HomeMy WebLinkAboutM001.2SHEET KEYNOTES
1 TRANSITION LINED SUPPLY DUCT IN RISE TO FULL SIZE OF RTU SUPPLY OPENING. CONNECT TO FULL
SIZE OF RTU SUPPLY OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND SA DUCTWORK
TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION. REFER TO RTU SECTION
DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
2 TRANSITION LINED RETURN DUCT IN RISE TO FULL SIZE OF RTU RETURN OPENING. CONNECT TO FULL
SIZE OF RTU RETURN OPENING WITH FLEX CONNECTION BELOW ROOF DECK. EXTEND RA DUCTWORK
TO BOTTOM OF STRUCTURE WITH FULL OPENING FOR FUTURE CONNECTION. REFER TO RTU SECTION
DETAIL ON SHEET M0.1 FOR ADDITIONAL INFORMATION.
3 SMOKE DETECTOR MOUNTED IN RETURN DUCT. DETECTOR SHALL BE PROVIDED AND WIRED BY
ELECTRICAL CONTRACTOR, MOUNTED BY MECHANICAL CONTRACTOR. COORDINATE WITH GENERAL
CONTRACTOR TO PROVIDE 24/24 ACCESS PANEL FOR DUCT MOUNTED SMOKE DETECTOR. ACCESS
PANEL MAY BE OMITTED IT DETECTOR IS ACCESSIBLE THROUGH LAY-IN DIFFUSER, OR IF DETECTOR IS
LOCATED IN AREA WITH NO CEILING.
GENERAL SHEET NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
SCALE: 1/4" = 1'-0"
1
M101
MECHANICAL PLAN
1
A
2 3 4
B
2 1
SD
3
OUTLINE OF RTU-2 ON ROOF
1 2
SD
3
ROOFTOP HVAC UNIT SCHEDULE
TAG SERVICE MFR MODEL No.
NOMINAL
TONS
EER
MIN OA
(CFM)
SUPPLY FAN DATA DX COOLING DATA GAS HEATING DATA UNIT CHARACTERISTICS
AIR FLOW NOTES/ACCESSORIES
(CFM)
ESP
(IN WC)
MOTOR
(HP)
FAN
(RPM)
EAT °DB/°WB
(°F)
LAT °DB/°WB
(°F)
SENSIBLE
(MBH)
TOTAL
(MBH)
COOLING
STAGES
EAT/LAT
(°F)
OUTPUT
(MBH)
HEATING
STAGES
VOLTAGE
(V-ɸ-Hz)
UNIT MCA UNIT MOCP
OPERATING
WEIGHT
(LBS)
RTU-1 JAVA HOUSE TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 900 1-18
RTU-2 JAVA HOUSE TRANE YSC060 5 12.0 100 2000 0.75 1.00 1150 80.0/67.0 59.7/58.3 48.2 59.9 MOD 50.0/87.8 81.0 2 208-3-60 29.0 40.0 900 1-18
NOTES/ACCESSORIES
1. 95° CONDENSING TEMPERATURE
2. REFRIGERANT - R410A
3. REFERENCE ENTHALPY ECONOMIZER WITH FAULT DIAGNOSTIC DETECTION
4. BAROMETRIC RELIEF
5. 14"INSULATED ROOF CURB
6. UNIT MOUNTED NON FUSED DISCONNECT
7. UNPOWERED GFCI RECEPTACLE
8. SUPPLY FAN VFD WITH SINGLE ZONE VAV CONTROLLER
9. THROUGH THE BASE ELECTRICAL
10. HAIL GUARD - WITH TOOL LESS REMOVAL
11. RTU MFANUACTURER'S PROGRAMMABLE SEVEN DAY AUTO CHANGE OVER THERMOSTAT WITH OCCUPANCY OUTSIDE AIR CONTROL.
12. HINGED ACCESS DOORS
13. ONCE THE RTU’S ARE OPERATIONAL - PROVIDE 2” MERV 8 FILTERS. INSPECT FILTERS DAILY. REPLACE AS NEEDED BUT NOT LONGER THAN 7 DAYS UNTIL UNIT IS ADJUSTED BY BALANCE CONTRACTOR. AT THE
DISCRETION OF THE TENANT CONSTRUCTION REPRESENTATIVE THIS FILTER REPLACEMENT CAN BE EXTENDED PAST THE 7 DAY LIMIT. ALL UN-USED FILTERS TO REMAIN ON SITE
FOR FUTURE USE BY TENANT. NEVER OPERATE THE RTU(S) IN COOLING DURING ANY SANDING OR DEMOLITION OR IF ANY TYPE OF FINE PARTICULATE COULD BE AIR BORNE. ALL RETURN AIR GRILLES OPENING IN
RETURN AIR DUCTWORK SHALL BE COVERED WITH CHEESE CLOTH OR A THROW AWAY FILTER (CHEAP CUT TO FIT FILTER ROLL) UNTIL UNITS ARE ADJUSTED BY THE
BALANCING CONTRACTOR. REMOVE THIS CHEESE CLOTH FILTER UPON TESTING BY BALANCE CONTRACTOR.
14. MICRO-PROCESSOR CONTROLS
15. 5 YEAR PARTS AND LABOR COMPRESSOR WARRANTY
16. STAINLESS STEEL HEAT EXCHANGER WITH STAGED HEAT
17. 10 YEAR PARTS WARRANTY ON HEAT EXCHANGER
18. APPROVED ALTERNATES: CARRIER, AAON, YORK/JOHNSON CONTROLS, AND LENNOX
OUTLINE OF RTU-1 ON ROOF
ISSUE DATE
200311
THIS DRAWING AND THE IDEAS, DESIGNS
AND CONCEPTS CONTAINED HEREIN ARE
THE EXCLUSIVE INTELLECTUAL PROPERTY
OF CURRAN ARCHITECTURE, AND ARE NOT
TO BE USED OR REPRODUCED, WHOLE OR
IN PART, WITHOUT THE WRITTEN
CONSENT OF CURRAN ARCHITECTURE.
C
PROJECT INFORMATION
CERTIFICATION
ISSUE DATES
NOT FOR CONSTRUCTION
PRELIMINARY
12.31.2020
JDF DEVELOPMENT
THE AVENUE
AT BENNETT FARM
OUTLOT BUILDING
CARMEL, INDIANA
5719 LAWTON LOOP E. DR.
#212 INDIANAPOLIS, IN 46216
O :: 317 . 288 . 0681
F :: 317 . 288 . 0753
T E S
tesengineering.com E N G I N E E R I N G
F 440 871 7954
P 440 871 2410
25760 First Street
Cleveland, OH 44145
M101
MECHANICAL
PLAN
05/10/21