION. ILLUMINATED "EXIT" SIGN LIGHTING FIXTURE. CEILING MOUNTED OR WALL MOUNTED. PROVIDE DIRECTIONAL ARROWS AS INDICATED ON FLOOR PLANS. COMBINATION VOICE/DATA OUTLET - MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED. PROVIDE SINGLE GANG BOX WITH PLASTER RING AND 3/4" CONDUIT TO ABOVE THE ACCESSIBLE CEILING. "W" INDICATES WALL MOUNTED AT 54" AFF, "C" INDICATES MOUNTED 8" ABOVE COUNTER. DOOR BELL FIRE ALARM DUCT MOUNTED SMOKE DETECTOR WITH SAMPLING TUBE, FURNISHED AND WIRED BY EC, MOUNTED BY MC. LIGHTING FIXTURE WITH 1 BALLAST WIRED TO EMERGENCY AND/OR NIGHT LIGHTING CKT. SWITCH - SINGLE POLE TOGGLE TYPE - 120/277 VOLT, 1-HP RATED, 20 AMPERE, MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED: "P" INDICATES DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE COMBINATION DUPLEX RECEPTACLE AND VOICE/DATA OUTLET MOUNTED IN FLOOR BOX. DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN FLOOR BOX. SINGLE (SIMPLEX) RECEPTACLE, TYPE AND MOUNTING AS INDICATED ON THE DRAWINGS. DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, GROUNDING TYPE, 20 AMPERE, MOUNTED AT 18" AFF UNLESS OTHERWISE NOTED: TELEPHONE FIRE RATED PLYWOOD BACKBOARD - SIZE INDICATED ON PLAN DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN FLOOR BOX. C CONDUIT (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS) AUX AUXILIARY BAS BUILDING AUTOMATION SYSTEM DDC DIRECT DIGITAL CONTROL C/B CIRCUIT BREAKER D DEEP, DEPTH EC ELECTRICAL CONTRACTOR FPC FIRE PROTECTION CONTRACTOR HID HIGH INTENSITY DISCHARGE L LENGTH IBC INTERNATIONAL BUILDING CODE LED LIGHT EMITTING DIODE MECH MECHANICAL MC MECHANICAL CONTRACTOR N.C. NORMALLY CLOSED P POLE MCC MOTOR CONTROL CENTER PB PUSH BUTTON PC PLUMBING CONTRACTOR A AMP, AMPERES IN INCH, INCHES DELTA CT CURRENT TRANSFORMER G,GRD SE SERVICE ENTRANCE XFMR TRANSFORMER Y WYE Δ REMOTE ANNUNCIATOR LIGHT/AUDIBLE ALARM FOR DUCT SMOKE DETECTOR AWG AMERICAN WIRE GAUGE ADA AMERICANS WITH DISABILITIES ACT CUBIC FEET PER MINUTE CW COLD WATER CFM EF EXHAUST FAN EMT ELECTRICAL METALLIC TUBING FARA FIRE ALARM REMOTE ANNUNCIATOR MUA MAKE UP AIR O/H OVERHEAD RM RLA RUNNING LOAD AMPS ROOM RGS RIGID GALVANIZED STEEL TRANS TRANSFORMER TYP TYPICAL UPS UNINTERRUPTED POWER SUPPLY W/ WITH POWER POLE "4" INDICATES FOUR WAY SWITCH "3" INDICATES THREE WAY SWITCH SWITCH - DUAL TECHNOLOGY, CEILING MOUNTED - SINGLE POLE, TOGGLE TYPE - 120/277 VOLT, 20 AMPERE "4" INDICATES FOUR WAY SWITCH WP WEATHERPROOF REMOTE EMERGENCY WEATHERPROOF LIGHTING HEAD SUPPLIED FROM REMOTE BATTERY UNIT. DATA OUTLET MOUNTED IN FLOOR BOX FIRE ALARM REMOTE ANNUNCIATOR FIRE ALARM CONTROL PANEL DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE MOUNTED IN CEILING. FIRE ALARM HEAT DETECTOR DACT DIGITAL ALARM COMMUNICATING TRANSMITTER FIRE ALARM CARBON MONOXIDE DETECTOR TAMPER SWITCH FLOW SWITCH KITCHEN HOOD SUPPRESSION SYSTEM FIRE PUMP CONTROL PANEL ELECTRICAL SPECIFICATIONS DIVISION 26 - ELECTRICAL I. GENERAL PROVISIONS A. GENERAL CONDITIONS, CODES & STANDARDS 1. GENERAL CONDITIONS OF THE CONTRACT FOUND IN THE ARCHITECTURAL DRAWINGS, GENERAL AND SPECIAL CONDITIONS OF THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND ANY OF THE OWNER'S GENERAL REQUIREMENTS SHALL APPLY UNLESS NOTED OTHERWISE. 2. REFER TO THE GENERAL CONDITIONS ON THE ARCHITECTURAL DOCUMENTS AND THE GENERAL AND SPECIAL CONDITIONS OF THE AIA FOR ADDITIONAL REQUIREMENTS REGARDING; SAFETY, COORDINATION & COOPERATION, WORKMANSHIP, PROTECTION, CUTTING AND PATCHING, DAMAGE TO OTHER WORK, PRELIMINARY OPERATIONS, STORAGE, ADJUSTMENTS, CLEANING, ETC. 3. ALL WORK SHALL BE IN CONFORMANCE WITH ALL LOCALLY ENFORCED, FEDERAL, STATE, AND LOCAL CODES AND ORDINANCES INCLUDING ANY SPECIAL THE OWNER REQUIREMENTS IN ADDITION TO THOSE SPECIFIED. 4. CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS. 5. ALL EQUIPMENT AND MATERIALS USED SHALL BE NEW AND UL LISTED FOR THE APPLICATION, AND SHALL BEAR AN APPROPRIATE UL LABEL. B. SCOPE OF WORK 1. THIS CONTRACT SHALL INCLUDE THE FURNISHING, INSTALLING, CONNECTING, AND OPERATION OF ALL EQUIPMENT WHICH IS A PART OF THE ELECTRICAL SYSTEMS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY SIMILAR INSTALLATIONS. ANY MATERIAL OR LABOR WHICH IS NEITHER SHOWN ON THE DRAWINGS NOR CALLED FOR IN THE SPECIFICATIONS, BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK AND WHICH IS USUALLY INCLUDED IN WORK OF A SIMILAR CHARACTER SHALL BE FURNISHED AND INSTALLED UNDER THIS CONTRACT AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIALS REQUIRED TO PROVIDE THE OWNER A COMPLETE, CODE APPROVED AND OPERATIONAL ELECTRICAL SYSTEM. 2. CAREFULLY READ SPECIFICATION FOR ALL PARTS OF THE WORK SO AS TO BECOME FAMILIAR WITH ALL TRADES' WORK SCOPE. CONSULT WITH OTHER TRADES TO INSURE PROPER LOCATIONS AND AVOID INTERFERENCES. ANY CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF THE OWNER BEFORE WORK IS COMMENCED. 3. CONTRACTORS SHALL BE HELD TO HAVE EXAMINED THE PREMISES AND SITE SO AS TO COMPARE THEM WITH THE DRAWINGS AND SPECIFICATIONS, NOTE THE EXISTING CONDITIONS AND OTHER WORK THAT WILL BE REQUIRED, AND THE NATURE OF THE CONDITIONS UNDER WHICH THE WORK IS TO BE PERFORMED. NO ALLOWANCE SHALL BE MADE TO THE CONTRACTOR BY REASON OF THIS FAILURE TO HAVE MADE SUCH EXAMINATION OR OF ANY ERROR ON HIS PART. 4. ALL EXISTING UTILITY AND ELECTRICAL SERVICES SHALL BE FIELD VERIFIED. CORRECTIONS TO THE DESIGN AND INSTALLATION SHALL BE MADE WITHOUT ADDITIONAL COST TO THE OWNER. 5. PROVIDE ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF ELECTRICAL WORK. ALL CORE DRILLING OR CUTTING OF FIRE RATED FLOORS, SHAFTS, AND WALLS SHALL BE FIRESTOPPED PRIOR TO FINISH PATCHING. ALL PENETRATIONS SHALL BE FIRE SEALED TO MATCH THE FIRE RATING OF THE FLOORS, SHAFTS, AND WALLS PENETRATED. 6. TEMPORARY ELECTRICAL SERVICE, LIGHTING, AND RELATED WIRING SHALL BE PROVIDED TO OSHA REQUIREMENTS FOR THE USE OF ALL TRADES DURING CONSTRUCTION. 7. TEMPERATURE AND INTERLOCK CONTROL COMPONENTS AND ALL RELATED WIRING AND CONDUIT SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR UNLESS OTHERWISE INDICATED ON THE DRAWINGS. 9. ALL WORK INCLUDING, BUT NOT LIMITED TO PARTS, MATERIAL, EQUIPMENT AND LABOR SHALL BE GUARANTEED FOR ONE YEAR AFTER ACCEPTANCE BY THE ENGINEER AND OWNER. WHERE AN EQUIPMENT MANUFACTURER HAS A WARRANTY THAT EXCEEDS ONE YEAR, THAT WARRANTY PERIOD SHALL APPLY TO THIS PROJECT. C. DOCUMENTS 1. THE DRAWINGS ARE DIAGRAMMATIC; ALL WORK SHALL BE PERFORMED AS INDICATED ON THE DRAWINGS UNLESS EXISTING CONDITIONS OR COORDINATION ISSUES REQUIRE CHANGES. THESE CHANGES SHALL BE MADE WITH NO ADDITIONAL COST TO THE OWNER. 2. ANY INCIDENTAL ITEMS OR LABOR, ETC. NOT INCLUDED IN THE SPECIFICATIONS OR THE DRAWINGS BUT REASONABLY IMPLIED AS NECESSARY FOR THE COMPLETE INSTALLATION OF ALL APPARATUS SHALL BE INCLUDING IN BID. 3. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO SUPPLEMENT EACH OTHER AND ANY MATERIAL OR LABOR CALLED FOR IN ONE SHALL BE FURNISHED EVEN THOUGH NOT MENTIONED IN BOTH. 4. IF ERRORS ARE FOUND IN THE DRAWINGS OR SPECIFICATIONS OR DISCREPANCIES OCCUR BETWEEN THE SAME, OR BETWEEN THE FIGURES ON THE DRAWINGS, AND THE SCALE OF SAME OR BETWEEN THE LARGER AND SMALLER DRAWINGS, OR IN THE DESCRIPTIVE MATTER ON THE DRAWINGS SHALL BE REFERRED TO THE OWNER FOR REVIEW AND FINAL DECISION PRIOR TO THE BID DUE DATE. 5. THE BIDDING OF THIS WORK WILL CONTEMPLATE THE USE OF EQUIPMENT AND MATERIALS EXACTLY AS SPECIFIED HEREIN. WHERE MORE THAN ONE MANUFACTURER IS MENTIONED ANY ONE MAY BE UTILIZED. SUBSTITUTE MANUFACTURERS MAY BE OFFERED ONLY AS AN ALTERNATE TO THE SPECIFIED EQUIPMENT AND MATERIAL AND MUST BE SUBMITTED AS SPECIFIED IN THE ARCHITECTURAL DOCUMENTS. 6. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN THESE SPECIFICATIONS. REFER TO EACH SECTION FOR ANY SPECIFIC REQUIREMENTS. D. COORDINATION 1. CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. 2. EACH CONTRACTOR SHALL BE HELD RESPONSIBLE FOR ALL DAMAGE TO OTHER WORK CAUSED BY HIS WORK OR THROUGH THE NEGLECT OF HIS, OR HIS SUB-TRADE'S PERSONNEL. ALL PATCHING, REPAIRING, REPLACEMENT AND PAINTING, ETC. SHALL BE DONE AS DIRECTED BY THE OWNER BY THE CRAFTSMEN OF THE TRADES INVOLVED. THE COSTS OF SUCH WORK SHALL BE PAID BY THE CONTRACTOR CAUSING THE DAMAGE. 3. IT IS ESSENTIAL THAT ALL WORK AT THE PROJECT BE DONE AT SUCH TIME AND IN SUCH MANNER AS NOT TO INTERFERE WITH THE OPERATIONS OF THE SPACE, ADJACENT SPACES, OR FACILITY. A WORK SCHEDULE SHALL BE ARRANGED WITH THE OWNER, INCLUDING PREMIUM TIME WORK TO FACILITATE WORK WITH A MINIMUM OF INTERFERENCE TO THE OWNER'S OPERATIONS. E. METHODS 1. EXCAVATIONS SHALL BE MADE IN OPEN TRENCHES. FLOORS SHALL BE SAW CUT. CONDUIT SHALL BE LAID ON AN APPROPRIATELY GRADED 6" BED OF CLEAN AND DRY SAND. ENGINEERED FILL SHALL BE USED TO BACKFILL TO 6" ABOVE THE CONDUIT. BACKFILL THE REMAINDER OF THE TRENCH UTILIZING THE EXCAVATED MATERIAL IF APPROVED BY THE ARCHITECT OR THE OWNER. IF THE EXCAVATED MATERIALS ARE NOT ACCEPTABLE, ENGINEERED FILL ACCEPTABLE TO THE ARCHITECT SHALL BE UTILIZED TO BACKFILL THE REMAINDER OF THE TRENCH. BACKFILL SHALL BE ACCOMPLISHED IN 9" LIFTS WITH ALL LIFTS COMPACTED TO 95% PROCTOR. PATCH FLOOR TO MATCH EXISTING. 2. EQUIPMENT, CONDUIT, ETC. SHALL NOT BE SUPPORTED FROM ANY CEILINGS, OTHER PIPING, OTHER CONDUIT OR DUCTWORK, ROOF DECK, OR JOIST BRIDGING. ITEMS SHALL BE SUPPORTED FROM ACCEPTABLE STRUCTURAL BUILDING COMPONENTS AS DETERMINED BY THE ARCHITECT AND STRUCTURAL ENGINEER. 3. ALL ROOF PENETRATIONS, FLASHINGS AND COUNTER FLASHINGS SHALL BE PERFORMED BY THE OWNER'S ROOFING CONTRACTOR AT THE REQUESTING CONTRACTORS COST. F. SUBMITTALS 1. SHOP DRAWINGS SHALL BE PROVIDED TO THE ARCHITECT OF ALL EQUIPMENT AND ACCESSORIES PROVIDED FOR THE PROJECT WHETHER SPECIFIED HERE-IN OR ON THE DRAWINGS. REVIEW OF THE SHOP DRAWINGS SHALL BE FOR GENERAL DESIGN CONCEPT AND ADHERENCE WITH THE SPECIFICATIONS. QUANTITY OF SHOP DRAWINGS SUBMITTED SHALL BE AS SPECIFIED BY THE ARCHITECT. SHOP DRAWINGS SHALL BE PREPARED BY THE CONTRACTOR SHOWING LOCATIONS AND MEASUREMENTS FROM COLUMNS OF ALL CONCEALED AND EXPOSED PIPING, DUCTWORK, CONDUIT, EQUIPMENT, ACCESSORIES, ETC., AND SUBMITTED PRIOR TO INSTALLATION. THE OWNER MAY MAKE REPRODUCIBLE COPIES OF THEIR DRAWINGS AVAILABLE FOR USE IN PREPARATION OF SHOP DRAWINGS, HOWEVER THE OWNER SHALL NOT BE HELD RESPONSIBLE FOR NOT CONFIRMING ALL INFORMATION ON THE DRAWINGS PRIOR TO FABRICATION AND/OR INSTALLATION. 2. PROJECT RECORD DOCUMENTS - MAINTAIN AT THE JOBSITE ONE COPY OF ALL CONTRACT DOCUMENTS CLEARLY MARKED AS “PROJECT RECORD COPY”. THESE DRAWINGS ARE TO BE MAINTAINED IN GOOD CONDITION, UPDATED DAILY FOR CHANGES ENCOUNTERED AND AVAILABLE AT ALL TIMES FOR INSPECTION BY THE OWNER. DO NOT USE FOR FIELD CONSTRUCTION! PROJECT RECORD DOCUMENTS ARE TO BE KEPT CURRENT WITH EXACT DIMENSIONS OF ALL WORK, EQUIPMENT, DISTRIBUTION CONDUIT, CIRCUITS, ETC. MARK ALL INFORMATION IN RED LINES AND NOTES SO AS TO BE EASILY IDENTIFIED FROM THE BASE DRAWING. UPON COMPLETION OF THE WORK, ONE SET OF THESE DOCUMENTS SHALL BE TURNED OVER TO THE OWNER AS ONE QUALIFICATION FOR FINAL PAYMENT. 