HomeMy WebLinkAboutP001.0GENERAL SHEET NOTES
1. EXISTING PLUMBING INFORMATION IS BASED ON LIMITED EXISTING BUILDING DRAWINGS AND FIELD
WORK. THE CONTRACTOR SHALL FIELD VERIFY THE EXISTING CONDITIONS FOR ACCURACY.
CONTRACTOR SHALL NOTIFY OWNER, ARCHITECT AND ENGINEER OF ANY SITUATIONS THAT MODIFY OR
INCREASE THE SCOPE OF WORK FROM THAT IS DESCRIBED IN THE DOCUMENTS.
2. ANYTHING NOT NOTED AS EXISTING IS TO BE FURNISHED AND INSTALLED AS PART OF THIS PROJECT.
3. REFER TO DRAWINGS AND PROJECT SPECIFICATIONS OF OTHER DISCIPLINES FOR ADDITIONAL PROJECT
INFORMATION AND REQUIREMENTS. NOTIFY ENGINEER OF ANY CONFLICTS BETWEEN THE INFORMATION
PRESENTED AND FIELD CONDITIONS.
4. PRIOR TO ANY ISOLATION OF SYSTEMS, SHUTDOWNS OR DEMOLITION THE CONTRACTOR SHALL
PROVIDE NECESSARY INVESTIGATION AND NOTIFY THE FACILITIES ENGINEERING/MAINTENANCE
PERSONNEL OF WORK TO BE PERFORMED SO AS TO AVOID ANY DETRIMENTAL SHUTDOWN OF SYSTEMS
TO ADJACENT SPACES.
5. PROTECT EQUIPMENT, FIXTURES, PIPING, DUCTWORK, ETC. INDICATED TO REMAIN AGAINST DAMAGE
AND SOILING DURING SELECTIVE DEMOLITION. WHEN PERMITTED BY THE ARCHITECT, ITEMS MAY BE
REMOVED TO A SUITABLE, PROTECTED STORAGE LOCATION DURING SELECTIVE DEMOLITION AND THEN
CLEANED AND REINSTALLED IN THEIR ORIGINAL LOCATIONS.
6. WHERE PIPE, DUCTWORK, INSULATION, FIXTURES OR EQUIPMENT TO REMAIN IS DAMAGED OR
DISTURBED, REMOVE THE DAMAGED PORTIONS AND INSTALL NEW PRODUCTS OF EQUAL CAPACITY AND
QUALITY. WHERE IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS
WHOSE INSTALLED PERFORMANCE EQUALS OR SURPASSES THAT OF THE EXISTING MATERIALS.
7. MAINTAIN AND RESTORE, IF INTERRUPTED BY DEMOLITION OR IN THE PATH OF NEW CONSTRUCTION,
ALL UTILITIES PASSING THROUGH AND SERVING OUTSIDE OF DEMOLITION AREA.
8. PLUMBING INSTALLATION MUST MAINTAIN INTEGRITY OF WALLS, PARTITIONS AND FLOORS DESIGNATED
AS EITHER FIRE RATED OR "SMOKE TIGHT". SEAL AROUND ALL PENETRATIONS THROUGH RATED OR
SMOKE TIGHT ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND GENERAL CONTRACTOR.
9. SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR PLENUM. CONSTRUCTION MATERIALS ABOVE
CEILING SHALL BE NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SMOKE
DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM RATED PER NFPA 70.
10. PROVIDE STOP VALVES AT EVERY FIXTURE ON BOTH HOT AND COLD WATER SUPPLY LINES. VALVES,
ESCUTCHEONS, FITTINGS, ETC. MUST BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS
TO BE USED.
11. ALL SANITARY PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 1% SLOPE EXCEPT FOR 2" LINES
WHICH SHALL BE PITCHED AT 2% SLOPE.
