HomeMy WebLinkAboutCarrigan Single line diagram(N)JUNCTION
BOX OR EQUI.
3 2 1
PV MODULES
G
(N)HANWHA Q.PEAK DUO BLK-G6 340,
340W MODULES
20 MODULES WIRED IN
(1) SERIES OF 10 MODULES,
(1) SERIES OF 10 MODULES ,
SOLAREDGE POWER
OPTIMIZERS
(N)60A AC
DISCONNECT
AC DISCONNECT
FUSED,60A,1PH,
120/240V 2P
35A FUSE
3
(E)200A END FED
MAIN PANEL
UTILITY
GRID
(E)200A MAIN
BREAKER
(E) GROUND
ELECTRODE
SUPPLY SIDE TAP
EXISTING 120/240V 1PH 60HZ
M
(N)SOLAREDGE TECHNOLOGIES
SE6000H-US ENERGY HUB INVERTER
(240V), 6000W INVERTER
INVERTER
DC
AC
LOAD RATED DC DISCONNECT & AFCI
SOLAR
BATTERY
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 NONE (4) 10AWG PV WIRE NONE (1) 10 AWG BARE COPPER
2 3/4"IMC OR EQUIV (4) 10AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2
3 3/4"IMC OR EQUIV (2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2
NOTE:
MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A
LINE SIDE TAP: 100% ALLOWABLE BACKFEED IS =200A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION= INVERTER O/P I X CONTINUOUS LOAD(1.25)
=25x1.25x1=31.25A=>PV BREAKER = 35A
TOTAL REQUIRED PV BREAKER SIZE / FUSE SIZE=>35A PV BREAKER
SINGLE LINE DIAGRAM: DC SYSTEM SIZE - 6800W, AC SYSTEM SIZE - 6000W
ADDRESS:9646 CEDAR POINT DRIVE,
CARMEL, IN 46032
39.927377, -86.179933
APN: 291-310-301-057-000-018
CUSTOMER INFORMATION
NAME:JOHN CARRIGAN
DATE:4/27/21
SCALE:AS NOTED REV:A
AHJ:IL-CITY OF CARMEL
UTILITY:IPL
PRN NUMBER:GRN-24699
DESIGNER /CHECKED
BY: BC/BH
PAPER SIZE:17X11
SINGLE LINE DIAGRAM
E-1
OPTIMIZER CHARACTERISTICS
MODEL P340
MIN INPUT VOLTAGE 8 VDC
MAX INPUT VOLTAGE 60 VDC
MAX INPUT CURRENT 11 ADC
MAX OUTPUT CURRENT 15 ADC
SYSTEM CHARACTERISTICS
DC SYSTEM SIZE 6800W
INVERTER STRING VOLTAGE:Vmp 380V
MAX INVERTER SYSTEM VOLTAGE: Voc 480V
MAX SHORT CIRCUIT CURRENT 30A
OPERATING CURRENT 17.89A
INVERTER-1 SPECIFICATIONS
MODEL
SOLAREDGE TECHNOLOGIES
SE6000H-US ENERGY HUB
INVERTER (240V)
POWER RATING 6000W
MAX OUTPUT CURRENT 25A
CEC WEIGHTED EFFICIENCY 99%
MAX INPUT CURRENT 16.5A
MAX DC VOLTAGE 480V
MODULE SPECIFICATION
MODEL
HANWHA Q.PEAK DUO
BLK-G6 340
MODULE POWER @ STC 340W
OPEN CIRCUIT VOLTAGE:Voc 40.66V
MAX POWER VOLTAGE:Vmp 33.9V
SHORT CIRCUIT VOLTAGE:Isc 10.52A
MAX POWER CURRENT:Imp 10.02A
ELECTRICAL CALCULATIONS
DC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS>>
·REQUIRED CONDUCTOR AMPACITY: 125% PER 690.8(A)(1) X Isc(A) X #OF
PARALLEL STRINGS = MAX CURRENT PER 690.8(A)(1) X 125% PER
690.8(B)(2)(a)=MAX CURRENT PER 690.8(B)(2)(a)
·CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
AC WIRE SIZING CALCULATIONS BASED OF FOLLOWING EQUATIONS >>
·REQUIRED CONDUCTOR AMPACITY: INVERTER OUTPUT CURRENT X #OF
INVERTERSXMAX CURRENT PER 690.8(A)(3)X125% PER 690.8(B)(2)(A)
·CORRECTED AMPACITY CALCULATIONS:AMPACITY X TEMPERATURE DERATE
FACTOR X CONDUIT FILL DERATE = DERATED CONDUCTOR AMPACITY
·DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(2)(2) <
DERATED CONDUCTOR AMPACITY
DC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
1 1 X 15 X 1 = 15 X 1.25 = 18.75A 40 X 0.58 X 1 = 23.20A 18.75A < 23.20A
2 1 X 15 X 1 = 15 X 1.25 = 18.75A 40 X 0.71 X 0.8 = 22.72A 18.75A < 22.72A
AC WIRE CALCULATIONS:- MATERIAL:COPPER & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR AMPACITY CHECK
3 25 X 1 = 25 X 1.25 = 31.25A 75 X 0.87 X 1 = 65.25A 31.25A < 65.25A
ELECTRICAL NOTES:
1.CONDUCTORS EXPOSED TO SUNLIGHT SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC 310.10(D).
2.CONDUCTORS EXPOSED TO WET LOCATIONS SHALL BE SUITABLE FOR USE
IN WET LOCATIONS PER NEC 310.10(C).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL BE NO MORE THAN 2%.
4.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS OTHERWISE NOTED.
5.BREAKER/FUSE SIZES CONFORMS TO NEC 240.6 CODE SECTION.
6.AC GROUNDING ELECTRODE CONDUCTOR SIZED PER NEC 250.66.
7.AMBIENT TEMPERATURE CORRECTION FACTOR IS BASED ON NEC 690.31(C).
8.AMBIENT TEMPERATURE ADJUSTMENT FACTOR IS BASED ON NEC
310.15(B)(2).
9.MAX. SYSTEM VOLTAGE CORRECTION IS PER NEC 690.7.
10.CONDUCTORS ARE SIZED PER WIRE AMPACITY TABLE NEC 310.15(B)(16).
05/10/21