3. THREE COMPLETE SETS OF AS-BUILT DOCUMENTATION SHALL BE PROVIDED. IT SHALL INCLUDE, BUT NOT BE LIMITED TO ACCURATE PLAN DRAWINGS, WIRING DIAGRAMS AND OPERATION AND MAINTENANCE MANUALS. 4. SUBMIT OVERCURRENT DEVICE COORDINATION STUDY INCLUDING EQUIPMENT EVALUATION REPORTS, ONE LINE DIAGRAM, PROTECTIVE DEVICE COORDINATION STUDY AND TIME-CURRENT COORDINATION CURVES. STUDY ELECTRICAL DISTRIBUTION SYSTEM FROM NORMAL AND ALTERNATE POWER SOURCES. THE STUDY SHALL COMPLY WITH IEEE 399 FOR GENERAL STUDY REQUIREMENTS. II. PRODUCTS A. CONDUIT 1. CONDUIT SHALL BE HEAVY WALL RIGID GALVANIZED STEEL WHERE EXPOSED AND SUBJECT TO DAMAGE, 8'-0" AFF AND BELOW, AND IN WET LOCATIONS WHERE INDICATED ON THE DRAWINGS. UNDERGROUND CONDUIT SHALL BE SCHEDULE 40 PVC AND SHALL BE CONCRETE ENCASED (3' MINIMUM) WHERE INDICATED ON THE DRAWINGS. A TRANSITION SHALL BE MADE TO HEAVY WALL RIGID GALVANIZED STEEL BEFORE PVC CONDUITS PENETRATE THE FLOOR SLAB. INTERIOR CONDUITS SHALL BE ELECTRICAL METALLIC TUBING (EMT). METAL CLAD (MC) CABLE MAY BE USED IF APPROVED BY THE OWNER, AND INSTALLED IN LOCATIONS PERMITTED BY CODE. 2. FLEXIBLE METAL CONDUIT SHALL BE USED FROM OUTLET BOX TO INDIVIDUAL RECESSED LIGHT FIXTURES, AND FOR FINAL CONNECTIONS TO MOTORS AND OTHER DEVICES SUBJECT TO VIBRATION. B. CONDUIT FITTINGS AND BOXES 1. INTERIOR OUTLET BOXES SHALL BE STANDARD GALVANIZED SHEET STEEL TYPE, NOT LESS THAN 14 GAUGE IN THICKNESS, WITH KNOCKOUT OPENINGS, EXTENSIONS, PLASTER RINGS AND COVER PLATES TO ACCOMMODATE THE DEVICES INSTALLED. COVER PLATES SHALL BE SMOOTH PLASTIC TO MATCH DEVICE COLOR. USE STEEL PLATES WITH ROUNDED CORNERS FOR SURFACE BOXES. OUTDOOR (WET LOCATION) OUTLET BOXES SHALL BE CAST ALUMINUM TYPE WITH DEVICE COVERS TO SUIT. 2. OUTLET BOXES SHALL NOT BE LESS THAN 4 INCHES SQUARE, 1-1/2 INCHES DEEP. 3. COUPLINGS AND CONNECTORS FOR EMT SHALL BE DIE CAST ZINC OR STEEL. BUSHING SHALL BE GROUNDING TYPE WITH INSULATING PLASTIC INSERT. C. WIRE AND CABLE 1. CONDUCTORS FOR POWER AND LIGHTING SHALL BE NEW 600-VOLT, 90°C, TYPE XHHW, THHW, OR THWN INSULATION, MINIMUM SIZE #12-AWG, EXCEPT FOR CONTROL WIRING WHICH MAY BE #14-AWG. OTHER SIZES SHALL BE AS NOTED ON THE DRAWINGS. CONDUCTORS SHALL BE COPPER, UNLESS OTHERWISE APPROVED BY THE OWNER. 2. BRANCH CIRCUIT RUNS EXCEEDING 100 FEET IN TOTAL LENGTH FROM THE PANELBOARD TO THE LAST DEVICE, SHALL BE #10-AWG CONDUCTORS UNLESS OTHERWISE NOTED. 3. COMPRESSION TYPE LUGS AND CONNECTORS SHALL BE USED FOR ALL TERMINATIONS AND SPLICES. 4. ALL LOW VOLTAGE COMMUNICATIONS, FIRE ALARM, DATA, SECURITY, TELEPHONE AND ALL OTHER MISCELLANEOUS LOW VOLTAGE WIRING INSTALLED IN CEILING SHALL BE PLENUM RATED. D. WIRING DEVICES 1. DUPLEX RECEPTACLES SHALL BE GROUNDING TYPE, NEMA 5-20R, RATED FOR 20 AMPS, 125 VOLTS, WITH PROVISIONS FOR BACK AND SIDE WIRING. 2. SWITCHES SHALL BE TOGGLE OPERATED, QUIET TYPE, RATED FOR 20 AMPS, 120/277 VOLTS, WITH PROVISIONS FOR BACK AND SIDE WIRING. THREE WAY AND FOUR WAY SWITCHES SHALL BE PROVIDED WHERE INDICATED. 3. COLORS OF DEVICES SHALL BE SELECTED BY ARCHITECT. 4. WIRING DEVICES SHALL BE SPECIFICATION GRADE, AS MANUFACTURED BY HUBBELL, PASS & SEYMOUR, ARROW HART, LEVITON AND GENERAL ELECTRIC. E. LIGHTING AND RECEPTACLE PANELBOARDS 1. BRANCH CIRCUIT PANELBOARDS SHALL BE DEAD FRONT TYPE, WITH MAIN LUGS OR MAIN OVERCURRENT DEVICE AS INDICATED, BRANCH OVERCURRENT DEVICES AS NOTED AND AN EQUIPMENT GROUND BAR, ALL IN A SURFACE OR FLUSH MOUNTED SHEET STEEL ENCLOSURE. MINIMUM SHORT CIRCUIT CAPACITY SHALL BE 10,000 AMPS SYMMETRICAL FOR 120/208V, APPLICATION UNLESS NOTED OTHERWISE. 2. CIRCUIT BREAKERS SHALL BE BOLT ON TYPE; WITH MOLDED PLASTIC CASE; 1, 2, OR 3 POLE AS INDICATED; QUICK-MAKE, QUICK-BREAK; AND THERMAL-MAGNETIC TRIP DEVICE. 