12. ALL GREASE WASTE PIPING INSTALLED UNDERGROUND IS TO BE PITCHED @ 2% SLOPE.
13. ALL OVERHEAD PIPING IS TO BE ROUTED TIGHT TO BUILDING STRUCTURE.
14. PIPING IS NOT PERMITTED IN DEMISING WALLS.
15. ALL EXPOSED, EXTERIOR PIPING SHALL BE PAINTED WITH RUST INHIBITIVE PRIMER, COLOR CODED
FINISH, AND IDENTIFICATION LABELS.
16. VERIFY NATURAL GAS AVAILABILITY AND CAPACITY. COORDINATE PRESSURE, SERVICE CONNECTION,
AND METER INSTALLATION WITH THE LANDLORD AND LOCAL UTILITY COMPANY.
17. PROVIDE GAS PIPE SUPPORTS ON ROOF. PROVIDE 10'-0" ON CENTER AND AT ALL CHANGES OF
DIRECTION. REFER TO DETAIL 6 ON THIS SHEET.
18. CLEAN AND REFURBISH EXISTING PLUMBING FIXTURES TO BE RE-USED. FIELD VERIFY EXISTING
PLUMBING FIXTURES ARE IN PROPER WORKING ORDER. NOTIFY OWNER IMMEDIATELY SHOULD
OPERATIONAL CHECK OF FIXTURES REVEAL ANY MAJOR COMPONENT FAILURES.
19. DO NOT ROUTE ANY WATER CONVEYING PIPING OVER ELECTRICAL EQUIPMENT.
20. ALL ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH BOTTOM CLEANOUT PLUGS.
21. INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING SERVING HANDICAPPED LAVATORIES.
22. TENANT SPACES, THAT ARE UN-OCCUPIED AT TIME OF OPENING, ARE TO HAVE PROVIDED BY FIRE
PROTECTION CONTRACTOR BRANCH PIPING AND SPRINKLER SPACING BASED ON THE ORDINARY
HAZARD GROUP II OCCUPANCY PER NFPA 13.
23. ALL PIPING TO POINTS 5'-0" OUTSIDE THE BUILDING IS BY THE PLUMBING CONTRACTOR.
24. PROVIDE A WALL CLEANOUT AT THE BASE OF ALL VERTICAL STORM AND SANITARY RISERS 1'-0" AFF.
25. FINISHED FLOOR ELEVATION = XXX.00
26. ALL STORM PIPING OUTSIDE THE PERIMETER OF THE BUILDING REQUIRES COORDINATION WITH THE
STRUCTURAL FOOTERS TO AVOID TRENCHING AND PIPE PLACEMENT WITHIN THE FOOTING ANGLE OF
REPOSE.
27. NOTHING IS PERMITTED TO BE ATTACHED TO, SUSPENDED FROM, OR PENETRATE THE ROOF DECK.
CONTRACTOR MAY ATTACH TO OR SUSPEND FROM THE TOP CHORD OF THE JOIST OR THE STRUCTURAL
STEEL WHICH EXISTS ABOVE THE SPACE.
28. CONTRACTOR SHALL VERIFY IF SPRINKLER HEADS UNDER STOCK SHELVING ARE REQUIRED.
29. ALL CONCEALED PIPING SHALL BE TESTED AND PROVEN LEAK PROOF AND FREE FROM DEFECTS PRIOR
TO CONCEALMENT.
30. ALL FLOOR DRAINS AND CLEANOUTS ARE TO BE INSTALLED FLUSH WITH THE FINISHED FLOOR.
31. ALL FLOOR SINKS ARE TO BE INSTALLED EITHER FLUSH WITH FINISHED FLOOR, OR RAISED PER LOCAL
CODE REQUIREMENTS.
ABBREVIATIONS
TMV THERMOSTATIC MIXING VALVE
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORIES, INC.