3. ALL BREAKERS FEEDING HVAC EQUIPMENT SHALL BE HACR RATED, UNLESS OTHERWISE NOTED. 4. ALL EQUIPMENT RATED LESS THAN 100A SHALL HAVE 60 DEGREE C MINIMUM TERMINATIONS. ALL EQUIPMENT RATED 100A OR OVER SHALL HAVE 75 DEGREE MINIMUM TERMINATIONS. 5. INDIVIDUAL SINGLE POLE CIRCUIT BREAKERS, WITH IDENTIFIED TIES, OR 2/3 POLE BREAKERS SHALL BE PROVIDED FOR EACH UNGROUNDED CONDUCTOR IN ALL MULTI-WIRE BRANCH CIRCUITS. 6. PANELBOARDS SHALL BE AS MANUFACTURED BY SQUARE D, GENERAL ELECTRIC, SIEMENS, AND CUTLER HAMMER. F. SAFETY SWITCHES AND MOTOR STARTERS 1. SAFETY SWITCHES SHALL BE FUSIBLE OR NON-FUSIBLE AS INDICATED ON THE DRAWINGS. SWITCHES SHALL BE QUICK-MAKE, QUICK-BREAK, HEAVY DUTY VISIBLE BLADE TYPE. ENCLOSURES SHALL BE NEMA 1 TYPE UNLESS OTHERWISE INDICATED ON THE DRAWINGS. FUSES SHALL BE DUAL ELEMENT - TIME DELAY TYPE. 2. ALL MOTORS OVER 1/8 HP SHALL BE PROVIDED WITH THERMAL OVERLOAD PROTECTION. OVERLOAD PROTECTION SHALL BE PROVIDED INTEGRAL WITH THE MOTOR WINDINGS AND/OR MOTOR CONTROLLER (PROVIDED BY OTHERS) UNLESS OTHERWISE INDICATED ON DRAWINGS. 3. ALL EQUIPMENT RATED LESS THAN 100A SHALL HAVE 60 DEGREE C MINIMUM TERMINATIONS. ALL EQUIPMENT RATED 100A OR OVER SHALL HAVE 75 DEGREE MINIMUM TERMINATIONS. G. LUMINAIRES AND LAMPS 1. ALL LUMINAIRES SHALL BE SPECIFIED ON THE LUMINAIRE SCHEDULE. 2. ALL FIXTURE / BALLAST / LAMP COMBINATIONS SHALL BE ENERGY SAVING TYPE. H. FIRE ALARM SYSTEM 1. A COMPLETE FIRE ALARM SYSTEM SHALL BE PROVIDED AS DESCRIBED ON THE DRAWINGS. ALL DEVICES, WIRING, BACKBOXES, PROGRAMMING, START-UP, INSTRUCTION AND TESTING REQUIRED FOR A COMPLETE OPERATING SYSTEM SHALL BE PROVIDED. 2. THE ELECTRICAL CONTRACTOR SHALL FURNISH SHOP DRAWINGS, COMPLETE WITH EQUIPMENT CUTS AND FLOOR PLANS (WITH WIRING INDICATED), AS WELL AS BATTERY CALCULATIONS, AND VOLTAGE DROP CALCULATIONS FOR REVIEW AND APPROVAL BY THE ARCHITECT, ENGINEER, AND ALL AUTHORITIES HAVING JURISDICTION. FLOOR PLAN DRAWINGS SHALL BE STAMPED BY A PROFESSIONAL ENGINEER RETAINED BY THE CONTRACTOR AND/OR SUPPLIER. NICET 4 CERTIFICATION AND STAMP IS ACCEPTABLE, IF APPROVED BY THE AUTHORITY HAVING JURISDICTION. 3. THE ELECTRICAL CONTRACTOR SHALL FURNISH FIRE ALARM DRAWINGS, CALCULATIONS, AND EQUIPMENT INFORMATION FOR ALL REQUIRED LOCAL MUNICIPALITY, OR STATE PERMITS. THE ELECTRICAL CONTRACTOR SHALL ARRANGE AND COORDINATE ALL REQUIRED TESTING AND INSPECTIONS REQUIRED BY THE LOCAL MUNICIPALITY FIRE DEPARTMENT. THE ELECTRICAL CONTRACTOR SHALL INCLUDE FIRE DEPARTMENT COSTS IN BID. 4. ALL HVAC UNITS OR GROUP OF HVAC UNITS WITH A COMMON PLENUM AND A DESIGN CAPACITY GREATER THAN 2000 CFM SHALL AUTOMATICALLY SHUT DOWN ASSOCIATED HVAC UNIT OR UNITS. WHERE A DUCT SMOKE DETECTOR IS NOT VISIBLE OR ACCESSIBLE FROM THE FLOOR, REMOTE AUDIBLE/VISUAL ALARM INDICATOR/TEST SWITCHES SHALL BE PROVIDED IN AN APPROVED LOCATION, AT A HEIGHT ACCESSIBLE AND VISIBLE FROM THE FLOOR. HVAC DUCT DETECTORS SHALL BE CONNECTED TO A CENTRAL STATION MONITORING SYSTEM UNDER SEPARATE CONTRACT WITH THE OWNER. 5. FIRE ALARM SIGNAL SHALL INITIATE THE FOLLOWING ACTIONS: a. CONTINUOUSLY OPERATE ALARM NOTIFICATION APPLIANCES. b. IDENTIFY ALARM AND SPECIFIC INITIATION DEVICE AT FIRE CONTROL PANEL. c. TRANSMIT ALARM TO LANDLORD SYSTEM. d. TRANSMIT ALARM SIGNAL TO REMOTE RECEIVING STATION. e. INTERRUPT TENANT SOUND SYSTEM. f. UNLOCK ELECTRIC DOORS IN EGRESS PATHS. g. RELEASE FIRE AND SMOKE DOORS HELD OPEN BY MAGNETIC DOOR HOLDERS. h. SHUT DOWN AIR HANDLING SYSTEMS. i. ACTIVATE EMERGENCY GAS AND HOOD EQUIPMENT SHUTOFFS. j. SWITCH HVAC EQUIPMENT CONTROLS TO FIRE ALARM MODE. 6. ALL FIRE ALARM VISIBLE DEVICES SHALL BE ADA COMPLIANT WITH A MINIMUM CANDELA RATING OF 75. CEILING MOUNTED DEVICES SHALL HAVE A RATING WITH THE LISTED REQUIREMENTS FOR A SPECIFIC CEILING HEIGHT. 7. ALL WALL MOUNTED STROBES, SPEAKER-STROBES, OR HORN STROBES SHALL BE MOUNTED SUCH THAT THE LENS IS NOT LESS THAN 80 INCHES AND NOT MORE THAN 96 INCHES ABOVE THE FINISHED FLOOR. 8. ALL AUDIBLE NOTIFICATION APPLIANCES SHALL BE SET TO ACHIEVE A SOUND PRESSURE AT LEAST 15dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL. 9. ALL CABLES FOR THE FIRE ALARM SYSTEM SHALL BE RATED FOR THE INTENDED USE. 10. FIRE ALARM SYSTEM MONITORING SHALL BE BY OTHERS UNDER SEPARATE CONTRACT WITH THE OWNER. 11. PROVIDE A SEPARATE LINE ITEM COST FOR A (1), (3), (5) YEAR MAINTENANCE, TESTING AND MONITORING AGREEMENT. AGREEMENT TO INCLUDE MONITORING TO A UL LISTED CENTRAL STATION PER NFPA 72 REQUIREMENTS, ALL CODE REQUIRED TESTING OF THE FIRE ALARM SYSTEM PER NFPA 72 AND OBC (MONTHLY VISUAL INSPECTION SHALL BE BY THE OWNER), CLEANING OF DEVICES SHALL BE DONE UPON SYSTEM REQUEST, AND ALL COST ASSOCIATED WITH MAINTENANCE OF THE SYSTEM SHALL BE PROVIDED (DUE TO DEFECTIVE EQUIPMENT ONLY). PROVIDE A YEARLY REPORT TO THE OWNER. 12. FIRE ALARM SYSTEM SHALL BE BY SIMPLEX, NOTIFIER, FCI, SIEMENS OR GAMEWELL. I. METER CENTER 1. METER CENTER SHALL BE RATED FOR 208/120V, THREE PHASE, FOUR WIRE OPERATION WITH TIN PLATED ALUMINUM BUSBARS, 100% RATED NEUTRAL BUS AND GROUND BUS. SWITCHBOARD SHALL BE SERVICE ENTRANCE RATED. REFER TO DRAWINGS FOR ADDITIONAL REQUIREMENTS. 2. METER CENTER SHALL BE FRONT ACCESSIBLE WITH SIDE ACCESS TO THE MAIN DEVICE. MAIN DEVICE SHALL BE INDIVIDUALLY MOUNTED. BRANCH DEVICES WITH HOT SEQUENCE UTILITY METERING SHALL BE INDIVIDUALLY MOUNTED. SECTIONS SHALL BE FRONT AND REAR ALIGNED, PROVIDE (3) METERS PER VERTICAL SECTION. 3. ENCLOSURE SHALL BE NEMA 3R WITH HINGED FRONT DOORS. 4. FUTURE DEVICES: EQUIP COMPARTMENTS WITH MOUNTING BRACKETS, SUPPORTS, BUS CONNECTIONS, AND APPURTENANCES AT FULL RATING OF BRANCH FEEDER COMPARTMENT. 5. MAIN HEAVY DUTY SWITCH: a. OPERATING MECHANISM: MANUAL HANDLE OPERATION TO CLOSE SWITCH. b. SERVICE-RATED SWITCHES: LABELED FOR USE AS SERVICE EQUIPMENT. 6. FUSED SWITCH: NEMA KS 1, TYPE HD; CLIPS TO ACCOMMODATE SPECIFIED FUSES; LOCKABLE HANDLE. 8. EQUIPMENT MOUNTING: INSTALL METERING CENTER ON CONCRETE BASE, 4-INCH NOMINAL THICKNESS WITH CHAMFERED EDGES. 9. DEVICE NAMEPLATES: LABEL EACH DISCONNECTING AND OVERCURRENT PROTECTIVE DEVICE AND EACH METER AND CONTROL DEVICE MOUNTED IN COMPARTMENT DOORS WITH A NAMEPLATE. III. EXECUTION A. GENERAL MISCELLANEOUS 1. ALL CONDUIT RUN IN FINISHED AREAS SHALL BE CONCEALED. CONDUIT SMALLER THAN 3/4" SHALL NOT BE USED FOR ANY CIRCUIT HOMERUNS. 2. RACEWAYS EXPOSED TO DIFFERENT TEMPERATURES SHALL BE FILLED WITH AN APPROVED MATERIAL IN ACCORDANCE WITH ARTICLE 300.7 OF THE NATIONAL ELECTRICAL CODE. 3. HANGERS, SUPPORTS, OR FASTENINGS SHALL BE PROVIDED AT EACH ELBOW, AT THE ENDS OF STRAIGHT RUNS TERMINATING AT BOXES OR CABINETS, AND AT INTERMEDIATE POINTS AS REQUIRED BY CODE. CONDUITS OR BOXES SHALL NOT BE SUPPORTED BY CEILING SUPPORT WIRES OR OTHER CEILING SUPPORTING HARDWARE. 4. ACCESS PANELS SHALL BE PROVIDED FOR ALL JUNCTION BOXES AND PULL BOXES INSTALLED ABOVE DRYWALL CEILINGS, COORDINATE SIZE AND LOCATION WITH ARCHITECT. 5. FIXTURE SUPPORTS SHALL BE IN ACCORDANCE WITH ARTICLE 410-30 OF THE NATIONAL ELECTRICAL CODE, OR ANY LOCAL CODES WHICH MY APPLY. 6. PROVIDE PERMANENT NAMEPLATES WITH DESIGNATIONS FOR PANELBOARDS, FEEDER DEVICES, DISTRIBUTION EQUIPMENT AND STARTERS. 7. PROVIDE TYPEWRITTEN DIRECTORY CARDS WITH BRANCH CIRCUIT IDENTIFICATION FOR BRANCH CIRCUIT PANELBOARDS. PANELBOARDS, FEEDER DEVICES, DISTRIBUTION EQUIPMENT AND STARTERS SHALL BE FIELD MARKED TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS IN ACCORDANCE WITH NEC 110.16. 