MAKE-UP AIR
MECHANICAL
MANHOLE
MANUFACTURER
MINIMUM
MOUNTEDMTD
MUA
MECH
MFR
MIN
MH
1000 BTU PER HOUR
MAXIMUM
LOW PRESSURE
POUNDS
MAX
MBH
LBS, #
LP
HEIGHTH
KITCHEN EQUIPMENT CONTRACTORKEC
HEAD, HUB DRAIN
HORSEPOWER
HEATING, VENTILATING & A/C
HYDRANT
DOMESTIC HOT WATER
HERTZ
HVAC
HYD
HW
HZ
HD
HP
ELECTRICAL CONTRACTOR
GALLON
GALVANIZED
GENERAL CONTRACTOR
GREASE INTERCEPTOR
GALLONS PER MINUTE
GALLONS PER HOUR
GALLONS PER DAY
GAUGE
GREASE WASTE
GI
GPD
GPM
GPH
GW
GAL
GALV
GC
GA
DEGREES FAHRENHEIT
FOOT, FEET
EXISTING
FLOOR DRAIN
FLEXIBLE
FEET PER MINUTE
FLOOR SINK
FLOOR CLEANOUT
EXHAUST
°F
FT
FLEX
FPM
FCO
FD
FS
EX
EXH
EC
W/
W/O
WC
VTR
WITH
WATER COLUMN
WITHOUT
VENT THROUGH ROOF
VAC
UON
U/F
U/G
U/S
UL
TYP
VACUUM
VENT
UNDERGROUND
UNDERSLAB
UNDERFLOOR
TYPICAL
SQUARE FEET, SQUARE FOOT
REVOLUTIONS PER MINUTE
TOTAL STATIC PRESSURE
STORM WATER
POST INDICATOR VALVE
POUNDS PER SQUARE INCH
PRESSURE RELIEF VALVE
REFLECTED CEILING PLAN
REINFORCING, REINFORCED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MFR'S ASSOC.
NATIONAL FIRE PROTECTION ASSOC.
OUTSIDE STEM AND YOKE
OCCUPATIONAL SAFETY & HEALTH ADMIN.
AMERICAN WATER WORKS ASSOC.AWWA
EXTERNAL STATIC PRESSURE
ELECTRICAL
ELEVATION
EQUIPMENT
ENCLOSURE
DRAWING
EACH
ESP
ENCL
ELEC
EQUIP
ELEV
EA
DWG
DOMESTIC COLD WATER
DOWNSPOUT
DIAMETER
DEGREES
DIMENSION
DOWN
DS
DIA (OR Ø)
DN
DIM
CW
DEG
SPEC SPECIFICATION
THRU
TP
TSP
TDH
STD
SUSP
SURF
ST
SQ
TOTAL DYNAMIC HEAD
THROUGH
TOTAL PRESSURE
SUSPEND
STANDARD
SURFACE
SQUARE
SECT
SHT
SF
RPM
SECTION
SHEET
CONCRETE
CENTERLINE
COLUMN
CLEANOUT
CEILING
CUBIC FEET PER MINUTE
CUBIC FEET PER HOUR
L
CLG
COL
CO
C
CC
CFM
CFH
ASSEMBLYASSY
RD
REQ
REV
REINF
RCP
ROOF DRAIN
REQUIRED
REVISION, REVISE
PRV
PSI
PH, Ø
PIV
PLBG
PD
PLUMBING
PRESSURE DROP
PHASE
AMERICAN NAT'L STANDARDS INSTITUTE
AMERICAN SOCIETY OF TESTING & MATLS
AMERICAN SOCIETY OF MECHANICAL ENGRS
ABOVE FINISHED GRADE
AUXILIARY
ARCHITECT, ARCHITECTURAL
AMERICAN WELDING SOCIETY
ADJUSTABLE
ABOVE FINISHED FLOOR
ABOVE FINISHED CEILING
ASME
ASTM
AUX
AWS
AFG
ARCH
ANSI
ADJ
AFF
AFC
ABOVEABV
OS&Y
OSHA
OD
OC
NFPA
NTS
N.O.
NIC
OVERFLOW DRAINAGE
ON CENTER
NOT TO SCALE
NORMALLY OPEN
NOT IN CONTRACT
NEC
NEMA
N/A NOT APPLICABLE
EXISTING TO REMAINETR
REX REMOVE EXISTING
CLEANOUT PLUGCOP
OVERFLOW ROOF DRAINORD
RWC RAIN WATER CONDUCTOR
BOTTOM OF PIPE
BUILDING
BRITISH THERMAL UNIT
BOTTOM OF STRUCTURE
BUILDING AUTOMATION SYSTEM
BLDG
BOP
BOS
BTU
BAS
BELOW FLOOR
BUILDING MANAGEMENT SYSTEMBMS
DOMESTICDOM
FIRE PROTECTIONFP
FILTERED WATERFW
GROUNDGRD
MECHANICAL CONTRACTORMC
OVERHEADO/H
OPENINGOPNG
REL RELOCATED
SAN SANITARY
DEPTHD
GASG
CONNECT, CONNECTIONCONN
STUB UP FOR FUTURE
DCV
PLUMBING SYMBOLS
GAS MANIFOLD LOCATION
DOMESTIC WATER RISER
PLUMBING FIXTURES
DOUBLE CHECK BACKFLOW PREVENTER
SPRINKLER HEAD (SEMI-RECESSED)
SPRINKLER HEAD (FULLY-RECESSED)
SPRINKLER HEAD (UPRIGHT)
TENANT CONNECTION
NORMALLY CLOSEDN.C.
PB PUSH BUTTON
DOMESTIC HOT WATER RETURNHWR
B/F
CONNECT TO EXISTINGCTE
FINISHED FLOORFF
RR REMOVE AND RELOCATE
INSIDE DIAMETERID
INVERT ELEVATION
INCH, INCHES
INCHES OF WATER COLUMN (GAS)IN w.c
IN
IE
V
OS&Y VALVE
BALL VALVE
ELBOW DOWN
ELBOW UP
UNION
TEE OUTLET UP
TEE OUTLET DOWN
DIRECTION OF FLOW
VALVE IN DROP
EXPANSION JOINT
GATE VALVE
CALIBRATED BALANCING VALVE
PIPE GUIDE
3-WAY SELF OPERATING VALVE
BUTTERFLY VALVE
PRESSURE REDUCING VALVE
CHECK VALVE
MOTOR OPERATED VALVE
2-WAY SELF OPERATING VALVE
M
HOSE BIB
GREASE WASTEGW
EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE REMOVED
NEW PIPING / EQUIPMENT
FS
T&P RELIEF VALVE
PRESSURE SWITCH
CAP ON END LINE
FLOW SWITCH
PRESSURE GAUGE WITH GAUGE COCK
THERMOMETER
FLEXIBLE CONNECTION
PIPE FLANGE
THERMOMETER WELL
GAS VALVE
WALL CLEANOUT OR CLEAOUT PLUG
FLOOR CLEANOUT
WATER METERM
GAS REGULATORR
FLOOR SINK (FS)
FLOOR DRAIN WITH P-TRAP
DRAWING NOTE REFERENCE
NEW TO EXISTING
POINT OF CONNECTION -
1
PS
(ALL ABBREVIATIONS SHOWN ARE NOT
NECESSARILY USED ON DRAWINGS)
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON DRAWINGS)
PIPING ABOVE FLOOR
PIPING BELOW FLOOR
SAN SANITARY PIPING
OD
RWC
G
OVERFLOW DRAIN PIPING
HOT WATER (HW) PIPING
COLD WATER (CW) PIPING
NATURAL GAS PIPING
HOT WATER RECIRCULATION (HWR)
STORM PIPING (ABOVE GROUND)
SANITARY VENT PIPINGV
ST STORM PIPING (UNDERGROUND)
ISSUE DATE
200275
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
COPYRIGHT 2020, CURRANARCHITECTUREC
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
02.12.2021
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
MULTI-TENANT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR. #212
INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
E N G I N E E R I N Gtesengineering.com
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
P0.1
PLUMBING
LEGEND, NOTES, DETAILS
05/10/21