8. INSTALL HANDLE GUARDS ON ALL BREAKERS FOR NIGHT LIGHTING, EMERGENCY AND SIMILAR CIRCUITS. 9. THE ELECTRICAL CONTRACTOR SHALL BALANCE PANELBOARD LOADING TO WITHIN 10% ON EACH PHASE BASED ON INSTALLED CONDITIONS. LOAD BALANCING CIRCUIT CHANGES SHALL BE PERFORMED OUTSIDE THE NORMAL OCCUPANCY WORKING SCHEDULE AND AT A TIME DIRECTED BY LANDLORD. 10. THE FINAL LOCATIONS OF ALL EQUIPMENT, OUTLETS, ETC. SHALL BE SUBJECT TO REASONABLE CHANGES IN LOCATION UP TO THE TIME OF ROUGHING-IN, AT NO ADDITIONAL COST TO THE OWNER. 11. CONTACT ELECTRIC POWER COMPANY AND MAKE NECESSARY ARRANGEMENTS FOR ELECTRIC SERVICE. 12. CONTACT TELEPHONE COMPANY AND MAKE NECESSARY ARRANGEMENTS FOR TELEPHONE SERVICE. 13. AT ALL TIMES KEEP PREMISES AND BUILDING IN A NEAT AND ORDERLY CONDITION, FOLLOWING OWNER'S INSTRUCTION IN REGARD TO STORING OF MATERIALS, PROTECTIVE MEASURES AND DISPOSING OF DEBRIS. 14. ALL SERVICE EQUIPMENT SHALL BE IDENTIFIED AS BEING SUITABLE FOR USE AS SERVICE EQUIPMENT. SERVICE EQUIPMENT SHALL BE FIELD MARKED WITH THE MAXIMUM AVAILABLE FAULT CURRENT AND THE DATE THE CALCULATION WAS PERFORMED. FIELD MARKING SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE INSTALLATION ENVIRONMENT. 15. RACEWAYS BELOW DRIVEWAYS, PARKING LOTS, AND ANY RACEWAYS INSTALLED BELOW GRADE SHALL BE INSTALLED A MINIMUM OF 24" BELOW FINISHED GRADE PER NEC 300-5. B. GROUNDING 1. GROUND ALL CONDUITS, CABINETS, MOTORS, PANELS, AND OTHER EXPOSED NON-CURRENT CARRYING PARTS OF ELECTRICAL EQUIPMENT IN ACCORDANCE WITH NEC ARTICLE 250. 2. BOND METAL WATER PIPING AND OTHER METAL PIPING (INCLUDING GAS PIPING) AND EXPOSED STRUCTURAL METAL IN ACCORDANCE WITH NEC ARTICLE 250. 3. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF AN INSULATED GROUNDING CONDUCTOR INSTALLED WITH ALL FEEDERS AND BRANCH CIRCUIT CONDUCTORS IN ALL CONDUITS. FIRE ALARM NOTES 1. PRINCIPAL OCCUPANCY CLASSIFICATION IS GROUP M. 2. SPACE IS PROVIDED WITH FULL SPRINKLER COVERAGE. 3. OCCUPANT LOAD IS LESS THAN 500. 4. THE LANDLORD DOES REQUIRE ALL TENANTS TO INSTALL A FIRE ALARM SYSTEM MONITORED BY THE LANDLORD SYSTEM. 5. A FIRE ALARM SYSTEM IS REQUIRED. ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E0.2 ELECTRICAL SPECIFICATIONS 05/10/21 PER NEC 250.102.(C)(1) GROUNDING ELECTRODE CONDUCTOR (#2/0) PER NEC 250.66. GROUNDED OR NEUTRAL BUS SERVICE EQUIPMENT TC H-4 H-2 RESTAURANT EXTERIOR BUILDING LIGHTS ZONE SCHEDULE: 1. BUILDING MOUNTED LIGHTING; PS ON, PS OFF 2. MONUMENT SIGN; PS ON, TC OFF SCALE: NONE 4 E-1.1 LIGHTING CONTROL DIAGRAM (PACKAGED) RELAY PANEL WITH INTEGRATED DIGITAL TIME CLOCK, 8 LIGHTING RELAYS, WITH RELAY CONTROL CARD FOR MANUAL CONTROL OF ZONES OR INDIVIDUAL RELAYS. EATON LITEKEEPER LK8 OR EQUAL. OUTDOOR PHOTOSENSOR; FACE NORTH 3/C #18 LV CABLE PS SCALE: 18" MIN. 12" MIN. 30" MIN. 4" 4" 5" FINISHED GRADE RED MARKER TAPE "ELECTRICAL" SCHEDULE 40 CONDUITS (TYPICAL) TRENCHING AND SELECT CLEAN BACKFILL TO 95% COMPACTION BY E.C. NONE 7 UNDERGROUND CONDUIT DETAIL SCALE: 12" 24" (MIN.) 32" (MIN.) 18" (MIN.) 5" 5" 7 1/2" 5" FINISHED GRADE RED MARKER TAPE "ELECTRICAL" BASE SPACER ON 5'-0" MAX. CENTERS 4" SCHEDULE 40 CONDUITS (TYPICAL) TRENCHING AND SELECT CLEAN BACKFILL TO 95% COMPACTION BY E.C. NONE 6 E-1.1 PRIMARY POWER DUCT BANK DETAIL E-1.1 (3)4" PVC WITH (4)#600KCMIL, EACH 400AMP TENANT 101 M 200AMP TENANT 102 M 200AMP TENANT 103 M 400AMP TENANT 104 M 400AMP TENANT 105 M 200AMP TENANT 106 M 200AMP FUTURE TENANT 107 M 1200A, 120/208V 3ɸ,4W METER CENTER PANEL "H" 200A MCB 120/208V TYPICAL TENANT SPACE PANEL FOR TENANT SPACE MCB 120/208V (4)#3/0,(1)#6GND-2"C F=16,877 (MAX) F=16,066(MAX) F=(MAX) 1 SHEET KEYNOTES 1 PROVIDE CONDUIT AND WIRE AS INDICATED BELOW; SPACE 101: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 12,827 SPACE 102: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 12,471 SPACE 103: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 14,658 SPACE 104: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 16,445 SPACE 105: 400AMP SERVICE - PROVIDE; 4#500KCMIL,1#3GND-4"C. F(MAX) = 14,915 SPACE 106: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 11,216 SPACE 107: 200AMP SERVICE - PROVIDE; 4#3/0,1#6GND-3"C. F(MAX) = 8,844 M FACP M C C TS FS F F L V C H-8 20A/1P FIRE ALARM CONTROL PANEL SURFACE MOUNTED, #108. (DACT REQUIRES TWO ACTIVE PHONE LINES). PROVIDE CONTROL MODULE FOR REQUIRED FUNCTION (TYPICAL). PROVIDE MONITOR MODULE FOR REQUIRED FUNCTION (TYPICAL). INITIATING/ CONTROL LOOP SIGNALING LOOP SD HD SD C FIRE ALARM DETAIL NOTES 1. THIS DIAGRAM REPRESENTS A TYPICAL SYSTEM AND IS NOT INTENDED FOR INSTALLATION. SYSTEM SUPPLIER SHALL PROVIDE INSTALLATION DRAWINGS AND SCHEMATIC WIRING DIAGRAMS. EXACT SYSTEM REQUIREMENTS SHALL BE COORDINATED WITH THE SYSTEM SUPPLIER. SYSTEM INSTALLER SHALL BE NICET CERTIFIED, IF REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION. 2. SYSTEM SUPPLIER SHALL SUPERVISE INSTALLATION, PROGRAM AND TEST SYSTEM AND INSTRUCT OWNER ON SYSTEM OPERATION. 3. ALL FIRE ALARM WIRING SHALL BE PLENUM RATED. EXPOSED FIRE ALARM WIRING, 10'-0" AFF AND BELOW, SHALL BE INSTALLED IN CONDUIT TO ABOVE ACCESSIBLE CEILING SPACE OR STRUCTURE. 4. ALL CONTROL CABINETS SHALL BE GROUNDED PER NEC REQUIREMENTS AND PER SPECIFICATIONS. 5. COORDINATE CITY TIE-IN REQUIREMENTS WITH LOCAL AUTHORITY. 6. DUCT SMOKES ARE FURNISHED AND WIRED BY EC, AND INSTALLED PER CODE BY MC. 7. ALL FIRE ALARM DEVICES SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 & 'ADA'. PROVIDE WIRING PER MANUFACTURER'S INSTALLATION DRAWING (TYP) SYNCHRONIZING MODULE PROVIDE TELEPHONE LINE TO TERMINAL BOARD FOR CITY TIE-IN OR OFF-SITE MONITORING. PROVIDE TELEPHONE LINE FOR SECONDARY OFF-SITE MONITORING. 2#12 AWG, 1#12 AWG GND, 3/4"C. SCALE: NONE 3 E-1.1 ADDRESSABLE FIRE ALARM SYSTEM TYPICAL WIRING DIAGRAM PROVIDE WIRING TO EACH SECURITY DOOR MAG LOCK POWER SUPPLY LOCATION FOR UNLOCKING OF SECURITY DOORS DURING FIRE ALARM CONDITION. (COORDINATE WITH SECURITY SYSTEM SUPPLIER). PROVIDE WIRING TO PRE-ACTION (OR DRY TYPE) SPRINKLER SYSTEM CONTROL PANEL. PROVIDE WIRING TO STARTERS FOR FAN SHUTDOWN. PROVIDE WIRING AND RELAY REQUIRED TO SHUTDOWN TENANT SOUND SYSTEM UPON FIRE ALARM ACTIVATION. PANEL FOR TENANT 105 T5a 200A MCB 120/208V F=(MAX) 1 INCOMING SECTION WITH MAIN SWITCH 200AMP LANLDORD PANEL FOR TENANT 105 T5b 200A MCB 120/208V WIREWAY 1 TENANT 105 1 TENANT 106 PANEL FOR TENANT SPACE 106 MCB 120/208V F=(MAX) 1 2" CONDUIT AND PULLWIRE, STUB UP FROM METER CENTER TO TENANT 106 SPACE FOR FUTURE TENANT 107. COORDINATE STUB UP LOCATION WITH LANDLORD PRIOR TO INSTILLATION. F=(MAX) 1 H-10 SITE POLE LIGHTING H-12 RETAIL EXTERIOR BUILDING LTGS ISSUE DATE 200275 THIS DRAWING AND THE IDEAS, DESIGNS AND CONCEPTS CONTAINED HEREIN ARE THE EXCLUSIVE INTELLECTUAL PROPERTY OF CURRAN ARCHITECTURE, AND ARE NOT TO BE USED OR REPRODUCED, WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF CURRAN ARCHITECTURE. C COPYGRIHT 2020, CURRANARCHI TECTURE PROJECT INFORMATION CERTIFICATION ISSUE DATES NOT FOR CONSTRUCTION PRELIMINARY 02.12.2021 JDF DEVELOPMENT THE AVENUE AT BENNETT FARM MULTI-TENANT BUILDING CARMEL, INDIANA 5719 LAWTON LOOP E. DR. #212 INDIANAPOLIS, IN 46216 O :: 317 . 288 . 0681 F :: 317 . 288 . 0753 T E S tesengineering.com E N G I N E E R I N G F 440 871 7954 P 440 871 2410 25760 First Street Cleveland, OH 44145 E0.1 ELECTRICAL LEGEND, NOTES, DETAILS 05/10/21